Plan Review Details - Permit 07020773
Plan Review Stops For Permit 07020773
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-01-03 Cont ID  
Sent By shill Date 2008-01-03 Time 14:41 Rev Time 0.00
Received By shill Date 2008-01-03 Time 14:41 Sent To  
Notes
2008-01-03 14:42:06**PROVISO**SUBMIT RAILING SHOPS FOR REVIEW PRIOR TO
 INSTALLATION

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-10-30 Cont ID  
Sent By shill Date 2007-10-30 Time 15:24 Rev Time 0.00
Received By shill Date 2007-10-30 Time 15:24 Sent To  
Notes
2007-10-30 15:30:02****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FACFLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
  
 1.)ADDRESSED.
  
 2.)THE PERMIT FOR THE ROOF FRAMING, SHEATHING, AND
 FLOOR FRAMING IS EXPIRED, AS WELL AS THE WINDOW AND
 DOOR PERMIT (04070723, 04050602).INCLUDE THIS SCOPE
 OF WORK IN THIS PERMIT AND IN THE VALUE.
  
 3.-8.)ADDRESSED.
  
 9.)USE OF REMOVABLE SHUTTERS ON COMMERCIAL BUILDINGS
 REQUIRES APPROVAL BY THE BUILDING OFFICIAL, SEE
 ATTACHED POLICY, ITEM 13.PROVIDE A PRE STORM
 INSTALLATION PLAN INCLUDING ALL INFORMATION IN THE
 POLICY.THIS PROCESS MAY (AND SHOULD) BE COMPLETED
 SEPARATELY FROM THE RESUBMITTAL.A DRAFT MAY BE
 SUBMITTED VIA EMAIL.
  
 10-16.)ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-29 Cont ID  
Sent By mperson Date 2007-04-29 Time 10:57 Rev Time 0.00
Received By shill Date 2007-04-29 Time 10:57 Sent To FIRE
Notes
2007-04-29 10:59:12****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
 FACFLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
  
 1.)SEE ATTACHED.THERE IS A BALANCE OF $2883.60 FROM
 A 4X PLAN REVIEW FEE ONPERMIT APPLICATION 03111034.
 SEE NOTES REGARDING THIS FEE ON THE FRONT SCREEN OF
 PERMIT 03111034.THIS FEE MUST BE PAID WHEN
 RESUBMITTING.
  
 2.)THE PERMIT FOR THE ROOF FRAMING, SHEATHING, AND
 FLOOR FRAMING IS EXPIRED, AS WELL AS THE WINDOW AND
 DOOR PERMIT (04070723, 04050602).INCLUDE THIS SCOPE
 OF WORK IN THIS PERMIT AND IN THE VALUE.
  
 3.)ENERGY CALCS WERE SUBMITTED.FORM 600 A-01 WAS
 USED.GOVERNING CODE IS FBC2004, PLEASE SEE FBC13 AND
 USE THE CORRECT FORM.
  
 4.)ENERGY CALCS REQUIRED FOR THE FIRST FLOOR ALSO,
 WHICH IS NOT RESIDENTIAL, FBC13-101.1, FBC13-202, FBC
 EB 708.1.ENERGY CALCS REQUIRED FOR SHELL BUILDINGS,
 FBC13-101.2.
  
 5.)DECLARE LEVEL OF ALTERATION, FBC EB CHAPTER 3.
  
 6.)INCLUDE A CODE SUMMARY; BUILDING TYPE FBC6,
 BUILDING HEIGHT AND AREA FBC5, SPRINKLER INFORMATION,
 OCCUPANCY CLASSIFICATION FBC 3 AND AREA PER OCCUPANCY.
  
 7.)THE PLANS DO NOT PROVIDE ENOUGH INFORMATION TO
 DETERMINE CODE COMPLIANCE.FOR INSTANCE, SHEET 1 SHOWS
 A 5? AND 10? DISTANCE TO DOTTED LINES.IF THIS IS AN
 ASSUMED PROPERTY LINE, YOU NEED TO SHOW THE ADJACENT
 BUILDINGS AND THEIR DISTANCE TO THE PROPERTY LINE AS
 WELL AS BUILDING TYPE AND OCCUPANCY.A NOTE ON SHEET 2
 STATES THAT THESE WALLS EXCEED 1 HOUR FIRE RATING, BUT
 COMPLIANCE WITH FBC TABLE 704.8 (0 UNPROTECTED OPENINGS
 PERMITTED), FBC TABLE 503, FBC TABLES 601, 602 HAS NOT
 BEEN SHOWN.PLEASE CONTACT ME IF YOU NEED ASSISTANCE.
  
  
 8.)INFORMATION WAS NOT PROVIDED FOR THE FIRST FLOOR.
 THE BOARD ORDER WAS TO BRING THE ENTIRE BUILDING UP TO
 100% CODE COMPLIANCE.AREN?T THERE WINDOWS, DOORS,
 ETC. ON THE FIRST FLOOR?IT IS UNDERSTOOD THAT THIS
 WILL BE A SHELL BUT CODE COMPLIANCE FOR THE SHELL MUST
 BE ON THE PLAN; EGRESS, INCLUDING ACCESSIBLE
 ENTRANCE/EXIT FBC 13.NOTHING WAS SHOWN ON THE PLAN.
  
  
 9.)USE OF REMOVABLE SHUTTERS ON COMMERCIAL BUILDINGS
 REQUIRES APPROVAL BY THE BUILDING OFFICIAL, SEE
 ATTACHED POLICY, ITEM 13.PROVIDE A PRE STORM
 INSTALLATION PLAN INCLUDING ALL INFORMATION IN THE
 POLICY.THIS PROCESS MAY (AND SHOULD) BE COMPLETED
 SEPARATELY FROM THE RESUBMITTAL.A DRAFT MAY BE
 SUBMITTED VIA EMAIL.
  
 10.)PROVIDE A DETAIL FOR THE STAIR GUARDRAIL/HANDRAIL
 ON THE OPEN SIDE, FBC1012, 1009, 1009.11.1 EXCEPTION.
  
 11.)SEE FBC 1019.1.5 REGARDING STORAGE UNDER THE
 STAIRS AND SHOW COMPLIANCE ON THE PLAN.
  
 12.)THE FIRST RISER FOR THE STAIRS (SHEET 8) IS SHOWN
 AT 4?.SEE FBC1009.3.1, DIMENSIONAL UNIFORMITY.
  
 13.)DESIGN PRESSURES FOR COMPONENTS AND CLADDING ARE
 NOT ON THE PLAN; PLEASE PROVIDE.ALSO PROVIDE WIND
 DESIGN CRITERIA FBC1603.1.4.
  
 14.)A COMPLETE REVIEW OF PRODUCT APPROVALS CANNOT BE
 DONE WITHOUT DESIGN PRESSURES.HOWEVER, PLEASE NOTE
 THE FOLLOWING:
  
 A. THE STEEL DOOR IS INSWING, BUT OUTSWING IS SHOWN ON
 THE PLAN FOR THE SECOND FLOOR.NO INFORMATION PROVIDED
 FOR THE FIRST FLOOR.THIS DOOR IS NOT APPROVED WHERE
 WATER INFILTRATION IS REQUIRED.IT IS NOT CLEAR WHERE
 THIS DOOR WILL BE INSTALLED.
  
 B. THE SINGLE HUNG WINDOW IS SMALL MISSILE IMPACT
 RATED.LARGE MISSILE IS REQUIRED, FBC1609.1.4(1).
  
 C. SUBMIT PRODUCT APPROVALS FOR THE WINDOWS FOR THE
 FIRST FLOOR.
  
 D. EITHER COMPLETE THE SAMPLE INSTALLATION SCHEDULE
 (LAST PAGE OF THE POLICY) OR PROVIDE ALL INFORMATION IN
 ANOTHER FORMAT.
  
 15.)SEE FBC1023.3 AND SHOW COMPLIANCE (DISTANCE OF
 STAIRS TO OTHER BUILDINGS).
  
 16.)PROVIDE A COPY OF THE SURVEY FOR THIS PROPERTY.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-12-28 Cont ID  
Sent By btrobaug Date 2007-12-28 Time 14:42 Rev Time 0.00
Received By btrobaug Date 2007-12-28 Time 14:42 Sent To  
Notes
2007-12-28 14:49:28 
  
 PREVIIOUSLY REVIEWED/PASSED PLANS IN THIS SET./WRT.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-10-24 Cont ID  
Sent By btrobaug Date 2007-10-24 Time 14:51 Rev Time 0.00
Received By btrobaug Date 2007-10-24 Time 14:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-03-08 Cont ID  
Sent By btrobaug Date 2007-03-08 Time 10:20 Rev Time 0.50
Received By btrobaug Date 2007-03-08 Time 10:05 Sent To M
Notes
2007-03-08 10:20:02 
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-01-03 Cont ID  
Sent By mawillia Date 2008-01-03 Time 13:05 Rev Time 0.00
Received By mawillia Date 2008-01-03 Time 12:40 Sent To  
Notes
2008-01-03 12:58:36*****APPROVED*****
  
  
 PLANS SHEETS 2, 3, AND 8 WERE STAMPED, INITIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-10-30 Cont ID  
Sent By mwennerg Date 2007-10-30 Time 15:56 Rev Time 0.00
Received By mwennerg Date 2007-10-30 Time 15:56 Sent To  
Notes
2007-10-30 16:00:58***APPROVED/PROVISO
  
 1) OK
  
 2) OK
  
 3) OK
  
 4) ILLUSTRATE ADDRESS ON DRAWINGS OR ADD NOTE.
  
 5) PLANS STILL SHOW SMOKE DETECTORS. PLEASE MAKE
 APPROPRIATE CORRECTION ON DRAWINGS.
  
 6) OK
  
 7) OK
  
  
 PLANS WERE PASSED WITH PROVISO AND WILL BE STAMPED WHEN
 RESUBMITTED FOR CORRECTIONS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-06-04 Cont ID  
Sent By mawillia Date 2007-06-04 Time 14:30 Rev Time 0.00
Received By mawillia Date 2007-06-04 Time 12:18 Sent To  
Notes
2007-06-04 14:30:17*****DENIED*****
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FORMTHE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 3.THE DEMOLITION, RENOVATION, OR CONSTRUCTION
 OPERATIONS SHALL NOT HINDER OF INTERFERE WITH EMERGENCY
 RESPONSE ACCESS TO THE SAID PROPERTY OR VICINITY
 THEREOF (INCLUDING STREETS, ROADS ALLEYS, FIRE LANES).
  
 4.ON THE APPROPIATE EXTERIOR ELEVATION FRONTING 7TH
 STREET, DISPLAY THE NUMERICAL ADDRESS FOR THIS
 STRUCTURE.AS PER WEST PALM BEACH CODE, THOSE NUMBERS
 SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1"
 IN WIDTH.
  
 5.ON PLAN SHEET 3, IT IS NOTICED THAT A SMOKE
 DETECTOR (SD) IS LOCATED IN EACH OF THE BEDROOMS,
 WHEREAS A SMOKE ALARM (SA) IS LOCATED IN THE LIVING
 ROOM AND DINING ROOM.PLEASE BE ADVISED THAT SMOKE
 DETECTORS (SD) ARE TIED INTO A FIRE ALARM SYSTEM.
  
 6.IT IS NOTED ON SHEET 9 OF THE INTENT OF
 CONSTRUCTING A CBS WALL TO CREATE A STORAGE ROOM.
 PLEASE BE ADVISED THAT ROOMS OR SPACES FOR STORAGE
 (UNDERNEATH A EXIT STAIR) OF COMBUSTIBLE SUPPLIES AND
 EQUIPMENT SHALL BE SPRINKLERERED OR HAVE A 1 HOUR FIRE
 SEPARATION.
  
 7.SPECIFY THE INTERIOR WALL AND CEILING FINISH
 CLASSIFICATION IN THE EXITS, EXIT ACCESS CORRIDORS, AND
 ALL OTHER SPACES AS CLASS A, CLASS B, OR CLASS C.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-12-21 Cont ID  
Sent By mmiller Date 2007-12-21 Time 16:30 Rev Time 0.00
Received By spalmer Date 2007-12-26 Time 15:43 Sent To  
Notes
2007-12-26 15:43:22TO "BOB" # 5
2007-12-21 16:31:02WAITING FOR BOB MMILLER

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-12 Cont ID  
Sent By adarroug Date 2007-10-12 Time 09:52 Rev Time 0.00
Received By adarroug Date 2007-10-12 Time 09:52 Sent To  
Notes
2007-10-19 08:35:28TO "BOB"#10
2007-10-12 09:52:45WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-04 Cont ID  
Sent By mawillia Date 2007-06-04 Time 12:18 Rev Time 0.00
Received By mawillia Date 2007-03-01 Time 14:36 Sent To  
Notes
2007-03-01 15:01:05TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-12-27 Cont ID  
Sent By tgordon Date 2007-12-27 Time 11:32 Rev Time 0.30
Received By tgordon Date 2007-12-27 Time 11:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-10-19 Cont ID  
Sent By tgordon Date 2007-10-19 Time 15:33 Rev Time 0.30
Received By tgordon Date 2007-10-19 Time 15:33 Sent To  
Notes
2007-10-19 16:06:25PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SUBMIT ENERGY CALCULATIONSUSING FORM
 600A-04-"R" OR 600B-04-"R" OR 600C-04-"R", SEE 2004 FBC
 13-600.0, AND FBC/EXISTING 611.1.
  
 2) WHEN RE-SUBMITTING HAVE THE NEW ENERGY CALCULATIONS
 SIGNED BY OWNER/AGENT ALSO, PER 2004 FBC
 13-600.3.ABC.2.
  
 3) THE CLOTHES DRYER VENT MAY NOT DISCHARGE ON TO THE
 A/C CONDENSER UNIT, SEE 2004 FBC/M 501.2 AND FBC RES.
 R303.4.2 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-03-09 Cont ID  
Sent By tgordon Date 2007-03-09 Time 15:52 Rev Time 0.30
Received By tgordon Date 2007-03-09 Time 15:52 Sent To P
Notes
2007-03-09 16:04:18*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON FORM600A-04-R,
 SEE 2004 FBC 13-600.3.A (12-8-06 REVISION).
  
 2) WHEN RE-SUBMITTING HAVE THE NEW ENERGY CALCULATIONS
 SIGNED BY OWNER/AGENT ALSO, PER 2004 FBC
 13-600.3.ABC.2.
  
 3) THE CLOTHES DRYER VENT MAY NOT DISCHARGE ON TO THE
 A/C CONDENSER UNIT, SEE 2004 FBC/M 501.2 .
  
 4) THE 10" RETURN AIR TRANSFER DUCTS TO THE BEDROOMS
 NEED TO BE 12".
 *** 2004 FBC/R M1602.4 .BALANCED RETURN AIR MAY BE
 ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-01-02 Cont ID  
Sent By mperson Date 2008-01-02 Time 16:08 Rev Time 0.00
Received By mperson Date 2008-01-02 Time 16:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-10-31 Cont ID  
Sent By mperson Date 2007-10-31 Time 09:19 Rev Time 0.00
Received By mperson Date 2007-10-31 Time 09:19 Sent To PC
Notes
2007-10-31 10:56:43DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE ON THE
 RESUBMITTED PLANS:
  
 1. REFERENCE MECHANICAL COMMENTS #1 & 2 ON THE ENERGY
 CALCULATIONS.
  
 2. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3,
 PLUMBING: AN ISOMETRIC POTABLE WATER RISER DIAGRAM IS
 REQUIRED FOR BOTH THE HOT AND COLD WATER INDICATING THE
 PIPE SIZES, VALVE LOCATIONS, LOCATION OF THE WATER
 SUPPLY LINE WITH THE BACKFLOW PREVENTER **608, THERMAL
 EXPANSION CONTROL **607.3FOR THE WATER HEATER, AND
 THE LOCATION OF THE WATER-HAMMER ARRESTORS **604.9
 WHERE QUICK CLOSING VALVES ARE UTILIZED (WASHING
 MACHINES, DISHWASHERS, ICE MAKERS).
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-03-12 Cont ID  
Sent By mperson Date 2007-03-12 Time 15:25 Rev Time 0.45
Received By mperson Date 2007-03-12 Time 15:25 Sent To B
Notes
2007-03-12 16:08:09DENIED
 REFERENCE: FBC-2004 PLUMBING; FBC-2004 CHAPTER 1, CITY
 OF WEST PALM BEACH AMENDMENTS;
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PER FBC-2004 CHAPTER 1, 106.1.1 INFORMATION ON
 CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE
 BUILDING OFFICIAL.
 NOTE: THE SUBMITTED SANITARY ISOMETRIC RISER DIAGRAM ON
 SHEET 7 DOES NOT REFLECT THE FLOOR PLAN.
 A} PLEASE CORRECT AND RESUBMIT THE SANITARY RISER
 DIAGRAM INDICATING THE DOUBLE BOWL KITCHEN SINK WITH
 DISHWASHER AND THE CORRECT LOCATION OF THE LAVATORY OFF
 BEDROOM #2.
  
 B} 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
 NOTE: PLEASE CORRECT THE BRANCH DRAIN AND STACK TO BE
 THREE INCH (3") ON THE RESUBMITTAL.
  
 C} 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS FOR RODDING.
 NOTE: PLEASE INDICATE THE STANDPIPE ON THE
 RESUBMITTAL.
  
  
 D} 708.3.5 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION. THERE SHALL BE A
 CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER.
 NOTE: PLEASE INDICATE THE TWO-WAY CLEANOUT ON THE
 RESUBMITTAL.
  
 E} 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 NOTE: CLEANOUT FOR THE WASHING MACHINE SHALL BE THREE
 INCH (3"). PLEASE INDICATE THIS ON THE RESUBMITTAL.
  
 F} 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 NOTE: CLEANOUT FOR THE WASHING MACHINE TO BE LOCATED AT
 FOUR FEET ABOVE FINNISH FLOOR (4' A.F.F.). PLEASE
 INDICATE THIS ON THE RESUBMITTAL.
  
 ********IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  