Plan Review Details - Permit 07020735
Plan Review Stops For Permit 07020735
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-08-26 Cont ID  
Sent By jwitmer Date 2007-08-26 Time 08:56 Rev Time 25.00
Received By jwitmer Date 2007-08-26 Time 08:56 Sent To FIRE
Notes
2007-08-26 10:45:35302 DATURA 2ND REVIEW,
 9 STORY R-2,MERCANTILE& S-2
  
 BUILDING PLAN REVIEW
 PERMIT: 07020735
 ADDRESS: 302 DATURA ST
 CONT: PEGASUS CONSTRUCTION
 TEL: (954)946-4227
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
 2) 2ND REQUEST, (3) ORIGINAL SIGNED AND SEALED SOILS
 REPORTS WILL BE REQUIRED ONLY (2) SUBMITTED. FBC
 1802.2.1 QUESTIONABLE SOILS,
 WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION
 BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 . REPORTS
 HAVE COPIED SIGNATURES, NOT ORIGINALS.
  
 3) NOTE,FL S S 713.13NOTICE OF COMMENCEMENT, TO BE
 FILED WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF
 THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 4)2ND REQUEST,WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY S. 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE. CONTACT HAROLD PISKURA MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561) 805-6711 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 5-6 COMPLIED.
  
 7) BUILDING PROVISO:109.3.10*IMPACT OF
 CONSTRUCTION. ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PREFORMED IN A MANNERSO AS NOT TO
 ADVERSELY IMPACT THE CONDITION OF ADJACENT PROPERTY,
 UNLESS SUCH ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO CONSENT BY THE APPLICABLE PROPERTY
 OWNER, UNDER TERMS & CONDITIONS AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER. THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE, WATER OR
 DRAINAGE RUN-OFF, DEBRIS, AND THE STORAGE OF
 CONSTRUCTION MATERIALS. NEW CONSTRUCTION ACTIVITY SHALL
 NOT ADVERSELY IMPACT HISTORIC SURFACE WATER DRAINAGE
 FLOWS SERVING ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH ENGINEERING
 STANDARDS TO PRESERVE THE POSITIVE PATTERNS OF THE
 AFFECTED SITES. ACCORDINGLY, DEVELOPERS,CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL DEVELOPMENT,
 INCLUDING ADDITIONS, POOLS, PATIOS, DRIVEWAYS, DECKS,
 OR SIMILAR ITEMS, ON EXISTING PROPERTIES RESULTING IN A
 DECREASE IN EXCESS OF 800SQ FT OF PERMEABLE LAND AREA
 ON ANY PARCEL SHALL AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS PARAGRAPH. UPON
 COMPLETION OF THE IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO THE INSPECTOR
 IN ORDER TO RECEIVE APPROVAL OF THE FINAL INSPECTION.
  
  
 8) BUILDING PROVISO: 109.3.10.1 HURRICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW
 CONSTRUCTION RELATED MATERIALS EQUIPMENT AND DEBRIS TO
 REMAIN LOOSE OR OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE WATCH HAS BEEN
 ISSUED UNTIL THE HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER REMOVED FROM THE
 CONSTRUCTION SITE OR SECURED IN SUCH A MANNER AS TO
 MINIMIZE THE DANGER OF SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS CAUSING DAMAGE TO PERSONS OR
 PROPERTY FROM HIGH WINDS. ANY PERSONS WHO FAIL TO
 COMPLY TO REMOVE OR SECURE THE CONSTRUCTION MATERIALS
 EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
 9) THE ARCHITECTURAL COVERSHEET UNDER THE PROJECT DATA
 SUMMARY:
  
 9A)2ND REQUEST, LIFE SAFETY SHEET STILL INDICATES THE
 2004 WITHOUT UPDATES, PLANS ARE DESIGNED UNDER THE 2004
 FBC, PLANS SUBMITTED TO THE CITY AFTER DEC. 8, 2006 ARE
 TO BE DESIGNED TO THE 2006 FBC.
  
 9B) 2ND REQUEST, THE ARCHITECTURAL COVER SHEET BUILDING
 AREA CALCULATIONS STILL LIST MEZZANINE IN BODY OF TEXT.
 THEPLANS ALSO INDICATE THIS IS TO BE A 8 STORY
 BUILDING. THE SO CALLED MEZZANINE LEVEL DOES NOT MEET
 THE DEFINITION OF A MEZZANINE THIS IS THE SECOND STORY,
 CREATING A NINE STORY BUILDING. SEE 502 DEFINITION OF
 MEZZANINE.
  
 9C) COMPLIED.
  
 10) COMPLIED.
  
 11) THE LIFE SAFETY SHEET LS.1 DOES NOT CORRELATE WITH
 A2.31 ON THE SOUTH AND EAST GARAGE WALLS. SEE A2.31.
  
 12-13) COMPLIED.
  
 14)2ND REQUEST,A2.01INDICATES THE USE OF CAR
 LIFTS. PLEASE PROVIDE MANUFACTURERS SPECS ON THESE
 UNITS, ADDITIONAL COMMENTS MAY APPEAR ON LATTER REVIEWS
 WITH ADDITIONAL INFORMATION. NOT FOUND WITH THE PRODUCT
 APPROVALS. 106.1.2 ADDITIONAL INFORMATION REQUIRED.
 11-4.3.8 CHANGES IN LEVEL.
 CHANGES IN LEVELS ALONG AN ACCESSIBLE ROUTE SHALL
 COMPLY WITH SECTION 11-4.5.2 . IF AN ACCESSIBLE ROUTE
 HAS CHANGES IN LEVEL GREATER THAN ? INCH (13 MM), THEN
 A CURB RAMP, RAMP, ELEVATOR, OR PLATFORM LIFT (AS
 PERMITTED IN SECTION 11-4.1.3 AND 11-4.1.6 ) SHALL BE
 PROVIDED THAT COMPLIES WITH SECTION 11-4.7 , 11-4.8 ,
 11-4.10 , OR 11-4.11 , RESPECTIVELY. AN ACCESSIBLE
 ROUTE DOES NOT INCLUDE STAIRS, STEPS, OR ESCALATORS.
 SEE DEFINITION OF "EGRESS, MEANS OF" IN SECTION 11-3.5
 [SEE FIGURE 7 (C) AND FIGURE 7 (D)].
  
 15) 2ND REQUEST, THIS COMMENT IS COMMON TO MANY SHEETS,
 THE PLANS FAIL TO IDENTIFY VARIOUS COMMON DOORS THROUGH
 OUT THE PROJECT, PLEASE LABEL DOORS TO IDENTIFY FOR
 REQUIRED DOOR RATINGS. 106.1.2.* ADDITIONAL INFORMATION
 REQUIRED, TABLE 715.3 ETC.
  
 15A) SHEET A2.30 THE STOREFRONT DOORS ARE NOT LABELED
 ON THE DOOR SCHEDULE FOUND ON
 A2.80- A2.80- A2.83.
  
 16) 2ND REVIEW, THIS IS A REQUIRED STAIRWAY WHEN AN
 OCCUPANT LOAD OF 93, A2.01 STAIRWAY# 3 IS INDICATED AS
 PART OF THE POOL DECK MEANS OF EGRESS PLEASE SEE: LS .
 3 THIS SHEET ALSO INDICATES THIS TO BE THE SECOND MEANS
 OF EGRESS FROM THE POOL DECK.
 1022.5 LOCATION.EXTERIOR EXIT RAMPS AND STAIRWAYS
 SHALL BE LOCATED IN ACCORDANCE WITH SECTION 1023.3 .
 1023.3 EXIT DISCHARGE LOCATION.EXTERIOR BALCONIES,
 STAIRWAYS AND RAMPS SHALL BE LOCATED AT LEAST 10 FEET
 (3048 MM) FROM ADJACENT LOT LINES AND FROM OTHER
 BUILDINGS ON THE SAME LOT UNLESS THE ADJACENT BUILDING
 EXTERIOR WALLS AND OPENINGS ARE PROTECTED IN ACCORDANCE
 WITH SECTION 704 BASED ON FIRE SEPARATION DISTANCE.
  
 THE PURPOSE OF THIS SECTION IS TO PROTECT THE USERS OF
 EXTERIOR STAIRWAYS FROM FIRE IN AN ADJACENT BUILDING BY
 REQUIRING SPECIFIC SEPARATION DISTANCE FROM THAT
 ADJACENT BUILDING. THE REASON FOR THE REQUIRED DISTANCE
 TO A LOT LINE IS TO PROVIDE FOR A FUTURE BUILDING THAT
 COULD BE BUILT ON THE ADJACENT LOT.TAKEN FROM THE
 2004 FBC BUILDING CODE COMMENTARY.
  
 1004.8 OUTDOOR AREAS.
 YARDS, PATIOS, COURTS AND SIMILAR OUTDOOR AREAS
 ACCESSIBLE TO AND USABLE BY THE BUILDING OCCUPANTS
 SHALL BE PROVIDED WITH MEANS OF EGRESS AS REQUIRED BY
 THIS CHAPTER. THE OCCUPANT LOAD OF SUCH OUTDOOR AREAS
 SHALL BE ASSIGNED BY THE BUILDING OFFICIAL IN
 ACCORDANCE WITH THE ANTICIPATED USE. WHERE OUTDOOR
 AREAS ARE TO BE USED BY PERSONS IN ADDITION TO THE
 OCCUPANTS OF THE BUILDING, AND THE PATH OF EGRESS
 TRAVEL FROM THE OUTDOOR AREAS PASSES THROUGH THE
 BUILDING, MEANS OF EGRESS REQUIREMENTS FOR THE BUILDING
 SHALL BE BASED ON THE SUM OF THE OCCUPANT LOADS OF THE
 BUILDING PLUS THE OUTDOOR AREAS.
  
  
 17) A2.01 THE NEW RAMP THAT IS LOCATED NEXT TO PARKING
 SPACE# 22 DOESN?T INDICATE THE LOWER LANDING AT THE
 GARAGE FLOOR. PLEASE INDICATE THE LOWER LANDING ON THE
 PLANS IT APPEARS THAT IT WILL STICK OUT INTO THE
 VEHICLE TRAFFIC LANE. 11-4.8.4.(2) LANDINGS. ALL
 LANDINGS
 ON RAMPS SHALL NOT BE LESS THAN 60" CLEAR, & THE BOTTOM
 OF EACH RAMP SHALL HAVE NOT LESS THAN 72" OF STRAIGHT &
 LEVEL CLEARANCE.
  
 18) 2ND REQUEST, SHEET A2.01 THE PROPERTY LINE IS
 INDICATED ON THE EAST PORTION OF THE BUILDING, WHERE
 THERE ARE TWO DISPLAY CASES WHERE THE DOORS DO SWING
 OUT OVER THE PROPERTY LINE. 3202.2 ENCROACHMENTS ABOVE
 GRADE AND BELOW 8 FEET IN HEIGHT.
 ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY ABOVE GRADE
 AND BELOW 8 FEET (2438 MM) IN HEIGHT SHALL BE
 PROHIBITED EXCEPT AS PROVIDED FOR IN SECTIONS 3202.2.1
 THROUGH 3202.2.3 . DOORS AND WINDOWS SHALL NOT OPEN OR
 PROJECT INTO THE PUBLIC RIGHT-OF-WAY.
  
 19) COMPLIED, SHEET C-4 INDICATES GRADE ON THE EXTERIOR
 AND A2.32 FOR THE INTERIOR.
  
 20A) SHEET A9.20 DOES SHOW WALL CUT DETAILS WALL
 DESIGNATION 800 A 2HR BLOCK WALL INDICATES A TEST
 HW-D1003 BUT NOT WHAT LAB? PLEASE INDICATEU.L.,
 PLEASE ALSO INCLUDE THIS STANDARD SINCE THE INSPECTORS
 WILL NOT HAVE A U.L. BOOK AT THE JOB SITE. THIS
 PARTICULAR
 DETAIL LIST MANY COMPANY PRODUCTS FOR THE FORMING
 MATERIAL(3A) BUT ONLY 3M COMPANY FB-2000 FOR PART 3B.
  
  
 20B) SHEET A2.30 RETAIL UNIT R-301 INDICATES A WALL
 TYPE 105 NO SUCH WALL TYPE PLEASE CORRECT.
  
 20C) SHEET A2.38 ?A2.43 ALL INDICATE TENANT SEPARATION
 WALLS WITH ASSOCIATED WALL TAGS,
 A9.01 INDICATES THE ACTUAL U.L. ASSEMBLIES IN PICTORIAL
 BUT THE SOUND TEST REFERENCE ONLY PROVIDES A SOUND TEST
 STANDARD NOT THE ACTUAL RESULTS OF SAID SOUND TEST.
 PLANS INDICATE VARIOUS SOUNDTEST STANDARDS PLEASE
 PRODUCE THESE STANDARDS. WHEN INVESTIGATINGTHE **
 RAL-TL-90-166**EXTERIOR WALL SYSTEMS WITH EFIS
 FINISHES WAS BROUGHT UP. PLEASE PRODUCE THE TEST
 STANDARD THE NOTE AT THE BOTTOM OF THE SHEET NEEDS TO
 REFLECT THE DETAILS MEETING CODE COMPLIANCE.3 5/8?
 STUD WITH 1 LAYER OF 5/8? DRYWALL AND INSULATION HAS A
 STC RATING OF 46 NOT THE REQUIRED 50. SEE 1207.2.
  
 21) COMPLIED.
  
 22) SEMI-COMPLIED, PLEASE PROVIDE THE REQUIRED SIGNAGE
 FOR THE VAN ACCESSIBLE PARKING SPACES LOCATED WITHIN A
 PARKING STRUCTURE SHALL HAVE AN ADDITIONAL SIGN
 READING
 ** VAN ACCESSIBLE** MOUNTED BELOW THE SYMBOL OF
 ACCESSIBILITY. SUCH SIGNS SHALL NOT BE LOCATED SO THEY
 CAN NOT BE OBSCURED BY A VEHICLE PARKED IN THE SPACE.
  
 23) COMPLIED.
  
 24) WE ARE LOOKING FOR FOR A MANUFACTURERS SPEC NOT A
 SPEC NUMBER.) SHEET A2.03 H. C. LIFT PLEASE PROVIDE
 THE SPECS IN COMPLIANCE WITH:
 11-4.11 PLATFORM LIFTS (WHEELCHAIR LIFTS ). 11-4.11.1
 LOCATION.
 PLATFORM LIFTS (WHEELCHAIR LIFTS ) PERMITTED BY SECTION
 11-4.1 SHALL COMPLY WITH THE REQUIREMENTS OF SECTION
 11-4.11 .
 11-4.11.2 OTHER REQUIREMENTS.
 IF PLATFORM LIFTS (WHEELCHAIR LIFTS ) ARE USED, THEY
 SHALL COMPLY WITH SECTIONS 11-4.2.4 , 11-4.5 , 11-4.27
 , AND ASME A17.1, SAFETY CODE FOR ELEVATORS AND
 ESCALATORS , SECTION XX, 1990.
 11-4.11.3 ENTRANCE.
 IF PLATFORM LIFTS ARE USED THEN THEY SHALL FACILITATE
 UNASSISTED ENTRY, OPERATION, AND EXIT FROM THE LIFT IN
 COMPLIANCE WITH SECTION 11-4.11.2 .
 FAIR HOUSING : ANSI A117.1 ELEVATORS 4.10.
  
 25A-B) FAIR HOUSING GUIDELINE **PREFACE** NOTES THAT
 THE MANUAL (FAIR HOUSING GUIDELINE) USES TERMS SUCH AS
 RECOMMENDED, PREFERRED, SHOULD , COULD OR USES ITALICS
 THE DESIGNER MAY USE OTHER METHODS. SHEET A2.91DETAILS
 3& 6 BOTH INCORPORATE RAMPS TO TRY TO ACCOMPLISH THE
 INTENT OF FAIR HOUSING GUIDELINE. ONE OF THE ISSUES
 THAT WE SEE IS
 NOTE # 9. ATTACHED TO THIS REVIEW IS AN EXAMPLE OF THE
 DOCUMENT THAT WOULD NEED TO BE RECORDED TO ALLOW FUNDS
 TO BE AVAILABLE THROUGH ESCROW FOR ANYTIME IN THE
 FUTURE FOR ANY UNITS THAT MAY NEED TO BE CONVERTED FOR
 THE DISABLED. IT COULD POSSIBLY EFFECT EVERY SECONDARY
 DOOR (SLIDING GLASS DOORS) WITHIN THE ENTIRE PROJECT,
 SO FUNDS HAVE TO BE AVAILABLE FOR SUCH WORK TO BE
 ACCOMPLISHED AND NOT FINANCIALLY AFFECTING THE DISABLED
 PERSON MOVING INTO ANY UNIT.
  
 25C) DEPENDING ON THE ANSWER TO 25A-B, THE STRUCTURAL
 PLANS WILL ALSO NEED TO CORRELATE THEIR DETAIL SHEETS
 TO MEET THE REQUIREMENTS STATED ABOVE, FAIR HOUSING
 SECONDARY SLIDING GLASS DOORS.
  
 25D-E)COMPLIED.
  
 26-27) COMPLIED
  
 28) 2ND REQUEST,SHEET A2.03 ELEVATOR LOBBY DOORS ONE
 DOOR INDICATES A 20MIN RATING THE OTHER NONE. PLEASE
 SEE TABLE 715.3. THE 20 MIN AND ? HR FIRE PARTITIONS OR
 CORRIDOR WALLS REQUIRED BY SECTION 1016.1. THE MORE
 RESTRICTIVE ELEVATOR LOBBIES WOULD REQUIRE THE ? HR
 OPENING PROTECTIVE. SEE CODE COMMENTARY UNDER 709.5
 SMOKE BARRIERS STATING FIRE PARTITIONS, OTHER THAN
 CORRIDOR WALLS, ARE REQUIRED TO HAVE AN OPENING
 ASSEMBLY RATING OF 45 MINUTES IN ACCORDANCE WITH TABLE
 715.3. SEE LIFE SAFETY PLAN LS3 AND DOOR SCHEDULE
 A2.80.
 29-32) COMPLIED.
  
 33) 2ND REQUEST, A2.03 THE SAME ISSUE WITH THE GATE
 NEXT TO THE SYMBOL EOD, THIS GATE REQUIRES 18? ON THE
 LATCH SIDE. FAIR HOUSING TABLE 404.2.4.1, FIGURE
 404.2.1(A). RESPONSE INDICATED A REVISED SHEET AS
 REQUIRED BY SECTION 404.2.1 ?
  
 34-37) COMPLIED.
  
 38)2ND REQUEST,THE REVISED DETAIL STILL WILL HOLD
 2? AT THE OVERFLOW AND 6? AT THE DRAIN. IF THE MAXIMUM
 OF 4? IS HELD AT THE OVERFLOW, THEN 8? OF WATER WILL BE
 HELD AT THE ROOF DRAIN 16 FEET AWAY, WITH THE MINIMUM
 WATER LOCATED SHEET A2.05 DETAIL# 13 INDICATE AN
 EMERGENCY OVERFLOW, THE SITUATION IS THE WAY THE DETAIL
 IS DRAWN WITH A MINIMUM OF 4? BEFORE RAINWATER STARTS
 TO RUN INTO THE OVERFLOW, WHERE THE PLUGGED UP ROOF
 DRAIN IS THE WATER MAY 7? OR 8? DEEP DEPENDING ON THE
 LOCATION OF THE ROOF DRAIN FROM THE OVERFLOW. 1503.4.3
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT
 PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR
 PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4
 INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND
 SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED
 VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET
 SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING.
  
 39) COMPLIED.
  
 40) SHEET A.205 MAINTENANCE SHOP OR STORAGE AS
 INDICATED IN THE RESPONSE, PLEASE SEE DEFINITION OF
 PENTHOUSE 1509.2,THIS USAGE WILL CLASSIFY THIS AS A
 10 STORY BUILDING. ALSO CHANGE COVERSHEET TO REFLECT
 THE NEW STORY PLUS PROVIDE THE FLOOR LIVE LOADING FOR
 LIGHT STORAGE. STRUCTURAL SHEETS WILL ALSO NEED TO
 REFLECT THE ADDITIONAL LOADING.
  
 41-42)COMPLIED.
  
 43) THE NEW DETAILS INDICATES THE USE OF CONCRETE
 MOLDINGS. PLEASE PROVIDE ATTACHMENT DETAILS.
 ARCHITECTURAL TRIM THAT EXCEEDS 40 FEET (12 192 MM) IN
 HEIGHT ABOVE GRADE PLANE SHALL BE CONSTRUCTED OF
 APPROVED NONCOMBUSTIBLE MATERIALS AND SHALL BE SECURED
 TO THE WALL WITH METAL OR OTHER APPROVED NONCOMBUSTIBLE
 BRACKETS.1406.2.2
  
 44) COMPLIED.
  
 45A) 2ND REQUEST, SHEET A2.30 PRE-CAST CONC. MOLDING
 DETAIL 3 OF A3.09PLEASE INDICATE SLAB SIZES AND
 ANCHORAGE. . ARCHITECTURAL TRIM THAT EXCEEDS 40 FEET
 (12 192 MM) IN HEIGHT ABOVE GRADE PLANE SHALL BE
 CONSTRUCTED OF APPROVED NONCOMBUSTIBLE MATERIALS AND
 SHALL BE SECURED TO THE WALL WITH METAL OR OTHER
 APPROVED NONCOMBUSTIBLE BRACKETS.1406.2.2
  
 1405.5 ANCHORED MASONRY VENEER.ANCHORED MASONRY
 VENEER SHALL COMPLY WITH THE PROVISIONS OF SECTIONS
 1405.5 , 1405.6 , 1405.7 AND 1405.8 AND SECTIONS 6.1
 AND 6.2 OF ACI 530/ASCE 5/TMS 402.
 1405.5 ANCHORED MASONRY VENEER.
 1405.6 STONE VENEER
 1405.7 SLAB-TYPE VENEER
 DESIGNERS CAN?T JUST RESTATE THE CODE SECTION FOR CODE
 COMPLIANCE.
 45B)PLEASE SEE DETAIL 4 SHEET A8.05 AT WHAT HEIGHT IS
 THIS EFIS BAND LOCATED?
  
 46-49) COMPLIED.
  
 50) FIRE COMMAND ROOM: )FIRE COMMAND ROOM PLEASE
 PROVIDE COMPLIANCE WITH: 403.8 FIRE COMMAND . A FIRE
 COMMAND CENTER COMPLYING WITH SECTION 911 SHALL BE
 PROVIDED IN A LOCATION APPROVED BY THE FIRE
 DEPARTMENT.
  
 WHERE REQUIRED BY OTHER SECTIONS OF THIS CODE, A FIRE
 COMMAND CENTER FOR FIRE DEPARTMENT OPERATIONS SHALL BE
 PROVIDED. THE LOCATION AND ACCESSIBILITY OF THE FIRE
 COMMAND CENTER SHALL BE SEPARATED FROM THE REMAINDER OF
 THE BUILDING BY NOT LESS THAN A 1-HOUR
 FIRE-RESISTANCE-RATED FIRE BARRIER. THE ROOM SHALL BE A
 MINIMUM OF 96 SQUARE FEET (9 M 2 ) WITH A MINIMUM
 DIMENSION OF 8 FEET (2438 MM). A LAYOUT OF THE FIRE
 COMMAND CENTER AND ALL FEATURES REQUIRED BY THE SECTION
 TO BE CONTAINED THEREIN SHALL BE SUBMITTED FOR APPROVAL
 PRIOR TO INSTALLATION. THE FIRE COMMAND CENTER SHALL
 COMPLY WITH NFPA 72 AND SHALL CONTAIN THE FOLLOWING
 FEATURES.
 1.THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM
 UNIT.
 2.THE FIRE DEPARTMENT COMMUNICATIONS UNIT.
 3.FIRE DETECTION AND ALARM SYSTEM ANNUNCIATOR
 UNIT.
 4.ANNUNCIATOR UNIT VISUALLY INDICATING THE
 LOCATION OF THE ELEVATORS AND WHETHER THEY ARE
 OPERATIONAL.
 5.STATUS INDICATORS AND CONTROLS FOR AIR-HANDLING
 SYSTEMS.
 6.THE FIRE-FIGHTER?S CONTROL PANEL REQUIRED BY
 SECTION 909.16 FOR SMOKE CONTROL SYSTEMS INSTALLED IN
 THE BUILDING.
 7.CONTROLS FOR UNLOCKING STAIRWAY DOORS
 SIMULTANEOUSLY.
 8.SPRINKLER VALVE AND WATER-FLOW DETECTOR DISPLAY
 PANELS.
 9.EMERGENCY AND STANDBY POWER STATUS INDICATORS.
 10.A TELEPHONE FOR FIRE DEPARTMENT USE WITH
 CONTROLLED ACCESS TO THE PUBLIC TELEPHONE SYSTEM. 11.
 FIRE PUMP STATUS INDICATORS. SEE ELECTRICAL AND
 MECHANICAL COMMENTS THAT DEAL WITH THE FIRE PUMP. 12.
 SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL FLOOR
 PLAN AND DETAILING THE BUILDING CORE, MEANS OF EGRESS,
 FIRE PROTECTION SYSTEMS, FIRE-FIGHTING EQUIPMENT AND
 FIRE DEPARTMENT ACCESS.
 13.WORKTABLE.
 14.GENERATOR SUPERVISION DEVICES, MANUAL START AND
 TRANSFER FEATURES. SEE ELECTRICAL AND MECHANICAL
 COMMENTS ABOUT GENERATOR AND FUEL STORAGE.
 15.PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY
 REQUIRED BY OTHER SECTIONS OF THIS CODE.
  
  
 51-55) COMPLIED.
  
 56A) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE
 DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 ANDASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1
 M) ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 56B) WITH MULTIPLE PRODUCTS OF THE SAME TYPE LARGE
 MISSILE, SMALL MISSILE AND NON-MISSILE RATED, INTERIOR
 ZONES AND END ZONES A COLOR COORDINATED CHART ON THE
 S-12 & S-13 SHEETS WILL ONLY BE THE WAY TO DESIGNATE
 WHAT PRODUCT GOES WHERE WITH THE CORRECTNESS NEEDED FOR
 THIS PROJECT
  
 56C) THE STRUCTURAL S-12& S13 DO NOT ACCURATELY
 INDICATE THE END ZONES, THEY ARE TAKING THEM FROM
 AWNINGS PROTRUDING FROM THE BUILDING AND NOT THE
 CORNERS PLUS END ZONES ARE FIGURED USING 10 PERCENT OF
 THE LEAST HORIZONTAL DIMENSION ASCE 7-02, FIGURE 6-17
 NOTE
 8 (A).
  
  
 56D)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES,
 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING
 REPORTS, MISSING REPORTS ARE AS FOLLOWS:
 A) FIXED GLASS
 B) STOREFRONT GLASS: WINDOW WALL
 * CRAWFORD TRACY CORP PROVIDE FLORIDA
 COVERSHEETLARGE MISSILE 100+-
 * R.C. ALUMINUM PROVIDE FLORIDA COVERSHEET
 LMI , PICK A GLASS TYPE
 * YKK YHS-50 FS PROVIDE FLORIDA COVERSHEET
 PLUS THE BACK UP REPORT, TYPE OF
 MULLION AND GLAZING.
 C) OPERABLE WINDOWS : CASEMENT
 *RC ALUMINUM WINDOWS , PROVIDE THE FLORIDA
 COVERSHEET, THE BACKUP REPORT IS A
 MIAMI-DADE NOA GOOD FOR LARGE MISSILE+-
 80 PSF SEE LIMITATION TO SIZE
 * EFCO 2700 PROVIDE FLORIDA COVERSHEET,
 GOOD TO -135 SEE LIMITATION SIZE WIND
 ONLY NO MISSILE TESTING
 * EFCO PROVIDE FLORIDA COVERSHEET, UPDATE
 NOA TO THE 2004 FBC VERSION, SEE
 SIZE LIMITATION
  
 C) OPERABLE WINDOWS: HOPPER/ PROJECT OUT STYLE
 * EFCO PROVIDE FLORIDA COVERSHEET +90/-100 LMI/ SMI
 *YKK YOW H PROVIDE FLORIDA COVERSHEET
 ACTUAL CASEMENT
  
 D) MULLIONS HORIZONTAL & VERTICAL
 E) SKYLIGHTS
 F) GLASS BLOCK
 G) LOUVERS
 * 4 MANUFACTURES WERE SUBMITTED PICKED
 PICK ONE
 H) HOLLOW METAL DOORS/ ROOF HATCHES
 * CURRIES 3070 PROVIDE FLORIDA
 COVERSHEET, +-80
 * DAYBAR PROVIDE FLORIDA COVERSHEET,
 +-90 SINGLE
 I) GLASS DOORS SWING
 * EFCO D300/318 PROVIDE FLORIDA COVERSHEET
 LMI/SMI +- 60
 *YKK 35H PROVIDE FLORIDA COVERSHEET, LMI
 HIGHLIGHT CHARTS SIZES TO BE USED FOR
 PRESSURES
 J) OVERHEAD DOORS/ COIL DOORS
 * BEST PROVIDE FLORIDA COVERSHEET HIGHLIGHT
 DOOR WIDTH TABLE 1 FOR PRESSURES
 K) SLIDING GLASS DOORS
 * EFCO 3005PROVIDE FLORIDA COVERSHEET,
 HIGHLIGHT CHARTS FOR REINFORCEMENT, AND
 * KAWNEER HPX PROVIDE FLORIDA COVERSHEET,
 +100/-125PRESSURES
 L) AUTOMATIC HORIZONTAL SLIDING DOORS
 M)PANEL WALL SYSTEM: SOFFITS, EFIS
 N) ROOFING ASSEMBLIES TO MANY TO LIST , ONCE
 CONTRACTOR HAS PICKED PRODUCT AND BEEN
 REVIEWED BY THE DESIGNER OF RECORD WE THEN WILL
 REVIEW THE DOCUMENTS SUBMITTED.
 4 DIFFERENT ROOF TILE MANUFACTURES SUBMITTED
 SARNAFIL 60 PAGE ROOF SUBMITTAL WITH NO SUB-SYSTEM
 HIGHLIGHTED AS TO WHICH WILL BE
 INSTALLED ON THIS STRUCTURE
 2 INSULATION BOARD COMPANIES
 O) PANEL WALL SYSTEMS- SIDING- NO PRODUCT
 APPROVALS
 57)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA PRODUCT
 APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 58) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 59) THIS NEXT ISSUE HAS BECOME A LARGE ISSUE ON
 PROJECTS!!!! WINDOWS NOT BEING LABELED.
 TESTING AND LABELING. 1714.5.2.1EXTERIOR WINDOWS AND
 GLASS DOORS SHALL BE TESTED BY AN APPROVED INDEPENDENT
 TESTING LABORATORY, AND SHALL BE LABELED WITH AN
 APPROVED LABEL IDENTIFYING THE MANUFACTURER,
 PERFORMANCE CHARACTERISTICS AND APPROVED PRODUCT
 CERTIFICATION AGENCY, TESTING LABORATORY, EVALUATION
 ENTITY OR MIAMI-DADE PRODUCT APPROVAL TO INDICATE
 COMPLIANCE WITH THE REQUIREMENTS OF ONE OF THE
 FOLLOWING SPECIFICATIONS:ANSI/AAMA/NWWDA 101/I.S.2 OR
 101/I.S. 2/NAFS OR TAS 202 (HVHZ SHALL COMPLY WITH TAS
 202 UTILIZING ASTME E 1300 OR SECTION 2404 .
 GLASS STRENGTH: DETERMINATION OF LOAD RESISTANCE OF
 GLASS FOR SPECIFIED LOADS OF PRODUCTS TESTED AND
 CERTIFIED IN ACCORDANCE WITH SECTION 1714.5.2.1 SHALL
 BE DESIGNED TO COMPLY WITH ASTM E 1300 IN ACCORDANCE
 WITH SECTION 2404 .
  
 60)SHEET A2.90; THIS SHEET SHOWS MULLIONS USED BOTH
 VERTICALLY AND HORIZONTALLY, BEFORE A REVIEW OF THE
 PRODUCT APPROVALS WILL BE ABLE TO BEGIN THE DESIGN TEAM
 WILL NEED TO HIGHLIGHT WHICH MULLION WILL BE THE ONE
 THAT WILL CONTINUE FROM A STRUCTURAL FRAMING MEMBER TO
 THE OPPOSITE SIDE.
  
 1714.5.5 MULLIONS OCCURRING BETWEEN INDIVIDUAL WINDOW
 AND GLASS DOOR ASSEMBLIES. 1714.5.5.1 MULLIONS.
 MULLIONS, OTHER THAN MULLIONS WHICH ARE AN INTEGRAL
 PART OF A WINDOW OR GLASS DOOR ASSEMBLY TESTED AND
 LABELED IN ACCORDANCE WITH SECTION 1714.5.2.1 , SHALL
 BE TESTED BY AN APPROVED TESTING LABORATORY OR BE
 ENGINEERED IN ACCORDANCE WITH ACCEPTED ENGINEERING
 PRACTICE. BOTH METHODS SHALL USE PERFORMANCE CRITERIA
 CITED IN SECTIONS 1714.5.5.2 , 1714.5.5.3 AND
 1714.5.5.4 .
  
 1714.5.5.2 LOAD TRANSFER.
 MULLIONS SHALL BE DESIGNED TO TRANSFER THE DESIGN
 PRESSURE LOADS APPLIED BY THE WINDOW AND DOOR
 ASSEMBLIES TO THE ROUGH OPENING SUBSTRATE.
  
 1714.5.5.3 DEFLECTION.
 MULLIONS SHALL BE CAPABLE OF RESISTING THE DESIGN
 PRESSURE LOADS APPLIED BY THE WINDOW AND DOOR
 ASSEMBLIES TO BE SUPPORTED WITHOUT DEFLECTING MORE THAN
 L/175, WHERE L IS THE SPAN OF THE MULLION IN INCHES.
  
 1714.5.5.4 STRUCTURAL SAFETY FACTOR.
 MULLIONS SHALL BE CAPABLE OF RESISTING A LOAD OF
 ONE-AND-ONE-HALF TIMES THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW AND DOOR ASSEMBLIES TO BE
 SUPPORTED WITHOUT EXCEEDING THE APPROPRIATE MATERIAL
 STRESS LEVELS. IF TESTED BY AN APPROVED LABORATORY, THE
 ONE AND ONE-HALF TIMES THE DESIGN PRESSURE LOAD SHALL
 BE SUSTAINED FOR 10 SECONDS, AND THE PERMANENT
 DEFORMATION SHALL NOT EXCEED 0.4 PERCENT OF THE MULLION
 SPAN AFTER THE ONE-AND-ONE-HALF TIMES DESIGN PRESSURE
 LOAD IS REMOVED.
  
 61) 2ND REQUEST,ANOTHER BIG ISSUE WITH PRODUCT
 APPROVALS THAT THE DESIGN TEAM WILL SIGN OFF ON
 REVIEWED IS THEY WILL NOT ?HIGHLIGHT? WHICH GLAZING
 SYSTEM THEY HAVE APPROVED AND THE CORRESPONDING
 PRESSURES, NOR WILL THEY HIGHLIGHT IN SLIDING GLASS
 DOOR SYSTEMS WHICH
 RAIL SYSTEM WILL BE USED. THERE ARE 4 DESIGN CRITERIA
 USUALLY IN THESE PACKAGES. ONE WITH NO REINFORCEMENT,
 LIGHT , MEDIUM AND HEAVY REINFORCEMENT HIGHLIGHT WHICH
 SYSTEM IS TO BE USED.
  
 62)ROOF REPORT WAS SUBMITTED IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
 _X__ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT.
 (FLAT ROOF)
 ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH. _X__
 CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE USED.
 _X__ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE
 _2&3__ .
 SINCE THE ROOFING REPORT DOESN?T HAVE THE SUBSYSTEM
 HIGHLIGHTED THE NEXT 2 ITEMS ARE HIGHLIGHTED._X__ THE
 SYSTEM PROVIDED STATESLIMITATION# 7, SHOULD THE
 FASTENERRESISTANCE BE LESS THAN THAT REQUIRED, AS
 DETERMINED BY THEBUILDING OFFICIAL, A REVISED
 FASTENERSPACING, PREPARED , SIGNED AND SEALED BY A
 FLORIDA REGISTEREDPROFESSIONAL ENGINEER,
 REGISTEREDARCHITECT OR REGISTERED ROOF CONSULTANT
 MAY BE SUBMITTED.
 _X__THE SYSTEM PROVIDED INDICATESLIMITATION#
 9, NO ENHANCEDFASTENING ALLOWED.
  
 63) SLOPED ROOF (7/ A8.06) INDICATES THE USE OF EITHER
 CLAY TILE OR CONCRETE TILE. SUBMIT REPORT AND HIGHLIGHT
 WHICH TYPE OF SYSTEM WILL BE USED TO RESIST THE MOMENT
 OF UPLIFT?
  
 64)PLEASE SUBMIT INFORMATION ON HOW THE RIDGE TILE
 ARE GOING TO BE SECURED TO THE ROOFING SYSTEM. 1507.3.7
 ATTACHMENT.
 CLAY AND CONCRETE ROOF TILES SHALL BE FASTENED IN
 ACCORDANCE WITH SECTION 1609 OR IN ACCORDANCE WITH
 FRSA/RTI INSTALLATION MANUAL.
 1507.3.8 APPLICATION.
 TILE SHALL BE APPLIED ACCORDING TO THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS OR RECOMMENDATIONS OF THE
 FRSA/RTI 07320- 04.
  
 65) A3.30 INDICATES THE USE OF METAL PANEL ROOFING
 PLEASE PROVIDE ROOFING REPORT.
  
 66)SHIMS FOR WINDOWS AND DOORS, SHEET A2.93 DETAIL#
 9.
 1714.5.4.3 WOOD OR OTHER APPROVED FRAMING MATERIALS.
 WHERE THE FRAMING MATERIAL IS WOOD OR OTHER APPROVED
 FRAMING MATERIAL, WINDOW AND GLASS DOOR ASSEMBLIES
 SHALL BE ANCHORED THROUGH THE MAIN FRAME OR BY JAMB
 CLIP OR SUBFRAME SYSTEM OR THROUGH THE FLANGE IN
 ACCORDANCE WITH THE MANUFACTURER?S PUBLISHED
 INSTALLATION INSTRUCTIONS. SHIMS SHALL BE MADE FROM
 MATERIALS CAPABLE OF SUSTAINING APPLICABLE LOADS,
 LOCATED AND APPLIED IN A THICKNESS CAPABLE OF
 SUSTAINING APPLICABLE LOADS. ANCHORS SHALL BE PROVIDED
 TO TRANSFER LOAD FROM THE WINDOW OR DOOR FRAME TO THE
 ROUGH OPENING SUBSTRATE.
  
 67-69) COMPLIED.
  
 70) CODE BACK UP STATEMENT FOR 56D) (H) MULTIPLE
 MANUFACTURERS PRODUCTS SUBMITTED,
 EXTERIOR DOOR ASSEMBLIES NOT COVERED BY SECTION
 1715.4.2 OR SECTION 1714.5.3.1 SHALL BE TESTED FOR
 STRUCTURAL INTEGRITY IN ACCORDANCE WITH ASTM E 330
 PROCEDURE A, AT A LOAD OF 1.5 TIMES THE REQUIRED DESIGN
 PRESSURE LOAD. THE LOAD SHALL BE SUSTAINED FOR 10
 SECONDS WITH NO PERMANENT DEFORMATION OF ANY MAIN FRAME
 OR PANEL MEMBER IN EXCESS OF 0.4 PERCENT OF ITS SPAN
 AFTER THE LOAD IS REMOVED. HIGH-VELOCITY HURRICANE
 ZONES SHALL COMPLY WITH TAS 202. AFTER EACH SPECIFIED
 LOADING, THERE SHALL BE NO GLASS BREAKAGE, PERMANENT
 DAMAGE TO FASTENERS, HARDWARE PARTS, OR ANY OTHER
 DAMAGE WHICH CAUSES THE DOOR TO BE INOPERABLE.
 THE MINIMUM TEST SIZES AND MINIMUM DESIGN PRESSURES
 SHALL BE AS INDICATED IN TABLE 1714.5.3 .
  
 71-73COMPLIED, WERE INFORMATIONAL FOR AWNINGS THAT ARE
 REQUIRED UNDER SEPARATE PERMIT.
  
 74-78) COMPLIED.
  
 79) )2ND REQUEST, A8.05 EXTERIOR SOFFITS, VARIOUS
 DETAILS INDICATE THE SOFFIT OR DROPPED CEILING, THERE
 IS NO INFORMATION ON THE TYPE OF STUDS, SPACING,
 ATTACHMENT TO DECK ABOVE OR TYPE OF LATH AND SPACING OF
 HORIZONTAL FRAMING MEMBERS IS THE WIRE LATH TIED UP OR
 SCREWED IN PLACE?
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 80) 2ND REQUEST,A8.06 DETAIL# 11 INDICATES THE USE OF
 5V METAL CRIMP SIDING DIRECTLY APPLIED TO THE METAL
 FRAMING, WHAT TYPE OF BRACING IS TO BE USED? PLEASE
 PROVIDE THE PRODUCT APPROVAL INDICATING THIS IS
 STRUCTURAL SHEATHING NO SHEATHING REQUIRED. THIS IS A
 PRODUCT THAT IS CONSIDERED COMPONENTS AND CLADDING BY
 RULE 9B-72 AND WILL BE ADDRESSED BEFORE A PERMIT WILL
 BE ISSUED. EVEN ALL METAL BUILDINGS WITH METAL SIDING
 AND ROOFING ARE REQUIRED TO PROVIDE PRODUCT APPROVALS
 WITH A THIRD PARTY QUALITY ASSURANCE PROGRAM APPROVED
 THROUGH THE STATE. THIS COMMENT ALSO REVERTS BACK TO
 COMMENTS
 56D,57 & 58.
  
 81)COMPLIED.
  
 82) SHEET A9.01:
  
 82A) 2ND REQUEST, YOU CAN NOT JUST QUOTE CODE SECTION
 AND SAY THIS SATISFIES THE REQUEST, 106.1.1, &
 106.1.2*. A9.01 VARIOUS DETAILS INDICATE A DESIGN SOUND
 TEST NUMBER, PLEASE INDICATE THE SOUND TRANSMISSION
 CLASS NUMERICALLY, 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION ASSEMBLIES
 FOR PIPING; ELECTRICAL DEVICES; RECESSED CABINETS;
 BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR EXHAUST
 DUCTS SHALL BE SEALED, LINED, INSULATED OR OTHERWISE
 TREATED TO MAINTAIN THE REQUIRED RATINGS. THIS
 REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT ENTRANCE
 DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT FITTING TO
 THE FRAME AND SILL.
  
 82B)2ND REQUEST, YOU CAN NOT JUST QUOTE CODE SECTION
 AND SAY THIS SATISFIES THE REQUEST, 106.1.1, &
 106.1.2*. PLEASE PROVIDE COMPLIANCE WITH SOUND
 TRANSFERENCE THROUGH THE FLOOR SYSTEM?
 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 83) A9.01 NOTES 2-4 ALL DEAL WITH THE BACKING BENEATH
 MARBLE AND TILE NOTE 2 INDICATES THE USE OF A
 CEMENTITITOUS BACKER BOARD AND NOTE 3 INDICATES THE USE
 OF GLASS MAT WATER RESISTANT BOARD BUT NOTE 4 INDICATES
 TILE BACKER BOARD, WHAT TYPE?
  
 84-86) COMPLIED.
  
  
  
  
 87) PROVISO: 87) ADJACENT TO EXCAVATIONS.
 EVERY EXCAVATION ON A SITE LOCATED 5 FEET (1524 MM) OR
 LESS FROM THE STREET LOT LINE SHALL BE ENCLOSED WITH A
 BARRIER NOT LESS THAN 6 FEET (1829 MM) HIGH. WHERE
 LOCATED MORE THAN 5 FEET (1524 MM) FROM THE STREET LOT
 LINE, A BARRIER SHALL BE ERECTED WHEN REQUIRED BY THE
 BUILDING OFFICIAL. BARRIERS SHALL BE OF ADEQUATE
 STRENGTH TO RESIST WIND PRESSURE AS SPECIFIED IN
 CHAPTER 16 .
  
 88) COMPLIED.
  
 89) SECOND REQUEST,S-8 INDICATES A TABLE OF CONCRETE
 COVERAGE HOW DOES THIS TABLE COMPLY WITH TABLE 601 THE
 HOUR RATINGS FOR STRUCTURAL FRAMES COLUMNS, GIRDERS OR
 BEAMS, FLOOR AND ROOF SLABS? THIS TABLE IS MINIMUM
 CONCRETE COVERAGE WHEN CONCRETE IS EXPOSED TO EARTH
 TABLE 1907.1.
  
 90) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 91) A2.3.2 THE HANDICAPPED RAMP PLAN DOESNOT INDICATE
 THE REQUIRED 6?-0? BOTTOM LANDING. 11-4.8.4.(2)
 LANDINGS. ALL LANDINGS ON RAMPS SHALL NOT BE LESS THAN
 60"
 CLEAR, & THE BOTTOM OF EACH RAMP SHALL HAVE NOT LESS
 THAN 72" OF STRAIGHT & LEVEL CLEARANCE.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-05-03 Cont ID  
Sent By jwitmer Date 2007-05-03 Time 12:06 Rev Time 39.00
Received By jwitmer Date 2007-05-03 Time 12:06 Sent To  
Notes
2007-05-03 12:09:55 
 DATURA & OLIVE
 RESIDENCE
 9 STORY R-2, MERCANTILE& S-2
  
 BUILDING PLAN REVIEW
 PERMIT: 07020735
 ADDRESS: 302 DATURA ST
 CONT: PEGASUS CONSTRUCTION
 TEL: (954)946-4227
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
 2)FBC 1802.2.1 QUESTIONABLE SOILS,
 WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION
 BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 . REPORTS
 HAVE COPIED SIGNATURES, NOT ORIGINALS.
  
 3)FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 4)WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION
 SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY S. 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE. CONTACT HAROLD PISKURA MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561) 805-6711 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 5)W.P.B. AMENDMENT 105.13.4.4 ALL PLANS FOR THE
 BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY
 THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 6)FL S. S. 553.71(7) " THRESHOLD BUILDING" MEANING
 ANY BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT
 IN HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DENIED IN THE FLORIDA BUILDING CODE
 WHICH EXCEEDS 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS. 105.13.1 THE
 ENFORCING AGENCY SHALLREQUIRE A SPECIAL INSPECTOR TO
 PERFORM STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING
 PURSUANT TO A STRUCTURALINSPECTION PLAN PREPARED BY
 THE ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE
 ISSUANCE
 OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A
 THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE
 ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED
 DOCUMENTS.
  
 7) 109.3.10*IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PREFORMED IN A
 MANNERSO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS
 OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATE FROM A LICENSED ENGINEER SHALL BE SUBMITTED
 TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL OF THE
 FINAL INSPECTION.
  
  
 8 ) 109.3.10.1 HURRICANE PROTECTION.IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER REMOVED FROM THE
 CONSTRUCTION SITE OR SECURED IN SUCH A MANNER AS TO
 MINIMIZE THE DANGER OF SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS CAUSING DAMAGE TO PERSONS OR
 PROPERTY FROM HIGH WINDS. ANY PERSONS WHO FAIL TO
 COMPLY TO REMOVE OR SECURE THE CONSTRUCTION MATERIALS
 EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
 9) THE ARCHITECTURAL COVERSHEET UNDER THE PROJECT DATA
 SUMMARY:
 9A) PLANS ARE DESIGNED UNDER THE 2004 FBC, PLANS
 SUBMITTED TO THE CITY AFTER DEC. 8, 2006 ARE TO BE
 DESIGNED TO THE 2006 FBC.
  
 9B) PLANS ALSO INDICATE THIS IS TO BE A 8 STORY
 BUILDING. THE SO CALLED MEZZANINE LEVEL DOES NOT MEET
 THE DEFINITION OF A MEZZANINE THIS IS THE SECOND STORY,
 CREATING A NINE STORY BUILDING.
  
 9C)PLANS FAIL TO IDENTIFY WHAT TYPE BUILDING TYPE
 THIS BUILDING WAS DESIGNED TOO? TABLE 503/ TABLE 601?
  
 10) SHEET A0.02 GENERAL NOTE# 15 REFERS TO THE 2001
 FBC, PLEASE MAKE THE CORRECTION.
  
 11) A2.01 THE PLANS TO HAVE OPENINGS IN THE PARKING
 GARAGE ON THE FIRST AND SECOND FLOOR
 (MEZZANINE LEVEL) OF THE PARKING GARAGE ON THE SOUTH
 WALL. PLEASE SEE TABLE 602 FOR TYPE 1A & 1B BUILDINGS
 REQUIRE 3 HR RATED WALLS BASED ON FIRE SEPARATION AND
 TABLE 704.8 FOR UNPROTECTED OPENINGS 0-3? FROM THE
 PROPERTY LINE ARE NOT PERMITTED. FOOTNOTE ?G? ALLOWS
 OPENINGS WHEN THE EXTERIOR BEARING WALLS, EXTERIOR NON
 BEARING WALLS AND EXTERIOR STRUCTURAL FRAME ARE NOT
 REQUIRED TO BE FIRE-RESISTANCE RATING.SEE LOUVERED
 OPENINGS IN THE SOUTH WALL AND OPENING ?B? EAST WALL.
 704.8.2 FIRST STORY.
 IN OCCUPANCIES OTHER THAN GROUP H, UNLIMITED
 UNPROTECTED OPENINGS ARE PERMITTED IN THE FIRST STORY
 OF EXTERIOR WALLS FACING A STREET THAT HAVE A FIRE
 SEPARATION DISTANCE OF GREATER THAN 15 FEET (4572 MM),
 OR FACING AN UNOCCUPIED SPACE. THE UNOCCUPIED SPACE
 SHALL BE ON THE SAME LOT OR DEDICATED FOR PUBLIC USE,
 SHALL NOT BE LESS THAN 30 FEET (9144 MM) IN WIDTH, AND
 SHALL HAVE ACCESS FROM A STREET BY A POSTED FIRE LANE
 IN ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE .
  
 12)SHEET A9.02 MAKES REFERENCE TO TABLE 709.3.1 FOR
 EQUIVALENT THICKNESS OF MASONRY UNITS BUT THIS TABLE IS
 REFERENCED UNDER THE FBC 2001 CODE, PLEASE CORRECT.
  
 13THE SOUTH &EAST CORNERS OF THE PARKING GARAGE APPEAR
 TO BE LESS THAN 3?-0? FROM THE PROPERTY , PLEASE
 PROVIDE THE EQUIVALENT THICKNESS OF THE CONCRETE BLOCK
 AND HR RATING?
 TABLE 721.3.2.
  
 14) A2.01INDICATES THE USE OF CAR LIFTS. PLEASE
 PROVIDE MANUFACTURERS SPECS ON THESE UNITS, ADDITIONAL
 COMMENTS MAY APPEAR ON LATTER REVIEWS WITH ADDITIONAL
 INFORMATION.
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 15) THIS COMMENT IS COMMON TO MANY SHEETS, THE PLANS
 FAIL TO IDENTIFY VARIOUS COMMON DOORS THROUGH OUT THE
 PROJECT, PLEASE LABEL DOORS TO IDENTIFY FOR REQUIRED
 DOOR RATINGS.
 106.1.2.* ADDITIONAL INFORMATION REQUIRED, TABLE 715.3
 ETC.
  
 16) A2.01 STAIRWAY# 3 IS INDICATED AS PART OF THE POOL
 DECK MEANS OF EGRESS PLEASE SEE:
 1022.5 LOCATION.EXTERIOR EXIT RAMPS AND STAIRWAYS
 SHALL BE LOCATED IN ACCORDANCE WITH SECTION 1023.3 .
 1023.3 EXIT DISCHARGE LOCATION.EXTERIOR BALCONIES,
 STAIRWAYS AND RAMPS SHALL BE LOCATED AT LEAST 10 FEET
 (3048 MM) FROM ADJACENT LOT LINES AND FROM OTHER
 BUILDINGS ON THE SAME LOT UNLESS THE ADJACENT BUILDING
 EXTERIOR WALLS AND OPENINGS ARE PROTECTED IN ACCORDANCE
 WITH SECTION 704 BASED ON FIRE SEPARATION DISTANCE.
  
 17) A2.01 STAIRS THAT ARE LOCATED NEXT TO PARKING
 SPACE# 22 INDICATE THE LOWER LANDING OR GARAGE FLOOR AT
 12.5? AND THE TOP LANDING AT 13.5?, PLEASE SEE
 1003.5.2
 WHERE CHANGE IN ELEVATION OF 12 INCHES (305 MM) OR LESS
 OCCURS IN EXIT ACCESS CORRIDORS, EXITS AND EXIT
 DISCHARGE, RAMPS COMPLYING WITH1010 SHALL BE
 PROVIDED.
 1003.5.3 ACCESSIBILITY.
 FOR ACCESSIBILITY PROVISIONS RELATED TO CHANGES IN
 LEVELS, SEE SECTION 11-4.3.8 .
  
 REQUIREMENT2. ACCESSIBLE AND USABLE PUBLIC AND COMMON
 USE AREAS.
  
 SECTION 100.205(C)(1) PROVIDES THAT COVERED MULTIFAMILY
 DWELLINGS WITH A BUILDING ENTRANCE ON AN ACCESSIBLE
 ROUTE SHALL BE DESIGNED IN SUCH A MANNER THAT THE
 PUBLIC AND COMMON USE AREAS ARE READILY ACCESSIBLE TO
 AND USABLE BY HANDICAPPED PERSONS.
  
 GUIDELINE
  
 THE FOLLOWING CHART IDENTIFIES THE PUBLIC AND COMMON
 USE AREAS THAT SHOULD BE MADE ACCESSIBLE, CITES THE
 APPROPRIATE SECTION OF THE ANSI STANDARD, AND DESCRIBES
 THE APPROPRIATE APPLICATION OF THE SPECIFICATIONS,
 INCLUDING MODIFICATIONS TO THE REFERENCED STANDARD.
 FAIR HOUSING 4.3(D).
  
 18) SHEET A2.01 THE PROPERTY LINE IS NOT INDICATED ON
 THIS PORTION OF THE BUILDING THERE MAY OR MAY NOT BE
 PROBLEMS AS FAR AS TABLE 602AND THE AMOUNT OF OPENINGS
 THAT ARE ALLOWED. TABLE 704.8.
  
 19)THE EAST END OF THE BUILDING DOESN?T PROVIDE THE
 ELEVATION OF THE FINISHED SIDEWALKS,
 THERE MAY BE A RAMPED EXIT PASSAGEWAY FROM STAIR TOWER
 # 1 IF THE RAMP DOESN?T HAVE SLOPE GREATER THAN 1:20 IT
 IS TRULY A RAMP AND THE ELEVATION CHANGE WOULD NEED TO
 BE KNOWN?
  
 20) SHEET A2.01 DOESN?T PROVIDE ANY HOURLY RATING ON
 ANY WALLS. PLEASE PROVIDE WALL IDENTIFICATION TAGS FOR
 ALL WALLS, SHAFTS OCCUPANCY SEPARATION, ETC SEE 707.4,
 TABLE 302.3.2.
  
 21)SHEET A2.01 THERE ARE TWO ABBREVIATIONS THAT OCCUR
 ON THE VARIOUS DECKS
 (HP) AND (LP) THAT ARE NOT FOUND ON A0.02 ABBREVIATION
 SHEET? 106.1.2*
 ADDITIONAL INFORMATION REQUIRED.
  
 22) PLEASE PROVIDE INFORMATION FOR THE HANDICAPPED VAN
 PARKING SPACES, PROVIDE
 THE 98? CLEAR HEIGHT, ENTRY AND EXIT PATH FOR AN
 ACCESSIBLE VAN? 11-4.1.2(5)(B)
 IN PARKING STRUCTURES, ONE IN EVERY EIGHT
 ACCESSIBLE SPACES, BUT NOT LESS THAN ONE, SHALL BE ?VAN
 ACCESSIBLE? AND SHALL BE DESIGNED AS REQUIRED BY
 SECTION 11-4.6.3 . THE VERTICAL CLEARANCE AT SUCH
 SPACES SHALL COMPLY WITH SECTION 11-4.6.5 . ALL SUCH
 SPACES MAY BE GROUPED ON ONE LEVEL OF A PARKING
 STRUCTURE. WHEN SUCH SPACES ARE PROVIDED IN A PARKING
 STRUCTURE AND ONLY ONE IN EIGHT MEET THE HEIGHT
 REQUIREMENT OF SECTION 11-4.6.5 , THEY SHALL BE
 DESIGNATED AS REQUIRED BY SECTION 11-4.6.4 .
  
 23)SHEET A2.02 (COMMON TO ALL FLOORS) THIS PLAN
 DOESN?T INDICATE DOOR ORWALL TYPES NOR THE HR RATING
 OF SUCH SYSTEMS. WHEN YOU LOOK AT THE LIFE SAFETY PLAN
 THERE ARE WALL RATINGS SOME DOORS BUT THERE IS NO
 NOMENCLATURE TO THE TYPE OF ROOM? 106.1.2* ADDITIONAL
 INFORMATION REQUIRED.
 302.3.2, 707,708 & TABLE 715.3.
  
 24) SHEET A2.03 H. C. LIFT PLEASE PROVIDE THE SPECS IN
 COMPLIANCE WITH:
 11-4.11 PLATFORM LIFTS (WHEELCHAIR LIFTS ). 11-4.11.1
 LOCATION.
 PLATFORM LIFTS (WHEELCHAIR LIFTS ) PERMITTED BY SECTION
 11-4.1 SHALL COMPLY WITH THE REQUIREMENTS OF SECTION
 11-4.11 .
 11-4.11.2 OTHER REQUIREMENTS.
 IF PLATFORM LIFTS (WHEELCHAIR LIFTS ) ARE USED, THEY
 SHALL COMPLY WITH SECTIONS 11-4.2.4 , 11-4.5 , 11-4.27
 , AND ASME A17.1, SAFETY CODE FOR ELEVATORS AND
 ESCALATORS , SECTION XX, 1990.
 11-4.11.3 ENTRANCE.
 IF PLATFORM LIFTS ARE USED THEN THEY SHALL FACILITATE
 UNASSISTED ENTRY, OPERATION, AND EXIT FROM THE LIFT IN
 COMPLIANCE WITH SECTION 11-4.11.2 .
 FAIR HOUSING : ANSI A117.1 ELEVATORS 4.10.
  
 25)SHEET A2.03: INDICATES DETAIL 7 OF A3.31 TYPICAL
 OF LANAI LEVEL SHEET A2.91 DETAILS
 7 & 8. THESE DETAILS ARE COMMON TO ALL FLOORS, THEY DO
 NOT MEET FAIR HOUSING REQUIREMENTS FOR SECONDARY
 DOORS.
  
 25A) SEE DETAIL 7 & 8 SHEET A2.03, THE SLIDING GLASS
 DOOR TRACK ASSEMBLY AS SHOWN DOES NOT MEET FAIR HOUSING
 GUIDELINES,FOR SECONDARY DOORS (SLIDING GLASS DOORS)
 THE GUIDELINE SPECIFY THAT THE THRESHOLDS AT THESE
 DOORS SHALL BE NO HIGHER THAN ? ?.THE GUIDELINES
 FURTHER STATE THAT CHANGES IN LEVEL AT THESE LOCATIONS
 MUST BE BEVELED WITH A SLOPE NO GREATER THAN 1:2.
  
 25B) FAIR HOUSING DOOR AT CONCRETE LANDINGS THE MAXIMUM
 ALLOWABLE CHANGE IN LEVEL AT EXTERIOR SLIDING GLASS
 DOORS (SECONDARY ENTRANCE) TO BALCONY OR PATIO WILL BE
 4 INCHES TO THE FINISH DECK.
 NOTE: INCORPORATE THE HEIGHT OF THE HIGH RISE TRACK
 INTO THE DESIGN CRITERIA.
  
 25C) THE STRUCTURAL PLANS WILL ALSO NEED TO CORRELATE
 THEIR DETAIL SHEETS TO MEET THE REQUIREMENTS STATED
 ABOVE, FAIR HOUSING SECONDARY SLIDING GLASS DOORS.
  
 25D) THE TRACK DETAIL ALSO INDICATES THAT THE TRACK IS
 TO BE SET IN LEVELING GROUT. ALL PRODUCT APPROVALS WILL
 REQUIRE MECHANICAL FASTENING OF TRACK INTO THE MAIN
 STRUCTURE.
  
 25E) SHEET A2.91 NOTE# 5 INDICATES PLANS WILL MEET ALL
 WIND REQUIREMENTS OF THE STD. BUILDING CODE AND PALM
 BCH CTY. THE LAST STANDARD BUILDING CODE WAS THE 1997
 STANDARD BUILDING CODE. CURRENTLY ALL OF FLORIDA IS
 UNDER THE 2004 FLORIDA BUILDING CODE WITH 2006
 REVISIONS. THERE ARE NO PALM BCH CTY. AMENDMENTS.
 PLEASE CORRECT.
  
 26)SHEET A2.03 ( COMMON TO ALL FLOORS)THIS PLAN
 INDICATE NO DOOR ORWALL TYPES NOR THE HR RATING OF
 SUCH SYSTEMS. WHEN YOU LOOK AT THE LIFE SAFETY PLAN
 THERE ARE WALL RATINGS SOME DOORS BUT THERE IS NO
 NOMENCLATURE TO THE TYPE OF ROOM? 106.1.2* ADDITIONAL
 INFORMATION REQUIRED.
 302.3.2, 707,708 & TABLE 715.3.
  
 27) SHEET A2.03 ELEVATOR LOBBY INDICATES THE TWO DOORS
 ON HOLD OPEN DEVICES, PLEASE PROVIDE INFORMATION ON
 THESE DEVICES, HOW THEY WILL PERFORM ONCE THE SMOKE
 ANNOUNCES
 SMOKE.
  
 28) SHEET A2.03 ELEVATOR LOBBY DOORS ONE DOOR INDICATES
 A 20MIN RATING THE OTHER NONE. PLEASE SEE TABLE 715.3.
 THE 20 MIN AND ? HR FIRE PARTITIONS OR CORRIDOR WALLS
 REQUIRED BY SECTION 1016.1. THE MORE RESTRICTIVE
 ELEVATOR LOBBIES WOULD REQUIRE THE ? HR OPENING
 PROTECTIVE. SEE CODE COMMENTARY UNDER 709.5 SMOKE
 BARRIERS STATING FIRE PARTITIONS, OTHER THAN CORRIDOR
 WALLS, ARE REQUIRED TO HAVE AN OPENING ASSEMBLY RATING
 OF 45 MINUTES IN ACCORDANCE WITH TABLE 715.3. SEE LIFE
 SAFETY PLAN LS3
  
 29) SEE LS-3 & LS-4 DOORS SWING OPPOSITE WAYS 3TH FLOOR
 VERSES FLOORS ABOVE?
 OCCUPANT LOADS GREATER THAN 50 SHALL SWING IN THE
 DIRECTION OF TRAVEL TO AN EXIT.1008.1.2.
  
 30) SEE LS-3 THE TRASH CHUTE ACCESS ROOM DOOR INDICATES
 A FIRE RATING NOT DEPICTED IN THE LIFE SAFETY LEGEND ?
 707.13.3? HR OPENING PROTECTIVE REQUIRED.
  
 31) SEE LS-3 TRY CALCULATIONS FOR THE POOL DECK AND
 APPROX 2446 SQ FT WITH THE OTHER LOADS A TOTAL OCCUPANT
 LOAD OF 116 REQUIRING THE ENTRY DOOR TO BE AN IN SWING
 DOOR 1008.1.2.
  
 32)A2.03 THE LANAI FOYER DOOR APPEARS TO BE MISSING
 THE 18? REQUIRED ON THE PULL SIDE
 FAIR HOUSING ANSI 117.1TABLE 404.2.4.1 . FIGURE
 404.2.1(A).
  
 33) A2.03 THE SAME ISSUE WITH THE GATE NEXT TO THE
 SYMBOL EOD, THIS GATE REQUIRES 18?
 ON THE LATCH SIDE. FAIR HOUSING TABLE 404.2.4.1, FIGURE
 404.2.1(A).
  
 34) SHEET A2.03 THERE ARE THREE PAIR OF DOORS THAT LEAD
 INTO THE RECREATION ROOM, THEY ARE NOR FOUND ON THE
 DOOR SCHEDULE BUT SCALE TO BE (3)PAIR OF 2?-0? DOORS.
 MUST MEET THE REQUIREMENT OF CLEAR WIDTH DOOR OPENINGS
 SHALL HAVE A CLEAR OPENING WIDTH OF 32?.
 404.2.2 DOUBLE- LEAF DOORWAYS. AT LEAST ONE OF THE
 ACTIVE LEAVES OF DOORWAYS WITH 2 INDEPENDENTLY OPERATED
 LEAVES SHALL COMPLY WITH SECTIONS 404.2.3 AND 404.2.4.
 DOORS SF-L/1 AND SF-L/2.
  
 35)POOL WILL REQUIRE A SEPARATE PERMIT, AND WILL NOT
 BE PART OF THIS PERMIT PACKAGE.
  
 36) NOTE POOL REQUIREMENTS FOR SAFETY FENCING WILL NEED
 TO BE ADDRESSED FOR THE LANAI LEVEL BEFORE A PERMIT CAN
 BE ISSUED.424.1 PUBLIC SWIMMING POOLS AND BATHING
 PLACES. PUBLIC SWIMMING POOLS AND BATHING PLACES SHALL
 COMPLY WITH THE DESIGN AND CONSTRUCTION STANDARDS OF
 THIS SECTION.
 NOTE: OTHER ADMINISTRATIVE AND PROGRAMMATIC PROVISIONS
 MAY APPLY. SEE DEPARTMENT OF HEALTH (DOH) RULE 64E-9,
 FLORIDA ADMINISTRATIVE CODE AND CHAPTER 514, FLORIDA
 STATUTES.ZONING MAY HAVE ADDITIONAL COMMENTS ON THIS
 ISSUE.
  
 37) SHEET A2.04 THE ELEVATOR LOBBY DOORS DO NOT HAVE
 ANY IDENTIFYING TAGS, ( COMMON TO ALL FLOORS)THIS
 PLAN INDICATE NO DOOR ORWALL TYPES NOR THE HR RATING
 OF SUCH SYSTEMS. WHEN YOU LOOK AT THE LIFE SAFETY PLAN
 THERE ARE WALL RATINGS SOME DOORS BUT THERE IS NO
 NOMENCLATURE TO THE TYPE OF ROOM? 106.1.2* ADDITIONAL
 INFORMATION REQUIRED.
 302.3.2, 707,708 & TABLE 715.3.
  
 38) SHEET A2.05 DETAIL# 13 INDICATE AN EMERGENCY
 OVERFLOW, THE SITUATION IS THE WAY THE DETAIL IS DRAWN
 WITH A MINIMUM OF 4? BEFORE RAINWATER STARTS TO RUN
 INTO THE OVERFLOW, WHERE THE PLUGGED UP ROOF DRAIN IS
 THE WATER MAY 7? OR 8? DEEP DEPENDING ON THE LOCATION
 OF THE ROOF DRAIN FROM THE OVERFLOW. 1503.4.3 WHEN
 OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT
 PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR
 PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4
 INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND
 SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED
 VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET
 SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING.
  
 39 THE SAME DETAIL THAT IS MENTIONED ABOVE INDICATES
 THE USE OF EITHER A MANSARD OR SHED TYPE ROOF SYSTEM,
 WITH THE USE OF METAL TRUSSES, 1 ?? METAL DECKING,
 THERE IS ANOTHER MEMBER NOT LABELED SOME TYPE OF
 SHEATHING ? PLEASE PROVIDE WHAT TYPE OF
 ROOF SHEATHING IS TO BE USED?PLEASE SEE TABLE 601,
 ROOF CONSTRUCTION, FOOTNOTE
 2(I), 2(II) & 2(III).
  
 40) SHEET A2.05 ALSO INDICATES THAT A MAINTENANCE SHOP
 ON THE ROOF, WHAT TYPE OF
 ACTIVITIES WILL TAKE PLACE THERE WILL THIS BE MORE FOR
 STORAGE OR A ACTUAL MAINTENANCE
 SHOP? IF STORAGE WHAT TYPE OF MATERIALS?
  
 41) SHEET A2.05 DETAIL#9 SHEET A3.32 ROOF FEATURE
 DOESN?T INDICATE WHAT TYPE OF ROOF SHEATHING THAT WILL
 BE USED?PLEASE SEE TABLE 601, ROOF CONSTRUCTION,
 FOOTNOTE
 2(I), 2(II) & 2(III).IN THIS CASE THERE IS 20?-0? CLEAR
 FROM THE FLOOR SEE FOOTNOTE(III).
  
 42)DETAIL# 5 SHEET A7.09 TRASH CHUTE ROOF DETAIL
 INDICATES THE USE OF COMBUSTIBLE PLYWOOD ON THE ROOF,
 SEE TABLE 601.
  
 43) SHEET A3.32 DETAIL# 9 INDICATES THERE ARE VARIOUS
 AREAS OF EFIS TRIM TO BE USED, MUST MEET THE TEST FOR
 NONCOMBUSTIBILITY, ASTM E-84.1406.2.2 ARCHITECTURAL
 TRIM.
 IN BUILDINGS OF TYPE I, II, III AND IV CONSTRUCTION
 THAT DO NOT EXCEED THREE STORIES OR 40 FEET (12 192 MM)
 IN HEIGHT ABOVE GRADE PLANE, EXTERIOR WALL COVERINGS
 SHALL BE PERMITTED TO BE CONSTRUCTED OF WOOD WHERE
 PERMITTED BY SECTION 1405.4 OR OTHER EQUIVALENT
 COMBUSTIBLE MATERIAL. COMBUSTIBLE EXTERIOR WALL
 COVERINGS, OTHER THAN FIRE-RETARDANT-TREATED WOOD
 COMPLYING WITH SECTION 2303.2 FOR EXTERIOR
 INSTALLATION, SHALL NOT EXCEED 10 PERCENT OF AN
 EXTERIOR WALL SURFACE AREA WHERE THE FIRE SEPARATION
 DISTANCE IS 5 FEET (1524 MM) OR LESS. ARCHITECTURAL
 TRIM THAT EXCEEDS 40 FEET (12 192 MM) IN HEIGHT ABOVE
 GRADE PLANE SHALL BE CONSTRUCTED OF APPROVED
 NONCOMBUSTIBLE MATERIALS AND SHALL BE SECURED TO THE
 WALL WITH METAL OR OTHER APPROVED NONCOMBUSTIBLE
 BRACKETS.
  
 44)SHEET A2.30 DISPLAY CABINET OR ROOM R-104 IS
 MISSING THE DOOR MARKER, TYPE OF DOOR? 106.1.2*
 ADDITIONAL INFO REQUIRED.
  
 45) SHEET A2.30 PRE-CAST CONC. MOLDING DETAIL 3 OF
 A3.09PLEASE INDICATE SLAB SIZES AND
 ANCHORAGE. 1405.5 ANCHORED MASONRY VENEER. ANCHORED
 MASONRY VENEER SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1405.5 , 1405.6 , 1405.7 AND 1405.8 AND
 SECTIONS 6.1 AND 6.2 OF ACI 530/ASCE 5/TMS 402.
 1405.5 ANCHORED MASONRY VENEER.
 1405.6 STONE VENEER
 1405.7 SLAB-TYPE VENEER
  
 46A) SHEET A2.31 TRASH HOLDING ROOM PLANS INDICATE A
 5?-0? OVERHEAD ON THE PROPERTY LINE SIDE OF THE
 PROPERTY, WHICH 0-3? NO OPENINGS. 704.8.2 FIRST STORY.
  
 IN OCCUPANCIES OTHER THAN GROUP H, UNLIMITED
 UNPROTECTED OPENINGS ARE PERMITTED IN THE FIRST STORY
 OF EXTERIOR WALLS FACING A STREET THAT HAVE A FIRE
 SEPARATION DISTANCE OF GREATER THAN 15 FEET (4572 MM),
 OR FACING AN UNOCCUPIED SPACE. THE UNOCCUPIED SPACE
 SHALL BE ON THE SAME LOT OR DEDICATED FOR PUBLIC USE,
 SHALL NOT BE LESS THAN 30 FEET (9144 MM) IN WIDTH, AND
 SHALL HAVE ACCESS FROM A STREET BY A POSTED FIRE LANE
 IN ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE .
  
 46B) SEE TABLE 704.8 & TABLE 602. PLANS ALSO INDICATE A
 GATE ON THE OTHER END OF THE ROOM, THIS SHOULD HAVE A
 DOOR A CHANGE IN OCCUPANCY S-1 OCCUPANCY.
  
 47) SHEET A2.31 THE EAST PROPERTY LINE WALL IS SHOWN AS
 WALL TYPE (800), A9.02
 WALL RATING NOTE# 10 INDICATES ALL BLOCK WORK TO BE A
 MINIMUM OF 2 HR RATED BLOCK. PLEASE SEE TABLE 602 LESS
 THAN 5?-0? FROM THE PROPERTY LINE. PLEASE CORRECT. THE
 SAME WILL HOLD TRUE FOR THE SOUTH WALL.
  
 48) A2.32 SWITCH GEAR ROOM THE STEPS IN FRONT SHOULD
 HAVE 13? TREADS.1003.5.1
 WHERE A CHANGE IN LEVEL MEANS OF EGRESS NOT EXCEEDING
 21 INCHES (533 MM) IS ACHIEVED BY A STAIR, THE MINIMUM
 TREAD DEPTH OF SUCH STAIR SHALL BE 13 INCHES (330 MM)
 AND THE PRESENCE AND LOCATION OF EACH STEP SHALL BE
 READILY APPARENT.
  
 49) A2.32 THE EMERGENCY GENERATOR ROOM, 7? STAIR:
 1003.5.2
 WHERE CHANGE IN ELEVATION OF 12 INCHES (305 MM) OR LESS
 OCCURS IN EXIT ACCESS CORRIDORS, EXITS AND EXIT
 DISCHARGE, RAMPS COMPLYING WITH SECTION 1010 SHALL BE
 PROVIDED.
  
 50)FIRE COMMAND ROOM PLEASE PROVIDE COMPLIANCE WITH:
 403.8 FIRE COMMAND .
 A FIRE COMMAND CENTER COMPLYING WITH SECTION 911 SHALL
 BE PROVIDED IN A LOCATION APPROVED BY THE FIRE
 DEPARTMENT.
 WHERE REQUIRED BY OTHER SECTIONS OF THIS CODE, A FIRE
 COMMAND CENTER FOR FIRE DEPARTMENT OPERATIONS SHALL BE
 PROVIDED. THE LOCATION AND ACCESSIBILITY OF THE FIRE
 COMMAND CENTER SHALL BE SEPARATED FROM THE REMAINDER OF
 THE BUILDING BY NOT LESS THAN A 1-HOUR
 FIRE-RESISTANCE-RATED FIRE BARRIER. THE ROOM SHALL BE A
 MINIMUM OF 96 SQUARE FEET (9 M 2 ) WITH A MINIMUM
 DIMENSION OF 8 FEET (2438 MM). A LAYOUT OF THE FIRE
 COMMAND CENTER AND ALL FEATURES REQUIRED BY THE SECTION
 TO BE CONTAINED THEREIN SHALL BE SUBMITTED FOR APPROVAL
 PRIOR TO INSTALLATION. THE FIRE COMMAND CENTER SHALL
 COMPLY WITH NFPA 72 AND SHALL CONTAIN THE FOLLOWING
 FEATURES.
 1.THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM
 UNIT.
 2.THE FIRE DEPARTMENT COMMUNICATIONS UNIT.
 3.FIRE DETECTION AND ALARM SYSTEM ANNUNCIATOR
 UNIT.
 4.ANNUNCIATOR UNIT VISUALLY INDICATING THE
 LOCATION OF THE ELEVATORS AND WHETHER THEY ARE
 OPERATIONAL.
 5.STATUS INDICATORS AND CONTROLS FOR AIR-HANDLING
 SYSTEMS.
 6.THE FIRE-FIGHTER?S CONTROL PANEL REQUIRED BY
 SECTION 909.16 FOR SMOKE CONTROL SYSTEMS INSTALLED IN
 THE BUILDING.
 7.CONTROLS FOR UNLOCKING STAIRWAY DOORS
 SIMULTANEOUSLY.
 8.SPRINKLER VALVE AND WATER-FLOW DETECTOR DISPLAY
 PANELS.
 9.EMERGENCY AND STANDBY POWER STATUS INDICATORS.
 10.A TELEPHONE FOR FIRE DEPARTMENT USE WITH
 CONTROLLED ACCESS TO THE PUBLIC TELEPHONE SYSTEM. 11.
 FIRE PUMP STATUS INDICATORS.
 12.SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL
 FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF
 EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING
 EQUIPMENT AND FIRE DEPARTMENT ACCESS.
 13.WORKTABLE.
 14.GENERATOR SUPERVISION DEVICES, MANUAL START AND
 TRANSFER FEATURES.
 15.PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY
 REQUIRED BY OTHER SECTIONS OF THIS CODE.
  
 51) SHEET A2.33 PLANS INDICATE WALL RATING OF 800, WHEN
 REVIEWING THIS WALL TYPE THERE IS NO REFERENCE TO THE
 WALL RATING. SHEETA9.02 NOTE# 10 MAKE REFERENCE THAT
 ALL BLOCK TYPE ARE TO BE 2 HR RATED WALLS.PLEASE HAVE
 THE BLOCK MANUFACTURER PROVIDE THE EQUIVALENT THICKNESS
 OF THE BLOCK AND TYPE OF AGGREGATE TO BE USED? IF
 RINKER BLOCK ARE TO BE USED WILL ANY T007 BLOCK BE
 USED?
 721.3.2 CONCRETE MASONRY WALLS.
 THE FIRE-RESISTANCE RATING OF WALLS AND PARTITIONS
 CONSTRUCTED OF CONCRETE MASONRY UNITS SHALL BE
 DETERMINED FROM TABLE 721.3.2 . THE RATING SHALL BE
 BASED ON THE EQUIVALENT THICKNESS OF THE MASONRY AND
 TYPE OF AGGREGATE USED.
 EQUIVALENT .
  
 52) SHEET A9.02 INDICATES THAT THE BLOCK ARE TO BE
 MORTARED TO THE DECK ABOVE. THIS WILL NO PROVIDE A
 SMOKE TYPE SEAL.713.1 GENERAL. JOINTS INSTALLED IN OR
 BETWEEN FIRE-RESISTANCE-RATED WALLS, FLOOR OR
 FLOOR/CEILING ASSEMBLIES AND ROOFS OR ROOF/CEILING
 ASSEMBLIES SHALL BE PROTECTED BY AN APPROVED
 FIRE-RESISTANT JOINT SYSTEM DESIGNED TO RESIST THE
 PASSAGE OF FIRE FOR A TIME PERIOD NOT LESS THAN THE
 REQUIRED FIRE-RESISTANCE RATING OF THE WALL, FLOOR OR
 ROOF IN OR BETWEEN WHICH IT IS INSTALLED.
 FIRE-RESISTANT JOINT SYSTEMS SHALL BE TESTED IN
 ACCORDANCE WITH SECTION 713.3 . THE VOID CREATED AT THE
 INTERSECTION OF A FLOOR/CEILING ASSEMBLY AND AN
 EXTERIOR CURTAIN WALL ASSEMBLY SHALL BE PROTECTED IN
 ACCORDANCE WITH SECTION 713.4 .
  
 53) SHEET A2.35 THE POOL EQUIPMENT ROOM APPEARS TO HAVE
 A VENT ON THE EAST SIDE OF THE BUILDING. THIS IS A 3 HR
 RATED WALL ON THE PROPERTY LINE ,NO OPENINGS 0-3?-0
 FROM THE PROPERTY LINE.
  
 54)A2.35 & A2.36 BOTH HAVE LOUVERED OPENINGS IN A
 WALL THAT SITS 0-3?-0? FROM THE PROPERTY LINE, NO
 OPENINGS ALLOWED. TABLE 704.8.
  
 55) A2.80 DOOR SCHEDULE INDICATES DOOR TYPE ?F? TO HAVE
 VIEW PANELS, PLANS INDICATE 150 SQ INCHES FOR A ?B?
 LABEL DOOR PLEASE SEE TABLE 715.4.3 1 ? HR DOOR 100 SQ
 INCHES.
  
 56) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE
 DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 ANDASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1
 M) ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE
 2 COPIES,
 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING
 REPORTS, MISSING REPORTS ARE AS FOLLOWS:
 A) FIXED GLASS
 B) STOREFRONT GLASS
 C) OPERABLE WINDOWS
 D) MULLIONS HORIZONTAL & VERTICAL
 E) SKYLIGHTS
 F) GLASS BLOCK
 G) LOUVERS
 H) HOLLOW METAL DOORS/ ROOF HATCHES
 I) GLASS DOORS SWING
 J) OVERHEAD DOORS/ COIL DOORS
 K) SLIDING GLASS DOORS
 L) AUTOMATIC HORIZONTAL SLIDING DOORS
 M)PANEL WALL SYSTEM: SOFFITS, EFIS
 N) ROOFING ASSEMBLIES
  
 57)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA PRODUCT
 APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 58) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 59) THIS NEXT ISSUE HAS BECOME A LARGE ISSUE ON
 PROJECTS!!!! WINDOWS NOT BEING LABELED.
 TESTING AND LABELING. 1714.5.2.1EXTERIOR WINDOWS AND
 GLASS DOORS SHALL BE TESTED BY AN APPROVED INDEPENDENT
 TESTING LABORATORY, AND SHALL BE LABELED WITH AN
 APPROVED LABEL IDENTIFYING THE MANUFACTURER,
 PERFORMANCE CHARACTERISTICS AND APPROVED PRODUCT
 CERTIFICATION AGENCY, TESTING LABORATORY, EVALUATION
 ENTITY OR MIAMI-DADE PRODUCT APPROVAL TO INDICATE
 COMPLIANCE WITH THE REQUIREMENTS OF ONE OF THE
 FOLLOWING SPECIFICATIONS:ANSI/AAMA/NWWDA 101/I.S.2 OR
 101/I.S. 2/NAFS OR TAS 202 (HVHZ SHALL COMPLY WITH TAS
 202 UTILIZING ASTME E 1300 OR SECTION 2404 .
 GLASS STRENGTH: DETERMINATION OF LOAD RESISTANCE OF
 GLASS FOR SPECIFIED LOADS OF PRODUCTS TESTED AND
 CERTIFIED IN ACCORDANCE WITH SECTION 1714.5.2.1 SHALL
 BE DESIGNED TO COMPLY WITH ASTM E 1300 IN ACCORDANCE
 WITH SECTION 2404 .
  
 60)SHEET A2.90; THIS SHEET SHOWS MULLIONS USED BOTH
 VERTICALLY AND HORIZONTALLY, BEFORE A REVIEW OF THE
 PRODUCT APPROVALS WILL BE ABLE TO BEGIN THE DESIGN TEAM
 WILL NEED TO HIGHLIGHT WHICH MULLION WILL BE THE ONE
 THAT WILL CONTINUE FROM A STRUCTURAL FRAMING MEMBER TO
 THE OPPOSITE SIDE.
  
 1714.5.5 MULLIONS OCCURRING BETWEEN INDIVIDUAL WINDOW
 AND GLASS DOOR ASSEMBLIES. 1714.5.5.1 MULLIONS.
 MULLIONS, OTHER THAN MULLIONS WHICH ARE AN INTEGRAL
 PART OF A WINDOW OR GLASS DOOR ASSEMBLY TESTED AND
 LABELED IN ACCORDANCE WITH SECTION 1714.5.2.1 , SHALL
 BE TESTED BY AN APPROVED TESTING LABORATORY OR BE
 ENGINEERED IN ACCORDANCE WITH ACCEPTED ENGINEERING
 PRACTICE. BOTH METHODS SHALL USE PERFORMANCE CRITERIA
 CITED IN SECTIONS 1714.5.5.2 , 1714.5.5.3 AND
 1714.5.5.4 .
  
 1714.5.5.2 LOAD TRANSFER.
 MULLIONS SHALL BE DESIGNED TO TRANSFER THE DESIGN
 PRESSURE LOADS APPLIED BY THE WINDOW AND DOOR
 ASSEMBLIES TO THE ROUGH OPENING SUBSTRATE.
  
 1714.5.5.3 DEFLECTION.
 MULLIONS SHALL BE CAPABLE OF RESISTING THE DESIGN
 PRESSURE LOADS APPLIED BY THE WINDOW AND DOOR
 ASSEMBLIES TO BE SUPPORTED WITHOUT DEFLECTING MORE THAN
 L/175, WHERE L IS THE SPAN OF THE MULLION IN INCHES.
  
 1714.5.5.4 STRUCTURAL SAFETY FACTOR.
 MULLIONS SHALL BE CAPABLE OF RESISTING A LOAD OF
 ONE-AND-ONE-HALF TIMES THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW AND DOOR ASSEMBLIES TO BE
 SUPPORTED WITHOUT EXCEEDING THE APPROPRIATE MATERIAL
 STRESS LEVELS. IF TESTED BY AN APPROVED LABORATORY, THE
 ONE AND ONE-HALF TIMES THE DESIGN PRESSURE LOAD SHALL
 BE SUSTAINED FOR 10 SECONDS, AND THE PERMANENT
 DEFORMATION SHALL NOT EXCEED 0.4 PERCENT OF THE MULLION
 SPAN AFTER THE ONE-AND-ONE-HALF TIMES DESIGN PRESSURE
 LOAD IS REMOVED.
  
 61) ANOTHER BIG ISSUE WITH PRODUCT APPROVALS THAT THE
 DESIGN TEAM WILL SIGN OFF ON REVIEWED IS THEY WILL NOT
 ?HIGHLIGHT? WHICH GLAZING SYSTEM THEY HAVE APPROVED AND
 THE CORRESPONDING PRESSURES, NOR WILL THEY HIGHLIGHT IN
 SLIDING GLASS DOOR SYSTEMS WHICH
 RAIL SYSTEM WILL BE USED. THERE ARE 4 DESIGN CRITERIA
 USUALLY IN THESE PACKAGES. ONE WITH NO REINFORCEMENT,
 LIGHT , MEDIUM AND HEAVY REINFORCEMENT HIGHLIGHT WHICH
 SYSTEM IS TO BE USED.
  
 62)NO ROOF REPORT WAS SUBMITTED IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
 _X__ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT.
 (FLAT ROOF)
 ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH. _X__
 CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE USED.
 _X__ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE
 _2&3__ .
 SINCE THE ROOFING REPORT DOESN?T HAVE THE SUBSYSTEM
 HIGHLIGHTED THE NEXT 2 ITEMS ARE HIGHLIGHTED._X__ THE
 SYSTEM PROVIDED STATESLIMITATION# 7, SHOULD THE
 FASTENERRESISTANCE BE LESS THAN THAT REQUIRED, AS
 DETERMINED BY THEBUILDING OFFICIAL, A REVISED
 FASTENERSPACING, PREPARED , SIGNED AND SEALED BY A
 FLORIDA REGISTEREDPROFESSIONAL ENGINEER,
 REGISTEREDARCHITECT OR REGISTERED ROOF CONSULTANT
 MAY BE SUBMITTED.
 _X__THE SYSTEM PROVIDED INDICATESLIMITATION#
 9, NO ENHANCEDFASTENING ALLOWED.
  
 63) SLOPED ROOF (7/ A8.06) INDICATES THE USE OF EITHER
 CLAY TILE OR CONCRETE TILE. SUBMIT REPORT AND HIGHLIGHT
 WHICH TYPE OF SYSTEM WILL BE USED TO RESIST THE MOMENT
 OF UPLIFT?
  
 64)PLEASE SUBMIT INFORMATION ON HOW THE RIDGE TILE
 ARE GOING TO BE SECURED TO THE ROOFING SYSTEM. 1507.3.7
 ATTACHMENT.
 CLAY AND CONCRETE ROOF TILES SHALL BE FASTENED IN
 ACCORDANCE WITH SECTION 1609 OR IN ACCORDANCE WITH
 FRSA/RTI INSTALLATION MANUAL.
 1507.3.8 APPLICATION.
 TILE SHALL BE APPLIED ACCORDING TO THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS OR RECOMMENDATIONS OF THE
 FRSA/RTI 07320- 04.
  
 65) A3.30 INDICATES THE USE OF METAL PANEL ROOFING
 PLEASE PROVIDE ROOFING REPORT.
  
 66)SHIMS FOR WINDOWS AND DOORS, SHEET A2.93 DETAIL#
 9.
 1714.5.4.3 WOOD OR OTHER APPROVED FRAMING MATERIALS.
 WHERE THE FRAMING MATERIAL IS WOOD OR OTHER APPROVED
 FRAMING MATERIAL, WINDOW AND GLASS DOOR ASSEMBLIES
 SHALL BE ANCHORED THROUGH THE MAIN FRAME OR BY JAMB
 CLIP OR SUBFRAME SYSTEM OR THROUGH THE FLANGE IN
 ACCORDANCE WITH THE MANUFACTURER?S PUBLISHED
 INSTALLATION INSTRUCTIONS. SHIMS SHALL BE MADE FROM
 MATERIALS CAPABLE OF SUSTAINING APPLICABLE LOADS,
 LOCATED AND APPLIED IN A THICKNESS CAPABLE OF
 SUSTAINING APPLICABLE LOADS. ANCHORS SHALL BE PROVIDED
 TO TRANSFER LOAD FROM THE WINDOW OR DOOR FRAME TO THE
 ROUGH OPENING SUBSTRATE.
  
 67)SHEETS S-12 AND S-13 ARE MISSING THE PRESSURES ON
 THE LOUVERS ON THE SOUTH AND WEST WALLS.
  
 68) THE STRUCTURAL PLANS DO NOT INDICATE PRESSURES ON
 THE POOL PAVILION NOR THE SOUTHWEST
 INSET CORNER OF THE POOL DECK AND VERTICAL ELEMENT.
  
 69) PLANS ALSO FAIL TO PROVIDE WIND PRESSURE ZONES FOR
 THE ROOF ELEMENTS IN ZONES 1,2 & 3.
  
 70) EXTERIOR DOOR ASSEMBLIES NOT COVERED BY SECTION
 1715.4.2 OR SECTION 1714.5.3.1 SHALL BE TESTED FOR
 STRUCTURAL INTEGRITY IN ACCORDANCE WITH ASTM E 330
 PROCEDURE A, AT A LOAD OF 1.5 TIMES THE REQUIRED DESIGN
 PRESSURE LOAD. THE LOAD SHALL BE SUSTAINED FOR 10
 SECONDS WITH NO PERMANENT DEFORMATION OF ANY MAIN FRAME
 OR PANEL MEMBER IN EXCESS OF 0.4 PERCENT OF ITS SPAN
 AFTER THE LOAD IS REMOVED. HIGH-VELOCITY HURRICANE
 ZONES SHALL COMPLY WITH TAS 202. AFTER EACH SPECIFIED
 LOADING, THERE SHALL BE NO GLASS BREAKAGE, PERMANENT
 DAMAGE TO FASTENERS, HARDWARE PARTS, OR ANY OTHER
 DAMAGE WHICH CAUSES THE DOOR TO BE INOPERABLE.
 THE MINIMUM TEST SIZES AND MINIMUM DESIGN PRESSURES
 SHALL BE AS INDICATED IN TABLE 1714.5.3 .
  
 71) A3.08 & A3.30 DETAIL# 1 BOTH INDICATE THE
 INSTALLATION OF FABRIC AWNINGS ON STEEL TUBING, AWNINGS
 ARE TO BE COVERED UNDER A SEPARATE PERMIT IF THE
 FOLLOWING INFORMATION IS NOT INCLUDED IN THIS PACKAGE:
  
  
 3105.4.1
 DESIGN OF THE FRAMING MEMBERS SHALL NOT BE BASED ON
 REMOVAL OR REPOSITIONING OF PARTS, OR THE WHOLE, DURING
 PERIODS OF 75 MPH WIND VELOCITY.
  
 3105.4.2
 DESIGN OF THE STRUCTURAL FRAMING MEMBERS SHALL BE BASED
 ON RATIONAL ANALYSIS, USING THE APPLICABLE WIND LOADS
 OF CHAPTER 16 AS SHOWN BELOW:
  
 3105.4.2.1
 THE WIND DESIGN LOADS FOR ANY FABRIC OR
 MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK
 REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC AT WIND
 VELOCITIES OF 75 MPH, SHALL BE BASED ON THE FOLLOWING
 CRITERIA:
 1.MINIMUM WIND VELOCITY OF 3-SECOND WIND GUST 90
 MPH
 2.IMPORTANCE FACTOR BASED ON LOW HAZARD TO HUMAN
 LIFE OF 0.77.
 3.EXPOSURE CATEGORY B FOR OR C AS DEFINED IN
 CHAPTER 16 .
  
 3105.4.2.2
 THE WIND DESIGN LOADS FOR ANY FABRIC OR MEMBRANE
 COVERED STRUCTURE DESIGNED WITH A PERMANENT OR
 NONREMOVABLE FABRIC OR MEMBRANE, SHALL BE BASED ON THE
 FOLLOWING CRITERIA:
 1.MINIMUM WIND VELOCITY AS REQUIRED IN CHAPTER 16
 .
 2.IMPORTANCE FACTOR BASED ON LOW HAZARD TO HUMAN
 LIFE OF 0.77.
 3.EXPOSURE CATEGORY B OR C AS DEFINED IN CHAPTER
 16 .
  
 3105.4.2
 THE FABRIC PORTIONS OF AWNINGS FABRIC COVERED FRAMES
 SHALL BE SECURELY LACED, TIED OR OTHERWISE FASTENED TO
 THE FRAME; NO RAFTER OR FRONT BAR WILL BE PERMITTED IN
 POCKETS; AND IN NO CASE SHALL A ROLLING CURTAIN BE
 CAUSED TO OPERATE OVER A CANOPY FRAME.
  
 72) A3.30 DETAILS 3 & 4 BOTH INDICATE A RIGID OR SOLID
 ROOF SYSTEM, PLANS DO NOT INDICATE WHAT TYPE OF
 MATERIALS WILL BE USED. PLEASE PROVIDE DETAIL WITH TYPE
 OF FRAMING MEMBERS
 TYPE OF FACIA FINISH, CEILING AND TYPE OF ATTACHMENTS?
 106.1.2 ADD INFO REQUIRED.
  
 73) A4.01 DETAIL# 4 INDICATES THE USE OF PLYWOOD AS
 ROOF SHEATHING AS PART OF THE CABANA ROOFSYSTEM?
 TABLE 601.
  
 74) A40.01 CUT SECTION OF THE CABANA, PLEASE PROVIDE A
 DETAIL INDICATING THE HEIGHT OF THE SINK AT THE BAR
 AREA?
  
 75) A7.01 & A7.02 STAIR 1 & 2FIRST FLOOR BENEATH THE
 STAIRS TO COMPLY WITH FAIR HOUSING ANSI 307.4 REDUCED
 VERTICAL CLEARANCE WHEN HEADROOM IS LESS THAN 80?.
  
 76) A7.09 DETAIL# 5 REFUSE CHUTE ROOFING DETAIL
 INDICATES THE USE OF PLYWOOD SHEATHING, SEE TABLE 601.
  
 77)A8.03 DETAIL 6 PLEASE CORRECT THE CODE REFERENCE
 TO THE CODE SECTION FOR FIRE TREATED WOOD AND THE CODE
 REFERENCE.
  
 78) A8.03 DETAILS 3,4,5,8&9 ALL REQUIRE FIRE RETARDANT
 TREATED PLYWOOD: 803.4.2 SET-OUT CONSTRUCTION. WHERE
 WALLS AND CEILINGS ARE REQUIRED TO BE OF
 FIRE-RESISTANCE-RATED OR NONCOMBUSTIBLE CONSTRUCTION
 AND WALLS ARE SET OUT OR CEILINGS ARE DROPPED DISTANCES
 GREATER THAN SPECIFIED IN SECTION 803.4.1 , CLASS A
 FINISH MATERIALS SHALL BE USED EXCEPT WHERE INTERIOR
 FINISH MATERIALS ARE PROTECTED ON BOTH SIDES BY AN
 AUTOMATIC SPRINKLER SYSTEM OR ATTACHED TO
 NONCOMBUSTIBLE BACKING OR FURRING STRIPS INSTALLED AS
 SPECIFIED IN SECTION 803.4.1 . THE HANGERS AND ASSEMBLY
 MEMBERS OF SUCH DROPPED CEILINGS THAT ARE BELOW THE
 MAIN CEILING LINE SHALL BE OF NONCOMBUSTIBLE MATERIALS,
 EXCEPT THAT IN TYPE III AND V CONSTRUCTION,
 FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED. THE
 CONSTRUCTION OF EACH SET-OUT WALL SHALL BE OF
 FIRE-RESISTANCE-RATED CONSTRUCTION AS REQUIRED
 ELSEWHERE IN THIS CODE.
  
 79)A8.05 EXTERIOR SOFFITS, VARIOUS DETAILS INDICATE
 THE SOFFIT OR DROPPED CEILING, THERE IS NO INFORMATION
 ON THE TYPE OF STUDS, SPACING, ATTACHMENT TO DECK ABOVE
 OR TYPE OF LATH AND SPACING OF HORIZONTAL FRAMING
 MEMBERS IS THE WIRE LATH TIED UP OR SCREWED IN PLACE?
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 80) A8.06 DETAIL# 11 INDICATES THE USE OF 5V METAL
 CRIMP SIDING DIRECTLY APPLIED TO THE METAL FRAMING,
 WHAT TYPE OF BRACING IS TO BE USED? PLEASE PROVIDE THE
 PRODUCT APPROVAL
 INDICATING THIS IS STRUCTURAL SHEATHING NO SHEATHING
 REQUIRED.
  
 81) A8.06 DETAIL# 10 DETAIL INDICATES THE USE OF
 PLYWOOD NOT FIRE RATED!
  
 82A)A9.01 VARIOUS DETAILS INDICATE A DESIGN SOUND
 TEST NUMBER, PLEASE INDICATE THE SOUND TRANSMISSION
 CLASS NUMERICALLY, 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION ASSEMBLIES
 FOR PIPING; ELECTRICAL DEVICES; RECESSED CABINETS;
 BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR EXHAUST
 DUCTS SHALL BE SEALED, LINED, INSULATED OR OTHERWISE
 TREATED TO MAINTAIN THE REQUIRED RATINGS. THIS
 REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT ENTRANCE
 DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT FITTING TO
 THE FRAME AND SILL.
  
 82B) PLEASE PROVIDE COMPLIANCE WITH SOUND TRANSFERENCE
 THROUGH THE FLOOR SYSTEM?
 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 83)A9.01 NOTE # 2 USE OF CEMENTITITOUS BACKER BOARD,
 PLEASE PROVIDE THE MANUFACTURERS SPEC THAT A VAPOR
 BARRIER WOULD NOT BE REQUIRED?
  
 84) DISCREPANCY BETWEEN A9.01 NOTE# 2 USE OF
 CEMENTITITOUS BACKER BOARD AND A2.71 NOTE# 2 FIBERGLASS
 BACKER BOARD? PLEASE CORRECT.
  
 85)SHEET A4.01 CABANA RESTROOMS FINISH SCHEDULE IS
 ELUSIVE NOTE 5 INDICATES SCHEDULE TO BE ON A2.71 WHICH
 IS FOR UNITS ONLY, A2.70 IS THE FINISH SCHEDULE FOR THE
 COMMON AREAS BUT THE FINISH SCHEDULE IS NOT FOUND THERE
 EITHER. NOTE 8 INDICATES REFERS TO THE INTERIOR DESIGN
 PACKAGE, WHERE?
 85A) WALL TYPES & THICKNESS
 85B) CEILING TYPES & THICKNESS
 85C) ARETHE CEILINGS DROPPED IN ANY AREAS
 NOTE:2509.1 WET AREAS.
 SHOWERS AND PUBLIC TOILET WALLS SHALL CONFORM TO
 SECTIONS 1210.2 AND 1210.3 .
 2509.3 LIMITATIONS.
 WATER-RESISTANT GYPSUM BACKING BOARD SHALL NOT BE USED
 IN THE FOLLOWING LOCATIONS:
 1.OVER A VAPOR RETARDER IN SHOWER OR BATHTUB
 COMPARTMENTS.
 2.WHERE THERE WILL BE DIRECT EXPOSURE TO WATER OR
 IN AREAS SUBJECT TO CONTINUOUS HIGH HUMIDITY.
 3.ON CEILINGS WHERE FRAME SPACING EXCEEDS 12
 INCHES (305 MM) O.C. FOR ?-INCH-THICK (12.7 MM)
 WATER-RESISTANT GYPSUM BACKING BOARD AND MORE THAN 16
 INCHES (406 MM) O.C. FOR 5 / 8 -INCH-THICK (15.9 MM)
 WATER-RESISTANT GYPSUM BACKING BOARD.
  
 86) S-1 INDICATES THAT FOUNDATION WORK IN AREAS WILL
 COME UP TO THE PROPERTY LINE, SHOW COMPLIANCE WITH
 3307.1 PROTECTION OF ADJACENT PROPERTY.
  
 87) ADJACENT TO EXCAVATIONS.
 EVERY EXCAVATION ON A SITE LOCATED 5 FEET (1524 MM) OR
 LESS FROM THE STREET LOT LINE SHALL BE ENCLOSED WITH A
 BARRIER NOT LESS THAN 6 FEET (1829 MM) HIGH. WHERE
 LOCATED MORE THAN 5 FEET (1524 MM) FROM THE STREET LOT
 LINE, A BARRIER SHALL BE ERECTED WHEN REQUIRED BY THE
 BUILDING OFFICIAL. BARRIERS SHALL BE OF ADEQUATE
 STRENGTH TO RESIST WIND PRESSURE AS SPECIFIED IN
 CHAPTER 16 .
  
  
 88) WHILE UNDER CONSTRUCTION A STANDPIPE SHALL MEET THE
 REQUIREMENTS OF: 3311.1 WHERE REQUIRED.BUILDINGS FOUR
 STORIES OR MORE IN HEIGHT SHALL BE PROVIDED WITH NOT
 LESS THAN ONE STANDPIPE FOR USE DURING CONSTRUCTION.
 SUCH STANDPIPES SHALL BE INSTALLED WHERE THE PROGRESS
 OF CONSTRUCTION IS NOT MORE THAN 40 FEET (12 192 MM) IN
 HEIGHT ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT
 ACCESS. SUCH STANDPIPE SHALL BE PROVIDED WITH FIRE
 DEPARTMENT HOSE CONNECTIONS AT ACCESSIBLE LOCATIONS
 ADJACENT TO USABLE STAIRS. SUCH STANDPIPES SHALL BE
 EXTENDED AS CONSTRUCTION PROGRESSES TO WITHIN ONE FLOOR
 OF THE HIGHEST POINT OF CONSTRUCTION HAVING SECURED
 DECKING OR FLOORING.
  
 89) S-8 INDICATES A TABLE OF CONCRETE COVERAGE HOW DOES
 THIS TABLE COMPLY WITH TABLE
 601 THE HOUR RATINGS FOR STRUCTURAL FRAMES COLUMNS,
 GIRDERS OR BEAMS, FLOOR AND ROOF SLABS?
  
 90) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-07-09 Cont ID  
Sent By dpalmer Date 2007-07-09 Time 19:52 Rev Time 0.00
Received By dpalmer Date 2007-07-07 Time 19:15 Sent To I
Notes
2007-07-09 19:52:342007-07-09 19:52:34
  
  
 **** UNSAT2RDREVIEW ****
  
 *** DATURA & OLIVE ***
  
  
 ** PLEASE SEE THERE ARE STILL SEVERAL ITEMS FROM THE
 PREVIOUS REVIEW WHICHIS STILL IN NEED OF ADDRESSING.
  
 ** PLEASE SEE THERE ARE SOME NEW COMMENTS BASED ON
 CHANGES, REVISIONS NOW MADE TO PLANS WHICH WERE NOT ON
 PREVIOUS REVIEWED PLANS.
 PLEASE ALSO SEE NEW NOTES.
  
 ** PLEASE KNOW THAT AS SOME INFORMATION HAS NOT BEEN
 SUBMITTED FOR REVIEW YET THERE MAY VERY WELL BE NEW
 COMMENTS ON THE NEXT REVIEW.
  
 ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1
 IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE
 ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY
 THE CITY OF WEST PALM BEACH.
  
  
 1) NOTE: PLEASE SEE THE LETTER SUBMITTED BY MR. ROBERT
 SWEDROE FOR SIGNATURE VERIFICATION NEEDS TO BE
 NOTARIZED CORRECTLY PER FS 117.05.
 THIS WAS IN NOTE #5 FROM PREVIOUS REVIEW.
 PLEASE SEE THIS SECTION OF THE FS WHICH CONTAINS
 INFORMATION ON WHAT IS REQUIRED FOR NOTARY STATEMENT(S)
 ETC.
  
 2) NOTE: PLEASE SEE FBC 2004 W/ 2006 FOR THE FLORIDA
 ENERGY CODE AND RELEVANT CODES FOR THIS BUILDING.
 PLEASE SEE THERE IS INFORMATION NOT YET PROVIDED FOR
 LIGHTING CONTROLS.
 PLEASE SEE MISSING MAXIMUM TIMES ON OS TYPE DEVICES.
 PLEASE SEE THE ENERGY CALCULATIONS DO NOT CORRELATE
 WITH THE PLANS COMPLETELY. PLEASE SEE THE FIXTURE
 LEGEND AND ENERGY CALCULATIONS FOR WATTAGE, TYPE AND
 CONTROLS. PLEASE SEE IT IS NOT POSSIBLE FOR THE
 LIGHTING CONTROL METHODS TO BE SHOWN AS *MANUAL ON/OFF*
 WHEN MANY OF THESE ARE IN FACT AUTOMATED CONTROLS.
 PLEASE SEE THE ENERGY CALCULATIONS WOULD ACTUALLY BE
 MORE DETAILED FOR AREAS IN WHICH THESE LUMINARIES ARE
 LOCATED, THE NUMBER OF LUMINARIES, TYPES ETC. PLEASE
 SEE THE SUMMARY SHEETS AND INPUT DATA REPORTS DO NOT
 INDICATE ANY EXTERIOR LIGHTING. HOW IS THIS POSSIBLE
 WHEN THE PLANS CONTAIN NUMEROUS EXTERIOR LIGHT
 FIXTURES? 13-415.ABC.2, 13-415.1.ABC.1.4,
 13-415.ABC.1.3.
 PLEASE SEE 13-415.1.AB.1, 13-415.1.A, AND 13-415.2
  
 ** PLEASE SEE THE OWNER AGENT WAS NOT SIGNED ON THE
 CERTIFICATION SHEETS OF ENERGY CALCULATIONS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THERE ARE AREAS WHICH DO NOT SHOW LIGHTING
 CONTROLS AS REQUIRED PER 13-415.1.ABC.1.1, .1.2 AND
 .1.3.
 PLEASE SEE THAT THE ENERGY CALCULATIONS DO NOT INDICATE
 AUTOMATED CONTROLS FOR LIGHTING. SHOWS MANUAL ON/OFF
 FOR CONTROL METHODS.
 PLEASE SEE 13-415.2 FOR PERFORMANCE OF INTERIOR
 LIGHTING.
 PLEASE PROVIDE INFORMATION IN DETAIL FOR THIS. PLEASE
 SEE THE LIGHTING SHOWN ON PLANS DOES NOT CORRELATE WITH
 THE ENERGY CALCULATIONS.
 PLEASE SEE ALL OF THE REVISED CHAPTER 13 ITEMS ALONG
 WITH THE EXISTING IN THE 2004.
  
 3) NOTE:PLEASE SUBMIT THE MANUFACTURE'S SPECS/CUT
 SHEETS FOR THE FOLLOWING.FIRE PUMP, FIRE PUMP
 CONTROLLER, GENERATOR, ATS, FUEL TANK(S).
 PLEASE KNOW ANY OTHER EQUIPMENT SPECS MAY BE REQUESTED
 FROM OTHER TRADES.
 PLEASE SEE ONLY ONE COPY OF THE GENERATOR SPECS/CUT
 SHEETS WAS SUBMITTED. NO OTHER SHEETS FOR ANY OTHER
 EQUIPMENT ETC. THIS WAS REQUESTED ON PREVIOUS NOTE #8.
 110.3, 90.7.
 FBC 106.1.2
  
 4) NOTE: PLEASE CLARIFY THE NEW SPECS WHICH INDICATES
 THE GENERATOR AS BEING *BI-FUEL*. THIS SEEMS AS THIS IS
 INSTALLING AN AFTERMARKET PRODUCT ON THE GENERATOR
 UNIT. THISIS A LIFE SAFETY/EMERGENCY SYSTEMS AND
 LEGALLY REQUIRED GENERATOR AND ANY ALTERATION OF
 EQUIPMENT WITH AFTER MARKER PRODUCTS WILL VOID EPA
 CERTIFICATIONS, ANY LISTING STANDARD AND POSSIBLY
 WARRANTY OF UNIT.
 PLEASE KNOW THE WARRANTY IS NOT AN ISSUE FOR THE AHJ
 HOWEVER ANY VOIDING OF EPA AND LISTING STANDARD IS NOT
 PERMITTED PER 110.3.
 ** PLEASE SEE NOTES WITH RESPECT TO FUEL CONSUMPTION.
  
 5) NOTE: PLEASE SEE THE FUEL CONSUMPTION MAY NOT BE
 BASED ON THE USE OF NATURAL GAS. ANY LEGALLY REQUIRED,
 OR EMERGENCY/LIFE SAFETY SYSTEM MAY NOT DEPEND ON THE
 UTILITY.
 PLEASE SEE 701.11B3.
 PLEASE SEE THE TIME OF 100% IS BASED ON THE MINIMUM
 TIMES AS REQUIRED IN NFPA-110, NFPA-101 AND NFPA-20.
 THE OTHER RUNNING TIMES FOR LOADS REQUIRED UNDER THE
 NEW HOUSE BILL 7121 IS THAT OF THE OTHER LEGALLY
 REQUIRED LOADS.
 PLEASE ADJUST CALCULATIONS.
  
 6) NOTE: PLEASE CORRELATE PLANS FOR ON-SITE FUEL.
 PLEASE SEE THE PLANS REFERENCE TO SEE *P* SHEETS FOR
 FUEL PIPING ETC HOWEVER THE *P* SHEET P.3.04 SHOWS A
 NOTE #27 WHICH INDICATES 500 GALLON DAY TANK, YET RISER
 SHOWS A 50 GALLON DAY TANK. PLEASE SEE THE OTHER SHEETS
 IN ELECTRICAL PLANS CONTAIN A NOTE AND INFORMATION FOR
 THIS SAME TANK AS 500 GALLONS.
 PLEASE COORDINATE ALL INFORMATION.
 PLEASE SEE NOTE #5 ABOVE WITH RESPECT TO THE FUEL
 CONSUMPTION AS THE SUMMARY ON THE RISER SHEET E4.01
 STATES 1500 GALLONS OF FUEL PROVIDED. HOW IS THIS
 POSSIBLE WHEN THE PLANS INDICATE 2000 GALLONS OF FUEL?
 ** PLEASE SEE COMMENTS FROM OTHER TRADES WITH RESPECT
 TO THE TANK, PIPING ETC WHERE DESIGN OF FUEL PIPING
 SHOULD BE PART OF THE MECHANICAL PLANS.
 PLEASE ALSO SEE COMMENTS WITH RESPECT TO THE SIZE OF
 THE TANK AND NEEDING DERM REVIEW, AND STAMPED PLANS FOR
 SUBMITTAL.
 FBC 106.1.2 FOR COORDINATION.
  
 7) NOTE: PLEASE SEE THE PREVIOUS NOTE #9 REQUESTED
 EMERGENCY BACK UP LIGHTS IN SOME OF THE ROOMS LISTED
 BELOW, HOWEVER ONLY THE GENERATOR ROOM NEEDED THE 30FT
 CANDLE LEVEL.
 PLEASE SEE THE NUMBER OF FIXTURES IS NOT PROHIBITED
 JUST UNUSUALLY HIGH IN SOME ROOMS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE FOLLOWING LOCATIONS SHALL CONTAIN
 EMERGENCY BATTERY BACK UP LIGHTS OF SOME KIND.
 GENERATOR ROOM (TO A LEVEL OF 30FT CANDLES), FIRE
 COMMAND ROOM, MAIN ELECTRICAL ROOM, METER CENTER ROOMS,
 ELEVATOR EQUIPMENT ROOM(S).
 PLEASE SEE NEXT NOTE WITH RESPECT TO STAIRS.NFPA-70
 110.26, 700.16, 700.12E, NFPA-110 7.3, NFPA-20 5.12.3,
 AND .4, NFPA-72 CHAPTER 2 FOR FCRM.
  
 8) NOTE:PLEASE SEE PREVIOUS REVIEW NOTES #10 AND
 #21.
 PLEASE SEE MANY OF THE BATTERY BACK UP FIXTURES WERE
 ADDED TO PLANS HOWEVER THE FIXTURES WHICH WERE ADDED DO
 NOT COORDINATE WITH THE PHOTO-METRIC PLANS.
 PLEASE SEE OTHER AREAS OF PLANS WHERE LIGHTING LEVELS
 WERE NOT ADDED TO EGRESS AREAS OF STAIRS AND PATHS.
 PLEASE SEE EXIT STAIRS AROUND POOL AREAS, AND OUTSIDE
 THE REAR OF BUILDING.
 PLEASE BE SURE ALL LEVELS ARE SHOWN UNDER NORMAL AND
 EMERGENCY LEVELS.
 PLEASE SEE REAR EXIST STAIRS AND REQUIRED BATTERY BACK
 UP FIXTURE OF SOME TYPE WILL BE REQUIRED.
  
 ** PREVIOUS REVIEW NOTE #10**
 PLEASE SEE THE STAIRS AS ONE OF THE LIGHTING FIXTURES
 ON EACH LEVEL WILL BE REQUIRED TO CONTAIN A BATTERY
 BACK UP FIXTURE OF SOME TYPE. PLEASE ALSO PROVIDE THE
 MINIMUM PHOTO-METRICS FOR STAIRS UNDER NORMAL AND UNDER
 EMERGENCY CONDITIONS.
 PLEASE SEE NFPA-101, 7.8., 7.9
 ** PREVIOUS REVIEW NOTE # 21
 PLEASE PROVIDE THE NORMAL AND EMERGENCY PHOTO-METRICS
 FOR ALL EGRESS PATHS. PLEASE KNOW THIS WOULD ALSO
 INCLUDE POOL DECK AREAS. ETC
 LS 101 7.8, 7.9
 FBC 106.1.2
  
 9) NOTE: PLEASE SEE PREVIOUS NOTE #14 AS NO
 MANUFACTURES SPECS/CUT SHEETS WERE SUBMITTED FOR
 REVIEW.
 PLEASE SUBMIT. FBC 106.1.2, NEC 110.3, 90.7
 ** PREVIOUS REVIEW NOTE #14 **
 PLEASE PROVIDE INFORMATION ON CAR LIFTS AND BE SURE
 EQUIPMENT INDICATES LISTING ON EQUIPMENT FROM A NRTL.
 110.3, 90.7
  
 10) NOTE: PLEASE SEE PREVIOUS NOTE #16 WHICH REQUESTED
 THE REQUIRED HEIGHT OF THE EPSS EQUIPMENT TO BE STATED
 ON PLANS FOR MINIMUM ELEVATION OF EQUIPMENT. PLEASE SEE
 THE RESPONSE PLACED A NOTE ON PLANS FOR THIS SECTION OF
 THE CODE TO BE MET. PLEASE KNOW THAT QUOTING THE CODE
 IN LIEU OF DESIGN DETAILS OR SPECIFIC INFORMATION IS
 NOT ACCEPTED BY THE FBC.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE ELEVATIONS FOR THE EPSS SYSTEM WHICH
 MUST MEET THE ELEVATIONS AS SET-FORTH ON THE 100YEAR
 STORM SURGE CHARTS OR *SLOSH* CHARTS PER CHAPTER 7,
 7.3.1 NFPA-110.
  
 11) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #25 WHICH
 REQUESTED THE MINIMUM WIND LOADS FOR POLES TO BE STATED
 ON PLANS AS WELL AS CALCULATIONS FOR THE POLES SPECIFIC
 TO THE INSTALLATION.
 PLEASE SEE THE RESPONSE TAKES THE REVIEW TO THE *S*
 SHEETS WHICH ONLY STATES THE DESIGNS (FOR PROJECT) ARE
 TO BE PER FBC EXPOSURE C ETC YET NO SPECIFIC
 INFORMATION WAS LOCATED FOR THESE.
 PLEASE PROVIDE MORE INFORMATION.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE WIND LOADS AND INFORMATION FOR SITE/ROOF
 TOP POLES WHICH ARE REQUIRED TO MEET FBC 140MPH. THIS
 WILL BE REVIEWED ONCE SUBMITTED BY THE STRUCTURAL
 REVIEWER. PLEASE KNOW THE EFFECTIVE PROJECTED AREA
 (EFA) OF FIXTURE.
 FBC 106.1.2
  
 12) NOTE: PLEASE SEE PREVIOUS NOTE #27 WHICH REQUESTED
 ALL ROOM AND AREA DESIGNATIONS TO BE PLACED ON PLANS.
 PLEASE SEE ONE OF THE MAIN LOCATIONS IS FOR
 DETERMINATION OF THE DINING ROOM/AREA CIRCUITING ALONG
 WITH OTHER AREAS FO THE LIKE AS STATED IN NEC 210.52B1.
 PLEASE SEE 210.11C1 AND 220.52 FOR LOADS AS THESE AREAS
 ARE NOT YET CONFIRMED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE TO PROVIDE ALL ROOM AND AREA
 DESIGNATIONS ON PLANS. PLEASE KNOW SOME AREA
 DESIGNATIONS ARE NEEDED TO DETERMINE ARE USE AND REVIEW
 FOR CIRCUITING CODE COMPLIANCE AND USE.
 FBC 106.1.2
  
 13) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #29. PLEASE
 SEE THE RESPONSE MENTIONS THE CONDUCTORS WERE ADJUSTED,
 HOWEVER BASED ON THE NEC 310.15B2A, 310.16 ETC THE SIZE
 OF THE CONDUCTORS FOR SOME OF THE FEEDERS PARTICULARLY
 THE FEEDERS TO REL AND RL ARE OF CONCERN. PLEASE SEE
 THESE FEEDERS AS SHOWN ARE NOT RATED FOR THE SIZE AND
 LOADS AS SHOWN.
 PLEASE SEE COMMENTS ALSO WITH RESPECT TO VOLTAGE DROP
 ETC WHICH WILL BE ADJUSTED.
 240.4, 310.16, ETC
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE COMPLETE DE-RATING CALCULATIONS FOR
 CONDUITS AND FEEDERS BEING RUN ACROSS ROOF-TOP AREA.
 PLEASE KNOW THE TYPE OF ROOF ALONG WITH OTHER FACTORS
 WILL HAVE AN AFFECT ON THE TEMPERATURE. PLEASE SEE NEC
 310.16, TABLES FOR DE-RATING AND THE NUMBER OF CURRENT
 CARRYING CONDUCTORS.
 THE FEEDERS AS SHOWN ON RISER AND PANELS FEEDING THESE
 OTHER PANELS ARE NOT OF SUFFICIENT SIZE AS SHOWN ON
 PLANS.
 PLEASE ADJUST.
 FBC 106.3.5.1.2, 106.1.2
 NEC 215.5, 215.3 ETC
  
 14) NOTE: PLEASE SEE PREVIOUS NOTE #30 WILL REMAIN AS
 THE NOTE ABOVE WHICH IS NOW #13 NEEDS ADJUSTMENT TO
 PLANS AND FEEDERS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE VOLTAGE DROP FOR THE SAME FEEDERS AS
 NOTED IN NOTE #29.
 PLEASE SEE FBC 13-413.ABC.1
 PLEASE ALSO PROVIDE WORST CASE VOLTAGE DROP FOR BRANCH
 CIRCUITS AND FEEDERS AS ON PLANS FOR LONGEST RUNS.
  
 15) NOTE: PLEASE SEE PREVIOUS NOTE #31. PLEASE SEE THE
 RESPONSE MENTIONS THAT A SMOKE DETECTOR DETAIL WAS
 ADDED TO FA SHEET. PLEASE SEE THERE MUST HAVE BEEN SOME
 MISCOMMUNICATION ON THE PREVIOUS REVIEW NOTE. PLEASE
 SEE THE DEVICES AS STATED AND SHOWN ON PLANS WOULD
 ACTUALLY BE SMOKE ALARMS.
 PLEASE SEE THE PLANS AND NOTES EVEN STATE THE DEVICES
 WILL INTERCONNECT AND SOUND AN ALARM FOR ALL DEVICES
 INSIDE UNIT. THIS MAKES THE DEVICE WHICH ARE SHOWN AS
 SD (SMOKE DETECTORS) ACTUALLY SA (SMOKE ALARMS). THIS
 WAS CONFIRMED LAST YEAR AT THE NFPA PANEL SECTION
 MEETING AS THE GENERAL ACCEPTED USE OF SD FOR SMOKE
 DETECTORS HAS BEEN ACCEPTED WHEN IN FACT THESE DEVICES
 SHOULD HAVE BEEN SA FOR SMOKE ALARMS. PLEASE ADJUST
 PLANS.
 PLEASE SEE IF THESE WERE INDEED *SMOKE DETECTORS* THESE
 WOULD REQUIRE OTHER EQUIPMENT ETC.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE NFPA-72, FBC FOR THE DEFINITIONS OF SMOKE
 DEVICES. PLEASE DETERMINE IF THESE ARE INDEED DEVICES
 WHICH ONLY DETECT AND DO NOT SOUND.
 IF DEVICES DETECT AND ONLY PROVIDE SIGNALING TO
 HORN/SIREN DEVICES THEN THESE WOULD BE SD/ SMOKE
 DETECTORS.
 IF DEVICES ARE 120V BATTERY BACK AS SHOWN ON PLANS
 WHICH DETECT AND SOUND, THEN THESE DEVICES WOULD BE
 CONSIDERED SA/ SMOKE ALARMS.
 PLEASE ADJUST PLANS.
 NFPA-72 11.5.1.1, 11.8.3
  
 16) NOTE: PLEASE SEE PREVIOUS NOTE #35 FOR ADJUSTMENT
 OF THE NOTES FOR SMOKE DEVICES AND PLACEMENT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INCLUDE NOTE ON PLANS FOR PLACEMENT OF SA/SD
 DEVICES PER NFPA-72 2002 11.5.1.1, 11.8.3
  
 17) NOTE:PLEASE CLARIFY RESPONSE TO COMMENT #38 FORM
 PREVIOUS REVIEW. THE NOTE WAS FOR ARC FAULT PROTECTION
 REQUIRED AND THE RESPONSE STATES ONLY BEDROOMS AND THE
 BATHROOM IS NOT INCLUDED? PLEASE SEE THE PREVIOUS
 COMMENT DID NOT REQUEST FOR BATHROOMS TO BE INCLUDED.
 THIS IS TO CLARIFY NOTE MADE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THAT ARC FAULT IS REQUIRED FOR ALL OUTLETS
 INCLUDINGRECETPS, LTS, FANS AND SMOKE ALARMS. PLEASE
 SEE 210.12.
  
 18) NOTE: PLEASE SEE PREVIOUS NOTE #42 WHICH REQUESTED
 FOR COORDINATION FO ALL CIRCUITS WITH THE PANEL
 SCHEDULES. PLEASE SEE 408.4. PLEASE SEE THE FOLLOWING
 TEXT IS EXTRACTED FROM THE NEC COMMENTARY AS THE USE OF
 GENERAL LIGHTING AND GENERAL RECEPTACLES ETC IS NOT
 PERMITTED. THIS IS PART OF THE REASON FOR COMMENT
 NUMBER 12 ABOVE.
 *
 SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANELBOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 PLEASE ADJUST CIRCUITING TO BE SPECIFIC TO ALL ROOMS
 AND AREAS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE COMPLETE ALL CIRCUITING ON PLANS AND CORRELATE
 WITH THE PANEL SCHEDULES AND OTHER CIRCUITS ON PLANS.
 PLEASE SEE THAT MOST OF THE CIRCUITS ARE SHOWN HOWEVER
 SEE REDLINED PLANS AND SEE 9, L8, L9 FOR SOME
 EXAMPLES.
 408.4, 310.16, 240.4.
 FBC 106.1.2
  
 19) NOTE: PLEASE SEE THIS IS A NEW NOTE. PLEASE SEE
 210.4B AS ALL CIRCUITS ON PANEL WHICH CONTAINS BREAKERS
 FEEDING THE SAME YOKE ON MULTI-WIRE BRANCH CIRCUITS
 REQUIRES A 2-POLE BREAKER. PLEASE ADJUST PANEL
 SCHEDULE.
  
 20) NOTE: PLEASE SEE PREVIOUS COMMENT #46. PLEASE SEE
 THE NOTE WAS MIS-TYPED WHICH SHOULD HAVE READ ( PLEASE
 PROVIDE ALL GENERATOR, ATS, FIRE PUMP AND FIRE PUMP
 CONTROLLER INFORMATION ON THE PLANS.
 FBC 106.3.5.1.2
  
 ** PREVIOUS REVIEW COMMENTS **
 PLEASE PROVIDE ALL GENERATOR, ATS, FIRE PUMP, FIRE
 PUMP CONTROLLER ON PLANS.
 FBC 106.3.5.1.2
  
 21) NOTE:PLEASE COORDINATE THE FIRE PUMP SIZE AND
 LOAD. PLEASE SEE NEC 430 TABLES AND THE LOAD SHOWN ON
 THE RISER LOAD SUMMARY.
 FBC 106.1.2
  
 22) NOTE: PLEASE SEE THE FEEDERS FROM THE MAIN
 ELECTRICAL ROOM RUNNING TO THE EAST ARE BEING SHOWN
 GOING THROUGH THE FIRE RATED EXIT CORRIDOR WHICH IS NOT
 PERMITTED. PLEASE SEE THIS IS A BUILDING CODE COMMENT.
 FBC 1019.1.2
  
 23) NOTE: PLEASE SEE RISER NOW HAS COMPLETED THE
 EQUIPMENT FOR MOST THE RETAIL SERVICE.
 PLEASE SEE THE RISER STILL SHOWS THIS AS MAIN #6, WHEN
 THE MAIN ELECTRICAL ROOM, LOAD SUMMARY ETC INDICATES
 THIS AS MAIN #5 WHICH IT IS.
 PLEASE ADJUST.
 230.2E
  
 24) NOTE: PLEASE SEE THE LOAD SUMMARY FOR THE RETAIL IS
 NOT COMPLETE FOR SPACE/RETAIL #5.
  
 25) NOTE: PLEASE SEE THE RISER DOES NOT GIVE ANY
 INFORMATION FOR NEW MAIN WHICH FEEDS TO NEW R5. PLEASE
 SEE NO OCP, SIZE, VOLTAGE, AIC RATINGS ETC IS SHOWN.
 PLEASE INCLUDE THE TAPPED FEEDERS FROM THE GUTTER AS
 NONE SHOWN ON RISER.
 PLEASE COMPLETE.
 230.70, 240, 240.21, 310.16,110.9 ETC.
  
 26) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS FOR
 RETAIL UNIT AND CORRELATE WITH THE PANEL SCHEDULE.
 EXAMPLE: A/C SYSTEM AND EQUIPMENT.
  
 27) NOTE: PLEASE SEE MISSING WALL FOR THIS SAME RETAIL
 #5 WHERE THERE ARE RECEPTACLES SHOWN AT THE EAST SIDE
 HOWEVER NO WALL IS PRESENT.
 FBC 106.1.2
  
 28) NOTE: PLEASE SEE THE EXIT LIGHT IN THIS RETAIL
 SPACE IS BEING SHOWN ON THE HOUSE PANEL WHICH SHOULD BE
 CIRCUITED PER 700.12F OF THE NEC.
  
 29) NOTE: PLEASE SEE MISSING SIGN CIRCUIT PER 600.5 AND
 LOAD REQUIRED FOR SIGN CIRCUIT.
  
 30) NOTE: PLEASE SEE MISSING SHOW WINDOW RECEPTACLES
 PER 210.62, LOADS PER 220.53 ETC.
 PLEASE COMPLETE.
  
 31) NOTE: PLEASE SEE THE OTHER FUTURE RETAIL SPACES
 WILL BE REQUIRED TO CONTAIN A MINIMUM LIGHT FIXTURE AND
 CONTROL.THIS WILL BE REQUIRED BY THE FIRE MARSHAL.
 PLEASE SEE LS 101 7.8. PLEASE SEE DEPENDING ON THE SIZE
 OF THE SPACE,AND FIRE MARSHAL REVIEW A BATTERY BACK
 UP LIGHT MAY BE REQUIRED. PLEASE SEE FBC
 13-415.1.ABC.1.1 AND .1.2 FOR AUTOMATED LIGHTING
 CONTROLS REQUIRED.
 PLEASE ADJUST PLANS. PLEASE BE SURE TO DELETE EXIT LT
 FROM RETAIL #5.
  
 32) NOTE: PLEASE SEE THE LOADS ON RDP ARE NOT COMPLETED
 AND PLEASE CORRELATE WITH THE SUMMARY ON E4.01. NEC
 220.
  
 33) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH REQUESTED
 FOR ALL CONTINUOUS LOADS TO BE SHOWN AT 125%. PLEASE
 SEE DUE TO SOME OF THE COMMENTS ABOVE THE NOTE REMAINS
 AND ADJUSTMENTS WILL BE NEEDED.
 PLEASE ALSO SEE THE ALL CONTINUOUS LOADS WHICH ARE THAT
 AS DEFINED AT 3 OR MORE HOURS ARE TO BE FIGURED. PLEASE
 SEE THIS WOULD INCLUDE MOTOR LOADS SUCH AS POOL PUMPS
 ETC.
 215.3, 230.42 ETC,.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE ALL CONTINUOUS LOADS AND LARGEST MOTOR
 LOADS AT 125% ON EACH PANEL AND THEN FOR THE SERVICE
 LOADS.
 230.42, 215.3 ETC.
 PLEASE SHOW IN LOAD CALCULATIONS
  
 34) NOTE: PLEASE SEE THE ELEVATOR ROOM LAYOUT OF
 DISCONNECTS DO NOT SEEM TO MEET 110.26 BASED ON THE
 SCALE ON PLANS.
 PLEASE ADJUST.
  
 35) NOTE: PLEASE SEE THE RESPONSE FOR PREVIOUS NOTE #
 18 MENTIONS TO SEE LETTER FROM MR. STEVEN FELLER PE.
 PLEASE SEE THAT NO LETTER IN THE SUBMITTED PACKAGE AND
 SUPPORTING DOCUMENTS COULD LOCATE ANY LETTER FOR A
 RESPONSE.
 THIS PREVIOUS NOTE WAS FOR THE MENTIONED HOUSE BILL
 7121 AND REQUIRED FUEL.
 PLEASE CLARIFY.
  
 36) NOTE: PLEASE KNOW ALL LOW VOLTAGE SYSTEMS ASSHOWN
 ON PLANS ARE REQUIRED TO BE UNDER SEPARATE PERMITS.
 PLEASE SEE THE CATV, PHONE, CAMERAS AS SHOWN MAY BE ON
 ONE PERMIT AND MAY REFERENCE BACK TO THESE PLANS
 HOWEVER THE VALUE AND PERMIT FEES FOR THIS SCOPE OF
 WORK WILL BE REQUIRED TO BE SEPARATE.
 PLEASE SEE THE LOW VOLTAGE FOR FIRE ALARM WILL REQUIRE
 SEPARATE PLANS FOR PERMITTING.
 PLEASE SEE THAT ANY LOW VOLTAGE SECURITY/BURGLAR ALARMS
 SYSTEMS IS SEPARATE PERMIT AS THESE SYSTEMS ARE
 REPORTED THROUGH THE POLICE DEPT.
 ** THIS NOTE WAS GIVEN FOR INFORMATIONAL PURPOSE AND NO
 CHANGES ARE NEEDED TO PLANS.
  
 37) NOTE: PLEASE SEE AS SOME COMMENTS ARE REPEATED FROM
 PREVIOUS REVIEW, PLEASE SEE COPY OF FS 553.80(2)(B) IS
 GIVEN AS A NOTICE ONLY AT THIS TIME.
  
 ** PLEASE KNOW AS THERE ARE SOME ITEMS NOT YET
 SUBMITTED FOR REVIEW, THERE ARE ITEMS WHICH CAN NOT BE
 REVIEWED AT THIS TIME.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-07-09 07:29:452007-07-09 07:29:45
 REVIEW IN PROGRESS
2007-07-07 19:16:472007-07-07 19:16:47
 ON ROLL OF ELECTRICAL AN ARCHITECTURAL IN ELEC FOR
 REVIEW. REMOVED FROM INCOMING AND WILL BE RETURNED TO
 INCOMING WAITING FOR COMM BOARD ONCE ELECTRICAL REVIEW
 IS COMPLETED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-22 Cont ID  
Sent By dpalmer Date 2007-03-22 Time 19:42 Rev Time 0.00
Received By dpalmer Date 2007-03-11 Time 13:21 Sent To  
Notes
2007-03-22 19:47:312007-03-22 19:47:31
  
 ****** UNSAT ******
  
  
 *** DATURA & OLIVE ***
  
 ** PLEASE KNOW THAT AS SOME INFORMATION HAS NOT BEEN
 SUBMITTED FOR REVIEW YET THERE MAY VERY WELL BE NEW
 COMMENTS ON THE NEXT REVIEW.
  
 ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1
 IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE
 ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY
 THE CITY OF WEST PALM BEACH.
  
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
 2003 NFPA-20
 2002 NFPA-110
 ** SOME OP THESE CODES MAY BE PRESENT ON PLANS HOWEVER
 PLEASE SEE PLANS FOR ELECTRICAL AS THERE ARE SEVERAL
 CODE SECTIONS WHICH ARE REFLECTED ON PLANS FROM THE
 PREVIOUS CODES AND ANY NEW CODE SECTIONS SHOULD BE
 REFLECTED.
  
 2) NOTE: PLEASE SEE THE ARCHITECTURAL FIRM TITLE BLOCKS
 ARE MISSING INFORMATION AS REQUIRED PER FLORIDA
 ADMINISTRATIVE CODE 61G1-16.004 AS REQUIRED UNDER
 FLORIDA STATUTES 481.219
  
 3) NOTE: PLEASE SEE LANDSCAPE PLANS WHICH CONTAIN A
 *RUBBER STAMP* FOR THE REQUIRED ORIGINAL SIGNATURE.
 THIS IN PROHIBITED UNDER FS 481.221 AND MUST BE AN
 ORIGINAL SIGNATURE AND DATE.
  
 4) NOTE: PLEASE SEE THE SHEETS WHICH ARE DONE BY STEVEN
 FELLER SHALL CONTAIN THE LEGAL SIGNATURE OF THE
 INDIVIDUAL AS RECOGNIZED, ON FILE, AND ON RECORD BY
 THIS OFFICE. PLEASE SEE FS 471.025 AND FAC 61G15-23.002
 WHICH REQUIRES ALL DOCUMENTS TO CONTAIN THE ORIGINAL
 SIGNATURE, DATE AND SEAL.
 PLEASE SEE OTHER DOCUMENTS SUBMITTED AS THESE ARE ALSO
 NOT SIGNED WITH SIGNATURE FROM THE ENGINEER OF RECORD
 KNOWN TO THIS OFFICE.
 PLEASE KNOW THAT THIS OFFICE HAS GIVEN NOTICE ON
 SEVERAL OCCASIONS FOR THIS SAME ISSUE AND PLANS MAY BE
 RETAINED BY THIS OFFICE FOR REVIEW FROM THE FLORIDA
 BOARD OF PROFESSIONAL ENGINEERS.
  
 5) NOTE: PLEASE KNOW THAT ALL PLANS SHALL CONTAIN
 ORIGINAL SIGNATURES, DATES AND RAISED SEALS FROM ALL
 DESIGN PROFESSIONALS. PLEASE SEE THE ARCHITECTURAL
 SHEETS SEEMED TO BE *SIGNED* WITH INITIALS, AND ARE NOT
 DATED. IF THIS IS INDEED THE LEGAL SIGNATURE OF THE
 DESIGN PROFESSIONAL, PLEASE SUBMIT A SIGNED, DATED AND
 SEALED LETTER FOR SIGNATURE VERIFICATION. (FS 471.025,
 481.221) THIS WILL BE PLACED IN OUR SIGNATURE FILE FOR
 FUTURE REFERENCE.
 PLEASE BE SURE LETTER IS PROPERLY NOTARIZED PER FS
 117.05 FOR NOTARIES.
  
 6) NOTE: PLEASE SEE FBC 2004 W/ 2006 FOR THE FLORIDA
 ENERGY CODE AND RELEVANT CODES FOR THIS BUILDING.
 PLEASE SEE THERE ARE AREAS WHICH DO NOT SHOW LIGHTING
 CONTROLS AS REQUIRED PER 13-415.1.ABC.1.1, .1.2 AND
 .1.3.
 PLEASE SEE THAT THE ENERGY CALCULATIONS DO NOT INDICATE
 AUTOMATED CONTROLS FOR LIGHTING. SHOWS MANUAL ON/OFF
 FOR CONTROL METHODS.
 PLEASE SEE 13-415.2 FOR PERFORMANCE OF INTERIOR
 LIGHTING.
 PLEASE PROVIDE INFORMATION IN DETAIL FOR THIS. PLEASE
 SEE THE LIGHTING SHOWN ON PLANS DOES NOT CORRELATE WITH
 THE ENERGY CALCULATIONS.
 PLEASE SEE ALL OF THE REVISED CHAPTER 13 ITEMS ALONG
 WITH THE EXISTING IN THE 2004.
  
 7) NOTE: PLEASE SEE THAT THE MAIN ELECTRICAL ROOM AND
 ELECTRICAL EQUIPMENT LOCATED IN THE GENERATOR ROOM
 SHALL BE GONE OVER WITH THE FIRE MARSHAL'S OFFICE.
 PLEASE SEE AT THIS TIME, DIRECT ACCESS TO THE MAIN
 ELECTRICAL ROOM THROUGH ANY RATED CORRIDOR, OR DIRECT
 DOOR ACCESS IS NOT SHOWN AT THIS TIME AND FURTHER
 REVIEW WILL BE NEEDED. PLEASE SEE THE LOCATION OF THE
 EDP WILL ALSO BE NOTED IN LATER NOTES FOR THE LOCATION
 OF CONTROL OF EM LOADS IN THE EVENT OF AN EMERGENCY.
 ACCESS AND LOCATION OF THIS EQUIPMENT SHOULD BE
 CONSIDERED AS DURING AN EVENT; ANY FIRE DEPARTMENT
 PERSONNEL MUST ACCESS ROOM AND CONTROL EQUIPMENT WHILE
 THE GENERATOR IS RUNNING AT CAPACITY. THE NOISE,
 LOCATION, HEAT, FUEL AND DISTRACTIONS COULD CREATE A
 HAZARD TO THESE PERSONS AND NOT BEING ABLE TO CONTROL
 ITEMS IN ORDER ETC. PLEASE CALL TO GO OVER THESE
 LOCATIONS ONCE ALL REVIEWS ARE DONE. THIS OFFICE WILL
 CONSULT WITH THE FM OFFICE AT A LATER DATE. NFPA-110
 7.2
  
 8) NOTE: PLEASE SUBMIT THE MANUFACTURE'S SPECS/CUT
 SHEETS FOR THE FOLLOWING.FIRE PUMP, FIRE PUMP
 CONTROLLER, GENERATOR, ATS, FUEL TANK(S).
 PLEASE KNOW ANY OTHER EQUIPMENT SPECS MAY BE REQUESTED
 FROM OTHER TRADES.
 110.3, 90.7.
 FBC 106.1.2
  
 9) NOTE: PLEASE SEE THE FOLLOWING LOCATIONS SHALL
 CONTAIN EMERGENCY BATTERY BACK UP LIGHTS OF SOME KIND.
  
 GENERATOR ROOM (TO A LEVEL OF 30FT CANDLES), FIRE
 COMMAND ROOM, MAIN ELECTRICAL ROOM, METER CENTER ROOMS,
 ELEVATOR EQUIPMENT ROOM(S).
 PLEASE SEE NEXT NOTE WITH RESPECT TO STAIRS.NFPA-70
 110.26, 700.16, 700.12E, NFPA-110 7.3, NFPA-20 5.12.3,
 AND .4, NFPA-72 CHAPTER 2 FOR FCRM.
  
 10) NOTE: PLEASE SEE THE STAIRS AS ONE OF THE LIGHTING
 FIXTURES ON EACH LEVEL WILL BE REQUIRED TO CONTAIN A
 BATTERY BACK UP FIXTURE OF SOME TYPE. PLEASE ALSO
 PROVIDE THE MINIMUM PHOTO-METRICS FOR STAIRS UNDER
 NORMAL AND UNDER EMERGENCY CONDITIONS.
 PLEASE SEE NFPA-101, 7.8., 7.9
  
 11 NOTE: PLEASE PROVIDE NOTES FOR FAIL SAFE OPERATION
 OF GATES/DOORS WHICH MAY NOT INTERFERE WITH EGRESS IN
 THE EVENT OF POWER FAILURE.
 PLEASE SEE NFPA-101 CHAPTER 7, 7.1.9,7.2.1.5.
  
 12) NOTE: PLEASE SEE DOORS ON WEST WALL WHICH SEEM TO
 SWING IN PATH OF EGRESS. PLEASE ALSO VERIFY THE MAKE UP
 AIR, AND/OR EXHAUST ALONG THIS SAME AREA OF EGRESS.
 PLEASE SEE THAT THIS MAY ALSO BE IN THE COMMENTS FROM
 OTHER TRADES.
 PLEASE VERIFY WITH ALL TRADES AND REVIEWER(S).
 FBC 106.1.2
  
 13) NOTE: PLEASE PLACE A SCHEDULE/ LIST FOR ALL
 COMPONENTS IN THE FIRE COMMAND ROOM AS REQUIRED PER
 NFPA-101 11.8.5
  
 14) NOTE: PLEASE PROVIDE INFORMATION ON CAR LIFTS AND
 BE SURE EQUIPMENT INDICATES LISTING ON EQUIPMENT FROM A
 NRTL.
 110.3, 90.7
  
 15) NOTE: PLEASE BE SURE ALL DEVICE AND LEVELS FOR
 HORNS AND STROBES MEET FBC ADA 11-4.28, .1, .2 AND
 .3(4).
  
 16) NOTE: PLEASE PROVIDE ELEVATIONS FOR THE EPSS SYSTEM
 WHICH MUST MEET THE ELEVATIONS AS SET-FORTH ON THE
 100YEAR STORM SURGE CHARTS OR *SLOSH* CHARTS PER
 CHAPTER 7, 7.3.1 NFPA-110.
  
 17) NOTE: PLEASE PROVIDE INFORMATION ON FUEL
 CONSUMPTION ON GENERATOR FOR 100% LOAD OF THE FIRE PUMP
 AND ALL EMERGENCY SYSTEMS PER 700 AND 701.
 PLEASE SEE NFPA-110, NFPA-20 9.6.2.2
  
 18) NOTE: PLEASE SEE THE NEW FLORIDA STATE STATUTES
 WITH RESPECT TO THE NEW HOUSE BILL 7121 WHICH WAS
 SIGNED INTO LAW JULY OF 07.
 PLEASE SEE THERE ARE SEVERAL STATUTES WHICH WERE
 AFFECTED. PLEASE SEE THAT A INDUSTRY BULLETIN IS BEING
 PLACED IN WITH THE REVIEW NOTES AS ADDITIONAL
 INFORMATION.
 *ONCE THIS INFORMATION IS READ AND STATUTES REVIEWED,
 PLEASE PROVIDE ALL INFORMATION AS REQUIRED ON PLANS AND
 DOCUMENTATION FOR REVIEW.
 PLEASE KNOW THAT SOME OF THIS INFORMATION WILL ALSO BE
 NEEDED BY THE FIRE MARSHAL, STATE BOARD FOR ELEVATORS
 ETC.
  
 19) NOTE: PLEASE BE SURE THE FOLLOWING STATEMENT IS
 PLACED ON PLANS AS REQUIRED PER FBC 109.3.6.4.4 PLEASE
 SEE A STATEMENT OF SIMILAR WORDING IS ALREADY ON THE
 LIFE SAFETY PLANS.
 " TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE BUILDING CODES AND THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER
 633, FLORIDA STATUTES"
  
 20) NOTE: PLEASE SEE PART OF FIRE PUMP FEEDS FROM FPL
 APPEARS TO BE ROUTED THROUGH ONE OF THE CORRIDORS ON
 SHEET E1.01. PLEASE CLARIFY THIS AS THE RISER DOES NOT
 SHOW DETAIL FOR THIS.
 PLEASE SEE 695.6A.
  
 21) NOTE: PLEASE PROVIDE THE NORMAL AND EMERGENCY
 PHOTO-METRICS FOR ALL EGRESS PATHS. PLEASE KNOW THIS
 WOULD ALSO INCLUDE POOL DECK AREAS. ETC
 LS 101 7.8, 7.9
 FBC 106.1.2
  
 22) NOTE: PLEASE PROVIDE NOTE FOR POOL AREA LIGHTS:
 LIGHTING SHALL BE INSTALLED A MINIMUM OF 5FT FROM
 WATERS EDGE FOR 120V W/GFI PROTECTION AND A MINIMUM OF
 10FTFOR LOW VOLTAGE TYPE FIXTURES. (WORDS TO THIS
 AFFECT)
 680.22, 411.4B
  
 23) NOTE: PLEASE PROVIDE NOTE FOR POOL AREA AND THE
 EQUAL-POTENTIAL BONDING GRID WHICH IS REQUIRED PER
 680.26. PLEASE KNOW THE POOL PERMIT WILL BE UNDER A
 SEPARATE PERMIT, HOWEVER AS THE STRUCTURAL ELEMENTS
 MOST LIKELY WILL BE IN PLACE BEFORE PERMITTING OF POOL,
 PLEASE INCLUDE NOTE AT THIS TIME.
  
 24) NOTE: PLEASE INCLUDE NOTE FOR ANY LIGHTNING
 PROTECTION SYSTEMS SHALL MEET NFPA-780. (EVEN WHEN
 PERMITTED SEPARATELY OR IF A SYSTEM IS NOT GOING TO BE
 INSTALLED AT THIS TIME).
  
 25) NOTE: PLEASE PROVIDE WIND LOADS AND INFORMATION FOR
 SITE/ROOF TOP POLES WHICH ARE REQUIRED TO MEET FBC
 140MPH.
 THIS WILL BE REVIEWED ONCE SUBMITTED BY THE STRUCTURAL
 REVIEWER. PLEASE KNOW THE EFFECTIVE PROJECTED AREA
 (EFA) OF FIXTURE.
 FBC 106.1.2
  
 26) NOTE: PLEASE PROVIDE NOTE FOR NO NIGHT-TIME OR DUSK
 TO DAWN SWIMMING PERMITTED UNLESS THE INTENT IS THAT
 NIGHT-TIME SWIMMING WILL BE ALLOWED. IF THIS IS THE
 CASE PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR POOL AREA
 WHICH WILL BE REQUIRED TO BE STAMPED BY THE PALM BEACH
 COUNTY HEALTH DEPARTMENT.
 FBC 106.1.2
  
 27) NOTE: PLEASE BE SURE TO PROVIDE ALL ROOM AND AREA
 DESIGNATIONS ON PLANS. PLEASE KNOW SOME AREA
 DESIGNATIONS ARE NEEDED TO DETERMINE ARE USE AND REVIEW
 FOR CIRCUITING CODE COMPLIANCE AND USE.
 FBC 106.1.2
  
 28) NOTE: PLEASE PROVIDE MORE INFORMATION FOR ELEVATOR
 ROOMSAND THE DEDICATE CIRCUITS REQUIRED PER 620.22,
 23 AND 24. SOME OF THESE ARE SHOWN ON PLANS, HOWEVER
 NOT ALL.
 PLEASE SEE COMMENT #9 ABOVE WITH RESPECT TO LIGHTING
 REQUIRED. PLEASE ALSO SEE THAT THE ROOF TOP APPEARS TO
 SHOW ANOTHER AREA WHICH CONTAINS MAINS FOR EACH OF THE
 ELEVATORS, YET THE PLANS DO NOT APPEAR TO SHOW ANY ROOM
 FOR EQUIPMENT?? PLEASE CLARIFY THIS AREA AS REDLINED ON
 PLANS. IF THERE IS A SECOND ROOM, PLEASE PROVIDE
 INFORMATION AND ELECTRICAL AS REQUIRED FOR ROOM. FBC
 106.1.2
  
 29) NOTE: PLEASE PROVIDE COMPLETE DE-RATING
 CALCULATIONS FOR CONDUITS AND FEEDERS BEING RUN ACROSS
 ROOF-TOP AREA. PLEASE KNOW THE TYPE OF ROOF ALONG WITH
 OTHER FACTORS WILL HAVE AN AFFECT ON THE TEMPERATURE.
 PLEASE SEE NEC 310.16, TABLES FOR DE-RATING AND THE
 NUMBER OF CURRENT CARRYING CONDUCTORS.
 THE FEEDERS AS SHOWN ON RISER AND PANELS FEEDING THESE
 OTHER PANELS ARE NOT OF SUFFICIENT SIZE AS SHOWN ON
 PLANS.
 PLEASE ADJUST.
 FBC 106.3.5.1.2, 106.1.2
 NEC 215.5, 215.3 ETC
  
 30) NOTE: PLEASE PROVIDE VOLTAGE DROP FOR THE SAME
 FEEDERS AS NOTED IN NOTE #29.
 PLEASE SEE FBC 13-413.ABC.1
 PLEASE ALSO PROVIDE WORST CASE VOLTAGE DROP FOR BRANCH
 CIRCUITS AND FEEDERS AS ON PLANS FOR LONGEST RUNS.
  
 31) NOTE: PLEASE SEE NFPA-72, FBC FOR THE DEFINITIONS
 OF SMOKE DEVICES. PLEASE DETERMINE IF THESE ARE INDEED
 DEVICES WHICH ONLY DETECT AND DO NOT SOUND.
 IF DEVICES DETECT AND ONLY PROVIDE SIGNALING TO
 HORN/SIREN DEVICES THEN THESE WOULD BE SD/ SMOKE
 DETECTORS.
 IF DEVICES ARE 120V BATTERY BACK AS SHOWN ON PLANS
 WHICH DETECT AND SOUND, THEN THESE DEVICES WOULD BE
 CONSIDERED SA/ SMOKE ALARMS.
 PLEASE ADJUST PLANS.
 NFPA-72 11.5.1.1, 11.8.3
  
 32) NOTE: PLEASE SEE WHAT APPEARS TO BE MISSING GFI
 RECEPTACLES ON SOME PENINSULAS IN KITCHENS PER
 210.52C1-5. PLEASE SEE LOCATION OF SOME DO NOT SEEM TO
 MEET THE DISTANCE PERMITTED.
 PLEASE SEE UNIT #4, #5 WHICH SHOW MORE THAN 6INCH
 OVERHANG.
 PLEASE SEE THAT THERE ARE OTHER UNITS WHICH ARE ALSO
 MISSING SOME COVERAGE PER ABOVE. PLEASE GO OVER PLANS
 AND SEE REDLINED PLANS FOR SOME OF THESE WHICH MAY BE
 MARKED ON REVIEWED SET.
  
 33) NOTE: PLEASE SEE SOME UNITS WHICH DO NOT APPEAR TO
 SHOW ANY LIGHTING FIXTURE IN BEDROOMS. PLEASE SEE
 210.70, LS 7.8 WHICH WILL REQUIRE A LIGHT FIXTURE IF
 SOME SORT INSTALLED FOR FINAL.
  
 34) NOTE: PLEASE SEE UNIT #5, AS THE CLOSET IN
 DEN/BEDROOM #3 SEEMS TO SHOW A GFI IN CLOSET? PLEASE
 CLARIFY.
 FBC 106.1.2
  
 35) NOTE: PLEASE INCLUDE NOTE ON PLANS FOR PLACEMENT OF
 SA/SD DEVICES PER NFPA-72 2002 11.5.1.1, 11.8.3
  
 36) NOTE: PLEASE SEE UNIT #6 WHICH APPEARS TO SHOW A
 FLOOR BOX IN THE DOORWAY WHICH IS A TRIPPING HAZARD.
 PLEASE SEE 210.52 FOR LOCATIONS WHICH ARE PROHIBITED.
  
 37) NOTE: PLEASE SEE 210.52D AS THE GFI RECEPTACLE IN
 BATHROOMS ARE REQUIRED TO CONTAIN THE DEVICE WITHIN 3FT
 OF THE SINK EDGE. PLEASE KNOW THAT THE CROSSING OVER
 ONE SINK TO REACH THE DEVICE ON THE OTHER SIDE IS NOT
 PERMITTED. PLEASE EITHER ADD A DEVICE OR RELOCATE.
 PLEASE SEE UNIT #7 FOR EXAMPLE. THIS IS NOT AN ISSUE IN
 ALL UNITS.
  
 38) NOTE: PLEASE SEE THAT ARC FAULT IS REQUIRED FOR ALL
 OUTLETS INCLUDINGRECETPS, LTS, FANS AND SMOKE
 ALARMS.
 PLEASE SEE 210.12.
  
 39) NOTE: PLEASE SEE UNIT H FOR 10FT OF HALLWAY PER
 210.52H
  
 40) NOTE: PLEASE SEE SOME WALLS/UNITS MISSING
 RECEPTACLES FOR WALL SPACES.UNITS L-9, 9,PLEASE SEE
 210.52. EXAMPLE FOR SOME ARE REDLINED ON PLANS.
  
 41) NOTE: PLEASE SEE UNIT L-8 WHICH PANEL SCHEDULE
 CALLS CIRCUIT #23 AS A BEDROOM. THIS IS NOT CLEAR AS
 THE ROOM IS APPROXIMATELY 6FT BY 10FT AND IS RIGHT OFF
 THE DINING/ KITCHEN AREA WITH NO DOOR?
 PLEASE CLARIFY THIS.
  
 42) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND
 CORRELATE WITH THE PANEL SCHEDULES AND OTHER CIRCUITS
 ON PLANS.
 PLEASE SEE THAT MOST OF THE CIRCUITS ARE SHOWN HOWEVER
 SEE REDLINED PLANS AND SEE 9, L8, L9 FOR SOME
 EXAMPLES.
 408.4, 310.16, 240.4.
 FBC 106.1.2
  
 43) NOTE: PLEASE PROVIDE NOTES ON ELECTRICAL ROOMS/FIRE
 COMMAND ROOMS SHEETS ALONG WITH THE RISER SHEETS FOR
 REQUIREMENTS FOR SIGNAGE FOR ALL SERVICES, MAINS,
 LOCATIONS.
 230.2E, 700.8, 701.9 ETC
  
 44) NOTE: PLEASE BE SURE TO CORRELATE LABELING OF ALL
 UNITS ON RISER WITH PANELS. PLEASE PROVIDE THE OCP FOR
 EACH UNIT ON METER SCHEDULE OR SCHEDULE OF SOME KIND
 FOR EACH.
 NEED FOR REVIEW OF CODE COMPLIANCE FOR EACH UNIT
 FEEDERS ETC
 215.5, 240.4,
 FBC 106.3.5.1.2
  
 45) NOTE: PLEASE SEE THAT THE EDP WILL REQUIRE A MCB AS
 THE POWER BEING SHUT OFF FROM THE GENERATOR CAN NOT BE
 VERIFIED. PLEASE KNOW THAT THE DISCONNECTING MEANS
 SHALL BE READILY ACCESSIBLE WITHOUT EXPOSING ANY
 PERSONS TO LIVE PARTS. 110.27.
 230.70, 701, 700 ETC.
 ADDITIONAL INFORMATION IS NEEDED, AND PLEASE KNOW ONE
 CONSULTATION IS DONE BY THIS OFFICE WITH THE FIRE
 MARSHAL FOR LOCATION OF SAID EQUIPMENT SHUT DOWN/EDP
 THEN THIS CAN BE GONE OVER WITH THE ENGINEERS/DESIGNERS
 OF PROJECT.
  
 46) NOTE: PLEASE PROVIDE ALL GENERATOR, ATS, FIRE PUMP,
 FIRE PUMP CONTROLLER ON PLANS.
 FBC 106.3.5.1.2
  
 47) NOTE: PLEASE SEE THE SERVICE ENTRANCE CONDUCTORS
 FOR THE FIRE PUMP ARE SHOWN RATED FOR 205AMPS, YET THE
 LOAD IS SHOWN HIGHER AT 221 AMPS. PLEASE SEE 430.50,
 AND SIZING OF THE CONDUCTORS WHICH ARE REQUIRED TO BE
 @125%.
 430.22, 230.208, 240.4, 310.16 ETC.
 PLEASE SEE THE CONDUCTORS FROM THE GENERATOR ARE SIZE
 FOR MORE THAN ONE RUN OF THE SAME SIZE CONDUCTORS.
  
 48) NOTE: PLEASE SEE JUST BELOW THE LOAD SUMMARY ON
 SHEET 4.01 WHICH CONTAINS AN *AND MAG ONLY CB. PLEASE
 SEE THE LOAD SUMMARY DOES NOT INDICATE ANY * ON ANY OF
 THE ITEMS ABOVE THIS NOTE.
 PLEASE CLARIFY THIS NOTE.
 FBC 106.1.2
  
 49) NOTE: PLEASE SEE THE MAIN #5 FOR ONE 100AMP RETAIL
 SERVICE IS NOT BEING PERMITTED AT THIS TIME UNDER THE
 EXCEPTIONS OF 230.2.
 PLEASE KNOW THAT THIS SINGLE TENANT FEED WILL BE
 REQUIRED TO COME FROM WHAT IS MAIN #6 AT THIS TIME
 WHICH WILL BE REQUIRED TO BECOME MAIN #5 FOR RETAIL.
 PLEASE SEE THE FOLLOWING COMMENT WITH RESPECT TO WHAT
 IS BEING SHOWN NOW FOR MAIN 6.
  
 50) NOTE: PLEASE SEE RISER WHICH CURRENTLY SHOWS MAIN
 #6 AS BEING FUTURE HOWEVER THE RISER SHOWS CONDUITS AND
 SERVICE ENTRANCE CONDUCTORS BEING INSTALLED AT THIS
 TIME? PLEASE KNOW THAT ALL EQUIPMENT MUST BE INSTALLED
 IN ITS COMPLETENESS IN ORDER FOR THE CONDUCTORS TO BE
 TERMINATED IN REQUIRED FASHION.
 PLEASE SEE RISER WHICH ACTUALLY SHOWS THE GUTTER BEING
 INSTALLED AT THIS TIME? HOW IS THIS POSSIBLE? PLEASE
 SEE THAT THE MAIN WHICH IS SHOWN IN THE MAIN ELECTRICAL
 ROOM NEXT TO THE EMERGENCY MAIN WILL NOT BE PERMITTED.
 THIS MAIN #6 WHICH WILL BECOME MAIN #5 WILL BE REQUIRED
 TO BE MOVED/RELOCATED.
 PLEASE ALSO SEE THE SCHEDULE FOR THIS RDP SHOWS THIS A
 BEING A MLO PANEL??
 PLEASE SEE ELECTRICAL PLANS INDICATE A MAIN? PLEASE
 ALSO KNOW A MAIN WILL BE REQUIRED TO GRANT THE
 ADDITIONAL SERVICE AS SHOWN.
 PLEASE SEE 230.70, 230.71, 230.72, 230.2.
 PLEASE KNOW IF THIS SERVICE IS GOING TO BE INSTALLED
 AND DEPENDING TO WHAT POINT THE EQUIPMENT WILL BE
 INSTALLED AT THIS TIME WILL DETERMINE WHAT WILL BE
 REQUIRED TO BE SHOWN. PLEASE KNOW IT APPEARS THE MAIN,
 AND GUTTER AT A MINIMUM WILL BE REQUIRED AT THIS TIME.
 PLEASE KNOW IF THIS IS THE CASE, PLEASE INCLUDE THE
 CONDUCTORS FROM THIS MAIN TO GUTTER. 310.16, 240.4,
 250.110, 250.122, 250.24B ETC.
 ** PLEASE KNOW THAT THERE ARE MANY ITEMS WHICH MAY NOT
 BE KNOWN AT THIS TIME DUE TO CHANGES IN SERVICE(S) FROM
 NOTES #49 AND #50.
  
 51) NOTE: PLEASE PROVIDE MORE INFORMATION ON WHICH
 CONDUCTORS ARE GOING TO BE COPPER. PLEASE SEE NOTE ON
 PANEL PLANS MENTIONS ALL CONDUCTORS ARE GOING TO BE
 ALUMINUM UNLESS OTHER WISE NOTED, YET THE FOLLOWING
 NOTE MENTIONS ALL GROUNDS TO BE COPPER? PLEASE CLARIFY
 WHAT CONDUCTORS ARE GOING TO BE COPPER AND ALUM. PLEASE
 KNOW AT THAT NO GROUNDING ELECTRODE SYSTEMS OR
 CONDUCTORS TO THIS SYSTEM WILL BE PERMITTED TO BE
 ALUM.
 PLEASE SEE 110.3, 90.4
  
 52) NOTE: PLEASE SEE THAT THE RISER SHEET CONTAIN A
 NOTE #1 AT THE GENERATOR WHICH POINTS TO THE BASE OF
 THE UNIT, HOWEVER THE NOTE #1 IS FOR VERTICAL SUPPORT
 OF CONDUCTORS?
 PLEASE COORDINATE.
 FBC106.1.2
  
 53) NOTE: PLEASE INDICATE AMPERAGE ON METER CENTERS AND
 FOR OVER CURRENT PROTECTION TO UNITS.
 240.4, 310.16, 230.94 ETC.
 FBC 106.1.2
  
 54) NOTE: PLEASE SEE LOAD CALCULATIONS AND THE SECTION
 OF THE CODES IN DIFFERENT PLACES WHICH ARE FROM THE
 PREVIOUS CODE. PLEASE SEE THE 2005 NEC AND UPDATE CODE
 SECTIONS.
 FBC 106.1.2
  
 55) NOTE: PLEASE SEE THE CONDUCTORS WHICH ARE SHOWN
 GOING TO WHAT IS NOW BEING SHOWN AS MAIN #6 IS ONLY
 RATED FOR 1000 AMPS, YET THIS EQUIPMENT WILL HAVE A
 MAIN OF 1200AMPS OR MORE.
 PLEASE SEE 240.4C FOR DEVICES RATED OVER 800AMPS.
  
 56) NOTE: PLEASE KNOW AS NOTICE FOR FUTURE RETAIL
 TENANT METERS, AS THESE WILL BE REQUIRED TO CONTAIN
 *FLOATING NEUTRAL KITS* AS THE BONDING WILL BE DONE AT
 THE FIRST MEANS OF DISCONNECT PER 250.24B AND THE
 EQUIPMENT GROUNDING WILL BE FOLLOW.
 PLEASE KNOW THAT THE NEUTRALS AND EQUIPMENT GROUNDING
 WILL BE REQUIRED TO BE SEPARATED TO AVOID OBJECTIONABLE
 CURRENTS.
 250.6
  
 57) NOTE: PLEASE INDICATE ALL CONTINUOUS LOADS AND
 LARGEST MOTOR LOADS AT 125% ON EACH PANEL AND THEN FOR
 THE SERVICE LOADS.
 230.42, 215.3 ETC.
 PLEASE SHOW IN LOAD CALCULATIONS.
  
 58) NOTE: PLEASE SEE THE FEEDERS TO PANEL *HA* ARE ONLY
 RATED FOR 100AMPS, AND THESE ARE ON A 150AMP BREAKER
 FOR OVER CURRENT PROTECTION.
 PLEASE SEE 240.4 AND 310.16 (SHOWN AS ALUM).
  
 59) NOTE: PLEASE SEE THE FEEDERS TO PANEL *P* AS THESE
 ARE SHOWN AS 100AMP RATED FEEDERS ON OVER CURRENT
 PROTECTION WHICH IS HIGHER AT 150AMPS.
 PLEASE CORRELATE AND ADJUST PER 240.4, 310.16. (SHOWN
 AS ALUM, EVEN AS COPPER AND #1, THESE WOULD NOT BE OF
 SUFFICIENT SIZE).
  
 60) NOTE: PLEASE KNOW THAT MANY LOCATIONS MAY HAVE BEEN
 REDLINED ON ONE SET OF THE PLANS, HOWEVER PLEASE DO NOT
 RELY ON THESE MARK UPS FOR ALL LOCATIONS OR
 CORRECTIONS.
 PLEASE BE SURE TO GO OVER PLANS IN DETAIL AS THERE MAY
 BE ITEMS NOT YET IDENTIFIED.
  
 NOTE ADDED 3/29
  
 61) NOTE: PLEASE SEE 422.13 AS THE LOADS FOR STORAGE
 TYPE WATER HEATERS SHALL BE SHOWN AND FIGURED AT 125%.
 PLEASE SEE THIS CHANGE IN THE 2005 NEC.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-03-21 19:57:532007-03-21 19:57:53
 REVIEW TO CONTINUE AND BE COMPLETE ON 3/22/07 NOTES TO
 FOLLOW AS PLANS WILL BE GOING TO A *F* STATUS.
2007-03-12 07:47:34REVIEW CONTINUED
2007-03-11 13:21:55ONE ROLL AND SUBMITTALS IN ELEC FOR REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2007-08-22 Cont ID  
Sent By rchokshi Date 2007-08-22 Time 10:58 Rev Time 0.00
Received By rchokshi Date 2007-08-22 Time 10:36 Sent To  
Notes
2007-08-22 10:57:57PLEASE PROVIDE FOLLOWING INFO:
  
 WE HAVE A NEW FOLLOWING REQUIREMENTS, PLEASE RESPOND
 THIS TOO.
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 THIS IS KIND OF A NEW REQUIREMENTS. YOU MAY HAVE
 ALREADY APPLIED FOR NOI. JUST SEND US A COPY OFNOI
 THAT YOU APPLY AT FDEP, NPDES STORM WATER SECTION,.
  
 2.PLEASE SHOW IN YOUR CALCULATION THAT YOUR FIRST FLOOR
 ELEVATION IS ENOUGH HIGH TO MEETFL BLDG CODES, FLOOD
 ZONE AREA ,CENTER LINE OF ROAD , SIDEWALK ELEVATION ,
 5, 10, 15, 25, 100 YEAR FLOOD CRITERIA.PLEASE SHOW
 DETAIL CALCULATIONS.
 3. PLEASE RESUBMIT A COPY OF SFWMD PERMIT, GEO-TECH
 REPORT, SOIL CONDUCTIVITY, WATER QUALITY CALS.ETC
 4. HOW YOU CONNECT TO THE STORM WATER PIPES IN YOUR
 SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER PIPES
 AROUND YOUR SITE SO, WE CANSEE THE BEST PIPE TO
 CONNECT WITH THE STORM WATERFROM ALL OTHER STORM
 WATER PIPES. PLEASE SHOW DETAIL OF THE CONTROL
 STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, AFTER BLEEDING WHERE THE STORM WATER GOES
 FOR EXAMPLE EITHER IN SFWM CANAL, OR CITY OF WPB
 SYSTEM.
 5. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-03-09 Cont ID  
Sent By rchokshi Date 2007-03-09 Time 09:55 Rev Time 0.00
Received By rchokshi Date 2007-03-09 Time 09:55 Sent To  
Notes
2007-03-09 09:55:32PLEASE PROVIDE FOLLOWING INFO:
  
 1. STANDARDS NOTES OF CITY OF WPB SHOWN ON DRAWINGS
 FOR SIDEWALK WIDTH , ITS SLOPE, DRIVEWAY, PARKING,
 HANDICAP PARKING, PAINTPER CITY CODES ETC AETC. ARE
 ALL MINIMUM STANDARDS,PLEASE USE LATEST STANADARD NOTES
 REVISED IN 2006,MAKE SURE YOU ALSO MEET
 FDOT,STATE,HANDICAP ADA,,FDEP ETC.,
 2. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 3. FIRST FLOOR ELEVATION, MUST MEET FL BLDG CODES,
 FLOOD ZONE,CENTER LINE OF ROAD , SIDEWALK ELEVATION ,
 PLEASE SHOW ALL THESE ELEVATIONON THE DRAWINGS.
 4. PLEASE PROVIDE A COPY OF SFWMD PERMIT,GEO-TECH
 REPORT, SOIL CONDUCTIVITYETC
 5.PLEASE SHOW STORM WATER CALCULATIONS, WHAT CRITERIA
 YOU ASSUMEDFOR RUNOFF CAL.,, LIKE 1" OVER ENTIRE SITE
 OR2.5"CRITERIA, ? TOTALPERVIOUS AREA, LIKE GREEN,
 LAKES, ETC,IMPERVIOUS AREA CAL.,
 6. WHAT IS THE SITE AREA, YOU ARE DEVELOPING FOR THIS
 PROJECT ONLY ? SO, PERVIOUS AREA, IMPERVIOUS AREA.ETC?
 7. HOW YOU CONNECT TO THE STORM WATER PIPES IN YOUR
 SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER PIPES
 AROUND YOUR SITE SO, WE CANSEE THE BEST PIPE TO
 CONNECT WITH THE STORM WATERFROM ALL OTHER STORM
 WATER PIPES. PLEASE SHOW DETAIL OF THE CONTROL
 STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, EXFILTRATION TRENCH LENGTH CALCULATIONS.
 8. POLLUTION PREVENTION PRE & POSTLIKE DURING
 DEMOLATION AND DURING CONSTRUCTION. PLEASE SHOW SILT
 FENCE AROUND THE SITE ALSO DURING DEMOLATION,
 DETAILS,CLOTHES USED FOR SILT ETC.,SILT FENCE HEIGHT
 SHOWN IN SHEET C-16 & C-8 NOT CONSISTENT. SILT FENCE
 HEIGHT SHOULD BE 5 FEET OR ABOVE
 9. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED
 10. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-09-05 Cont ID  
Sent By mcarsill Date 2007-09-05 Time 13:19 Rev Time 0.00
Received By mcarsill Date 2007-09-04 Time 11:38 Sent To  
Notes
2007-09-05 13:19:331. NO RESPONSES PROVIDED WITH APPLICATION PACKET
 ADDRESSING PREVIOUS PLAN REVIEW COMMENTS PROVIDED BY
 FIRE RESCUE. REQUESTED THIS INFORMATION.
  
 2. GROUND LEVEL SITE PLAN ON PAGE A1.00 DOES NOT
 DISPLAY NEW OR EXISTING FIRE HYDRANTS.
  
 3. IT APPEARS THAT THE FIRE DEPARTMENT CONNECTIONS
 EXTEND BEYOND THE PROPERTY LINE.
  
 4. THE FIRE DEPARTMENT CONNECTIONS ARE REQUIRED TO BE
 EQUIPPED WITH KNOX-BOX LOCKING CAPS.
  
 5. ALL FABRIC CANOPIES ILLUSTRATED ON THE PLANS SHALL
 BE FLAME RETARDANT WHEN SUBMITTED UNDER A SEPARATE
 PERMIT.
  
 6. FIRE PUMP ROOM SHOWN ON PAGE A2.02. PLEASE EXPLAIN
 THE LOCATION CHOSEN.
  
 7. THE WORD MEZZANINE STILL APPEARS ON THE PLANS.
 PLEASE ADVISE RATIONALE.
  
 8. PLEASE INDICATE ON PLANS THE STRETCHER ACCESSIBLE
 ELEVATOR(S). THE APPROPRIATE ELEVATORS SHALL BE
 IDENTIFIED WITH NECESSARY SIGNAGE.
  
 9. PORTIONS OF THE ROOF APPEAR TO OVERHANG THE PROPERTY
 LINE. PLEASE PROVIDE INFORMATION.
  
 10. WALL SEPARATING GARAGE AND RETAIL SPACES ON PAGE
 A2.30 APPEARS TO BE ONLY ONE HOUR FIRE RATED. THIS WALL
 SHALL BE AT LEAST TWO HOUR FIRE RATED.
  
 11. BUILDING ADDRESS NOT DISPLAYED ON ANY ELEVATION
 DRAWINGS.
  
 12. PLAN NOTE REVISION CLOUD # 3 ON PAGES E1.01- E1.03
 NEEDS TO BE FURTHER CLARIFIED. NOTE DOES NOT CLEARLY
 DESCRIBE THE CODE REQUIREMENTS UNDER SPECIAL LOCKING
 ARRANGEMENTS.
  
 13. DUCT DETECTOR NOTE ON PAGE FA1.08 IS INCORRECT.
 ACTIVATION OF A DUCT SMOKE DETECTOR SHALL CAUSE AN
 ALARM CONDITION.
  
 14. WHAT WINDOWS ARE PLANNED TO BE USED AS SMOKE
 OPENINGS IDENTIFIED IN THE DRAWINGS.
  
 15. SINCE NO RESPONSE COMMENT SHEETS WERE PROVIDED NOT
 ALL PREVIOUS COMMENTS COULD BE VERIFIED IF THEY HAVE
 BEEN CORRECTED.
  
 16. SEPARATE PLANS AND PERMITS REQUIRED FOR UNDERGROUND
 FUEL STORAGE TANK DISPLAYED ON THE PLANS.
  
 17. PLEASE EXPLAIN WHY THE ROOM CONTAINING THE FUEL DAY
 TANKS ARE NOT TWO HOUR FIRE RATED.
  
 18. COULD NOT LOCATE "STACK EFFECT" WORDING ON THE
 MECHANICAL PLANS. PLEASE ADVISE WHERE THIS CAN BE
 LOCATED.
  
 19. COULD NOT LOCATE ANY SPECIFIC LABELING OR SAFETY
 MARKINGS FOR THE DAY FUEL TANKS BEING PROPOSED.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-05-01 Cont ID  
Sent By mcarsill Date 2007-05-01 Time 10:57 Rev Time 0.00
Received By mcarsill Date 2007-05-01 Time 09:47 Sent To  
Notes
2007-05-01 10:57:191. BUILDING ADDRESS REQUIRED ON PROPER ELEVATION. A
 MINIMUM OF AT LEAST 6" HIGH AND AT LEAST 1" WIDE
 NUMBERS ARE REQUIRED.
  
 2. DEMOLITION ACTIVITIES TO COMPLY WITH NFPA 241.
  
 3. EXIT STAIRS ARE TO BE KEPT UP WITH CONSTRUCTION.
  
 4. DEBRIS SHAHLL BE REMOVED FROM THE SITE DAILY.
  
 5. A TEMPORARY STANDPIPE SYSTEM IS REQUIRED WHEN THE
 BUILDING REACHES THREE STORIES OR THIRTY FEET IN
 HEIGHT.
  
 6. ALL CUTTING AND WELDING OPERATIONS TO COMPLY WITH
 NFPA 51B.
  
 7. THE BUILDING WILL BE REQUIRED TO BE COMPLETELY FIRE
 SPRINKLER PROTECTED.
  
 8. THE BUILDING WILL BE CONSIDERED A HIGH-RISE BUILDING
 AND SHALL COMPLY WITH THE FLORIDA BUILDING CODE AND THE
 FLORIDA FIRE PREVENTION CODE.
  
 9. SITE PLAN, PAGE A.100 DOES NOT ILLUSTRATE ANY FIRE
 HYDRANT LOCATIONS.
  
 10. THE BUILDING WILL BE CONSIDERED A MULTIPLE
 OCCUPANCY BUILDING SINCE STORAGE, MERCANTILE, AND
 REDIENTIAL OCCUPANCIES WILL EXIST.
  
 11. PLEASE EXPLAIN EXIT DISCHARGE RATIONALE FROM EXIT
 DOORS.
  
 12. PLEASE ILLUSTRATE DIMENSIONS FROM THE PROPOSED
 BUILDING TO THE EXISTING TWO STORY BUILDING.
  
 13. A TWO HOUR FIRE SEPARATION IS REQUIRED BETWEEN THE
 PARKING GARAGE AND ALL OTHER AREAS OF THE BUILDING.
 PROPERLY RATED OPENING PROTECTIVES WILL BE REQUIRED.
  
 14. GROUND LEVEL SITE PLAN DOES NOT ILLUSTRATE THE
 LOCATION OF THE FIRE COMMAND ROOM.
  
 15. PROPER TENANT SEPARATIONS WILL BE REQUIRED BETWEEN
 EACH RETAIL TENANT SPACE.
  
 16. ON PAGE A.200 PORTIONS OF THE BUILDING APPEAR TO
 EXTEND BEYONG THE PROPERTY. PLEASE PROVIDE MORE
 DETAILS.
  
 17. ON PAGE A2.01 IT IS NOTED THAT THE INTERIOR
 BUILD-OUTS WILL BE UNDER SEPARATE PERMIT. PLEASE BE
 ADVISED THAT ALL REQUIRED FIRE AND LIFE SAFETY DEVICES
 FOR THE BUILDING SHALL BE INSTALLED PRIOR TO REQUESTING
 A CERTIFICATE OF OCCUPANCY.
  
 18. EXIT SIGNS NOT DISPLAYED ON LIFE SAFETY SHEETS.
  
 19. ON PAGE LS.1 EXIT DISCHARGE IDENTIFIED IN SOME
 LOCALES ARE POSITIONED BETWEEN OBJECTS. PLEASE
 EXPLAIN.
  
 20. MISSING RATED DOOR SYMBOL NEAR PAGE LS.3.
  
 21. DOOR SWING APPEARS IMPROPER ON PAGE LS.3 LEAVING
 THE POOL DECK AREA.
  
 22. ELEVATOR WARNING SIGNS REQUIRED.
  
 23. WHY IS THE FIRE PUMP ROOM DISPLAYED ON THE
 MEZZANINE LEVEL ON PAGE A2.02.
  
 24. PLEASE EXPLAIN WHAT CHEMICALS ARE PLANNED TO BE
 STORED IN THE POOL EQUIPMENT ROOM ON PAGE A2.02.
  
 25. PLEASE EXPLAIN WHAT CHEMICALS IF ANY WILL BE STORED
 IN THE POOL STORAGE ROOM ON PAGE A2.03.
  
 26. PLEASE INDICATE ON PLANS THE SLIP PROTECTION
 METHODS PLANNED FOR EXIT ACCESS AND EXIT STAIR
 ARRANGEMENTS LOCATED ON THE EXTERIOR.
  
 27. PLEASE PROVIDE FLAME SPREAD DETAILS ON ALL FABRIC
 CANOPIES PLANNED FOR USE.
  
 28. MORE DETAILS REQUIRED ON THE VEHICLE LIFTS
 ILLUSTRATED ON THE PLANS.
  
 29. PLEASE PROVIDE A DETAIL ILLUSTRATING WINDOW
 OPENINGS PRESENT ON THE ADJACENT BUILDING IN RELATION
 TO STAIR # 3.
  
 30. ELECTRIC POWERED SMOKE DETECTORS REQUIRED ON EVERY
 LEVEL OF THE RESIDENTIAL UNITS.
  
 31. SMOKE DETECTORS SHALL BE PLACED A MINIMUM OF AT
 LEAST THREE FEET FROM AIR CONDITIONER DIFFUSERS.
  
 32. SOME OF THE LIFE SAFETY SHEETS ILLUSTRATE TWENTY
 MINUTE FIRE DOORS BUT DOOR SCHEDULE SHEETS DO NOT
 INDICATE ANY TWENTY MINUTE FIRE DOORS.
  
 33. PLEASE PROVIDE DETAILS ON EPS FOAM MOLDING
 DISPLAYED ONELEVATION DRAWINGS.
  
 34. PLEASE INDICATE USES OF ALUMINUM LOUVERS SHOWN ON
 THE ELEVATION DRAWINGS.
  
 35. POOL HOUSE REFELECTED CEILING PLAN ON PAGE A4.01
 DISPLAYS AN EMERGENCY LIGHT BUT NO EXIT NO EXIT
 MARKINGS.
  
 36. PLEASE PROVIDE FLAME SPREAD DETAILS ON HIGH DENSITY
 FOAM PRODUCTS ILLUSTRATED ON THE DRAWINGS.
  
 37. EXIT SIGN PLACEMENT SHALL NOT EXTEND ONE HUNDRED
 FEET APART.
  
 38. EXIT SIGN PLACEMENT ON PAGE E1.04 DIFFERS FROM PAGE
 E1.05 CORRIDOR AREAS. PLEASE EXPLAIN.
  
 39. ONLY ONE EXIT SIGN PRESENT ON PAGE E1.06.
  
 40. SMOKE DETECTORS APPEAR TO BE MISSING OUTSIDE OF THE
 SLEEPING ROOMS ON UNIT 11 ON PAGE E2.04.
  
 41. MORE DETAILS REQUIRED ON DAY TANK ILLUSTRATED ON
 PAGE E3.01. SIZE, LISTINGS, MARKINGS, ETC.
  
 42. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM
 SYSTEM. FIRE ALARM SYSTEM SHALL BE MONITORED BY A UL
 LISTED CENTRAL STATION APPROVED FOR CENTRAL STATION
 SERVICE.
  
 43. WHY IS THERE NO MANUAL PULL STATION NEAR FOYER ON
 PAGE FA1.03 FROM POOL DECK.
  
 44. SMOKE DETECTOR INSTALLATION PLACEMENT SHALL NOT
 EXCEED MANUFACTURER OR CODE REQUIREMENTS.
  
 45. PLEASE INDICATE WHAT MESSAGE IS PLANNED FOR THE
 FIRE ALARM VOICE FEATURE OF THE FIRE ALARM SYSTEM.
  
 46. THE SMOKE CONTROL PANEL INDICATED ON PAGE FA1.07
 SHALL PROVIDE A GRAPHIC REPRESENTATION OF THE BUILDING
 IN ADDITION TO THE FIVE POSITION SWITCHES.
  
 47. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 COMPLETE AUTOMATIC FIRE SPRINKLER SYSTEM.
  
 48. BACKFLOW DEVICE DISPLAYED ON FP 1.01 SHALL ALSO BE
 EQUIPPED WITH A CHAIN AND LOCK.
  
 49. STANDPIPE HOSE VALVES THROUGHOUT THE BUILDING SHALL
 BE EQUIPPED WITH 1 1/2 REDUCERS. PLEASE ENSURE THAT ALL
 FP SHEETS ARE PROVIDED WITH THIS NOTE.
  
 50. NOTE 30 ON PAGE FP3.01 IS INCORRECT. A TEMPORARY
 STANDPIPE IS NEEDED WHEN THE BUILDING REACHES THREE
 STORIES OR THIRTY FEET IN HEIGHT.
  
 51. SMOKE CONTROL NOTE ON PAGE M0.00 INDICATES WINDOWS
 AND PANELS WILL BE USED FOR THE RETAIL AND LIVING
 AREAS. PLEASE IDENTIFY THESE LOCATIONS.
  
 52. ALLL REQUIRED FIRE AND SMOKE DAMPERS ARE TO BE DROP
 TESTED TO ENSURE PROPER FUNCTION AFTER INSTALLATION.
  
 53. ARCHITECTURAL FEATURES SUCH AS SOFFITS SHALL NOT
 INTERFERE WITH ANY FIRE SPRINKLER HEAD OPERATIONS.
  
 54. TCTILE SIGNAGE REQUIRED AT ALL EXITS.
  
 55. STAIRWELL IDENTIFICATION SIGNS REQUIRED. THESE
 SIGNS SHALL IDENTIFY STAIR NUMBER, FLOOR LEVEL,
 TERMINUS TOP AND BOTTOM.
  
 56. STAIRWELL PRESSURIZATION AND OTHER MECHANICAL SMOKE
 MANAGEMENT SYSTEMS SHALL CONSIDER STACK EFFECT. THE
 TERM "STACK EFFECT" SHALL APPEAR ON THE PLANS.
  
 57. THE FIRE PUMP APPEAR ON SOME PLANS ON THE LEFT SIDE
 AND OTHER DRAWINGS THEY APPEAR ON THE RIGHT SIDE. THE
 SAME OREINTATION SHOULD APPEAR.
  
 58. THE LOCATION OF THE FDC SHOULD FACE DATURA STREET
 SO THE HOSE WILL NOT KINK.
  
 59. ELECTRONIC SWITCHES, CHAIN AND LOCK WILL BE
 REQUIRED ON THE FIRE LINE BACKFLOW DEVICE NOTED ON PAGE
 C-13.
  
 60. ALL ELECTRICAL INSTALLATIONS TO COMPLY WITH NFPA
 70, THE NATIONAL ELECTRICAL CODE.
  
 61. ALL UNDERGROUND LINES SHALL BE LOCATED PRIOR TO ANY
 EXCAVATION ACTIVITIES.
  
 62. COULD NOT LOCATE ANY FIRE EXTINGUISHERS ON THE
 PLANS.
  
 63. WHAT USES ARE PLANNED FOR THE MEZZANINES IN THE
 RETAIL AREA.
  
 MIKE CARSILLO, BATTALION CHIEF OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-08-11 Cont ID  
Sent By kstevens Date 2007-08-11 Time 16:03 Rev Time 0.00
Received By kstevens Date 2007-08-11 Time 16:02 Sent To  
Notes
2007-08-11 16:03:31DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 ****FROM PREVIOUS REVIEW:
  
 92. SHT P2.14 INDICATES GAS PIPE SIZES BASED ON THE
 NFPA CHART. PIPING SHALL BE SIZED PER THE FBC-2004 FUEL
 GAS CODE. PLEASE CHANGE REFERENCE.
 ****RESPONSE NOTED, BUT SINCE THE PLANS HAVE BEEN
 FURTHER DEVELOPED SINCE THE FIRST REVIEW, THE TOTAL
 DEVELOPED LENGTH HAS EXCEEDED 200FT. FBC-2004 FUEL GAS
 CODE ONLY SHOWS 200FT OR LESS. PLEASE SUBMIT THE TABLE
 FROM NFPA-54 INDICATED ON COMMENT RESPONSE AND SHT
 P2.14 AND MAKE SURE NFPA-54 IS INDICATED ON THE TABLE.
  
 93. OK - SEE COMMENT 92.
  
 94. SHT P2.14 INDICATE THE LENGTH OF PIPES FROM THE
 REGULATOR TO THE POOL HEATER.
 ****RESPONSE NOTED, BUT NO PIPE LENGHTS ARE INDICATED.
  
 95. SHT P2.14 SUBMIT THE MANUF. SPECIFICATION SHEETS
 FOR THE POOL HEATER, AND THE REGULATOR. INDICATE THE
 MODEL FOR EACH AND SHOW THE LISTING. STANDARDS NFPA 54,
 NFPA 58, AND THE FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT NO MANUF. SPECIFICATION SHEETS
 FOR THE REGULATORS HAVE BEEN FOUND. - NOW A GENERATOR
 HAS BEEN ADDED TO THE SYSTEM. SUBMIT MANUF LISTING FOR
 THE BI-FUEL ADAPTORS FOR THE DIESEL GENERATOR. SUBMIT
 MANUF. INSTALLATION INSTRUCTIONS FOR THE GENERATOR
 SHOWING ALL CLEARANCES.
  
 96. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 ****RESPONSE NOTED. INDICATE WHERE IN THE MECHANICAL
 DRAWINGS THE CALCULATIONS CAN BE FOUND.
  
 97. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE
 AND TERMINATION OF THE GAS VENTS PER FBC-2004 FUEL GAS
 CODE SECS. 502 THRU 505.
 ****RESPONSE NOTED. INDICATE WHERE IN THE MECHANICAL
 DRAWINGS THE INFORMATION CAN BE LOCATED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-08-11 Cont ID  
Sent By kstevens Date 2007-04-02 Time 16:02 Rev Time 0.00
Received By kstevens Date 2007-04-02 Time 16:02 Sent To  
Notes
2007-08-11 16:05:16DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 FROM PLUMBING REVIEW:
  
 92. SHT P2.14 INDICATES GAS PIPE SIZES BASED ON THE
 NFPA CHART. PIPING SHALL BE SIZED PER THE FBC-2004 FUEL
 GAS CODE. PLEASE CHANGE REFERENCE.
  
 93. SHT P2.14 THE LONGEST RUN IS INDICATED AS 58'0",
 BUT ADDITION INDICATES 62' WITHOUT COUNTING THE LENGTH
 OF PIPES FROM THE METER TO THE FIRST RISER. PLEASE
 RECHECK THE ADDITION AND ADD THE PIPE LENGTH FROM THE
 METER TO THE FIRST RISER. FBC-2004 FUEL GAS CODE
 APPENDIX A - USE OF CAPACITY TABLES A.3.1(4).
  
 94. SHT P2.14 INDICATE THE LENGTH OF PIPES FROM THE
 REGULATOR TO THE POOL HEATER.
  
 95. SHT P2.14 SUBMIT THE MANUF. SPECIFICATION SHEETS
 FOR THE POOL HEATER, AND THE REGULATOR. INDICATE THE
 MODEL FOR EACH AND SHOW THE LISTING. STANDARDS NFPA 54,
 NFPA 58, AND THE FBC-2004 FUEL GAS CODE SEC 402.2.
  
 96. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-22 Cont ID  
Sent By adarroug Date 2007-06-22 Time 09:02 Rev Time 0.00
Received By adarroug Date 2007-06-22 Time 09:02 Sent To  
Notes
2007-07-10 13:28:38TO "COMM" BD#9/PLANS ON RACK--6ROLLS, 2 BOXES AND 2
 LARGE FOLDED PLANS
2007-06-22 09:03:13WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-05-03 Cont ID  
Sent By jwitmer Date 2007-05-03 Time 12:10 Rev Time 0.00
Received By jwitmer Date 2007-03-02 Time 11:31 Sent To  
Notes
2007-03-02 11:31:53TO "COMM" BD#63/PLANS ON RACK--3 ROLLS

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-07-30 Cont ID  
Sent By rregueir Date 2007-07-30 Time 12:04 Rev Time 0.00
Received By rregueir Date 2007-07-26 Time 13:39 Sent To  
Notes
2007-07-30 10:51:362ND REVIEW: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 REVISIONS FBC
 CH.1 AS AMMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS FOR CONTINUITY. ADDITIONAL NEW
 COMMENTS MAY APPEAR AT THE END AS A RESPONSE TO NEW
 INFORMATION PROVIDED.
  
 1. OK
  
 2. FIRE DAMPERS ARE STILL SHOWN ON SEF-2 DUCT AT TRASH
 ROOM AND ELEVATOR FOYER WALLS. RATHER THAN ADDRESSING
 THE COMMENT BY REPLACING FIRE DAMPERS IN SMOKE EXHAUST
 DUCT WITH APPROVED ALTERNATIVE PROTECTION (SUCH AS
 COMBINATION FIRE/SMOKE DAMPERS), THE SITUATION IS MADE
 WORSE BY THE ADDITION OF ANOTHER FIRE DAMPER IN THE
 SMOKE EXHAUST DUCT AT THE TRASH ROOM WALL. SEE FBC,M
 607.2.1: "WHERE THE INSTALLATION OF A FIRE DAMPER WILL
 INTERFERE WITH THE OPERATION OF A REQUIRED SMOKE
 CONTROL SYSTEM IN ACCORDANCE WITH SECTION 513, APPROVED
 ALTERNATIVE PROTECTION SHALL BE UTILIZED."
  
 3. A) SMOKE CONTROL RATIONAL ANALYSIS CALLS FOR 2850
 CFM OF MAKE-UP AIR FOR THE 3500 CFM OF SMOKE EXHAUST IN
 THE FIRST FLOOR LOBBY AREA. AHU-4 APPEARS TO BE THE
 ONLY SOURCE OF MAKE-UP AIR FOR THE FIRST FLOOR LOBBY.
 AHU-4 IS SHOWN AS 5 TON ON FLOOR PLAN BUT ON EQUIPMENT
 SCHEDULE AHU-4 IS SHOWN AS 3 TONS WITH 1090 CFM
 CAPACITY. EVEN A 5 TON AHU WILL NOT TYPICALLY DELIVER
 2850 CFM. B) THE DUCT AND DAMPER DESIGN FOR AHU-4 DOES
 NOT HAVE A MECHANISM IN PLACE TO FORCE ALL THE AIR FROM
 AHU-4 TO THE FIRST FLOOR LOBBY AREA SHOULD CONDITIONS
 CALL FOR EXHAUST IN THE FIRST FLOOR LOBBY AREA. THIS
 WOULD SEEM TO BE A NECESSARY COMPONENT OF THE SMOKE
 EXHAUST SYYSTEM FOR THE FIRST FLOOR LOBBY IF AHU-4 IS
 TO COME CLOSE TO PROVIDING THE REQUIRED CFM OF MAKE-UP
 AIR TO THE SPACE BEING EXHAUSTED. C) RATIONAL ANALYSIS
 INDICATES ON PAGE 17 THAT THE MAIN LOBBY SHOULD BE
 2-HOUR RATED WHILE THE LIFE SAFETY PLAN (LS.1) SHOWS
 LOBBY TO BE 1-HOUR RATED. PG 17 ALSO NOTES THAT LOBBY
 PRESSURIZATION DUCTS SHALL BE PROTECTED BY A 2-HOUR
 FIRE RESISTIVE RATING FROM THE SOURCE OF OUTDOOR AIR UP
 TO THE ENCLOSURE. SEE NOTE #2 ON PG 17. D) IS THERE A
 TIME OR CONDITION IN WHICH THE FIRST FLOOR LOBBY WOULD
 BE PRESSURIZED RATHER THAN EXHAUSTED? THAT CONDITION IS
 NOT COVERED IN THE SEQUENCE ON M0.00.
  
 4.ON PG M1.01 PLAN SHOWS A FIRE DAMPER AND FIRE/SMOKE
 DAMPER AT 2ND FLOOR SLAB PENETRATION. PLEASE REMOVE
 DESIGNATION FOR THE FD AS BOTH ARE NOT REQUIRED AND THE
 FD IS PROHIBITED PER FBC,M 607.2.1 (THIS WAS MOST
 LIKELY LEFT ON PLANS BY MISTAKE). ALSO, NOTE ON M1.02
 CALLS FOR A 20X18 OPENING IN SLAB FOR A 14X12
 FIRE/SMOKE DAMPER. PLEASE CONSULT FSD INSTALLATION
 INSTRUCTIONS FOR MIN/MAX ANNULAR SPACE REQUIREMENTS.
 THE SIZE ON PLAN IS LIKELY TO BE WELL OUTSIDE THE
 ALLOWANCE PER THE DAMPERS LISTING/INSTRUCTIONS. FBC,M
 607.2
  
 5. NOW THAT AHU-4 IS BEING USED FOR MAKE-UP AIR FOR THE
 MAIN LOBBY, THE DOWN-SIZING OF AHU-4 AND DUCT SYSTEM
 HAS ADVERSELY AFFECTED THE DESIGN OF THIS PORTION OF
 THE SMOKE CONTROL SYSTEM. SEE COMMENT 3 ABOVE AND THE
 RATIONAL ANALYSIS REPORT.
  
 6. RESPONSE STATES "PROTECTION OF OPENINGS PROVIDED."
 HOWEVER, NO PROTECTION IS SHOWN ON PLANS. A LOUVER IS
 NOT AN OPENING PROTECTIVE IN A RATED WALL.
  
 7. OK
  
 8. GENERATOR EXHAUST IS SHOWN DISCHARGING UNDER A
 TERRACE FOR AN UPPER FLOOR APARTMENT. ALSO, WHAT IS THE
 HEIGHT OF THE EXHAUST DISCHARGE IN RELATION TO
 ADJOINING GRADE?
  
 9. M1.02 SHOWS A FIRE DAMPER ON THE 30X14 O.A. DUCT AT
 THE MECHANICAL ROOM WALL. APPROVED ALTERMATIVE
 PROTECTION (SUCH AS A FSD) SHALL BE UTILIZED PER FBC,M
 607.2.1. ALSO, WHAT IS THE PURPOSE OF THE MOTORIZED
 DAMPER ON TOP OF AHU-4? WHERE IS THE DUCT SMOKE
 DETECTOR?
  
 10. M1.02: A LOUVER IS NOT AN OPENING PROTECTIVE IN A
 FIRE RATED ASSEMBLY. ALSO, 6X6 DUCT INTO TENANT STORAGE
 IS STILL SHOWN TO BE UNPROTECTED. NOTE: DUCTS NOT
 REQUIRED TO HAVE DAMPERS IN FIRE RESISTANCE RATED
 ASSEMBLIES SHALL COMPLY WITH FBC SEC.712.
  
 11. OK
  
 12. OK EXCEPT WEST STORAGE ROOM. SEE COMMENT 10 ABOVE.
  
 13. OK
  
 14. M1.02: 10X6 DUCT IS NOW SHOWN AS 10X10. FIRE
 DAMPERS ARE STILL SHOWN IN SMOKE EXHAUST DUCT. SEE
 FBC,M 607.2.1: "WHERE THE INSTALLATION OF A FIRE DAMPER
 WILL INTERFERE WITH THE OPERATION OF A REQUIRED SMOKE
 CONTROL SYSTEM IN ACCORDANCE WITH SECTION 513, APPROVED
 ALTERNATIVE PROTECTION SHALL BE UTILIZED."
  
 15.A)WHERE COMMUNICATING WITH THE OUTDOORS THROUGH
 HORIZONTAL DUCTS, EACH OPENING SHALL HAVE A MINIMUM
 FREE AREA OF 1 SQ.IN. PER 2,000 BTU/H PER FBC,FG
 304.6.1. AT 400,000 BTU/H, EACH DUCT REQUIRES A MINIMUM
 OF 200 SQ.IN. B) AHERE EXHAUST FANS ARE INSTALLED,
 MAKE-UP AIR SHALL BE PROVIDED TO REPLACE THE EXHAUSTED
 AIR PER FBC,FG 304.9.1. THIS WOULD BE IN ADDITION TO
 THE REQUIRED COMBUSTION AIR. C) COMBUSTION AIR DUCTS
 SHOULD NOT SHARE THE SAME LOUVER AND PLENUM PER FBC,FG
 304.11(4).
  
 16.OK
  
 17. OK
  
 18. OK
  
 19. NO INFORMATION COULD BE FOUND IN THE A/C EQUIPMENT
 SUBMITTALS PROVIDED REGARDING LINE LENGTHS OR ALLOWED
 VERTICAL DISTANCES. IF THERE IS NO PUBLISHED LITERATURE
 ON THESE SUBJECTS, PLEASE PROVIDE SITE SPECIFIC
 ENGINEERING FROM THE MANUFACTURER SHOWING THE
 FEASIBILITY OF THIS TYPE OF INSTALLATION. FBC 106.1.2.
 NOTE: BASED ON THE CLEARANCE REQUIREMENTS FOR SERVICE
 AND VENTILATION AS STATED IN LENNOX INSTALLATION
 INSTRUCTIONS, PLEASE VERIFY LAYOUT OF CONDENSERS ON
 ROOF MEETS ALL CLEARANCE REQUIREMENTS. SEE LENNOX 13ACD
 INSTALLATION INSTRUCTIONS PAGE 3.
  
 20. OK
  
 21. DAMPERS WERE ADDED PER THE PREVIOUS COMMENT.
 HOWEVER, BASED ON THE SMOKE CONTROL RATIONAL ANALYSIS
 AND FBC,M 607.5.4, FIRE ANS SMOKE DAMPERS ARE REQUIRED
 AT ALL FRESH AIR DUCTS PENETRATIONS OF CORRIDOR WALLS
 INTO APARTMENTS. CONTROL OF THESE DAMPERS SHOULD BE
 INCLUDED IN THE SEQUENCE OF OPERATIONS. ALSO, PLEASE
 VERIFY SMOKE CONTROL SEQUENCE AS SHOWN ON M0.00 IS
 COORDINATED WITH THE RATIONAL ANALYSIS AS THERE APPEAR
 TO BE SOME DISCREPANCIES BETWEEN THE TWO. PLEASE HAVE
 THE ENGINEER OF RECORD FOR THIS PROJECT PROVIDE A SHOP
 DRAWING REVIEW AND APPROVE THE ANALYSIS.
  
 22. FLOOR PLAN STILL SHOWS 2230 CFM AND RISER DIAGRAM
 STILL SHOWS 2600 CFM. THIS DOES NOT APPEAR TO HAVE BEEN
 CORRECTED.
  
 23. OK
  
 24. OK
  
 25. BOOSTER FANS WILL NOT BE ACCEPTED BY THIS AHJ
 UNLESS THE DRYER MANUFACTURER'S INSTALLATION
 INSTRUCTIONS MAKE PROVISIONS FOR THEIR USE. CLOTHES
 DRYERS SHALL BE EXHAUSTED IN ACCORDANCE WITH THE
 MANUFACTURER'S INSTRUCTIONS PER FBC,M 504.1.
 NOTE: 504.6.1 ALLOWS FOR EXTENDED DRYER EXHAUST DUCT
 LENGTHS BASED ON MANUFACTURER'S INSTRUCTIONS. PLEASE
 SEE EXCEPTION UNDER THIS SECTION: "EXCEPTION: WHERE THE
 MAKE AND MODEL OF THE CLOTHES DRYER TO BE INSTALLED IS
 KNOWN AND THE MANUFACTURER?S INSTALLATION INSTRUCTIONS
 FOR SUCH DRYER ARE PROVIDED TO THE CODE OFFICIAL, THE
 MAXIMUM LENGTH OF THE EXHAUST DUCT, INCLUDING ANY
 TRANSITION DUCT, SHALL BE PERMITTED TO BE IN ACCORDANCE
 WITH THE DRYER MANUFACTURER?S INSTALLATION
 INSTRUCTIONS." MANUFACTURER'S INSTRUCTIONS MAY MAKE THE
 USE OF BOOSTER FANS UNNECESSARY FOR THE LENGTH OF DUCT
 SHOWN ON PLANS.
  
 26. OK
  
 27. THIS WILL BE CHECKED IN CONJUNCTION WITH COMMENT
 #30.
  
 28. OK
  
 29. COMMENT HAS BEEN ADDRESSED. HOWEVER, IT WAS NOT
 NOTED IN PREVIOUS REVIEW THAT THE DRYER EXHAUST DUCT IS
 LOCATED IN A RETURN AIR PLENUM. THIS CONDITION IS
 PROHIBITED PER FBC,M 504.4 AND 601.3.
  
 30. THREE UNITS CHECKED; 3N, 3S AND 6. NONE OF THESE
 FLOOR PLANS BALANCE WITH EQUIPMENT SCHEDULE. PLEASE
 ADDRESS THIS COMMENT FULLY BEFORE RESUBMITTING PLANS.
  
 31. OK
  
 32. OK
  
 33. OK EXCEPT: SEE COMMENT #3 REGARDING AHU-4 SIZE AND
 SMOKE CONTROL.
  
 34. OK
  
 35. OK
  
 36. THIS DETAIL IS SUFFICIENT PENDING FIELD INSPECTOR'S
 APPROVAL. THERE MAY BE A CONCERN REGARDING THE LOVER
 BEING IN THE AIRFLOW OF THE DRYER EXHAUST AND
 COLLECTING LINT.
  
 37. S-10 SEC.4 SAYS "A/C STAND BY SUPPLIER." IS THIS A
 PRE-ENGINEERED SYSTEM? ALSO, STRUCTURAL ENGINEER'S
 WINDLOAD CALCULATIONS HAVE BEEN RECEIVED. HOWEVER,
 DETAIL DRAWINGS SHOWING THE INSTALLATION METHOD IN THE
 CALCULATIONS REPORT COULD NOT BE FOUND ON PLANS. PLEASE
 ALSO INCLUDE INFORMATION REGARDING THE ATTACHMENT OF
 THE EQUIPMENT TO THE CURB. FBC 106.1.2
  
 38. M6.01, THIS DETAIL DOES NOT APPEAR TO HAVE BEEN
 MODIFIED IN ANY WAY OTHER THAN ITS LOCATION ON THE
 PPAGE HAS CHANGED. RATED SHAFTS FOR REFRIGERANT RISERS
 HAVE BEEN ADDED TO ARCHITECTURAL PLANS BUT NO SUCH
 INFORMATION IS INDICATED ON MECHANICAL PLANS. ALSO,
 PROVIDE DETAIL FOR LISTED ASSEMBLY TO BE USED AT
 REFFRIGERANT PIPE PENETRATION OF RATED SHAFTS. THE ONES
 SHOWN ON M6.02 ARE NOT APPLICABLE TO THIS APPLICATION.
  
 39. OK
  
 40. THE DETAIL SHOWN ON S-10 SEC.4 IS APPLICABLE TO
 NEITHER DUCT SUPPORTS NOT ROOF CURB/RTU ATTACHMENTS.
 PLEASE SEE #37 ABOVE.
  
 41. THROUGH PENETRATION FIRESTOP DETAIL: THROUGH
 PENETRATION FIRE-STOP SYSTEMS USED IN FLOORS SHALL HAVE
 AN F AND T RATING OF NOT LESS THAN 1 HOUR BUT NOT LESS
 THAN THE REQUIRED RATING OF THE FLOOR BEING PENETRATED
 PER FBC 712.4.1.2. ALSO, NOTICE THE DETAIL SHOWN FOR
 INSULATED PIPE IS LIMITED TO 1" DIAMETER OR SMALLER.
 PERHAPS THIS DETAIL IS A MOOT POINT SINCE RATED SHAFTS
 HAVE BEEN ADDED TO ARCHITECTURALS PLANS FOR REFRIGERANT
 RISERS. HOWEVER, IF A THROUGH PENETRATION FIRE-STOP
 SYSTEM IS NEEDED IN THE BUILDING, A MORE SUITABLE
 SYSTEM WILL NEED TO BE SPECIFIED.
  
 42. OK
  
 43. UNABLE TO LOCATE ANY PLUMBING RESPONSE TO THIS
 COMMENT.
  
 44. OK
  
 45. OK
  
 46. NOTE IS STILL SHOWN WITH INCORRECT CODE SECTION IN
 THE "ENERGY EFFICIENCY" BOX ON M0.00
  
 47. OK
  
 48. AMF-1 ON M1.01 AND M1.02, ALSO GEF 3 AND GEF 4: SEE
 FBC,M 504.4 "APPLIANCES LOCATED IN PUBLIC GARAGES OR
 OTHER AREAS FREQUENTED BY MOTOR VEHICLES, SHALL BE
 INSTALLED A MINIMUM OF 8 FEET (2438 MM) ABOVE THE
 FLOOR. WHERE MOTOR VEHICLES EXCEED 6 FEET (1829 MM) IN
 HEIGHT AND ARE CAPABLE OF PASSING UNDER AN APPLIANCE,
 APPLIANCES SHALL BE INSTALLED A MINIMUM OF 2 FEET (610
 MM) HIGHER ABOVE THE FLOOR THAN THE HEIGHT OF THE
 TALLEST VEHICLE.
 EXCEPTION: THE REQUIREMENTS OF THIS SECTION SHALL NOT
 APPLY WHERE THE APPLIANCES ARE PROTECTED FROM MOTOR
 VEHICLE IMPACT AND INSTALLED IN ACCORDANCE WITH NFPA
 88B."
  
 NEW COMMENTS RELATED TO ENERGY CALCULATIONS:
  
 A. EXTERIOR WALL TYPE SHOWN ON CALCULATIONS CALL FOR
 R-11.9 IN THE INPUT DATA REPORT. HOWEVER, THE EXTERIOR
 MASONRY WALL DETAIL ON A9.02 CALLS FOR 1" POLYSTYRENE
 W/ MIN. R-5. PLEASE COORDINATE PLANS AND CONSTRUCTION
 TYPE TO BE ISED WITH THE INPUT DATA REPORT OF THE
 ENERGY CALCULATIONS. NO CONSTRUCTION METHOD IS SHOWN
 WHICH WOULD ACHIEVE THE R-11.9 WHICH IS CALLED FOR IN
 ENERGY CALCULATIONS.
  
 B. ROOF TYPE SHOWN IN CALCULATIONS IS "MATAL BLDG ROOF
 W/ R-19 BATT." THIS DOES NOT CORRELATE WITH TYPE OF
 CONSTRUCTION SHWON ON PLANS. THIS IS NT A METAL
 BUILDING AND THERE IS NO BATT INSULATION CALLED FOR ON
 PLANS FOR THE ROOF. PLANS CALL FOR A CONCRETE ROOF DECK
 WITH A REGID INSULATION BUILT-UP ROOF SYSTEM. PLEASE
 COORDINATE PLANS WITH THE INPUT DATA REPORT.
  
 C. PG M0.00 CALLS FOR MINIMUM R-11 INSULATION AT FLOORS
 ABOVE UNCONDITIONED SPACES (SUCH AS THE PARKING
 GARAGE). THIS IS NOT SHOWN ON PLANS OR ENERGY
 CALCULATIONS. PLEASE CLARIFY.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-04-04 Cont ID  
Sent By rregueir Date 2007-04-04 Time 14:04 Rev Time 0.00
Received By rregueir Date 2007-03-28 Time 15:08 Sent To  
Notes
2007-04-04 07:54:14-----------------DENIED--------------------
  
 FBC 2004 CODE FAMILY W/2006 REVISIONS
 FBC CHAPETER 1 AS AMENDED AND ADOPTED BY THE CITY OF
 WEST PALM BEACH
 ASHRAE 15-04
 ASHRAE 62-04
 NFPA 90A-02
 SMACNA-95
  
  
 1. M1.01: 16X10 INTAKE LOUVER IS PENETRATING A FIRE
 BARRIER (AS INDICATED ON A2.33) BETWEEN VESTIBULE AND
 COMMERCIAL SPACE #5. PLEASE SHOW HOW THIS OPENING IS TO
 BE PROTECTED PER FBC,M 607.5.2.
  
 2. M1.01: WHERE THE INSTALLATION OF A FIRE DAMPER WILL
 INTERFERE WITH THE OPERATION OF A SMOKE CONTROL SYSTEM,
 APPROVED ALTERNATE PROTECTION SHALL BE USED PER FBC,M
 607.2.1.FIRE DAMPERS ARE SHOWN AT THE BOTTOM OF SER-2
 SHAFT AND AT ELEVATOR FOYER PENETRATION. RISER DIAGRAM
 ON M4.01 CALLS FOR COMBO FIRE/SMOKE DAMPER AT SHAFT
 PENETRATION. COMBINATION FIRE/SMOKE DAMPERS MAY ALSO BE
 USED AT TRASH ROOM AND ELEVATOR FOYER PENETRATIONS AS
 AN APPROVED ALTERNATIVE PROTECTION.
  
 3. M1.01: WHAT IS THE SOURCE OF THE 2850 CFM OF MAKE-UP
 AIR FOR THE SMOKE EXHAUST IN THE ELEVATOR FOYER AND
 LOBBY? NONE IS SHOWN ON PLANS. PLEASE CLARIFY PER FBC
 106.1.1.
  
 4. M1.01 AND M1.02: THE 22X14 DUCT FROM AHU 4
 PENETRATING THE 2ND FLOOR SLAB IS AN UNPROTECTED
 OPNEING IN A FIRE BARRIER. PLEASE SHOW HOW THIS OPENING
 IS TO BE PROTECTED PER FBC,M 607.5.2.
  
 5. M1.01/M1.02: AHU 4 IS SHOWN ON EQUIPMENT SCHEDULE
 (M5.01) TO PRODUCE 1600 CFM. DUCT SYSTEM DESIGN AS
 DRAWN SHOWS 2200 CFM AT REGISTERS. PLEASE CLARIFY PER
 FBC 106.1.1.
  
 6. M1.01 THERE ARE UNPROTECTED OPENINGS IN FIRE
 BARRIERS AT SGF-1 AND DPF-1 (BASED ON A2.33). PLEASE
 SHOW HOW THESE OPENINGS WILL BE PROTECTED PER FBC,M
 607.5.2.
  
 7. M1.01 GENERATOR ROOM: EXTERIOR WALL (WEST) IS SHOWN
 ON A2.32 AS TWO-HOUR RATED. LS-1 SHOWS THIS WALL AS
 UNRATED. WHICH OF THESE CONDITIONS IS INTENDED, WITH
 CONSIDERATION FOR THE EXIT DISCHARGE PATH TRAVELING
 NORTH? IF WALL IS TO BE RATED, OPENING PROTECTION WILL
 BE REQUIRED AT TE RADIATOR EXHAUST AND INTAKE LOUVERS
 PER FBC,M 607.5.2. THIS CONDITION MAY IMPACT GEF 1 & 2
 WHICH ARE TO THE SOUTH IN THE SAME EXTERIOR WALL.
  
 8. M1.01 GENERATOR EXHAUST: PLEASE VERIFY DISCHARGE
 LOCATION TO BE IN COMPLIANCE WITH FBC,M 401.5.2.
  
 9. M1.02: WHAT IS THE SOURCE OF THE 300 CFM OF MAKE-UP
 AIR FOR SMOKE EXHAUST IN THE ELEVATOR FOYER?
  
 10. M1.02: THERE ARE UNPROTECTED OPENINGS IN FIRE
 BARRIERS IN TENANT STORAGE ROOMS, GEF 1&2 AND THE FIRE
 PUMP ROOM (BASED ON A2.36 & A2.37). PLEASE SHOW
 COMPLIANCE WITH FBC,M 607.5.2.
  
 11. M1.01: WHAT MEANS IS TO BE USED FOR VENTILATION OF
 THE TRASH ROOM?
  
 12. M1.02 TENANT STORAGE ROOMS: WHAT ARE THE SIZES OF
 O.A. LOUVERS AND CONNECTING DUCTS? PLEASE SHOW MEANS OF
 TYING O.A. DUCTS TO AHUS FOR MECHANICAL VENTILATION PER
 T403.3 AND 404.
  
 13. M1.01,M1.02,M4.01: SEF-2 RISER DIAGRAM SHOWS 1000
 CFM AT FIRST FLOOR AND MEZZANINE LEVELS. FLOOR PLAN
 CALLS FOR 3500 CFM ON 1ST FLOOR AND 350 CFM ON
 MEZZANINE LEVEL. PLEASE CLARIFY.ALSO, FEF-2 ON
 SCHEDULE AND RISER DIAGRAM IS RATED FOR 3200 CFM. HOW
 WILL IT MOVE 3500 CFM ON 1ST FLOOR?
  
 14. M1.02 10X6 SMOKE EXHAUST: PLEASE SEE RELATED
 COMMENT #2.
  
 15. M1.02 POOL EQUIPMENT ROOM: COMBUSTION AIR
 CALCULATIONS FOR LOUVER SIZING IS BASED ON 400,000
 BTU/H BUT CAPACITY IS LISTED ON PLAN AS 675,000 BTU/H.
 PLEASE CLARIFY PER FBC 106.1.1.
  
 16. M1.02 POOL EQUIPMENT ROOM: MECHANICAL EXHAUST SHALL
 BE DISCHARGED OUTDOORS AT A POINT WHERE IT WILL NOT
 CAUSE A NUISANCE AND FROM WHICH IT CAN NOT AGAIN BE
 READILY DRAWN IN BY A VENTILATING SYSTEM. AN ENCLOSED
 PARKING GARAGE IS NOT 'OUTDOORS.'
  
 17. M1.02: WHAT IS THE MEANS OF VENTILATION FOR THE
 TENANT STORAGE SPACES IN THE EAST END OF PARKING
 GARAGE?
  
 18. M1.03 RECREATION ROOM: AHU #9 ON PLANS SHOWS 1200
 CFM OF SUPPLY. SCHEDULE AND SIZE OF EQUIPMENT (M5.01)
 INDICATES 1000 CFM. PLEASE CLARIFY.
  
 19. M5.01 NOTE 11:PLEASE PROVIDE MANUFACTURER'S
 SUBMITTAL DATA AND INSTALLATION INSTRUCTIONS SHOWING
 THE MAXIMUM ALLOWABLE VIRTICAL DISTANCE BETWEEN AHUS
 AND REMOTE CONDENSING UNITS. FBC,M 304.1.
  
 20. M1.03/M1.04 PLEASE IDENTIFY OUTSIDE AIR RISERS AS
 THEY RELATE TO THEIR LABELS ON M4.02 (OAR1 & OAR2)
  
 21. M1.03/M1.04 THERE ARE SEVERAL UNPROTECTED OUTSIDE
 AIR DUCT PENETRATIONS THROUGH RATED FIRE BARRIERS FROM
 CORRIDOR INTO A/C CLOSETS. PLEASE SHOW HOW THESE
 OPENINGS ARE TO BE PROTECTED PER FBC,M 607.5.2.
  
 22. M1.03: PLAN SHOWS COMBINED 2230 CFM OUTSIDE AIR
 FROM BOTH RISERS. RISER DIAGRAM SHOWS 2600 CFM
 COMBINED. PLEASE CLARIFY.
  
 23. M1.05 PLEASE SHOW SIZE OF LOUVER AND OUTSIDE AIR
 DUCT IN BUILDING MAINTENANCE ROOM FOR AHU #10.
  
 24. GENERAL NOTE: PLEASE SHOW TYPE OF AIR DISTRIBUTION
 TO BE USED ON ALL COMMON AREA AHU'S PER FBC 106.1.1.
  
 25. M2.01-M2.04: PLEASE SHOW HOW THE REQUIREMENTS OF
 FBC,M 504.6.1 WILL BE MET. MOST, IF NOT ALL DRYER
 EXHAUST DUCTS EXCEED THE MAXIMUM ALLOWED LENGTH.
  
 26. M2.01: BEDROOM 2 RETURN AIR TRANSFER DUCT IS NOT
 DESIGNED TO MEET THE BALANCED R/A EXCEPTIONS OF FBC,M
 601.4. IF THE TRANSFER DOES NOT MEET THE EXCEPTIONS, A
 FIELD TEST WILL BE REQUIRED AT FINAL INSPECTION TO
 DEMONSTRATE A PRESSURE DIFFERENTIAL OF 0.01" WC OR LESS
 AS REQUIRED BY THIS SECTION.
  
 27. M2.01-M2.04 AND M5.01: UNIT 3 HAS ONLY ONE DUCT
 DESIGN SHOWN, BUT THERE ARE TWO DIFFERENT UNIT 3'S ON
 SPLIT SYSTEM SCHEDULE, EACH WITH DIFFERENT SIZE
 EQUIPMENT AND CFM REQUIREMENTS. PLEASE SHOW LAYOUTS FOR
 BOTH UNIT 3N AND #S WITH THEIR CORRESPONDING EQUIPMENT
 DESIGNATIONS AND DUCT DESIGNS WITH CFM'S MATCHING THE
 SCHEDULE. ALSO, PLEASE SEE RELATED COMMENT #30. FBC
 106.3.5.1.4
  
 28. M2.01 UNIT 3: 4" ROUNDFLEX IN LAUNDRY ROOM IS
 MISSING GRILL SIZE AND CFM DESIGNATION. FBC
 106.3.5.1.4
  
 29. M2.03 UNIT 12: ROUND FLEX DUCT DROP IN GUEST
 BATHROOM IS MISSING DUCT SIZE, GRILL SIZE AND CFM
 DESIGNATION. FBC 106.3.5.1.4
  
 30. M2.01-M2.04: THE FOLLOWING UNITS HAVE DUCT DESIGNS
 AND CFM DESIGNATIONS WHICH DO NOT CORRESPOND WITH
 EQUIPMENT DESIGN CFM AS STATED ON SPLIT SYSTEM SCHEDULE
 (M5.01):
 UNIT 3 (SEE CMMENT #27), WITH 1360 CFM ON FLOOR PLAN
 AND EITHER 625 OR 850 ON SCHEDULE.
 UNIT 6, WITH 1080 CFM ON FLOOR PLAN AND 850 ON
 SCHEDULE.
 UNIT 8, WITH 1040 CFM ON FLOOR PLAN, 945 ON SCHEDULE.
 UNITS 9 AND L9, WITH 720 CFM ON FLOOR PLAN AND 625 ON
 SCHEDULE.
 UNIT 11, WITH 1000 CFM ON FLOOR PLAN AND 815 ON
 SCHEDULE.
 UNIT 12, WITH 790 CFM ON FLOOR PLAN AND 625 ON
 SCHEDULE.
 PLEASE CORRECT EITHER THE DUCT DESIGN OR SCHEDULE AS
 NEEDED FOR PROPER DESIGN. PLEASE ENSURE ENERGY
 CALCULATIONS ARE ADJUSTED AS NEEDED TO REFLECT ANY
 CHANGES MADE TO COMPLY WITH THIS REVIEW COMMENT.
  
 31. M4.02: I AM UNABLE TO LOCATE SUFFICIENT DETAIL IN
 ARCHITECTURAL OR STRUCTURAL PLANS TO DETERMINE CLEAR
 OPENINGS IN SHAFTS FOR OAR 1 &2. PLEASE PROVIDE OR HELP
 ME LOCATE THIS INFORMATION TO ENSURE ADEQUATE SPACE FOR
 OA DUCT WITH INSULATION, ESPECIALLY ON UPPER FLOORS
 WHERE DUCT+INSULATION DIMENSIONS WILL BE 48X26.
  
 32. M5.01: COMMON AREA UNITS SCHEDULE: AHU-11 DOES NOT
 HAVE A CORRESPONDING CONDENSING UNIT. WHAT IS THE AREA
 SERVED BY THIS EQUIPMENT?
  
 33. M5.01 AHU 4,5 AND 10 ALL SHOW SAME MODEL # BUT HAVE
 DIFFERING CFM DESIGNATIONS, CONDENSERS AND ELECTRICAL
 RATINGS. ALSO, AHU-10 IS PAIRED ON SCHEDULE WITH CU-5.
 PLEASE CLARIFY, ENSURING THAT EQUIPMENT CORRESPONDS
 WITH THE AREA BEING SERVED AND DESIGN REQUIREMENTS. FBC
 106.1.1.
  
 34. M5.02 O.A. CALCULATIONS NOTES 1 &2: PLEASE
 REFERENCE ASHRA 62-04 AND VERIFY COMPLIANCE WITH THE
 CURRENT STANDARD. ASHRAE 62-04 STANDARD WAS ADOPTED AS
 PART OF THE 2006 REVISIONS TO THE FBC 2004.
  
 35. M6.01 FIRE DAMPER DETAIL: FIRE DAMPERS, SMOKE
 DAMPERS AND COMBINATION FIRE/SMOKE DAMPERS ARE TO BE
 INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS AND THEIR LISTING PER FBC,M
 607.2. PLEASE PROVIDE MANUFACTURER'S INSTRUCTIONS AND
 REMOVE ANY PORTION OF FIRE DAMPER DETAILS WHICH
 CONFLICT WITH SAME.
  
 36. M6.01 EXTERIOR WALL CAP DETAIL: IS IT THE INTENTION
 OF THIS DETAIL TO HAVE AN INLINE BACKDRAFT DAMPER AND A
 BACKDRAFT DAMPER IN THE WALL CAP? AN INLINE DAMPER AS
 WELL AS AN ACCESS PANEL IN THE DRYER EXHAUST DUCT IS
 PROHIBITED PER FBC,M 504.6 AS A SMOOTH INTERIOR SURFACE
 IS REQUIRED. PLEASE CLARIFY THE INTENT OF THIS DETAIL.
  
 37. M6.01 VIBRATION CURB DETAIL: OUTDOOR EQUIPMENT IS
 TO BE INSTALLED TO MEET WIND LOAD REQUIREMNTS PER FBC,M
 301.13. PROVIDE SUFFICIENT STRUCTURAL DETAILS WITH WIND
 LOAD CALCULATIONS FOR A BUILDING PLAN REVIEW TO
 DETERMINE COMPLIANCE WITH FBC CH 16.
  
 38. M6.01 TYPICAL VERTICAL A/C UNIT DIMENSIONAL DETAIL:
 PLEASE SHOW HOW REFRIGERANT PIPING WILL MEET THE
 REQUIREMENTS OF ASHRAE 15-810.3
  
 39. M6.02 DWELLING UNIT EXHAUST FAN DETAIL: EXHAUST
 DUCTS UNDER POSITIVE PRESSURE SHALL NOT PASS THROUGH A
 PLENUM PER FBC,M 601.3.
  
 40. M6.02 DUCT AND COONDENSING UNIT ROOF DETAIL: SEE
 COMMENT #37 REGARDING WIND LOADS AND OUTDOOR
 EQUIPMENT.
  
 41. M6.02 FIRESTOP DETAIL: HOW WILL THESE TWO SYSTEMS
 BE USED IN THIS APPLICATION GIVEN THE MAXIMUM ANNULAR
 SPACE ALLOWED IN THE FIRST DETAIL? HOW WILL THE 2ND
 DETAIL APPLY WHEN IT DOES NOT ALLOW FOR INSULATED PIPE
 AND ALLOWS ON 3 PIPES PER FIRE BARRIER OPENING?
  
 42. M6.02 AHU HANGING DETAIL: PLEASE SHOW MEANS OF
 SECONDARY/AUXILIARY DRAIN PROTECTION PER FBC,M 307.2.3.
 ALSO, SERVICE CLEARNCE IS TO COMPLY WITH FBC,M 306.3,
 NEC 110.26(A) AND MANUFACTURER'S INSTALLATION
 INSTRUCTIONS.
  
 43. M6.02 TYPICAL VERTICAL AHU DETAIL:
 A) PLEASE SHOW MEANS OF AUXILIARY/SECONDARY DRAIN
 PROTECTION PER FBC,M 307.2.3.
 B) FLOOR DRAIN MAY NOT BE LOCATED IN A PLENUM PER FBC,M
 602.
 C) IF CPVC IS TO BE USED FOR CONDENSATE, PLEASE PROVIDE
 SUBMITTAL DATA SHOWING CLEAR INSIDE DIMENSION OF PIPE
 (MIN. 3/4" I.D. PER FBC,M 307.2.2) AND SLAME
 SPREAD/SMOKE DEVELOPEMENT RATING PER FBC,M 602.2.1.
  
 44. PLEASE SEE ELECTRICAL COMMENT #4 REGARDING THE
 ENGINEER'S SIGNATURE.
  
 45. M0.00 EQUIPMENT IDENTIFICATION: IF PLASTIC
 NAMEPLATES ARE TO BE USEDIN PLENUMS, PLEASE PROVIDE
 FLAME SPREAD/SMOKE DEVELOPMENT RATING PER FBC,M
 602.2.1.
  
 46. M0.00 SMOKE CONTROL NOTE: FBC 412.5 DOES NOT RELATE
 TO SMOKE CONTROL OR HIGH-RISE CONSTRUCTION. PLEASE
 REMOVE OR CORRECT.
  
 47. PLEASE PROVIDE DETAIL SHOWING MEANS OF SUPPORT FOR
 DUCTS IN RISERS. FBC 106.1.1.
  
 48. M1.01 & M1.02: ARE GARAGE EXHAUST FANS TO RUN
 CONTINUOUS OR INTERMITTANTLY, CONTROLLED BY C.O.
 SENSORS? PLEASE SEE THE REQUIREMENTS OF FBC,M 404.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS:
  
 REVIEWED BY:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-08-11 Cont ID  
Sent By kstevens Date 2007-08-11 Time 16:00 Rev Time 0.00
Received By kstevens Date 2007-08-11 Time 16:00 Sent To  
Notes
2007-07-21 20:03:21DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINSTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
 3. OK - TO BE ADDRESSED BY MECHANICAL PLAN REVIEWER
  
 4. SHT A2.03 NOT ALL TERRACES, DECK DRAINS AROUND THE
 POOL & WALKWAYS SHOW EOD'S. SECTIONS 1107.1 & 1107.2 .
 PLEASE INDICATE THE LOCATION OF ALL REQUIRED SECONDARY
 DRAINS.
 ****RESPONSE NOTED, BUT DECK DRAIN WEST OF COL. LINE
 B/23 , NORTH SIDE OF POOL & TERRACE ON COL. LINE J/4
 SHOW NO SECONDARY DRAINAGE.
  
 5. OK
 6. OK
 7. OK
  
 8. SHT A2.41 SHOW SECONDARY DRAINS FOR THE TERRACES AND
 WALKWAY.SECTIONS 1107.1 & 1107.2.
 ****RESPONSE NOTED, BUT NO SECONDARY DRAIN IS SHOWN ON
 THE LAST TERRACE, (LN-1207). ALSO SHT A2.42 TERRACES
 LN-106, LN-111, LN-208, LN-307 SHOW NO DRAINAGE, BUT
 DETAIL 7/A801 (TYP) DOES NOT INDICATE DRAINAGE GAPS.
 PLEASE CLARIFY.-SHT A2.42 REFERS TO DETAIL 10/A807,
 BUT THAT DETAIL IS NOT FOUND. PLEASE CLARIFY.
  
 9.OK
 10. OK
 11. OK
 12. OK
 13. OK
 14. OK
 15. OK
 16. OK
  
 17. SHT P0.00 KEY NOTE #4 INDICATES A PERFORATED CAP
 FOR THE SECONDARY DRAIN. PLEASE CLARIFY. SECTION
 106.1.1. IF THE SECONDARY DRAIN IS FOR STORM, A FULL
 SIZE OPENING IS REQUIRED.
 ****RESPONSE NOTED, BUT WIRE MESH IS NOT APPROVED AS
 THIS CAN BE AN OBSTRUCTION. A CLEAR OPENING IS
 REQUIRED. SECTION 706.2. PLEASE REMOVE ALL OBSTRUCTIONS
 FROM THE END OF THE PIPE.
  
 18. OK
 19. OK
 20. OK
 21. OK
 22. OK
 23. OK
 24. OK
 25. OK
 26. OK
 27. OK
  
 28. SHT P1.03 TWO STORM LINES ARE NOT IDENTIFIED.
 SECTION 106.1.1.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED.
  
 29. OK
 30. OK
 31. OK
  
 32. SHT P1.03 KEY NOTE 19 SHOWN CONNECTING TO THE STORM
 RISER. CLARIFY. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT IT SEEMS LIKE 19 WAS CHANGED TO
 17. MANY OTHER CHANGES TO PLANS BESIDES COMMENT
 RESPONSES. THERE SEEM TO BE PLAN DEVELOPMENT BETWEEN
 REVIEWS AND AFTER THE 101 COMMENT RESPONSES ARE
 REVIEWED, I WILL HAVE TO DO A COMPLETE REVIEW LOOKING
 FOR ANY OTHER CHANGES TO THE PLANS NOT IDENTIFIED AS
 COMMENT RESPONSES.
  
 33. OK
 34. OK
 35. OK
 36. OK - KEY NOTE 11 ADDED.
 37. OK
 38. OK
 39. OK
 40. OK
 41. OK
 42. OK
 43. OK
 44. OK
 45. OK
 46. OK
 47. OK
 48. OK
 49. OK
 50. OK
 51. OK
 52. OK
 53. OK
 54. OK
 55. OK
 56. OK
  
 57. SHT P1.07 1 4" VTR IS SHOWN UNDER DUCT WORK FOR THE
 A/C SYSTEM. PLEASE CLARIFY. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT VTR WAS NOT MOVED. THE DUCT WAS
 DELETED FROM THE PLUMBING SHEETS, BUT UPON REVIEW OF
 THE MECHANICAL PLANS, THE DUCT IS STILL SHOWN OVER THE
 TOP OF THE VTR. PLEASE CLARIFY.
  
 58. OK
  
 59. SHT P1.07 KEY NOTES SEEM TO BE FOR MECHANICAL.
 PLEASE CLARIFY. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT NOTES 1 & 6 HAVE NOT BEEN
 FOUND. PLEASE CLARIFY.
  
 60. OK
 61. OK
 62. OK
 63. OK
 64. OK
 65. OK
 66. OK
 67. OK
 68. OK
 69. OK
 70. OK
 71. OK
  
 72. SHT P2.02 THE SANITARY COLLECTION SHOWS THE VENT
 FROM THE SHOWER CONNECTING TO RISER S/74. RISER S/74
 DOES NOT SHOW THE VENT CONNECTING TO THE RISER. PLEASE
 CLARIFY AND CORRELATE. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT SHT P2.02 HAS NOT BEEN REVISED.
 THERE ARE NOW 2 RISERS DESIGNATED S/74. PLEASE
 CLARIFY.
  
  
 73. SHT P2.02 RISER S/20 ON THE COLLECTION RISER IS
 SHOWN AS 88 DFU, BUT THE RISER DIAGRAM SHOWS IT AS 86
 DFU. PLEASE CLARIFY. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT NO CHANGE IS INDICATED ON S/20.
 PLEASE CLARIFY.
  
 74. OK
  
 75. SHT P2.06 2 RISERS ARE SUBMITTED FOR S/42. PLEASE
 CLARIFY. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THERE ARE STILL TWO S/42
 RISERS. ONE ON SHT P2.05 & ONE ON SHT P2.06. PLEASE
 CLARIFY.
  
 76. SHT P2.06 RISERS S/34, S/71, S/73, & S/41 ALL SHOW
 SHOWERS, BUT THE FLOOR PLAN SHOWS TUBS. PLEASE
 CORRELATE. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE SHOWERS WERE ALREADY SHOWN
 ON RISERS S/34, S/71 & S/73. NO CHANGE NOTED.
  
 77. OK
 78. OK
 79. OK
 80. OK
 81. OK
 82. OK
 83. OK
 84. OK
 85. OK
 86. OK
 87. OK
 88. OK
 89. OK
  
 90. SHT P2.13 THE SIZE OF THE DECK DRAINAGE PIPING
 SHALL NOT BE REDUCED IN THE DIRECTION OF FLOW. (6" TO
 4"). SECTION 704.2.
 ****RESPONSE NOTED, BUT TWO AREAS SHOW 8" REDUCED TO 6"
 IN THE DIRECTION OF FLOW AND ONE 4" RD DRAINING INTO 3"
 PIPE.
  
 91. SHT P2.13 THE TOTAL DRAINAGE AREA IS APPROX.
 20,140SF. THE SECONDARY DRAINS ADD UP TO 6,880SF.
 PLEASE CLARIFY. THE SECONDARY DRAINS SHALL DRAIN THE
 SAME AMOUNT OF SQUARE FOOTAGE AS THE PRIMARY DRAINS.
 SECTION 1107.3. SCUPPERS SHALL BE SIZED TO PREVENT THE
 DEPTH OF PONDING WATER FROM EXCEEDING THAT FOR WHICH
 THE ROOF WAS DESIGNED AS DETERMINED BY SECTION 1101.7.
 PLEASE KEEP IN MIND THE DEPTH OF THE WATER BEFORE THE
 SECONDARY DRAINAGE STARTS TO REMOVE THE STORM WATER AND
 THE HEIGHT OF THE SLIDING DOORS TO THE UNITS OFF THE
 TERACES.
 ****RESPONSE NOTED, BUT PLEASE CLARIFY WHAT NATURAL
 OVERFLOW PRETAINS TO. THIS IS A TERM I AM UNFAMILIAR
 WITH.-SHEET P1.04 INDICATES THE SLOPE OF THE DECK
 TO THE DECK DRAINS, BUT ALSO INDICATES THE SLOPE AWAY
 FROM THE DECK DRAINS IN THE SAME AREAS TOWARD THE POOL.
 PLEASE CLARIFY. PER SECTIONS 424.1 DEFINITION OF "WET
 DECK AREA" & SECTION 424.1.3.1.2 THE WET DECK SHALL
 SLOPE AWAY FROM THE POOL. PLEASE CLARIFY.
  
 92. SHT P2.14 INDICATES GAS PIPE SIZES BASED ON THE
 NFPA CHART. PIPING SHALL BE SIZED PER THE FBC-2004 FUEL
 GAS CODE. PLEASE CHANGE REFERENCE.
 ****RESPONSE NOTED, BUT REFERENCE NOTE NOT CHANGED.
 SINCE THE TOTAL DEVELOPED LENGTH IS NOW EXCEEDING THE
 200FT MAX ON FBC-2004 FUEL GAS TABLE FOR 2PSI THE TABLE
 FROM NFPA WILL BE ACCEPTABLE. PLEASE SUBMIT THE TABLE
 INDICATED. PLEASE MAKE SURE REFERENCE TO NFPA IS
 INDICATED ON THE SHEET WITH THE TABLE.
  
 93. SHT P2.14 THE LONGEST RUN IS INDICATED AS 58'0",
 BUT ADDITION INDICATES 62' WITHOUT COUNTING THE LENGTH
 OF PIPES FROM THE METER TO THE FIRST RISER. PLEASE
 RECHECK THE ADDITION AND ADD THE PIPE LENGTH FROM THE
 METER TO THE FIRST RISER. FBC-2004 FUEL GAS CODE
 APPENDIX A - USE OF CAPACITY TABLES A.3.1(4).
 ****RESPONSE NOTED. THIS COMMENT IS OK, BUT THE
 CONTINUING PLAN DEVELOPMENT BETWEEN REVIEWS HAS ADDED A
 GENERATOR THAT WILL GENERATE MORE COMMENTS.
  
 94. SHT P2.14 INDICATE THE LENGTH OF PIPES FROM THE
 REGULATOR TO THE POOL HEATER.
 ****RESPONSE NOTED, BUT THE LENGTHS IN QUESTION HAVE
 NOT BEEN INDICATED. COMMENT NOT ADDRESSED.
  
 95. OK
  
 96. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 ****RESPONSE NOTED, BUT PLEASE INDICATE WHERE IN THE
 MECHANICAL PLANS THIS CAN BE FOUND.
  
 97. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
 ****RESPONSE NOTED, BUT PLEASE INDICATE WHERE IN THE
 MECHANICAL PLANS THIS CAN BE FOUND.
  
 98. SHT P2.14 KEY NOTE #13 NOT APPROVED. SECTION
 504.7.2. SHOW TERMINATION FOR PAN DRAIN. ****RESPONSE
 NOTED, BUT KEY NOTE #13 STILL INDICATES TERMINATION IN
 THE GARAGE. THIS IS NOT APPROVED. IT IS POSSIBLE FOR
 CARBON MONOXIDE TO ENTER THE UNITS FROM THESE OPEN
 LINES. SUBMIT A ISOMETRIC RISER DIAGRAM FOR THE PAN
 DRAINS SHOWING ALL PIPE SIZES, MATERIAL AND TERMINATION
 POINT. SECTION 106.3.1.5.3(4)(13).
  
 99. SHT P3.02 INSTALLATION NOTES. SE SOVENT (SESCO) &
 TITE-RUFF SYSTEMS, DESIGN MANUAL 101/0 & TABLES. SUBMIT
 MANUF. SPECIFICATION FOR ALL. SHOW TESTING AND APPROVAL
 FOR ALL.
 ****RESPONSE NOTED, BUT THE SOVENT DETAILS DO NOT
 REFLECT THE DETAILS FROM THE DESIGN MANUAL 802. PLEASE
 CORRELATE DETAILS AND THE DESIGN MANUAL.
  
 100. OK
  
 101. PLEASE RESUBMIT THE SET OF PLUMBING PLANS WITH THE
 RED LINE MARK-UPS TO HELP EXPEDITE FOLLOWING PLAN
 REVIEWS.
 ****RESPONSE NOTED, BUT RED LINED MARK-UPS WERE NOT
 RESUBMITTED WITH THE PLANS. MANY EXTRA HOURS HAVE BEEN
 ADDED TO THE PLAN REVIEW AND BECAUSE OF THE PLAN
 DEVELOPMENT BETWEEN REVIEWS THIS WILL ADD TO THE REVIEW
 PROCESS.
  
 **********NEW COMMENTS***********
  
 1B. SHT P1.01 KEY NOTES #5 & #28 REMOVE REFERENCE TO
 WIRE MESH AS IT IS NOT APPROVED. SECTION 706.2.
  
 2B. SHT P1.01 KEY NOTE #36. THE POOL OVERFLOW SHALL
 CONNECT TO THE STORM SYSTEM.
  
 3B. SHT P1.01 KEY NOTES #28 & #29. PLEASE IDENTIFY WHAT
 WILL DRAIN INTO THESE DRAINS. SECTION 106.1.1.
  
 4B. SHT P1.02 KEY NOTE #15. PLEASE IDENTYFY WHAT WILL
 DRAIN INTO THIS DRAIN. SECTION 106.1.1.
  
 5B. SHT P1.02 REVISION #1 INDICATED ON SHEET IS NOT
 INDICATED ON THE REVISION INDEX. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 6B. SHT P1.02 KEY NOTES #22 THRU #25 ARE NEW ADDED TO
 INDEX BUT NOT INDICATED AS A REVISION WITH CLOUD OR
 REVISION NUMBER. PLEASE SHOW ALL REVISIONSWITH A
 CLOUD AND REVISION NUMBER. SECTION 106.1.3.
  
 7B. SHT P1.03 KEY NOTE #21 FLOOR DRAINS ARE NOT
 APPROVED INDIRECT WASTE RECEPTORS. A FLOOR SINK OR HUB
 DRAIN IS APPROVED PER SECTIONS 802.3 & 802.3.2.
  
 8B. SHT P1.03 KEY NOTE #23. PLEASE IDENTIFY WHAT WILL
 DRAIN INTO THIS LINE. SECTION 106.1.1.
  
 9B. SHT P1.03 KEY NOTES #25 THRU #27 ARE ADDED NEW
 WITHOUT A CLOUD OR REVISION NUMBER. PLEASE SHOW ALL
 REVISIONSWITH A CLOUD AND REVISION NUMBER. SECTION
 106.1.3.
  
 10B. SHT P1.03 IDENTIFY THE DRAIN THAT WAS INDICATED AS
 A PLANTER DRAIN ON PRIOR REVIEW SUBMITTAL, BUT IS NOW
 CONNECTED TO THE STORM OVERFLOW DRAIN LINE. SECTION
 106.1.1.
  
 11B. SHT P1.03 TWO 3" DRAINS SHOWN WITH NO INDICATION
 OF WHAT THEY DRAIN. PLEASE IDENTIFY THE DRAINS.
  
 12B. SHT P1.03A, (NEW SHEET), INTERSTITIAL LEVEL SHOWS
 TWO 4" DRAINS. PLEASE INDICATE WHAT SYSTEMS THESE
 CONNECT TO AND WHERE THEY CAN BE FOUND ON THE ISOMETRIC
 RISER DIAGRAMS.
  
 13B. SHT P1.04. SEE DEFINITION OF "WET DECK AREA" IN
 SECTION 424.1 OF THE BUILDING CODE AND SECTION
 424.1.3.1.2 THE REQUIREMENT FOR THE WET DECK AREA TO BE
 SLOPED AWAY FROM THE POOL. SLOPE INDICATORS ARE SHOWN
 TO BE SLOPING AWAY FROM THE POOL AND TOWARD THE POOL IN
 THE SAME AREAS. PLEASE CLARIFY. SECTION 106.1.1.
  
 14B. SHT P2.05 RISER S/45 DOES NOT REFLECT THE FLOOR
 PLAN ON FLOORS 3 THRU 8. PLEASE CORRELATE RISER AND
 FLOOR PLAN INFORMATION. SECTION 106.1.1.
  
 15B. SHT P2.10 BACKFLOW PROTECTION REQUIRED FOR THE
 WATER SUPPLY LINE TO THE FOUNTAIN. PLEASE INDICATE
 METHOD. SECTION 608.1.
  
 16B. SHT P2.14 KEY NOTE #13 IS NOT APPROVED. IT IS
 POSSIBLE FOR CARBON MONOXIDE TO ENTER THE UNITS FROM
 THESE OPEN LINES.
  
 17B. SHT P2.14 KEY NOTES 16, 17, 18, 19, 20 & 22 WERE
 NOT FOUND. PLEASE CLARIFY. SECTION 106.1.1.
  
 18B. SHT P3.04, (NEW SHEET), IS SHOWN WITH INFORMATION
 FOR THE DIESEL TANKS AND SYSTEM. THIS IS INFORMATION
 REQUIRED BY THE MECHANICAL PLAN REVIEWER ONLY. PLEASE
 RESUBMIT WITH THE INFORMATION ON THE MECHANICAL SHEETS
 ONLY.
  
 19B. NEW GAS COMMENT. SUBMIT MANUF. SPECIFICATIONS FOR
 THE GAS REGULATORS. INDICATE MODEL NUMBER AND SHOW
 LISTING.
  
 20B. MANUF. SPECIFICATIONS SHEETS FOR THE GENERATOR
 INDICATES THE GENERATOR WILL BE DIESEL. NO NATURAL GAS
 IS INDICATED. PLEASE SUBMIT MANUF. SPECIFICATIONS
 SHOWING LISTING FOR GAS, THE BTU'S AT 100% LOAD AND
 INSTALLATION INSTRUCTIONS WITH REQUIRED CLEARANCES.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-04-02 Cont ID  
Sent By kstevens Date 2007-04-02 Time 08:52 Rev Time 0.00
Received By kstevens Date 2007-03-26 Time 18:58 Sent To  
Notes
2007-04-02 18:30:41DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINSTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL ARCHITECTURAL SHEETS. A TITLE BLOCK MUST AT A
 MINIMUM CONTAIN THE FIRM LICENSE NUMBER. FAC
 61G1-16.004(2)
  
 2. IRRIGATION PERMIT AND PLANS ARE REQUIRED.
 (INFORMATIONAL)
  
 3. SHT A2.02 POOL EQUIPMENT ROOM SHALL BE VENTILATED.
 EITHER BY CROSS VENTILLATION OR BY FORCED DRAFT. PLEASE
 INDICATE METHOD. SECTION 424.1.5.4.
  
 4. SHT A2.03 NOT ALL TERRACES, DECK DRAINS AROUND THE
 POOL & WALKWAYS SHOW EOD'S. SECTIONS 1107.1 & 1107.2 .
 PLEASE INDICATE THE LOCATION OF ALL REQUIRED SECONDARY
 DRAINS.
  
 5. SHTS A2.03, A2.44 & A4.01 A URINAL IS REQUIRED IN
 THE MEN'S TOILET FOR THE POOL FACILITIES. TABLE
 424.1.6.1.
  
 6. SHT A2.05 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW THE SQUARE FOOTAGE OF EACH
 DRAINALONG WITH 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS, STAIRWAYS, MECH ROOMS ECT. ALONG
 WITH ALL AREAS OF ROOFS THAT DRAIN TO THE ROOF AREA
 FROM ABOVE. TABLE 1106.3.
  
 7. SHS A2.38, A2.39, A2.40 & A2.41 W/C'S IN BOTH MASTER
 BATHS, THAT ARE COMPARTMENTALIZED, DO NOT HAVE THE
 CLEAR FLOOR SPACE REQUIRED AS SHOWN ON PAGE 7.43. THE
 WALL CAN NOT EXTEND PAST 2' PER PAGE 7.44. SCALES OUT
 PAST 2'.
  
 8. SHT A2.41 SHOW SECONDARY DRAINS FOR THE TERRACES AND
 WALKWAY.SECTIONS 1107.1 & 1107.2.
  
 9. SHTS A2.71 & A2.72 NO FINISH INDICATED FOR THE POOL
 TOILET ROOMS. PLEASE SEE SECTION 424.1.6.1.2 AND
 SECTION 1210.2.
  
 10. SHT A5.01 BLOCKING FOR THE SHOWER SHALL COMPLY WITH
 PAGE 6.12. ALSO SHOW BLOCKING ON ALL THREE SIDES AS
 REQUIRED.
  
 11. SHT A5.02 UNITS 1,2,3,3M,5,6 & 7 BACKING REQUIRED
 ON ALL SIDES OF THE TUB PER PAGES 6..8 & 6.9, AND FOR
 THE SHOWERS PER PAGE 6.12 IN UNITS 1,3,3M,5,6, & 7.
  
 12. SHT A5.03 BACKING REQUIRED ON ALL SIDES OF THE TUB
 IN UNITS 03R,8,9,10,10R & 12 PER PAGES 6.8 & 6.9, AND
 FOR THE SHOWERS PER PAGE 6.12 IN UNITS 03R,8 & 9.
  
 13. SHT A5.03 DETAIL 16, THE CLEAR FLOOR SPACE IS
 REQUIRED FOR THE URINAL PER SECTION 11-4.18.3. PLEASE
 SHOW ON THE FLOOR PLAN.
  
 14. SHTS A5.03 & A5.04. W/C'S IN THE POOL TOILET ROOMS
 AND THE RETAIL TOILET ROOM SHALL BE 18" OFF THE WALL TO
 THE CENTERLINE OF THE FIXTURE. FIG. 11-28. THE LAVS
 SHALL BE 15" MINIMUM OFF THE WALL TO THE CENTERLINE OF
 THE FIXTURE TO CENTER ON THE CLEAR FLOOR SPACE 30".
 MINIMUM 30" FROM CENTERLINE OF THE W/C TO THE
 CENTERLINE OF THE LAVREQUIRED PER SECTION 405.3.1 &
 FIGURE 405.3.1.
  
 15. SHT A5.04 SHOW THE WATER CLOSET FLUSH CONTROLS AS
 REQUIRED IN SECTION 11-4.16.5, (WIDE SIDE).
  
 16. ALL PLUMBING, MECHANICAL, AND ELECTRICAL SHEETS.
 THE SIGNATURE OF THE ENGINEER IS REQUIRED. INITIALS ARE
 SHOWN. FAC 61G15-23.002(2) AND FS 471.025
  
 17. SHT P0.00 KEY NOTE #4 INDICATES A PERFORATED CAP
 FOR THE SECONDARY DRAIN. PLEASE CLARIFY. SECTION
 106.1.1. IF THE SECONDARY DRAIN IS FOR STORM, A FULL
 SIZE OPENING IS REQUIRED.
  
 18. SHT P1.01 INDICATE ALL RISER NUMBERS AT THE BASE OF
 EACH STACK AND THROUGH THE BUILDING TO TRACK EACH
 RISER. (EXAMPLE S/1, S/2, RWL/1, RWL/2, ETC.). SECTION
 106.1.2.
  
 19. SHT P1.01 KEY NOTES #5 & #12 NOT FOUND. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 20. SHT P1.01 STAIR 1 FIRE DRAIN IS LABELED "SD".
 PLEASE CLARIFY. SECTION 106.1.1.
  
 21. SHT P1.01 ONE "SD" LINE IS INDICATED AS A 6" SANT.
 LINE (6). PLEASE CLARIFY. SECTION 106.1.1.
  
 22. SHT P1.01 IDENTIFY THE RISER BETWEEN THE DRINKING
 FOUNTAIN AND THE FOUNTAIN DRAIN. (NO KEY NOTE NUMBER).
 SECTION 106.1.1.
  
 23. SHT P1.01 ONE CONDENSATE LINE TURNS INTO A STORM
 LINE. PLEASE CLARIFY. SECTION 106.1.1.
  
 24. SHT P1.01 "SD" LINE DOES NOT REFLECT THE RISER IN
 THE AREA OF THE THE GAS LINE & BY STAIR 2. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 25. SHT P1.01 THE SANT. LINE BY SWITCHGEAR ROOM DOES
 NOT REFLECT THE RISER. PLEAE CORRELATE. SECTION
 106.1.1.
  
 26. SHT P1.02 IDENTYFY ALL RISERS FOR ALL SYSTEMS.
 SECTION 106.1.1.
  
 27. SHT P1.02 KEY NOTES. THE FOLLOWING KEY NOTES WERE
 NOT FOUND. 4,11, & 15. NOTE 10 INDICATES IRRIGATION,
 COLD WATER AND "GAS PIPE".PLEASE CLARIFY. SECTION
 106.1.1.
  
 28. SHT P1.03 TWO STORM LINES ARE NOT IDENTIFIED.
 SECTION 106.1.1.
  
 29. SHT P1.03 RISERS D/3 & CD/3 ARE MISLABELED. SECTION
 106.1.1.
  
 30. SHT P1.03 ONE RISER IS LABELED AS BOTH KEY NOTES
 (17) & (18). PLEASE CLARIFY. SECTION 106.1.1.
  
 31. SHT P1.03W/1 DESIGNATIONAND KEY NOTE NUMBER
 NEAR A/C UNIT IN TENANT STORAGE ROOM ARE NOT LEGIBLE.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 32. SHT P1.03 KEY NOTE 19 SHOWN CONNECTING TO THE STORM
 RISER. CLARIFY. SECTION 106.1.1.
  
 33. SHT P1.03 KEY NOTES 3,9,11,13,16 & 20 WERE NOT
 FOUND. PLEASE CLARIFY. SECTION 106.1.1.
  
 34. SHT P1.03 RWL/4 DOES NOT LINE UP WITH THE RISERS ON
 THE NEXT LEVEL. SHOW OFFSET ON THE RISER DIAGRAM.
 SECTION 106.1.1.
  
 35. SHT P1.04 SHOWS THE URINAL IN THE WOMEN'S TOILET
 ROOM. THIS IS REQUIRED IN THE MEN'S TOILET ROOM PER
 SECTION 424.1.6.1.
  
 36. SHT P1.04 KEY NOTE (11) INDICATED ON THE FLOOR PLAN
 IS NOT SHOWN ON THE KEY NOTE SCHEDULE. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 37. SHT P1.04 THE PRL LINE FOR RISER S/64 IS NOT SHOWN
 ON THE FLOOR PLAN. THIS DOES NOT REFLECT THE RISER
 DIAGRAM. PLEASE CORRELATE. SECTION 106.1.1.
  
 38. SHT P1.04 THE PIPING FOR S/16 DOES NOT REFLECT THE
 RISER DIAGRAM. CORRELATE RISER & FLOOR PLAN. SECTION
 106.1.1.
  
 39. SHT P1.04 S/7 DESIGNATION SHOWN BUT DOES NOT POINT
 TO ANY RISER. PLEASE CLARIFY. SECTION 106.1.1.
  
 40. SHT P1.04 THE SINK INDICATED ON RISER S/10 IS NOT
 SHOWN ON THE FLOOR PLAN. PLEASE CLARIFY. SECTION
 106.1.1.
  
 41. SHT P1.04 MANY PLANTER DRAINS & DECK DRAIN AREAS
 SHOW WHAT APPEARS TO BE EXTRA DRAINS. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 42. SHT P1.04 THE OVERFLOW SCUPPERS SHALL BE LOCATED AS
 NEAR AS PRACTICAL TO THE REQUIRED VERTICAL LEADERS OR
 DOWNSPOUTS. SOME AREAS HAVE NOOVERFLOW SCUPPERS.
 SECTION 1503.4.3. OVERFLOW SCUPPERS SHALL BE SIZED PER
 SECTIONS 1101.7 & 1107.3 AS WELL AS TABLE 1106.7.
  
 43. SHT P1.04 SOME AREAS HAVE NO SECONDARY DRAINS ON
 THE DECK. SOME AREAS APPEAR TO BE ABLE TO DRAIN INTO
 THE THE UNIT BEFORE DRAINING INTO THE SECONDARY DRAIN
 BECAUSE OF THE DISTANCE FROM THE MAIN DRAIN TO THE
 OVERFLOW DRAIN. PLEASE CLARIFY. SECTIONS 106.1.1 AND
 1107.1.
  
 44. SHT P1.04 SOME PLANTER DRAINS, DECK DRAINS SIZES
 AND SQUARE FOOTAGE ARE NOT LEGIBLE AS THEY ARE
 SUPERIMPOSED OVER OTHER PLAN INFORMATION. PLEASE MAKE
 ALL INFORMATION LEGIBLE. SECTION 106.1.1.
  
 45. SHT P1.04 PIPING ON THE FLOOR PLAN DOES NOT REFLECT
 THE RISER AT THE BASE OF RISERS S/44, S/45, S/69 (W/M).
 PLEASE CORRELATE. SECTION 106.1.1.
  
 46. SHT P1.04 RISER CD/4 DESIGNATION NOT SHOWN. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 47. SHT P1.05 PIPING ON THE FLOOR PLAN DOES NOT REFLECT
 THE RISER AT RISERS S/4 (SINK), S/7, S/10 (SINK), S/11
 (W/M), S/23 (LAV), S/44, S/32. PLEASE CORRELATE
 INFORMATION. SECTION 106.1.1.
  
 48. SHT P1.05 RISER S/56 DESIGNATION IN NOT LEGIBLE.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 49. SHT P1.05 RISER CD/4 DESIGNATION NOT INDICATED.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 50. SHT P1.05 RWL/10 NOT SHOWN. PLEASE CLARIFY. SECTION
 106.1.1.
  
 51. SHT P1.06 PIPING ON THE FLOOR PLAN DOES NOT REFLECT
 THE RISER DIAGRAMS FOR S/4, S/7, S/10, S/11 & S/50.
 CORRELATE. SECTION 106.1.1.
  
 52. SHT P1.06 RISER S/56 DESIGNATION IS NOT LEGIBLE.
 CLARIFY. SECTION 106.1.1.
  
 53. SHT P1.06 RISER CD/4 NOT SHOWN. SECTION 106.1.1.
  
 54. SHT P1.07INDICATE THE STACK NUMBER FOR EACH VTR
 TO VERIFY ALL VENTS THRU THE ROOF. SECTION 106.1.1.
  
 55. SHT P1.07 INDICATE THE RWL NUMBER FOR EACH ROOF
 DRAIN. SECTION 106.1.1.
  
 56. SHT P1.07 MANY VTR'S, RD'S, SF AREAS, ETC ARE
 PRINTED OVER OTHER INFORMATION AND ARE NOT LEGIBLE.
 PLEASE CLEAR UP ALL INFORMATION. SECTION 106.1.1.
  
 57. SHT P1.07 1 4" VTR IS SHOWN UNDER DUCT WORK FOR THE
 A/C SYSTEM. PLEASE CLARIFY. SECTION 106.1.1.
  
 58. SHT P1.07 SOME AREAS FOR THE ROOF DRAINS DO NOT
 SHOW ALL THE AREAS THAT CONTRIBUTE TO THE TOTAL SF.
 SOME UPPER ROOFS (SUCH AS STAIR ROOFS, MAINT. ROOM
 ROOF, CIRCULAR ROOF), VERTICAL WALLS (SUCH AS STAIRS OR
 MAINTENANCE ROOM), DO NOT SHOW ANY CONTRIBUTION. PLEASE
 RECHECK ALL AREAS TO VERIFY TOTAL AREA FOR EACH DRAIN.
 TABLE 1106.3 AND SECTION 106.1.1.
  
 59. SHT P1.07 KEY NOTES SEEM TO BE FOR MECHANICAL.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 60. SHT P2.01 THE 3" BRANCH LINE DOWNSTREAM OF RISER
 S/72 DOES NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE.
 SECTION 106.1.1.
  
 61. SHT P2.01 PIPING LAYOUT ON THE FLOOR PLAN TO RISERS
 S/45 & S/46 DOES NOT REFLECT THE RISER DIAGRAM. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 62. SHT P2.01 INDICATE WHERE RISER S/41 CONNECTS TO THE
 BUILDING DRAIN/BRANCH LINE. SECTION 106.1.1.
  
 63. SHT P2.01 THE COLLECTION RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN DOWNSTREAM OF 6" HD. (SHOWS AN
 EXTRA FLOOR DRAIN). CORRELATE. SECTION 106.1.1.
  
 64. SHT P2.01 HUB DRAIN INDICATES A 10"X72" HUB PIPE
 SEALED AT THE TOP. THE FIRE LINE DRAIN SHALL DRAIN TO
 AN INDIRECT WASTE RECEPTOR, AND BY SEALING THE TOP, IT
 WILL BE A DIRECTION CONNECTION. PLEASE CLARIFY. SECTION
 802.1.5.
  
 65. SHT P2.01 A SECOND RISER S/31 IS INDICATED AS RISER
 S/28 ON THE FLOOR PLAN. PLEASE CORRELATE & CLARIFY.
 SECTION 106.1.1.
  
 66. SHT P2.01 PLEASE GIVE A DESIGNATION TO EACH
 BUILDING DRAIN INTO THE BUILDING IN ORDER TO TRACK THE
 PIPING AND EXPEDITE THE REVIEW PROCESS. SECTION
 106.1.1.
  
 67. SHT P2.02 RISERS S/62, S/67 & S/17 WERE NOT FOUND.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 68. SHT P2.02 SECTION (A) INDICATES THE REVENT
 CONNECTING TO RISER S/6. RISER S/6 DOES NOT SHOW VENT
 CONNECTION TO RISER. PLEASE CLARIFY. SECTION 106.1.1 &
 TABLE 916.1.
  
 69. SHT P2.02 RISER S/58 SHOWS DFU AS 70, BUT THE
 COLLECTION RISER INDICATES DFU AS 86. PLEASE CLARIFY.
 SECTION 106.1.1. & TABLES 710.1(1) & 710.1(2).
  
 70. SHT P2.02 THE SANITARY COLLECTION RISER DOES NOT
 REFLECT THE FLOOR PLAN BY THE SECOND RISER (S/74).
 PLEASE CORRELATE. SECTION 106.1.1.
  
 71. SHT P2.02 RISER S/18 IS SHOWN AS 84 DFUON THE
 COLLECTION RISER, BUT ONLY 14 DFU ON THE RISER DIAGRAM.
 PLEASE CLARIFY & CORRELATE. SECTION 106.1.1.
  
 72. SHT P2.02 THE SANITARY COLLECTION SHOWS THE VENT
 FROM THE SHOWER CONNECTING TO RISER S/74. RISER S/74
 DOES NOT SHOW THE VENT CONNECTING TO THE RISER. PLEASE
 CLARIFY AND CORRELATE. SECTION 106.1.1.
  
 73. SHT P2.02 RISER S/20 ON THE COLLECTION RISER IS
 SHOWN AS 88 DFU, BUT THE RISER DIAGRAM SHOWS IT AS 86
 DFU. PLEASE CLARIFY. SECTION 106.1.1.
  
 74. SHT P2.06 2 RISERS FOR S/2 AND S/59 ARE SHOWN. ONE
 IS A SOVENT SYSTEM AND THE OTHER IS A CONVENTIONAL
 SYSTEM.THE FLOOR PLAN INDICATES A SOVENT SYSTEM.
 PLEASE CORRELATE AND DELETE THE SYSTEM NOT USED.
 SECTION 106.1.1.
  
 75. SHT P2.06 2 RISERS ARE SUBMITTED FOR S/42. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 76. SHT P2.06 RISERS S/34, S/71, S/73, & S/41 ALL SHOW
 SHOWERS, BUT THE FLOOR PLAN SHOWS TUBS. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 77. SHT P2.09 KEY NOTE #1 & RISER DIAGRAM INDICATE AIR
 CHAMBERS. AIR CHAMBERS ARE NOT APPROVED. DELETE FROM
 THE RISER AND THE NOTES. SECTION 604.9 & PDI-WH 201.
  
 78. SHT P2.09 RISERS W/4, W/5, W/6, W/8, W/9, W/11,
 W/13, W/17 & W/18 SHOW 1" SUPPLY TO EACH UNIT, BUT ONLY
 ARE BEING FED BY 3/4" ON THE RISER AT THE 8TH FLOOR.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 79. SHT P2.09 RISER W/7 SHOWS 3/4" TO THE 8TH FLOOR &
 3/4"SUPPLY TO THE UNIT, BUT THE UNIT RISER SHOWS 1"
 SUPPLY TO THE UNIT. PLEASE CLARIFY. SECTION 106.1.1.
  
 80. SHT P2.09 RISER W/14 INDICATES A UNIT 14, BUT NO
 UNIT 14 HAS BEEN FOUND. PLEASE CLARIFY. SECTION
 106.1.1.
  
 81. SHT P2.10 RISER W/15 SHOWS 1-1/4" AT THE BASE OF
 THE RISER, BUT 1-1/2" IS SHOWN ON THE RISER ON SHT
 P2.09. PLEASE CLARIFY. SECTION 106.1.1.
  
 82. SHT P2.11 RWL/16 RISER SHOWS 750SF, BUT THE ROOF
 PLAN SHOWS 930SF. PLEASE CORRELATE. SECTION 106.1.1 &
 TABLE 1106.3.
  
 83. SHT P2.11 RWL/15 RISER SHOWS 930SF, BUT THE ROOF
 PLAN SHOWS 1440SF. PLEASE CORRLEATE. SECTION 106.1.1. &
 TABLE 1106.3.
  
 84. THE CONNECTION OF RWL/16 TO RWL/15 ON THE RISER
 DOES NOT REFLECT THE ISOMETRIC. ONE SHOWS THE
 CONNECTION ON THE HORIZONTAL AND THE OTHER SHOWS THE
 CONNECTION ON THE VERTICAL. CORRELATE. SECTION 106.1.1
 & TABLE 1106.3.
  
 85. THE SECTION OF HORIZONTAL PIPE BETWEEN RISERS RWL/8
 & RWL/11 SHALL BE A MINIMUM 5" PER TABLE 1106.3.
  
 86. SHT P2.12 THE RISER DOES NOT REFLECT THE FLOOR PLAN
 PIPING IN 3 AREAS ON THE GROUND FLOOR. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 87. SHT P2.13 RECHECK SQUARE FOOTAGE OF EACH AREA. SF
 OF ONE DECK DRAIN SHOWS 80SF, BUT BY SCALING THE AREA
 IT IS MORE. PLEASE CLARIFY. SECTION 106.1.1 & TABLE
 1106.3.
  
 88. SHT P2.13 ONE LINE SHOWS 4" @1700SF. A MINIMUM OF
 5" IS REQUIRED UNLESS THE SLOPE IS GREATER THAN
 1/8"/FT. PLEASE CLARIFY. TABLE 1106.3.
  
 89. SHT P2.13 THE RISER DOES NOT REFLECT THE FLOOR PLAN
 PIPING IN 3 AREAS. PLEASE CORRELATE. SECTION 106.1.1.
  
 90. SHT P2.13 THE SIZE OF THE DECK DRAINAGE PIPING
 SHALL NOT BE REDUCED IN THE DIRECTION OF FLOW. (6" TO
 4"). SECTION 704.2.
  
 91. SHT P2.13 THE TOTAL DRAINAGE AREA IS APPROX.
 20,140SF. THE SECONDARY DRAINS ADD UP TO 6,880SF.
 PLEASE CLARIFY. THE SECONDARY DRAINS SHALL DRAIN THE
 SAME AMOUNT OF SQUARE FOOTAGE AS THE PRIMARY DRAINS.
 SECTION 1107.3. SCUPPERS SHALL BE SIZED TO PREVENT THE
 DEPTH OF PONDING WATER FROM EXCEEDING THAT FOR WHICH
 THE ROOF WAS DESIGNED AS DETERMINED BY SECTION 1101.7.
 PLEASE KEEP IN MIND THE DEPTH OF THE WATER BEFORE THE
 SECONDARY DRAINAGE STARTS TO REMOVE THE STORM WATER AND
 THE HEIGHT OF THE SLIDING DOORS TO THE UNITS OFF THE
 TERACES.
  
 92. SHT P2.14 INDICATES GAS PIPE SIZES BASED ON THE
 NFPA CHART. PIPING SHALL BE SIZED PER THE FBC-2004 FUEL
 GAS CODE. PLEASE CHANGE REFERENCE.
  
 93. SHT P2.14 THE LONGEST RUN IS INDICATED AS 58'0",
 BUT ADDITION INDICATES 62' WITHOUT COUNTING THE LENGTH
 OF PIPES FROM THE METER TO THE FIRST RISER. PLEASE
 RECHECK THE ADDITION AND ADD THE PIPE LENGTH FROM THE
 METER TO THE FIRST RISER. FBC-2004 FUEL GAS CODE
 APPENDIX A - USE OF CAPACITY TABLES A.3.1(4).
  
 94. SHT P2.14 INDICATE THE LENGTH OF PIPES FROM THE
 REGULATOR TO THE POOL HEATER.
  
 95. SHT P2.14 SUBMIT THE MANUF. SPECIFICATION SHEETS
 FOR THE POOL HEATER, AND THE REGULATOR. INDICATE THE
 MODEL FOR EACH AND SHOW THE LISTING. STANDARDS NFPA 54,
 NFPA 58, AND THE FBC-2004 FUEL GAS CODE SEC 402.2.
  
 96. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 97. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 98. SHT P2.14 KEY NOTE #13 NOT APPROVED. SECTION
 504.7.2. SHOW TERMINATION FOR PAN DRAIN.
  
 99. SHT P3.02 INSTALLTION NOTES. SE SOVENT (SESCO)&
 TITE-RUFF SYSTEMS, DESIGN MANUAL 101/0 & TABLES. SUBMIT
 MANUF. SPECIFICATION FOR ALL . SHOW TESTING AND
 APPROVAL FOR ALL.
  
 100. THERMAL EXPANSION CONTROL IS REQUIRED PER SECTION
 607.3.2. PLEASE INDICATE METHOD.
  
 101. PLEASE RESUBMIT THE SET OF PLUMBING PLANS WITH THE
 RED LINE MARK-UPS TO HELP EXPEDITE FOLLOWING PLAN
 REVIEWS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2007-07-24 Cont ID  
Sent By mflis Date 2007-07-24 Time 08:52 Rev Time 0.00
Received By mflis Date 2007-07-24 Time 08:21 Sent To  
Notes
2007-07-24 09:03:51ZONING REVIEW: FAILED
  
 1) SIDEWALK MATERIAL SHALL BE CONCRETE. PLEASE REVISE
 ARCHITECTURAL SITE PLAN TO MATCH LH-1, REMOVING PAVERS
 FROM SIDEWALK. PAVERS PERMITTED WITHIN PLAZA ONLY.
 2) PLEASE INDICATE PLANT SCREENING MATERIAL FOR
 BACKFLOW PREVENTER WITHIN PLAZA.
 3) FUEL STORAGE TANK INDICATED BELOW PLAZA. PLEASE
 CONFIRM LANDSCAPE ARCHITECT HAS REVIEWED LOCATION AND
 IMPACT TO HISTORIC TREE.
 4) PARKING TOTALS APPEAR INCORRECT IN TABLE. TABLE
 INDICATES 63 GROUND FLOOR SPACES, DRAWINGS SHOW ONLY
 62. PARKING TOTAL SHOULD BE REVISED TO 140 IF THIS IS
 THE CASE.
 5) COLUMNS APPEAR TO IMPINGE UPON SEVERAL PARKING
 SPACES. ESP. SEE SPACE #4 ON GROUND FLOOR. PLEASE
 PROVIDE DETAILS TO CONFIRM THIS IS WORKING.
 6) PLEASE SHOW DRIVE LANE STRIPING FOR LANE SHIFT ON
 2.01. AS VEHICLES ENTER GARAGE, THEY WILL SHIFT NORTH
 TO GET AROUND COLUMN. UNCLEAR IN CURRENT DRAWINGS.
 7) PLEASE SHOW ONE-WAY DIRECTIONAL MARKING ON 2.01 AND
 2.02 FOR 12' WIDE LANES.
 8) PROVIDE DIMENSION STRINGS TO CONFIRM SPACE #20 MEETS
 ADA. SPACE IS UP AGAINST WALL.
 9) DOORS AT CORNER RETAIL MAY NOT SWING INTO SIDEWALK
 AREA. ENTRY SHALL BE RECESSED OR DOORS SHOULD SWING
 IN.
 10) PLEASE DESCRIBE HOW VEHICULAR STACKING WILL WORK
 WITH ROLL-UP DOORS.
 11) AIR RIGHTS EASEMENTS WILL BE NECESSARY FOR
 BALCONIES AND OTHER OVERHANGS. PLEASE SUBMIT FINALIZED
 EASEMENT DRAWINGS TO PLANNING STAFF.
 12) PLEASE DETAIL ON PROJECT DATA SHEET THE INFORMATION
 CONFIRMING COMPLIANCE WITH RIP PROGRAM. THIS MUST BE
 PROVIDED IN TABLE FORM.
 13) MAIN LOBBY ENTRANCE DOOR SHALL BE ACCESSED DIRECTLY
 FROM THE SIDEWALK. THIS IS A CRIME PREVENTION CONCERN.
 14) PLEASE CONFIRM COMPLIANCE WITH DAC APPROVAL.
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 1 Status F Date 2007-03-14 Cont ID  
Sent By aaponte Date 2007-03-14 Time 17:24 Rev Time 0.00
Received By aaponte Date 2007-03-14 Time 17:24 Sent To  
Notes
2007-03-14 17:55:001. SIDEWALK MATERIAL SHALL BE CONCRETE ALONG DATURA ST.
 PAVERS ARE NOT ALLOWED. THE OLIVE AVENUE SIDEWALK SHALL
 BE THE SAME THAT IS CURRENTLY IN PLACE, FOLLOWING THE
 NEW STREETSCAPE DESIGN.
 2. TREES ALONG OLIVE AVENUE SHALL MATCH EXISTING TREES
 ON THE EAST SIDE OF THE ROAD. TREES ALONG DATURA ST
 SHALL BE LIVE OAKS.
 3. WHY IS A PROPOSED CHANGE ON THE CURB DETAIL ALONG
 DATURA ST.
 4.ON LANDSCAPE DRAWINGS PLEASE CALL INDICATE HISTORIC
 TREE TO BE PRESERVED AND PROTECTIVE MEASURES DURING
 CONSTRUCTION.
 5. ON PARKING FLOOR PLANS PLEASE SHOW PARKING DETAIL TO
 ALLOW FOR AN ACCURATE MEASURE OF PARKING DIMENSIONS.
 6. PLEASE SHOW PROPERTY LINE PROJECTION ON UPPER LEVEL
 FLOOR PLANS.
 7. AN AIR RIGHTS EASEMENT IS REQUIRED FOR SOME
 BALCONIES AND ROOF OVERHANGS. PLEASE CONFIRM THAT
 PROPOSED AIR RIGHT EASEMENT MATCHES SUBMITTED DRAWINGS
 AND PROCEED WITH ITS APPROVAL THROUGH THE CITY
 COMMISSION.
 8. PLEASE DETAIL ON THE PAGE CONTAINING THE PROJECT
 DATA, THE INFORMATION CONFIRMING COMPLIANCE WITH RIP
 PROGRAM, SUCH AS, AMOUNT OF OPEN SPACE REQUIRED AND
 OTHERS.
 9. MAIN ENTRANCE DOOR SHALL BE LOCATED ON THE FRONTAGE
 LINE. PROPOSED LOCATION ON THE SIDE RAISES CEPTED
 CONCERNS.
 10. PLEASE CONFIRM COMPLIANCE WITH MAXIMUM ALLOWED
 OPENNINGS ALONG THE ALLEY PROPERTY LINE.
 11. GARAGE ENTRANCE ALONG OLIVE AVENUE SHALL BE
 MAINTAINED AT THE SIDEWALK LEVEL.
 12. PLEASE PRESENT DETAIL DRAWINGS FOR THE OPEN SPACE,
 INCLUDING THE TREATMENT PROPOSED TO BLANK WALLS AS
 SHOWNS DURING DAC APPROVAL PROCESS.
 13. LANDSCAPE UNITS SHALL BE INSTALLED, NEXT TO THE
 CURB, WITH A MAXIMUM SPACING OF 40 FEET ON CENTER.
 14. PLEASE CONFIRM LIGHTING PROPOSED FOR OPEN SPACE IS
 MEETING CEPTED PRINCIPLES.
 15. REQUIRED PARKING IS 145 SPACES, PROJECT IS ONLY
 PROVIDING 141 SPACES ACCORDING WITH SUBMITTED TABLE.


Account Summary | Usage Policy | Privacy Policy