Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-03-23 Cont ID  
Sent By shill Date 2007-03-23 Time 16:58 Rev Time 0.00
Received By shill Date 2007-03-23 Time 16:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-14 Cont ID  
Sent By btrobaug Date 2007-03-14 Time 10:27 Rev Time 0.50
Received By btrobaug Date 2007-03-14 Time 10:11 Sent To M
Notes
2007-03-14 10:27:00 
  
 DENIED/INCOMPLETE INFORMATION
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE VALUE ON THE APPLICATION MUST
 INCLUDE THE TOTAL COST OF LABOR AND
 MATERIAL FOR THE GENERATOR, EQUIPMENT
 (TRANSFER SWITCHES, PANELS ETC.)
 AND PAD PER 108.3 FBC AS AMENDED.
 INCREASE THE VALUE AT THE COUNTER WHEN
 RESUBMITTING, AND GET A RECEIPT FROM THE
 PERMIT CLERK.
  
 2} PROVIDE MANUFACTURERS SPECIFICATIONS
 INDICATING RECOMMENDED SETBACKS AND
 ELECTRICAL SPEC'S FOR THE TRANSFER SWITCH.
  
 3} PLEASE INDICATE CONDUIT ROUTING FROM THE GENERATOR
 TO THE ATS, ON THE SITE PLAN.
  
 4} LOCATE THE ATS ON THE SITE PLAN.
  
 5} LOCATE THE DISCONNECT SHOWNON THE RISER, ON THE SITE
 PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-03-15 Cont ID  
Sent By mperson Date 2007-03-15 Time 13:57 Rev Time 0.50
Received By mperson Date 2007-03-15 Time 13:56 Sent To B
Notes
2007-03-15 14:51:34DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING CORRECTIONS/CLARIFICATIONS ARE REQUIRED
 FOR GAS PLAN REVIEW ON THE RESUBMITTAL:
  
 1. A GAS PERMIT CAN NOT BE ISSUED UNTIL THE ZONING
 ISSUES HAVE BEEN RESOLVED DUE TO THE FACT THAT THE
 LOCATION OF THE GENERATOR AND PROPANE TANK MIGHT
 CHANGE.
  
 2. PLEASE NOTE THAT THERE ARE TWO DIFFERENT SETS OF GAS
 DRAWINGS THAT HAVE BEEN SUBMITTED. ONE SET IS BY THE
 CONTRACTOR SIGNED ONTHE GAS PERMIT APPLICATION
 (FLORIDA PUBLIC UTILITIES) WITH A COMPLETE DRAWING OF
 THE GAS SYSTEM TO BE INSTALLED INCLUDING THE 500 GAL.
 U/G LP TANK, GENERATOR, FUTURE POOL HEATER, WATER
 HEATER, RANGE, GRILL, AND FIREPLACE. THE OTHER SET IS
 FROM MAKO ENGINEERING CONSULTANTS, INC. FL. CA 26916
 AND SIGNED AND SEALED BY JAMES L. MAKO FL.PE 54111 WITH
 GAS TO THE GENERATOR FROM THE LP TANK. IT IS SUGGESTED
 TO DELETE THE GAS INFORMATION ON THE ENGINEERED
 DRAWINGS ON THE RESUBMITTAL DUE TO THE FACT THAT THE
 CONTRACTORS DRAWINGS INDICATE THE COMPLETE GAS SYSTEM
 OF THE RESIDENCE.
  
 3. PLEASE PROVIDE GENERATOR MANUFACTURER'S
 SPECIFICATIONS INDICATING RECOMMENDED SETBACKS TO
 STRUCTURES.
  
 4. THE VALUE ON THE PERMIT APPLICATION IS WAY TO LOW.
 VALUE ON THE APPLICATION MUST INCLUDE EVERYTHING ON
 ELECTRICAL COMMENT NUMBER ONE PLUS ALL OF THE GAS
 PERMIT APPLICATION MATERIALS, LABOR,AND DESIGN.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-07 Cont ID  
Sent By adarroug Date 2007-03-07 Time 11:54 Rev Time 0.00
Received By adarroug Date 2007-03-07 Time 11:54 Sent To E
Notes
2007-03-07 11:54:26TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By adarroug Date 2007-03-01 Time 16:16 Sent To  
Notes
2007-03-01 16:16:23TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-03-15 Cont ID  
Sent By tgordon Date 2007-03-15 Time 10:31 Rev Time 0.25
Received By tgordon Date 2007-03-15 Time 10:31 Sent To G
Notes
2007-03-15 10:33:38*** DENIED ***
 1) SEE NOTES BY OTHER REVIEWERS, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2007-03-06 Cont ID  
Sent By mcruz Date 2007-03-06 Time 14:08 Rev Time 0.00
Received By mcruz Date 2007-03-06 Time 14:08 Sent To I
Notes
2007-03-06 14:08:18PLANNING & ZONING: ** FAILED**
  
 1.PLEASE PROVIDE RESPONSE IN WRITING.
  
 2.PROVIDE A LETTER FROM THE IRONHORSE HOME OWNERS
 ASSOCIATION (HOA) AND/OR ARCHITECTURAL REVIEW BOARD
 ALLOWING THE INSTALLATION OF THE GENERATOR ON THE SIDE
 OF THE PROPERTY AND OF THE PROPANE TANK IN THE FRONT.
 PLEASE ENSURE THE LETTER SPECIFICALLY ADDRESSES THE
 LOCATION OF THE EQUIPMENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME.
  
 MARGARITA CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 561-822-1444