Plan Review Details - Permit 07030020
Plan Review Stops For Permit 07030020
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-12-10 Cont ID  
Sent By jwitmer Date 2007-12-10 Time 07:58 Rev Time 2.00
Received By jwitmer Date 2007-12-10 Time 07:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-07-18 Cont ID  
Sent By jwitmer Date 2007-07-18 Time 14:58 Rev Time 0.00
Received By jwitmer Date 2007-07-18 Time 14:58 Sent To  
Notes
2007-09-13 14:59:34BUILDING PLAN REVIEW
 PERMIT: 07030020
 ADD: 2216 PALM BEACH LAKES BLVD
 CONT: CRAMER & BREEN BUILD
 TEL: (561)541-9844
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS ( ADMINISTRATIVE)
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLEASE INDICATE IN DETAIL WHAT SCOPE OF WORK WILL BE
 COVERED UNDER THIS PERMIT, WHAT INSPECTIONS WILL BE
 NEEDED?DEPENDING ON THE ABOVE
 STATEMENT THE VALUEOF THIS PROJECT MAY BE LOW!
  
 4) PLANS FAIL TO INDICATE:
 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OF T HE CODE UNDER WHICH
 THIS PERMIT WILL BE ISSUED. PLANS INDICATE THE 2001
 FBC PLEASE CORRECT TO THE 2004 FBC.
 ALSO 2004 EXISTING BUILDING CODE, LEVEL OF ALTERATION.
  
  
 5) IF THE SCOPE OF WORK INCLUDED UNDER THIS PERMIT
 INCLUDES THE EXTERIOR ENVELOPE:
 ) 1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
  
 6)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 7) COMPLIED.
  
 8) NEW COMMENT DEALS WITH LETTER STATING DOOR HEIGTH OF
 DOORS 120,121, 122,126,140,141&141 ARE 75 " TALL.
 PLEASE SEE 1008.1.1THE HEIGHT OF DOORS SHALL NOT BE
 LESS THAN 80 INCHES (2032 MM).
 EXCEPTIONS LISTED DO NOT INCLUDE KENNELS.
  
 9) NEW COMMENT DEALS WITH LIGHT POLES, THERE ARE TWO
 DIFFERENT POLE MANUFACTURER'S SUBMITTED SHAKESPEARE
 POLES ARE CALCULATED TO ASCE 7-98. PCSI POLES ARE
 CALCULATED TO ASCE 7-04. PLEASE SEE CHAPTER 35OF THE
 2004 FBC, THE REFRENCED STANDARD IS ASCE 7-02. ALSO IF
 TWO REOPRTS ARE SUBMITTED THEN BOTH REPORTS WILL NEED
 TO BE ORIGINAL SIGNATURE, DATE AND RAISED EMBOSSED
 SEAL.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-02 Cont ID  
Sent By jwitmer Date 2007-04-02 Time 07:33 Rev Time 2.22
Received By jwitmer Date 2007-04-02 Time 07:33 Sent To FIRE
Notes
2007-07-18 15:26:18BUILDING PLAN REVIEW
 PERMIT: 07030020
 ADD: 2216 PALM BEACH LAKES BLVD
 CONT: CRAMER & BREEN BUILD
 TEL: (561)541-9844
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS ( ADMINISTRATIVE)
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLEASE INDICATE IN DETAIL WHAT SCOPE OF WORK WILL BE
 COVERED UNDER THIS PERMIT, WHAT INSPECTIONS WILL BE
 NEEDED?DEPENDING ON THE ABOVE
 STATEMENT THE VALUEOF THIS PROJECT MAY BE LOW!
  
 4) PLANS FAIL TO INDICATE:
 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OF T HE CODE UNDER WHICH
 THIS PERMIT WILL BE ISSUED. PLANS INDICATE THE 2001
 FBC PLEASE CORRECT TO THE 2004 FBC.
 ALSO 2004 EXISTING BUILDING CODE, LEVEL OF ALTERATION.
  
  
 5) IF THE SCOPE OF WORK INCLUDED UNDER THIS PERMIT
 INCLUDES THE EXTERIOR ENVELOPE:
 ) 1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
  
 6)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 7) COMPLIED.
  
 8) NEW COMMENT DEALS WITH LETTER STATING DOOR HEIGTH OF
 DOORS 120,121, 122,126,140,141&141 ARE 75 " TALL.
 PLEASE SEE 1008.1.1THE HEIGHT OF DOORS SHALL NOT BE
 LESS THAN 80 INCHES (2032 MM).
 EXCEPTIONS LISTED DO NOT INCLUDE KENNELS.
  
 9) NEW COMMENT DEALS WITH LIGHT POLES, THERE ARE TWO
 DIFFERENT POLE MANUFACTURER'S SUBMITTED SHAKESPEARE
 POLES ARE CALCULATED TO ASCE 7-98. PCSI POLES ARE
 CALCULATED TO ASCE 7-04. PLEASE SEE CHAPTER 35OF THE
 2004 FBC, THE REFRENCED STANDARD IS ASCE 7-02. ALSO IF
 TWO REOPRTS ARE SUBMITTED THEN BOTH REPORTS WILL NEED
 TO BE ORIGINAL SIGNATURE, DATE AND RAISED EMBOSSED
 SEAL.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
2007-04-02 07:51:20BUILDING PLAN REVIEW
 PERMIT: 07030020
 ADD: 2216 PALM BEACH LAKES BLVD
 CONT: CRAMER & BREEN BUILD
 TEL: (561)541-9844
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS ( ADMINISTRATIVE)
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLEASE INDICATE IN DETAIL WHAT SCOPE OF WORK WILL BE
 COVERED UNDER THIS PERMIT, WHAT INSPECTIONS WILL BE
 NEEDED?DEPENDING ON THE ABOVE
 STATEMENT THE VALUEOF THIS PROJECT MAY BE LOW!
  
 4) PLANS FAIL TO INDICATE:
 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OF T HE CODE UNDER WHICH
 THIS PERMIT WILL BE ISSUED.
 ALSO 2004 EXISTING BUILDING CODE, LEVEL OF ALTERATION.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601& TABLE 503.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 G) SQ. FT. A/C SPACE/ FL
 H) SQ. FT. FOOTPRINT
 I) SQ. FT. UNDER ROOF (TOTAL)
  
 5) IF THE SCOPE OF WORK INCLUDED UNDER THIS PERMIT
 INCLUDES THE EXTERIOR ENVELOPE:
 ) 1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
  
 6)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 7) PLANS SUBMITTED ARE LOOSE LEAF, COMPILE INTO
 STAPBLED SETS OF PLANS, 106.1.2* & 106.3.5.1.2* .
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-07-17 Cont ID  
Sent By dpalmer Date 2007-07-17 Time 17:30 Rev Time 0.00
Received By dpalmer Date 2007-07-17 Time 17:29 Sent To  
Notes
2007-07-17 17:36:23LTRS SUBMITTED BY TRHE GC, ELECTRICAL CONTRACTOR FOR
 COMPLETETION OF WORK.
 STAMPED LTRS AND PLACED WIHT ROLLS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-07-01 Cont ID  
Sent By dpalmer Date 2007-07-01 Time 11:06 Rev Time 0.00
Received By dpalmer Date 2007-07-01 Time 11:06 Sent To  
Notes
2007-07-01 11:07:53PLANS WERE REVIEWED IN ZONING AS PLANS WERE STILL
 INZONING BEING REVIEWED.
2007-07-01 11:06:57*** UNSAT ***
  
  
 1) NOTE: AS REQUESTED ON PREVIOUS REVIEW PLANS WERE NOT
 BOUND INTO COMPLETE SETS ATTACHED. SHEETS WERE STILL
 SUBMITTED LOOSELY WITH OUT THE CORRECT STAPLES.
  
 2) NOTE: AS REQUESTED IN PREVIOUS REVIEW AND REVIEW
 FROM WHEN PERMIT WAS FIRST ISSUED. PLEASE SUBMIT
 SIGNED, DATED AND SEALED WIND LOAD CALCULATIONS FOR
 SITE LIGHTING POLES.
 PLEASE SEE MOST OF THE SHEET SUBMITTED ARE
 PHOTO-COPIES, COLOR-PHOTO-COPIES ETC.
 PLEASE SEE FS 471.025, FAC 61G15-23.002.
 THIS COMMENT IS BEING MADE AT THIS TIME.
  
 3) NOTE: PLEASE SEE NO INFORMATION WAS SUBMITTED ALONG
 WITH PLANS FOR SCOPE OF WORK TO BE COMPLETED. THE PLANS
 WERE STAMPED FOR A RE-STAMP FOR FINALS, HOWEVER WILL
 REMAIN IN A *FAILED* STATUS UNTIL INFORMATION IS
 BROUGHT IN FOR COMPLETETION OF THE SCOPE OF WORK.
 THE SAME SHEETS WERE SUBMITTED BACK.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-09 Cont ID  
Sent By dpalmer Date 2007-03-09 Time 08:53 Rev Time 0.00
Received By dpalmer Date 2007-03-09 Time 07:54 Sent To  
Notes
2007-03-09 08:54:48** UNSAT **
  
 1) NOTE: PLEASE SEE PLANS ARE BEING SUBMITTED TO
 COMPLETE WORK FOR PREVIOUSLY PERMITTED WORK. PLEASE SEE
 THAT ANY REVISIONS DURING CONSTRUCTION SHOULD BE
 CHNAGED ON PLANS. PLEASE VEIRFY THIS.
 PLEASE SEE THE TOTAL VALUE BASED ON THE PLANS
 SUBMITTED IS EXTREMELY LOW EVEN IF COMPLETELY SCOPE OF
 WORK ALREADY PERMITTED AND APPLIED FOR UNDER PREVIOUS
 PERMIT. PLEASE PROVIDE SCOPE OF WORK IN DETAIL FOR THE
 WORK TO BE COMPLETED SO THAT A CORRECTED VALUE CAN BE
 DETERMINED.FBC 108.3
  
 PLEASE SUBMIT ALL PLANS INTO THREE COMPLETE SETS BOUND
 TOGETHER AND SECURELY FASTENED. PLEASE SEE SHEETS WERE
 SUBMITTED LOOSELY.
 FBC 106.1.2, 106.3.5.1.2
  
 2) NOTE: PLEASE SEE NOTES WHICH WERE ISSUED UNDER
 ORIGINAL PERMIT FOR SITE LIGHTING POLES WHICH THIS
 REVIEWER HAS NOT SEEN ANY REVISIONS SINCE 1-19-06.
  
 3) NOTE: PLEASE KNOW THAT AS THE SCOPE OF WORK IS NOW
 UNDER A NEW CONTRACTOR, A NEW RECORDED NOTICE OF
 COMMENCEMENT WILL BE REQUIRED FOR THE NEW CONTRACTOR.
 FS 713.13
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-07-20 Cont ID  
Sent By mwennerg Date 2007-07-20 Time 15:59 Rev Time 0.00
Received By mwennerg Date 2007-07-20 Time 15:59 Sent To  
Notes
2007-07-20 16:03:54***PROVISO***
  
 1) PLEASE NOTE THAT WHEN RESUBMITTING PLANS FOR
 CORRECTIONS, IT IS HELPFUL TO INCLUDE A RESPONSE LETTER
 INDICATING WHERE THE CORRECTION CAN BE FOUND.
  
 2) IT WOULD APPEAR THAT THE DOOR SWING IN A REQUIRED
 EXIT HAS NOT CHANGED FROM THE FIRST REVIEW. PLEASE
 RESPOND IN WRITING. THE PLANS WILL BE STAMPED WHEN
 RETURNED FOR OTHER REVIEW COMMENTS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-04-18 Cont ID  
Sent By mwennerg Date 2007-04-18 Time 10:28 Rev Time 0.00
Received By mwennerg Date 2007-04-18 Time 10:28 Sent To  
Notes
2007-04-18 10:35:30***DENIED***
  
 1) PLEASE NOTE THAT ALL SHEETS SHALL BE BOUND TOGETHER
 AND NOT SUBMITTED IN LOOSE FASHION.
  
 2) THIS WORK HAS BEEN PREVIOUSLY PERMITTED. PLEASE
 CLARIFY WHAT SCOPE OF WORK EXISTS UNDER THIS PERMIT,
 AND WHAT INSPECTIONS ARE NEEDED.
  
 3) ALL DOORS IN AN EXIT SHALL SWING IN DIRECTION OF
 TRAVEL WHEN SERVING AREAS WITH OCCUPANT LOAD GREATER
 THAN 50. SHT A-5 (VESTIBULE 152).
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-12-03 Cont ID  
Sent By adarroug Date 2007-12-03 Time 14:36 Rev Time 0.00
Received By adarroug Date 2007-12-03 Time 14:36 Sent To B
Notes
2007-12-03 14:36:38TO "JWITMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-15 Cont ID  
Sent By adarroug Date 2007-06-01 Time 16:21 Rev Time 0.00
Received By adarroug Date 2007-06-01 Time 16:21 Sent To  
Notes
2007-06-15 16:22:07TO "COMM" BD#37

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-18 Cont ID  
Sent By mwennerg Date 2007-04-18 Time 10:38 Rev Time 0.00
Received By mwennerg Date 2007-03-05 Time 11:28 Sent To  
Notes
2007-03-08 11:40:17TO "COMM" BD#43
2007-03-05 11:28:58WAITING FOR "COMM' BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-03-20 Cont ID  
Sent By rregueir Date 2007-03-20 Time 14:16 Rev Time 0.00
Received By rregueir Date 2007-03-20 Time 14:08 Sent To  
Notes
2007-03-20 14:16:32ALL MECHANICAL WORK RELATED TO THIS PROJECT WAS
 COMPLETED UNDER PERMIT # 05080540 W/ MASTER #
 04121374.
 MECHANICAL FINAL PASSED ON 12/20/2006.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-07-13 Cont ID  
Sent By kstevens Date 2007-07-13 Time 17:46 Rev Time 0.00
Received By kstevens Date 2007-07-13 Time 17:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-03-19 Cont ID  
Sent By kstevens Date 2007-03-19 Time 12:16 Rev Time 0.00
Received By kstevens Date 2007-03-19 Time 12:16 Sent To  
Notes
2007-03-19 12:31:21DENIED
 REFERENCE: FBC-2004 CHAPTER 1
  
 1. PLANS SHALL BE SUBMITTED IN COMPLETE SETS OF PLANS,
 NOT LOOSE SHEETS. MINIMUM 2 SETS OF PLANS SHALL BE
 SUBMITTED FOR REVIEW. SECTION 106.1.
  
 2. REVISIONS REQUIRED FOR PLUMBING. SEE INSPECTION
 RECORD. THESE SHOULD BE SUBMITTED AS SOON AS POSSIBLE
 TO AVOID DELAY IN GETTING A CERTIFICATE OF OCCUPANCY.
  
 3. THE VALUE OF THE WORK TO FINISH THE INTERIOR REMODEL
 SHALL REFLECT THE WORK TO BE DONE. THE VALUE FOR THAT
 WORK SHALL REFLECT THE WORK INDICATED ON THE PERMIT
 APPLICATION. SECTION 108.3.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2007-07-02 Cont ID  
Sent By bpowell Date 2007-07-02 Time 10:48 Rev Time 0.00
Received By bpowell Date 2007-07-02 Time 10:48 Sent To  
Notes
***NONE***