Plan Review Details - Permit 07020766
Plan Review Stops For Permit 07020766
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-08-24 Cont ID  
Sent By lmartine Date 2007-08-24 Time 17:58 Rev Time 0.00
Received By lmartine Date 2007-08-24 Time 17:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-08-23 Cont ID  
Sent By shill Date 2007-08-23 Time 10:11 Rev Time 0.00
Received By shill Date 2007-08-23 Time 10:11 Sent To  
Notes
2007-08-23 10:12:09****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)PLEASE PROVIDE TWO IDENTICAL COLLATED SETS FOR
 PERMIT ISSUANCE.OLD REVISED SHEETS ARE TO BE MARKED
 "VOID" AND SUBMITTED SEPARATELY FOR REFERENCE.
  
 **NO RESUB FEE**

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-07-10 Cont ID  
Sent By shill Date 2007-07-10 Time 10:58 Rev Time 0.00
Received By shill Date 2007-07-10 Time 10:58 Sent To  
Notes
2007-07-10 11:02:25****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)RUSSELL GOULDE PE IS NOT A QUALITY ASSURANCE
 ENTITY AUDITED BY THE FLORIDA BUILDING COMMISSION.A
 SIGNED, SEALED LETTER OF COMMITMENT STATING THAT HE
 WILL INSPECT THE INSTALLATION ON THE JOBSITE AND THEN
 SUBMIT A LETTER OF CODE COMPLIANCE TO THIS OFFICE WILL
 BE REQUIRED TO SATISFY THE REQUIREMENT FOR QUALITY
 ASSURANCE FAC9B72.
  
 2.)REGARDING THE HINGES, SHEET 5 OF 5, COMPARISON
 PRODUCT NOA STATES THAT TWO STEEL HINGES REF 1361409 BY
 AMEROCK CORP. WILL BE USED.WHAT IS THE SIZE OF THOSE
 STEEL HINGES AND WHAT IS THE SIZE OF THE THREE HEAVY
 DUTY BRASS HINGES PROPOSED?THE ENGINEER MUST SPECIFY
 SO THE CONTRACOTR AND INSPECTOR WILL KNOW IF THE
 CORRECT ONE IS BEING INSTALLED.
  
 3.)NO RESUB FEE (PRODUCT APPROVAL APPLICATION
 COMMENTS, NOT A PLAN REVIEW).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-22 Cont ID  
Sent By shill Date 2007-03-22 Time 16:13 Rev Time 0.00
Received By shill Date 2007-03-22 Time 16:13 Sent To  
Notes
2007-03-22 17:01:35****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 1.)QUALITY ASSURANCE BY A THIRD PARTY ENTITY IS
 REQUIRED.THE APPLICATION STATES THE FLORIDA BUILDING
 COMMISSION APPROVED THIRD PARTY QUALITY ASSURANCE
 AGENCY IS RUSSELL GOULDY, PE, BUT I WAS UNABLE TO FIND
 THEIR APPROVAL NUMBER ON THE WEBSITE,
 WWW.FLORIDABIULDING.ORG.
  
 2.)THERE IS NO APPLICANT ON THE APPLICATION.THIS
 SHOULD BE THE WINDOW MANUFACTURER.
  
 3.)THE SHOP DRAWINGS ARE A PART OF THE EVALUATION
 REPORT AND SHOULD BE SIGNED, SEALED, AND DATED BY THE
 ENGINEER WHO IS DESIGNING THE WINDOW.ALL INFORMATION
 REQUIRED BY FAC61G15-23.002 SHOULD BE ON EACH SHEET.
  
 4.)WHEN SUBMITTING, PLEASE PUT ALL SHEETS IN THE
 PACKAGE FACING THE SAME DIRECTION.SOME SHEETS WERE
 UPSIDE DOWN.HAVING THE PACKAGE EASILY READABLE HELPS
 TO EXPEDITE PLAN REVIEW.
  
 5.)THE WINDOW DRAWINGS ARE NOT NUMBERED.THE
 EVAULATION REPORT SHOULD REFER TO THE DRAWINGS BY
 NUMBER, INCLUDING ALL SHEETS.THE DRAWINGS ARE
 DIFFICULT TO READ AND DO NOT HAVE ALL REQUIRED
 INFORMATION; SEE OTHER COMMENTS.
  
 6.)THE ENGINEER STATES THAT THIS IS A RATIONAL
 ANALYSIS; NO RATIONAL ANALYSIS WAS PROVIDED.
  
 7.)THIS APPEARS TO BE A COMPARATIVE ANALYSIS BUT IS
 INCOMPLETE.THE REPORT FROM THE ENGINEER STATES FOR
 MANY ITEMS "NOT RATED".THE ENGINEER IS TO SHOW THAT
 THIS PRODUCT IS MEETS OR EXCEEDS THE DESIGN PRESSURE OF
 THE PRODUCT HE IS COMPARING TO.FOR INSTANCE, THE
 WINDOW MATERIAL IS PROVIDED, BUT NO ANALYSIS WAS
 PROVIDED TO SHOW THAT 1 3/4" MAHOGANY & SPANISH CEDAR
 IS EQUAL OR SUPERIOR TO WOOD FIBER.THE ENGINEER
 SPECIFIES "HEAVY DUTY BRASS HINGES", NO SIZE SPECIFIED.
 THE PRODUCT APPROVAL FOR THE ANDERSON WINDOW USED STEEL
 HINGES, BUT THE ENGINEER'S APPROVED PRODUCT INFORMATION
 STATES ONLY "NOT RATED" FOR HINGE INFORMATION.
  
 8.)PROVIDE ALL COMPARATIVE INFORMATION FOR BOTH
 PRODUCTS.
  
 9.)THE DRAWINGS ARE TO INCLUDE ALL STRUCTURAL
 INFORMATION FOR ALL COMPONENTS.FOR INSTANCE, THE
 FIRST SHEET STATES "SCREW".WHAT TYPE OF SCREW, WHAT
 SIZE, DIAMETER, LENGTH?
  
 10.)A SET HAS BEEN RETAINED.A COMPLETE PLAN REVIEW
 CANNOT BE DONE AS INCOMPLETE INFORMATION WAS PROVIDED.
  
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2007-02-27 Cont ID  
Sent By ssherman Date 2007-02-27 Time 12:35 Rev Time 0.00
Received By ssherman Date 2007-02-27 Time 12:34 Sent To  
Notes
2007-02-27 12:35:12HISTORICAL APPROVAL PER JILLIAN PAPA

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-07-27 Cont ID  
Sent By adarroug Date 2007-07-27 Time 13:54 Rev Time 0.00
Received By adarroug Date 2007-07-27 Time 13:54 Sent To B
Notes
2007-07-27 13:55:55TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-06-18 Cont ID  
Sent By adarroug Date 2007-06-18 Time 10:01 Rev Time 0.00
Received By adarroug Date 2007-06-18 Time 10:01 Sent To B
Notes
2007-06-18 10:02:07TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-07 Cont ID  
Sent By adarroug Date 2007-03-07 Time 14:43 Rev Time 0.00
Received By adarroug Date 2007-03-07 Time 14:43 Sent To B
Notes
2007-03-07 14:43:41TO "MISC" BOX#1

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-22 Cont ID  
Sent By shill Date 2007-03-22 Time 17:01 Rev Time 0.00
Received By shill Date 2007-03-01 Time 14:32 Sent To  
Notes
2007-03-01 14:32:28TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status N Date 2007-03-06 Cont ID  
Sent By jroach Date 2007-03-06 Time 16:23 Rev Time 0.00
Received By jroach Date 2007-03-06 Time 16:22 Sent To I
Notes
***NONE***