| 2007-05-03 12:09:55 | |
| | DATURA & OLIVE |
| | RESIDENCE |
| | 9 STORY R-2, MERCANTILE& S-2 |
| | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 07020735 |
| | ADDRESS: 302 DATURA ST |
| | CONT: PEGASUS CONSTRUCTION |
| | TEL: (954)946-4227 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1STREVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | 2)FBC 1802.2.1 QUESTIONABLE SOILS, |
| | WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN |
| | DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT |
| | SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| | OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION |
| | BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE |
| | PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 . REPORTS |
| | HAVE COPIED SIGNATURES, NOT ORIGINALS. |
| | |
| | 3)FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT. |
| | NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS |
| | NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE |
| | RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: |
| | 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT |
| | THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 4)WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION |
| | SERVICES DEPARTMENT |
| | REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS |
| | REQUIRED BY S. 553.79(5) FLORIDA |
| | STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS |
| | CODE. CONTACT HAROLD PISKURA MANAGER OF THE SPECIAL |
| | INSPECTOR PROGRAM AT (561) 805-6711 FOR FURTHER |
| | INFORMATION BEFORE THE PERMIT MAY BE ISSUED. |
| | |
| | 5)W.P.B. AMENDMENT 105.13.4.4 ALL PLANS FOR THE |
| | BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY |
| | THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| | THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| | LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 6)FL S. S. 553.71(7) " THRESHOLD BUILDING" MEANING |
| | ANY BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT |
| | IN HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY |
| | CLASSIFICATION AS DENIED IN THE FLORIDA BUILDING CODE |
| | WHICH EXCEEDS 5,000 SQ FT IN AREA AND AN OCCUPANT |
| | CONTENT OF GREATER THAN 500 PERSONS. 105.13.1 THE |
| | ENFORCING AGENCY SHALLREQUIRE A SPECIAL INSPECTOR TO |
| | PERFORM STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING |
| | PURSUANT TO A STRUCTURALINSPECTION PLAN PREPARED BY |
| | THE ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN |
| | MUST BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE |
| | ISSUANCE |
| | OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A |
| | THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL |
| | INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION |
| | PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE |
| | ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED |
| | DOCUMENTS. |
| | |
| | 7) 109.3.10*IMPACT OF CONSTRUCTION. ALL CONSTRUCTION |
| | ACTIVITY REGULATED BY THIS CODE SHALL BE PREFORMED IN A |
| | MANNERSO AS NOT TO ADVERSELY IMPACT THE CONDITION OF |
| | ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO |
| | AFFECT SAID PROPERTY PURSUANT TO CONSENT BY THE |
| | APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS |
| | AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS |
| | INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST, |
| | NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE |
| | STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION |
| | ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE |
| | WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY |
| | REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS |
| | OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS, |
| | CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL |
| | DEVELOPMENT, INCLUDING ADDITIONS, POOLS, |
| | PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING |
| | PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ |
| | FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A |
| | PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| | DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| | CERTIFICATE FROM A LICENSED ENGINEER SHALL BE SUBMITTED |
| | TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL OF THE |
| | FINAL INSPECTION. |
| | |
| | |
| | 8 ) 109.3.10.1 HURRICANE PROTECTION.IT SHALL BE |
| | UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED |
| | MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR |
| | OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS. |
| | AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE |
| | HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH |
| | CONSTRUCTION MATERIALS, |
| | EQUIPMENT AND DEBRIS SHALL BE EITHER REMOVED FROM THE |
| | CONSTRUCTION SITE OR SECURED IN SUCH A MANNER AS TO |
| | MINIMIZE THE DANGER OF SUCH CONSTRUCTION MATERIALS, |
| | EQUIPMENT AND DEBRIS CAUSING DAMAGE TO PERSONS OR |
| | PROPERTY FROM HIGH WINDS. ANY PERSONS WHO FAIL TO |
| | COMPLY TO REMOVE OR SECURE THE CONSTRUCTION MATERIALS |
| | EQUIPMENT AND DEBRIS WITHIN |
| | 24 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE |
| | SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION |
| | TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS |
| | SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO |
| | SECTION 113 OF THIS CHAPTER. |
| | |
| | 9) THE ARCHITECTURAL COVERSHEET UNDER THE PROJECT DATA |
| | SUMMARY: |
| | 9A) PLANS ARE DESIGNED UNDER THE 2004 FBC, PLANS |
| | SUBMITTED TO THE CITY AFTER DEC. 8, 2006 ARE TO BE |
| | DESIGNED TO THE 2006 FBC. |
| | |
| | 9B) PLANS ALSO INDICATE THIS IS TO BE A 8 STORY |
| | BUILDING. THE SO CALLED MEZZANINE LEVEL DOES NOT MEET |
| | THE DEFINITION OF A MEZZANINE THIS IS THE SECOND STORY, |
| | CREATING A NINE STORY BUILDING. |
| | |
| | 9C)PLANS FAIL TO IDENTIFY WHAT TYPE BUILDING TYPE |
| | THIS BUILDING WAS DESIGNED TOO? TABLE 503/ TABLE 601? |
| | |
| | 10) SHEET A0.02 GENERAL NOTE# 15 REFERS TO THE 2001 |
| | FBC, PLEASE MAKE THE CORRECTION. |
| | |
| | 11) A2.01 THE PLANS TO HAVE OPENINGS IN THE PARKING |
| | GARAGE ON THE FIRST AND SECOND FLOOR |
| | (MEZZANINE LEVEL) OF THE PARKING GARAGE ON THE SOUTH |
| | WALL. PLEASE SEE TABLE 602 FOR TYPE 1A & 1B BUILDINGS |
| | REQUIRE 3 HR RATED WALLS BASED ON FIRE SEPARATION AND |
| | TABLE 704.8 FOR UNPROTECTED OPENINGS 0-3? FROM THE |
| | PROPERTY LINE ARE NOT PERMITTED. FOOTNOTE ?G? ALLOWS |
| | OPENINGS WHEN THE EXTERIOR BEARING WALLS, EXTERIOR NON |
| | BEARING WALLS AND EXTERIOR STRUCTURAL FRAME ARE NOT |
| | REQUIRED TO BE FIRE-RESISTANCE RATING.SEE LOUVERED |
| | OPENINGS IN THE SOUTH WALL AND OPENING ?B? EAST WALL. |
| | 704.8.2 FIRST STORY. |
| | IN OCCUPANCIES OTHER THAN GROUP H, UNLIMITED |
| | UNPROTECTED OPENINGS ARE PERMITTED IN THE FIRST STORY |
| | OF EXTERIOR WALLS FACING A STREET THAT HAVE A FIRE |
| | SEPARATION DISTANCE OF GREATER THAN 15 FEET (4572 MM), |
| | OR FACING AN UNOCCUPIED SPACE. THE UNOCCUPIED SPACE |
| | SHALL BE ON THE SAME LOT OR DEDICATED FOR PUBLIC USE, |
| | SHALL NOT BE LESS THAN 30 FEET (9144 MM) IN WIDTH, AND |
| | SHALL HAVE ACCESS FROM A STREET BY A POSTED FIRE LANE |
| | IN ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE . |
| | |
| | 12)SHEET A9.02 MAKES REFERENCE TO TABLE 709.3.1 FOR |
| | EQUIVALENT THICKNESS OF MASONRY UNITS BUT THIS TABLE IS |
| | REFERENCED UNDER THE FBC 2001 CODE, PLEASE CORRECT. |
| | |
| | 13THE SOUTH &EAST CORNERS OF THE PARKING GARAGE APPEAR |
| | TO BE LESS THAN 3?-0? FROM THE PROPERTY , PLEASE |
| | PROVIDE THE EQUIVALENT THICKNESS OF THE CONCRETE BLOCK |
| | AND HR RATING? |
| | TABLE 721.3.2. |
| | |
| | 14) A2.01INDICATES THE USE OF CAR LIFTS. PLEASE |
| | PROVIDE MANUFACTURERS SPECS ON THESE UNITS, ADDITIONAL |
| | COMMENTS MAY APPEAR ON LATTER REVIEWS WITH ADDITIONAL |
| | INFORMATION. |
| | 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 15) THIS COMMENT IS COMMON TO MANY SHEETS, THE PLANS |
| | FAIL TO IDENTIFY VARIOUS COMMON DOORS THROUGH OUT THE |
| | PROJECT, PLEASE LABEL DOORS TO IDENTIFY FOR REQUIRED |
| | DOOR RATINGS. |
| | 106.1.2.* ADDITIONAL INFORMATION REQUIRED, TABLE 715.3 |
| | ETC. |
| | |
| | 16) A2.01 STAIRWAY# 3 IS INDICATED AS PART OF THE POOL |
| | DECK MEANS OF EGRESS PLEASE SEE: |
| | 1022.5 LOCATION.EXTERIOR EXIT RAMPS AND STAIRWAYS |
| | SHALL BE LOCATED IN ACCORDANCE WITH SECTION 1023.3 . |
| | 1023.3 EXIT DISCHARGE LOCATION.EXTERIOR BALCONIES, |
| | STAIRWAYS AND RAMPS SHALL BE LOCATED AT LEAST 10 FEET |
| | (3048 MM) FROM ADJACENT LOT LINES AND FROM OTHER |
| | BUILDINGS ON THE SAME LOT UNLESS THE ADJACENT BUILDING |
| | EXTERIOR WALLS AND OPENINGS ARE PROTECTED IN ACCORDANCE |
| | WITH SECTION 704 BASED ON FIRE SEPARATION DISTANCE. |
| | |
| | 17) A2.01 STAIRS THAT ARE LOCATED NEXT TO PARKING |
| | SPACE# 22 INDICATE THE LOWER LANDING OR GARAGE FLOOR AT |
| | 12.5? AND THE TOP LANDING AT 13.5?, PLEASE SEE |
| | 1003.5.2 |
| | WHERE CHANGE IN ELEVATION OF 12 INCHES (305 MM) OR LESS |
| | OCCURS IN EXIT ACCESS CORRIDORS, EXITS AND EXIT |
| | DISCHARGE, RAMPS COMPLYING WITH1010 SHALL BE |
| | PROVIDED. |
| | 1003.5.3 ACCESSIBILITY. |
| | FOR ACCESSIBILITY PROVISIONS RELATED TO CHANGES IN |
| | LEVELS, SEE SECTION 11-4.3.8 . |
| | |
| | REQUIREMENT2. ACCESSIBLE AND USABLE PUBLIC AND COMMON |
| | USE AREAS. |
| | |
| | SECTION 100.205(C)(1) PROVIDES THAT COVERED MULTIFAMILY |
| | DWELLINGS WITH A BUILDING ENTRANCE ON AN ACCESSIBLE |
| | ROUTE SHALL BE DESIGNED IN SUCH A MANNER THAT THE |
| | PUBLIC AND COMMON USE AREAS ARE READILY ACCESSIBLE TO |
| | AND USABLE BY HANDICAPPED PERSONS. |
| | |
| | GUIDELINE |
| | |
| | THE FOLLOWING CHART IDENTIFIES THE PUBLIC AND COMMON |
| | USE AREAS THAT SHOULD BE MADE ACCESSIBLE, CITES THE |
| | APPROPRIATE SECTION OF THE ANSI STANDARD, AND DESCRIBES |
| | THE APPROPRIATE APPLICATION OF THE SPECIFICATIONS, |
| | INCLUDING MODIFICATIONS TO THE REFERENCED STANDARD. |
| | FAIR HOUSING 4.3(D). |
| | |
| | 18) SHEET A2.01 THE PROPERTY LINE IS NOT INDICATED ON |
| | THIS PORTION OF THE BUILDING THERE MAY OR MAY NOT BE |
| | PROBLEMS AS FAR AS TABLE 602AND THE AMOUNT OF OPENINGS |
| | THAT ARE ALLOWED. TABLE 704.8. |
| | |
| | 19)THE EAST END OF THE BUILDING DOESN?T PROVIDE THE |
| | ELEVATION OF THE FINISHED SIDEWALKS, |
| | THERE MAY BE A RAMPED EXIT PASSAGEWAY FROM STAIR TOWER |
| | # 1 IF THE RAMP DOESN?T HAVE SLOPE GREATER THAN 1:20 IT |
| | IS TRULY A RAMP AND THE ELEVATION CHANGE WOULD NEED TO |
| | BE KNOWN? |
| | |
| | 20) SHEET A2.01 DOESN?T PROVIDE ANY HOURLY RATING ON |
| | ANY WALLS. PLEASE PROVIDE WALL IDENTIFICATION TAGS FOR |
| | ALL WALLS, SHAFTS OCCUPANCY SEPARATION, ETC SEE 707.4, |
| | TABLE 302.3.2. |
| | |
| | 21)SHEET A2.01 THERE ARE TWO ABBREVIATIONS THAT OCCUR |
| | ON THE VARIOUS DECKS |
| | (HP) AND (LP) THAT ARE NOT FOUND ON A0.02 ABBREVIATION |
| | SHEET? 106.1.2* |
| | ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 22) PLEASE PROVIDE INFORMATION FOR THE HANDICAPPED VAN |
| | PARKING SPACES, PROVIDE |
| | THE 98? CLEAR HEIGHT, ENTRY AND EXIT PATH FOR AN |
| | ACCESSIBLE VAN? 11-4.1.2(5)(B) |
| | IN PARKING STRUCTURES, ONE IN EVERY EIGHT |
| | ACCESSIBLE SPACES, BUT NOT LESS THAN ONE, SHALL BE ?VAN |
| | ACCESSIBLE? AND SHALL BE DESIGNED AS REQUIRED BY |
| | SECTION 11-4.6.3 . THE VERTICAL CLEARANCE AT SUCH |
| | SPACES SHALL COMPLY WITH SECTION 11-4.6.5 . ALL SUCH |
| | SPACES MAY BE GROUPED ON ONE LEVEL OF A PARKING |
| | STRUCTURE. WHEN SUCH SPACES ARE PROVIDED IN A PARKING |
| | STRUCTURE AND ONLY ONE IN EIGHT MEET THE HEIGHT |
| | REQUIREMENT OF SECTION 11-4.6.5 , THEY SHALL BE |
| | DESIGNATED AS REQUIRED BY SECTION 11-4.6.4 . |
| | |
| | 23)SHEET A2.02 (COMMON TO ALL FLOORS) THIS PLAN |
| | DOESN?T INDICATE DOOR ORWALL TYPES NOR THE HR RATING |
| | OF SUCH SYSTEMS. WHEN YOU LOOK AT THE LIFE SAFETY PLAN |
| | THERE ARE WALL RATINGS SOME DOORS BUT THERE IS NO |
| | NOMENCLATURE TO THE TYPE OF ROOM? 106.1.2* ADDITIONAL |
| | INFORMATION REQUIRED. |
| | 302.3.2, 707,708 & TABLE 715.3. |
| | |
| | 24) SHEET A2.03 H. C. LIFT PLEASE PROVIDE THE SPECS IN |
| | COMPLIANCE WITH: |
| | 11-4.11 PLATFORM LIFTS (WHEELCHAIR LIFTS ). 11-4.11.1 |
| | LOCATION. |
| | PLATFORM LIFTS (WHEELCHAIR LIFTS ) PERMITTED BY SECTION |
| | 11-4.1 SHALL COMPLY WITH THE REQUIREMENTS OF SECTION |
| | 11-4.11 . |
| | 11-4.11.2 OTHER REQUIREMENTS. |
| | IF PLATFORM LIFTS (WHEELCHAIR LIFTS ) ARE USED, THEY |
| | SHALL COMPLY WITH SECTIONS 11-4.2.4 , 11-4.5 , 11-4.27 |
| | , AND ASME A17.1, SAFETY CODE FOR ELEVATORS AND |
| | ESCALATORS , SECTION XX, 1990. |
| | 11-4.11.3 ENTRANCE. |
| | IF PLATFORM LIFTS ARE USED THEN THEY SHALL FACILITATE |
| | UNASSISTED ENTRY, OPERATION, AND EXIT FROM THE LIFT IN |
| | COMPLIANCE WITH SECTION 11-4.11.2 . |
| | FAIR HOUSING : ANSI A117.1 ELEVATORS 4.10. |
| | |
| | 25)SHEET A2.03: INDICATES DETAIL 7 OF A3.31 TYPICAL |
| | OF LANAI LEVEL SHEET A2.91 DETAILS |
| | 7 & 8. THESE DETAILS ARE COMMON TO ALL FLOORS, THEY DO |
| | NOT MEET FAIR HOUSING REQUIREMENTS FOR SECONDARY |
| | DOORS. |
| | |
| | 25A) SEE DETAIL 7 & 8 SHEET A2.03, THE SLIDING GLASS |
| | DOOR TRACK ASSEMBLY AS SHOWN DOES NOT MEET FAIR HOUSING |
| | GUIDELINES,FOR SECONDARY DOORS (SLIDING GLASS DOORS) |
| | THE GUIDELINE SPECIFY THAT THE THRESHOLDS AT THESE |
| | DOORS SHALL BE NO HIGHER THAN ? ?.THE GUIDELINES |
| | FURTHER STATE THAT CHANGES IN LEVEL AT THESE LOCATIONS |
| | MUST BE BEVELED WITH A SLOPE NO GREATER THAN 1:2. |
| | |
| | 25B) FAIR HOUSING DOOR AT CONCRETE LANDINGS THE MAXIMUM |
| | ALLOWABLE CHANGE IN LEVEL AT EXTERIOR SLIDING GLASS |
| | DOORS (SECONDARY ENTRANCE) TO BALCONY OR PATIO WILL BE |
| | 4 INCHES TO THE FINISH DECK. |
| | NOTE: INCORPORATE THE HEIGHT OF THE HIGH RISE TRACK |
| | INTO THE DESIGN CRITERIA. |
| | |
| | 25C) THE STRUCTURAL PLANS WILL ALSO NEED TO CORRELATE |
| | THEIR DETAIL SHEETS TO MEET THE REQUIREMENTS STATED |
| | ABOVE, FAIR HOUSING SECONDARY SLIDING GLASS DOORS. |
| | |
| | 25D) THE TRACK DETAIL ALSO INDICATES THAT THE TRACK IS |
| | TO BE SET IN LEVELING GROUT. ALL PRODUCT APPROVALS WILL |
| | REQUIRE MECHANICAL FASTENING OF TRACK INTO THE MAIN |
| | STRUCTURE. |
| | |
| | 25E) SHEET A2.91 NOTE# 5 INDICATES PLANS WILL MEET ALL |
| | WIND REQUIREMENTS OF THE STD. BUILDING CODE AND PALM |
| | BCH CTY. THE LAST STANDARD BUILDING CODE WAS THE 1997 |
| | STANDARD BUILDING CODE. CURRENTLY ALL OF FLORIDA IS |
| | UNDER THE 2004 FLORIDA BUILDING CODE WITH 2006 |
| | REVISIONS. THERE ARE NO PALM BCH CTY. AMENDMENTS. |
| | PLEASE CORRECT. |
| | |
| | 26)SHEET A2.03 ( COMMON TO ALL FLOORS)THIS PLAN |
| | INDICATE NO DOOR ORWALL TYPES NOR THE HR RATING OF |
| | SUCH SYSTEMS. WHEN YOU LOOK AT THE LIFE SAFETY PLAN |
| | THERE ARE WALL RATINGS SOME DOORS BUT THERE IS NO |
| | NOMENCLATURE TO THE TYPE OF ROOM? 106.1.2* ADDITIONAL |
| | INFORMATION REQUIRED. |
| | 302.3.2, 707,708 & TABLE 715.3. |
| | |
| | 27) SHEET A2.03 ELEVATOR LOBBY INDICATES THE TWO DOORS |
| | ON HOLD OPEN DEVICES, PLEASE PROVIDE INFORMATION ON |
| | THESE DEVICES, HOW THEY WILL PERFORM ONCE THE SMOKE |
| | ANNOUNCES |
| | SMOKE. |
| | |
| | 28) SHEET A2.03 ELEVATOR LOBBY DOORS ONE DOOR INDICATES |
| | A 20MIN RATING THE OTHER NONE. PLEASE SEE TABLE 715.3. |
| | THE 20 MIN AND ? HR FIRE PARTITIONS OR CORRIDOR WALLS |
| | REQUIRED BY SECTION 1016.1. THE MORE RESTRICTIVE |
| | ELEVATOR LOBBIES WOULD REQUIRE THE ? HR OPENING |
| | PROTECTIVE. SEE CODE COMMENTARY UNDER 709.5 SMOKE |
| | BARRIERS STATING FIRE PARTITIONS, OTHER THAN CORRIDOR |
| | WALLS, ARE REQUIRED TO HAVE AN OPENING ASSEMBLY RATING |
| | OF 45 MINUTES IN ACCORDANCE WITH TABLE 715.3. SEE LIFE |
| | SAFETY PLAN LS3 |
| | |
| | 29) SEE LS-3 & LS-4 DOORS SWING OPPOSITE WAYS 3TH FLOOR |
| | VERSES FLOORS ABOVE? |
| | OCCUPANT LOADS GREATER THAN 50 SHALL SWING IN THE |
| | DIRECTION OF TRAVEL TO AN EXIT.1008.1.2. |
| | |
| | 30) SEE LS-3 THE TRASH CHUTE ACCESS ROOM DOOR INDICATES |
| | A FIRE RATING NOT DEPICTED IN THE LIFE SAFETY LEGEND ? |
| | 707.13.3? HR OPENING PROTECTIVE REQUIRED. |
| | |
| | 31) SEE LS-3 TRY CALCULATIONS FOR THE POOL DECK AND |
| | APPROX 2446 SQ FT WITH THE OTHER LOADS A TOTAL OCCUPANT |
| | LOAD OF 116 REQUIRING THE ENTRY DOOR TO BE AN IN SWING |
| | DOOR 1008.1.2. |
| | |
| | 32)A2.03 THE LANAI FOYER DOOR APPEARS TO BE MISSING |
| | THE 18? REQUIRED ON THE PULL SIDE |
| | FAIR HOUSING ANSI 117.1TABLE 404.2.4.1 . FIGURE |
| | 404.2.1(A). |
| | |
| | 33) A2.03 THE SAME ISSUE WITH THE GATE NEXT TO THE |
| | SYMBOL EOD, THIS GATE REQUIRES 18? |
| | ON THE LATCH SIDE. FAIR HOUSING TABLE 404.2.4.1, FIGURE |
| | 404.2.1(A). |
| | |
| | 34) SHEET A2.03 THERE ARE THREE PAIR OF DOORS THAT LEAD |
| | INTO THE RECREATION ROOM, THEY ARE NOR FOUND ON THE |
| | DOOR SCHEDULE BUT SCALE TO BE (3)PAIR OF 2?-0? DOORS. |
| | MUST MEET THE REQUIREMENT OF CLEAR WIDTH DOOR OPENINGS |
| | SHALL HAVE A CLEAR OPENING WIDTH OF 32?. |
| | 404.2.2 DOUBLE- LEAF DOORWAYS. AT LEAST ONE OF THE |
| | ACTIVE LEAVES OF DOORWAYS WITH 2 INDEPENDENTLY OPERATED |
| | LEAVES SHALL COMPLY WITH SECTIONS 404.2.3 AND 404.2.4. |
| | DOORS SF-L/1 AND SF-L/2. |
| | |
| | 35)POOL WILL REQUIRE A SEPARATE PERMIT, AND WILL NOT |
| | BE PART OF THIS PERMIT PACKAGE. |
| | |
| | 36) NOTE POOL REQUIREMENTS FOR SAFETY FENCING WILL NEED |
| | TO BE ADDRESSED FOR THE LANAI LEVEL BEFORE A PERMIT CAN |
| | BE ISSUED.424.1 PUBLIC SWIMMING POOLS AND BATHING |
| | PLACES. PUBLIC SWIMMING POOLS AND BATHING PLACES SHALL |
| | COMPLY WITH THE DESIGN AND CONSTRUCTION STANDARDS OF |
| | THIS SECTION. |
| | NOTE: OTHER ADMINISTRATIVE AND PROGRAMMATIC PROVISIONS |
| | MAY APPLY. SEE DEPARTMENT OF HEALTH (DOH) RULE 64E-9, |
| | FLORIDA ADMINISTRATIVE CODE AND CHAPTER 514, FLORIDA |
| | STATUTES.ZONING MAY HAVE ADDITIONAL COMMENTS ON THIS |
| | ISSUE. |
| | |
| | 37) SHEET A2.04 THE ELEVATOR LOBBY DOORS DO NOT HAVE |
| | ANY IDENTIFYING TAGS, ( COMMON TO ALL FLOORS)THIS |
| | PLAN INDICATE NO DOOR ORWALL TYPES NOR THE HR RATING |
| | OF SUCH SYSTEMS. WHEN YOU LOOK AT THE LIFE SAFETY PLAN |
| | THERE ARE WALL RATINGS SOME DOORS BUT THERE IS NO |
| | NOMENCLATURE TO THE TYPE OF ROOM? 106.1.2* ADDITIONAL |
| | INFORMATION REQUIRED. |
| | 302.3.2, 707,708 & TABLE 715.3. |
| | |
| | 38) SHEET A2.05 DETAIL# 13 INDICATE AN EMERGENCY |
| | OVERFLOW, THE SITUATION IS THE WAY THE DETAIL IS DRAWN |
| | WITH A MINIMUM OF 4? BEFORE RAINWATER STARTS TO RUN |
| | INTO THE OVERFLOW, WHERE THE PLUGGED UP ROOF DRAIN IS |
| | THE WATER MAY 7? OR 8? DEEP DEPENDING ON THE LOCATION |
| | OF THE ROOF DRAIN FROM THE OVERFLOW. 1503.4.3 WHEN |
| | OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT |
| | PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR |
| | PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4 |
| | INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND |
| | SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED |
| | VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET |
| | SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN |
| | ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING. |
| | |
| | 39 THE SAME DETAIL THAT IS MENTIONED ABOVE INDICATES |
| | THE USE OF EITHER A MANSARD OR SHED TYPE ROOF SYSTEM, |
| | WITH THE USE OF METAL TRUSSES, 1 ?? METAL DECKING, |
| | THERE IS ANOTHER MEMBER NOT LABELED SOME TYPE OF |
| | SHEATHING ? PLEASE PROVIDE WHAT TYPE OF |
| | ROOF SHEATHING IS TO BE USED?PLEASE SEE TABLE 601, |
| | ROOF CONSTRUCTION, FOOTNOTE |
| | 2(I), 2(II) & 2(III). |
| | |
| | 40) SHEET A2.05 ALSO INDICATES THAT A MAINTENANCE SHOP |
| | ON THE ROOF, WHAT TYPE OF |
| | ACTIVITIES WILL TAKE PLACE THERE WILL THIS BE MORE FOR |
| | STORAGE OR A ACTUAL MAINTENANCE |
| | SHOP? IF STORAGE WHAT TYPE OF MATERIALS? |
| | |
| | 41) SHEET A2.05 DETAIL#9 SHEET A3.32 ROOF FEATURE |
| | DOESN?T INDICATE WHAT TYPE OF ROOF SHEATHING THAT WILL |
| | BE USED?PLEASE SEE TABLE 601, ROOF CONSTRUCTION, |
| | FOOTNOTE |
| | 2(I), 2(II) & 2(III).IN THIS CASE THERE IS 20?-0? CLEAR |
| | FROM THE FLOOR SEE FOOTNOTE(III). |
| | |
| | 42)DETAIL# 5 SHEET A7.09 TRASH CHUTE ROOF DETAIL |
| | INDICATES THE USE OF COMBUSTIBLE PLYWOOD ON THE ROOF, |
| | SEE TABLE 601. |
| | |
| | 43) SHEET A3.32 DETAIL# 9 INDICATES THERE ARE VARIOUS |
| | AREAS OF EFIS TRIM TO BE USED, MUST MEET THE TEST FOR |
| | NONCOMBUSTIBILITY, ASTM E-84.1406.2.2 ARCHITECTURAL |
| | TRIM. |
| | IN BUILDINGS OF TYPE I, II, III AND IV CONSTRUCTION |
| | THAT DO NOT EXCEED THREE STORIES OR 40 FEET (12 192 MM) |
| | IN HEIGHT ABOVE GRADE PLANE, EXTERIOR WALL COVERINGS |
| | SHALL BE PERMITTED TO BE CONSTRUCTED OF WOOD WHERE |
| | PERMITTED BY SECTION 1405.4 OR OTHER EQUIVALENT |
| | COMBUSTIBLE MATERIAL. COMBUSTIBLE EXTERIOR WALL |
| | COVERINGS, OTHER THAN FIRE-RETARDANT-TREATED WOOD |
| | COMPLYING WITH SECTION 2303.2 FOR EXTERIOR |
| | INSTALLATION, SHALL NOT EXCEED 10 PERCENT OF AN |
| | EXTERIOR WALL SURFACE AREA WHERE THE FIRE SEPARATION |
| | DISTANCE IS 5 FEET (1524 MM) OR LESS. ARCHITECTURAL |
| | TRIM THAT EXCEEDS 40 FEET (12 192 MM) IN HEIGHT ABOVE |
| | GRADE PLANE SHALL BE CONSTRUCTED OF APPROVED |
| | NONCOMBUSTIBLE MATERIALS AND SHALL BE SECURED TO THE |
| | WALL WITH METAL OR OTHER APPROVED NONCOMBUSTIBLE |
| | BRACKETS. |
| | |
| | 44)SHEET A2.30 DISPLAY CABINET OR ROOM R-104 IS |
| | MISSING THE DOOR MARKER, TYPE OF DOOR? 106.1.2* |
| | ADDITIONAL INFO REQUIRED. |
| | |
| | 45) SHEET A2.30 PRE-CAST CONC. MOLDING DETAIL 3 OF |
| | A3.09PLEASE INDICATE SLAB SIZES AND |
| | ANCHORAGE. 1405.5 ANCHORED MASONRY VENEER. ANCHORED |
| | MASONRY VENEER SHALL COMPLY WITH THE PROVISIONS OF |
| | SECTIONS 1405.5 , 1405.6 , 1405.7 AND 1405.8 AND |
| | SECTIONS 6.1 AND 6.2 OF ACI 530/ASCE 5/TMS 402. |
| | 1405.5 ANCHORED MASONRY VENEER. |
| | 1405.6 STONE VENEER |
| | 1405.7 SLAB-TYPE VENEER |
| | |
| | 46A) SHEET A2.31 TRASH HOLDING ROOM PLANS INDICATE A |
| | 5?-0? OVERHEAD ON THE PROPERTY LINE SIDE OF THE |
| | PROPERTY, WHICH 0-3? NO OPENINGS. 704.8.2 FIRST STORY. |
| | |
| | IN OCCUPANCIES OTHER THAN GROUP H, UNLIMITED |
| | UNPROTECTED OPENINGS ARE PERMITTED IN THE FIRST STORY |
| | OF EXTERIOR WALLS FACING A STREET THAT HAVE A FIRE |
| | SEPARATION DISTANCE OF GREATER THAN 15 FEET (4572 MM), |
| | OR FACING AN UNOCCUPIED SPACE. THE UNOCCUPIED SPACE |
| | SHALL BE ON THE SAME LOT OR DEDICATED FOR PUBLIC USE, |
| | SHALL NOT BE LESS THAN 30 FEET (9144 MM) IN WIDTH, AND |
| | SHALL HAVE ACCESS FROM A STREET BY A POSTED FIRE LANE |
| | IN ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE . |
| | |
| | 46B) SEE TABLE 704.8 & TABLE 602. PLANS ALSO INDICATE A |
| | GATE ON THE OTHER END OF THE ROOM, THIS SHOULD HAVE A |
| | DOOR A CHANGE IN OCCUPANCY S-1 OCCUPANCY. |
| | |
| | 47) SHEET A2.31 THE EAST PROPERTY LINE WALL IS SHOWN AS |
| | WALL TYPE (800), A9.02 |
| | WALL RATING NOTE# 10 INDICATES ALL BLOCK WORK TO BE A |
| | MINIMUM OF 2 HR RATED BLOCK. PLEASE SEE TABLE 602 LESS |
| | THAN 5?-0? FROM THE PROPERTY LINE. PLEASE CORRECT. THE |
| | SAME WILL HOLD TRUE FOR THE SOUTH WALL. |
| | |
| | 48) A2.32 SWITCH GEAR ROOM THE STEPS IN FRONT SHOULD |
| | HAVE 13? TREADS.1003.5.1 |
| | WHERE A CHANGE IN LEVEL MEANS OF EGRESS NOT EXCEEDING |
| | 21 INCHES (533 MM) IS ACHIEVED BY A STAIR, THE MINIMUM |
| | TREAD DEPTH OF SUCH STAIR SHALL BE 13 INCHES (330 MM) |
| | AND THE PRESENCE AND LOCATION OF EACH STEP SHALL BE |
| | READILY APPARENT. |
| | |
| | 49) A2.32 THE EMERGENCY GENERATOR ROOM, 7? STAIR: |
| | 1003.5.2 |
| | WHERE CHANGE IN ELEVATION OF 12 INCHES (305 MM) OR LESS |
| | OCCURS IN EXIT ACCESS CORRIDORS, EXITS AND EXIT |
| | DISCHARGE, RAMPS COMPLYING WITH SECTION 1010 SHALL BE |
| | PROVIDED. |
| | |
| | 50)FIRE COMMAND ROOM PLEASE PROVIDE COMPLIANCE WITH: |
| | 403.8 FIRE COMMAND . |
| | A FIRE COMMAND CENTER COMPLYING WITH SECTION 911 SHALL |
| | BE PROVIDED IN A LOCATION APPROVED BY THE FIRE |
| | DEPARTMENT. |
| | WHERE REQUIRED BY OTHER SECTIONS OF THIS CODE, A FIRE |
| | COMMAND CENTER FOR FIRE DEPARTMENT OPERATIONS SHALL BE |
| | PROVIDED. THE LOCATION AND ACCESSIBILITY OF THE FIRE |
| | COMMAND CENTER SHALL BE SEPARATED FROM THE REMAINDER OF |
| | THE BUILDING BY NOT LESS THAN A 1-HOUR |
| | FIRE-RESISTANCE-RATED FIRE BARRIER. THE ROOM SHALL BE A |
| | MINIMUM OF 96 SQUARE FEET (9 M 2 ) WITH A MINIMUM |
| | DIMENSION OF 8 FEET (2438 MM). A LAYOUT OF THE FIRE |
| | COMMAND CENTER AND ALL FEATURES REQUIRED BY THE SECTION |
| | TO BE CONTAINED THEREIN SHALL BE SUBMITTED FOR APPROVAL |
| | PRIOR TO INSTALLATION. THE FIRE COMMAND CENTER SHALL |
| | COMPLY WITH NFPA 72 AND SHALL CONTAIN THE FOLLOWING |
| | FEATURES. |
| | 1.THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM |
| | UNIT. |
| | 2.THE FIRE DEPARTMENT COMMUNICATIONS UNIT. |
| | 3.FIRE DETECTION AND ALARM SYSTEM ANNUNCIATOR |
| | UNIT. |
| | 4.ANNUNCIATOR UNIT VISUALLY INDICATING THE |
| | LOCATION OF THE ELEVATORS AND WHETHER THEY ARE |
| | OPERATIONAL. |
| | 5.STATUS INDICATORS AND CONTROLS FOR AIR-HANDLING |
| | SYSTEMS. |
| | 6.THE FIRE-FIGHTER?S CONTROL PANEL REQUIRED BY |
| | SECTION 909.16 FOR SMOKE CONTROL SYSTEMS INSTALLED IN |
| | THE BUILDING. |
| | 7.CONTROLS FOR UNLOCKING STAIRWAY DOORS |
| | SIMULTANEOUSLY. |
| | 8.SPRINKLER VALVE AND WATER-FLOW DETECTOR DISPLAY |
| | PANELS. |
| | 9.EMERGENCY AND STANDBY POWER STATUS INDICATORS. |
| | 10.A TELEPHONE FOR FIRE DEPARTMENT USE WITH |
| | CONTROLLED ACCESS TO THE PUBLIC TELEPHONE SYSTEM. 11. |
| | FIRE PUMP STATUS INDICATORS. |
| | 12.SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL |
| | FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF |
| | EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING |
| | EQUIPMENT AND FIRE DEPARTMENT ACCESS. |
| | 13.WORKTABLE. |
| | 14.GENERATOR SUPERVISION DEVICES, MANUAL START AND |
| | TRANSFER FEATURES. |
| | 15.PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY |
| | REQUIRED BY OTHER SECTIONS OF THIS CODE. |
| | |
| | 51) SHEET A2.33 PLANS INDICATE WALL RATING OF 800, WHEN |
| | REVIEWING THIS WALL TYPE THERE IS NO REFERENCE TO THE |
| | WALL RATING. SHEETA9.02 NOTE# 10 MAKE REFERENCE THAT |
| | ALL BLOCK TYPE ARE TO BE 2 HR RATED WALLS.PLEASE HAVE |
| | THE BLOCK MANUFACTURER PROVIDE THE EQUIVALENT THICKNESS |
| | OF THE BLOCK AND TYPE OF AGGREGATE TO BE USED? IF |
| | RINKER BLOCK ARE TO BE USED WILL ANY T007 BLOCK BE |
| | USED? |
| | 721.3.2 CONCRETE MASONRY WALLS. |
| | THE FIRE-RESISTANCE RATING OF WALLS AND PARTITIONS |
| | CONSTRUCTED OF CONCRETE MASONRY UNITS SHALL BE |
| | DETERMINED FROM TABLE 721.3.2 . THE RATING SHALL BE |
| | BASED ON THE EQUIVALENT THICKNESS OF THE MASONRY AND |
| | TYPE OF AGGREGATE USED. |
| | EQUIVALENT . |
| | |
| | 52) SHEET A9.02 INDICATES THAT THE BLOCK ARE TO BE |
| | MORTARED TO THE DECK ABOVE. THIS WILL NO PROVIDE A |
| | SMOKE TYPE SEAL.713.1 GENERAL. JOINTS INSTALLED IN OR |
| | BETWEEN FIRE-RESISTANCE-RATED WALLS, FLOOR OR |
| | FLOOR/CEILING ASSEMBLIES AND ROOFS OR ROOF/CEILING |
| | ASSEMBLIES SHALL BE PROTECTED BY AN APPROVED |
| | FIRE-RESISTANT JOINT SYSTEM DESIGNED TO RESIST THE |
| | PASSAGE OF FIRE FOR A TIME PERIOD NOT LESS THAN THE |
| | REQUIRED FIRE-RESISTANCE RATING OF THE WALL, FLOOR OR |
| | ROOF IN OR BETWEEN WHICH IT IS INSTALLED. |
| | FIRE-RESISTANT JOINT SYSTEMS SHALL BE TESTED IN |
| | ACCORDANCE WITH SECTION 713.3 . THE VOID CREATED AT THE |
| | INTERSECTION OF A FLOOR/CEILING ASSEMBLY AND AN |
| | EXTERIOR CURTAIN WALL ASSEMBLY SHALL BE PROTECTED IN |
| | ACCORDANCE WITH SECTION 713.4 . |
| | |
| | 53) SHEET A2.35 THE POOL EQUIPMENT ROOM APPEARS TO HAVE |
| | A VENT ON THE EAST SIDE OF THE BUILDING. THIS IS A 3 HR |
| | RATED WALL ON THE PROPERTY LINE ,NO OPENINGS 0-3?-0 |
| | FROM THE PROPERTY LINE. |
| | |
| | 54)A2.35 & A2.36 BOTH HAVE LOUVERED OPENINGS IN A |
| | WALL THAT SITS 0-3?-0? FROM THE PROPERTY LINE, NO |
| | OPENINGS ALLOWED. TABLE 704.8. |
| | |
| | 55) A2.80 DOOR SCHEDULE INDICATES DOOR TYPE ?F? TO HAVE |
| | VIEW PANELS, PLANS INDICATE 150 SQ INCHES FOR A ?B? |
| | LABEL DOOR PLEASE SEE TABLE 715.4.3 1 ? HR DOOR 100 SQ |
| | INCHES. |
| | |
| | 56) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE |
| | DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE |
| | PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS |
| | SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF |
| | GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE |
| | ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES |
| | POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH |
| | AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS |
| | OF SSTD 12, ASTM E 1886 ANDASTM E 1996, OR MIAMI-DADE |
| | TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1. |
| | GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE |
| | SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. |
| | 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 |
| | M) ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL |
| | MISSILE TEST. |
| | |
| | FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE |
| | 2 COPIES, |
| | 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING |
| | REPORTS, MISSING REPORTS ARE AS FOLLOWS: |
| | A) FIXED GLASS |
| | B) STOREFRONT GLASS |
| | C) OPERABLE WINDOWS |
| | D) MULLIONS HORIZONTAL & VERTICAL |
| | E) SKYLIGHTS |
| | F) GLASS BLOCK |
| | G) LOUVERS |
| | H) HOLLOW METAL DOORS/ ROOF HATCHES |
| | I) GLASS DOORS SWING |
| | J) OVERHEAD DOORS/ COIL DOORS |
| | K) SLIDING GLASS DOORS |
| | L) AUTOMATIC HORIZONTAL SLIDING DOORS |
| | M)PANEL WALL SYSTEM: SOFFITS, EFIS |
| | N) ROOFING ASSEMBLIES |
| | |
| | 57)PRODUCT APPROVALS SUBMITTED WITH PERMIT |
| | APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA PRODUCT |
| | APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE |
| | APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER |
| | SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, |
| | SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR |
| | SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 58) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 59) THIS NEXT ISSUE HAS BECOME A LARGE ISSUE ON |
| | PROJECTS!!!! WINDOWS NOT BEING LABELED. |
| | TESTING AND LABELING. 1714.5.2.1EXTERIOR WINDOWS AND |
| | GLASS DOORS SHALL BE TESTED BY AN APPROVED INDEPENDENT |
| | TESTING LABORATORY, AND SHALL BE LABELED WITH AN |
| | APPROVED LABEL IDENTIFYING THE MANUFACTURER, |
| | PERFORMANCE CHARACTERISTICS AND APPROVED PRODUCT |
| | CERTIFICATION AGENCY, TESTING LABORATORY, EVALUATION |
| | ENTITY OR MIAMI-DADE PRODUCT APPROVAL TO INDICATE |
| | COMPLIANCE WITH THE REQUIREMENTS OF ONE OF THE |
| | FOLLOWING SPECIFICATIONS:ANSI/AAMA/NWWDA 101/I.S.2 OR |
| | 101/I.S. 2/NAFS OR TAS 202 (HVHZ SHALL COMPLY WITH TAS |
| | 202 UTILIZING ASTME E 1300 OR SECTION 2404 . |
| | GLASS STRENGTH: DETERMINATION OF LOAD RESISTANCE OF |
| | GLASS FOR SPECIFIED LOADS OF PRODUCTS TESTED AND |
| | CERTIFIED IN ACCORDANCE WITH SECTION 1714.5.2.1 SHALL |
| | BE DESIGNED TO COMPLY WITH ASTM E 1300 IN ACCORDANCE |
| | WITH SECTION 2404 . |
| | |
| | 60)SHEET A2.90; THIS SHEET SHOWS MULLIONS USED BOTH |
| | VERTICALLY AND HORIZONTALLY, BEFORE A REVIEW OF THE |
| | PRODUCT APPROVALS WILL BE ABLE TO BEGIN THE DESIGN TEAM |
| | WILL NEED TO HIGHLIGHT WHICH MULLION WILL BE THE ONE |
| | THAT WILL CONTINUE FROM A STRUCTURAL FRAMING MEMBER TO |
| | THE OPPOSITE SIDE. |
| | |
| | 1714.5.5 MULLIONS OCCURRING BETWEEN INDIVIDUAL WINDOW |
| | AND GLASS DOOR ASSEMBLIES. 1714.5.5.1 MULLIONS. |
| | MULLIONS, OTHER THAN MULLIONS WHICH ARE AN INTEGRAL |
| | PART OF A WINDOW OR GLASS DOOR ASSEMBLY TESTED AND |
| | LABELED IN ACCORDANCE WITH SECTION 1714.5.2.1 , SHALL |
| | BE TESTED BY AN APPROVED TESTING LABORATORY OR BE |
| | ENGINEERED IN ACCORDANCE WITH ACCEPTED ENGINEERING |
| | PRACTICE. BOTH METHODS SHALL USE PERFORMANCE CRITERIA |
| | CITED IN SECTIONS 1714.5.5.2 , 1714.5.5.3 AND |
| | 1714.5.5.4 . |
| | |
| | 1714.5.5.2 LOAD TRANSFER. |
| | MULLIONS SHALL BE DESIGNED TO TRANSFER THE DESIGN |
| | PRESSURE LOADS APPLIED BY THE WINDOW AND DOOR |
| | ASSEMBLIES TO THE ROUGH OPENING SUBSTRATE. |
| | |
| | 1714.5.5.3 DEFLECTION. |
| | MULLIONS SHALL BE CAPABLE OF RESISTING THE DESIGN |
| | PRESSURE LOADS APPLIED BY THE WINDOW AND DOOR |
| | ASSEMBLIES TO BE SUPPORTED WITHOUT DEFLECTING MORE THAN |
| | L/175, WHERE L IS THE SPAN OF THE MULLION IN INCHES. |
| | |
| | 1714.5.5.4 STRUCTURAL SAFETY FACTOR. |
| | MULLIONS SHALL BE CAPABLE OF RESISTING A LOAD OF |
| | ONE-AND-ONE-HALF TIMES THE DESIGN PRESSURE LOADS |
| | APPLIED BY THE WINDOW AND DOOR ASSEMBLIES TO BE |
| | SUPPORTED WITHOUT EXCEEDING THE APPROPRIATE MATERIAL |
| | STRESS LEVELS. IF TESTED BY AN APPROVED LABORATORY, THE |
| | ONE AND ONE-HALF TIMES THE DESIGN PRESSURE LOAD SHALL |
| | BE SUSTAINED FOR 10 SECONDS, AND THE PERMANENT |
| | DEFORMATION SHALL NOT EXCEED 0.4 PERCENT OF THE MULLION |
| | SPAN AFTER THE ONE-AND-ONE-HALF TIMES DESIGN PRESSURE |
| | LOAD IS REMOVED. |
| | |
| | 61) ANOTHER BIG ISSUE WITH PRODUCT APPROVALS THAT THE |
| | DESIGN TEAM WILL SIGN OFF ON REVIEWED IS THEY WILL NOT |
| | ?HIGHLIGHT? WHICH GLAZING SYSTEM THEY HAVE APPROVED AND |
| | THE CORRESPONDING PRESSURES, NOR WILL THEY HIGHLIGHT IN |
| | SLIDING GLASS DOOR SYSTEMS WHICH |
| | RAIL SYSTEM WILL BE USED. THERE ARE 4 DESIGN CRITERIA |
| | USUALLY IN THESE PACKAGES. ONE WITH NO REINFORCEMENT, |
| | LIGHT , MEDIUM AND HEAVY REINFORCEMENT HIGHLIGHT WHICH |
| | SYSTEM IS TO BE USED. |
| | |
| | 62)NO ROOF REPORT WAS SUBMITTED IS MISSING OR NOT IN |
| | COMPLIANCE WITH THE FOLLOW ITEMS: |
| | _X__ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT. |
| | (FLAT ROOF) |
| | ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH. _X__ |
| | CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE USED. |
| | _X__ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE |
| | _2&3__ . |
| | SINCE THE ROOFING REPORT DOESN?T HAVE THE SUBSYSTEM |
| | HIGHLIGHTED THE NEXT 2 ITEMS ARE HIGHLIGHTED._X__ THE |
| | SYSTEM PROVIDED STATESLIMITATION# 7, SHOULD THE |
| | FASTENERRESISTANCE BE LESS THAN THAT REQUIRED, AS |
| | DETERMINED BY THEBUILDING OFFICIAL, A REVISED |
| | FASTENERSPACING, PREPARED , SIGNED AND SEALED BY A |
| | FLORIDA REGISTEREDPROFESSIONAL ENGINEER, |
| | REGISTEREDARCHITECT OR REGISTERED ROOF CONSULTANT |
| | MAY BE SUBMITTED. |
| | _X__THE SYSTEM PROVIDED INDICATESLIMITATION# |
| | 9, NO ENHANCEDFASTENING ALLOWED. |
| | |
| | 63) SLOPED ROOF (7/ A8.06) INDICATES THE USE OF EITHER |
| | CLAY TILE OR CONCRETE TILE. SUBMIT REPORT AND HIGHLIGHT |
| | WHICH TYPE OF SYSTEM WILL BE USED TO RESIST THE MOMENT |
| | OF UPLIFT? |
| | |
| | 64)PLEASE SUBMIT INFORMATION ON HOW THE RIDGE TILE |
| | ARE GOING TO BE SECURED TO THE ROOFING SYSTEM. 1507.3.7 |
| | ATTACHMENT. |
| | CLAY AND CONCRETE ROOF TILES SHALL BE FASTENED IN |
| | ACCORDANCE WITH SECTION 1609 OR IN ACCORDANCE WITH |
| | FRSA/RTI INSTALLATION MANUAL. |
| | 1507.3.8 APPLICATION. |
| | TILE SHALL BE APPLIED ACCORDING TO THE MANUFACTURER?S |
| | INSTALLATION INSTRUCTIONS OR RECOMMENDATIONS OF THE |
| | FRSA/RTI 07320- 04. |
| | |
| | 65) A3.30 INDICATES THE USE OF METAL PANEL ROOFING |
| | PLEASE PROVIDE ROOFING REPORT. |
| | |
| | 66)SHIMS FOR WINDOWS AND DOORS, SHEET A2.93 DETAIL# |
| | 9. |
| | 1714.5.4.3 WOOD OR OTHER APPROVED FRAMING MATERIALS. |
| | WHERE THE FRAMING MATERIAL IS WOOD OR OTHER APPROVED |
| | FRAMING MATERIAL, WINDOW AND GLASS DOOR ASSEMBLIES |
| | SHALL BE ANCHORED THROUGH THE MAIN FRAME OR BY JAMB |
| | CLIP OR SUBFRAME SYSTEM OR THROUGH THE FLANGE IN |
| | ACCORDANCE WITH THE MANUFACTURER?S PUBLISHED |
| | INSTALLATION INSTRUCTIONS. SHIMS SHALL BE MADE FROM |
| | MATERIALS CAPABLE OF SUSTAINING APPLICABLE LOADS, |
| | LOCATED AND APPLIED IN A THICKNESS CAPABLE OF |
| | SUSTAINING APPLICABLE LOADS. ANCHORS SHALL BE PROVIDED |
| | TO TRANSFER LOAD FROM THE WINDOW OR DOOR FRAME TO THE |
| | ROUGH OPENING SUBSTRATE. |
| | |
| | 67)SHEETS S-12 AND S-13 ARE MISSING THE PRESSURES ON |
| | THE LOUVERS ON THE SOUTH AND WEST WALLS. |
| | |
| | 68) THE STRUCTURAL PLANS DO NOT INDICATE PRESSURES ON |
| | THE POOL PAVILION NOR THE SOUTHWEST |
| | INSET CORNER OF THE POOL DECK AND VERTICAL ELEMENT. |
| | |
| | 69) PLANS ALSO FAIL TO PROVIDE WIND PRESSURE ZONES FOR |
| | THE ROOF ELEMENTS IN ZONES 1,2 & 3. |
| | |
| | 70) EXTERIOR DOOR ASSEMBLIES NOT COVERED BY SECTION |
| | 1715.4.2 OR SECTION 1714.5.3.1 SHALL BE TESTED FOR |
| | STRUCTURAL INTEGRITY IN ACCORDANCE WITH ASTM E 330 |
| | PROCEDURE A, AT A LOAD OF 1.5 TIMES THE REQUIRED DESIGN |
| | PRESSURE LOAD. THE LOAD SHALL BE SUSTAINED FOR 10 |
| | SECONDS WITH NO PERMANENT DEFORMATION OF ANY MAIN FRAME |
| | OR PANEL MEMBER IN EXCESS OF 0.4 PERCENT OF ITS SPAN |
| | AFTER THE LOAD IS REMOVED. HIGH-VELOCITY HURRICANE |
| | ZONES SHALL COMPLY WITH TAS 202. AFTER EACH SPECIFIED |
| | LOADING, THERE SHALL BE NO GLASS BREAKAGE, PERMANENT |
| | DAMAGE TO FASTENERS, HARDWARE PARTS, OR ANY OTHER |
| | DAMAGE WHICH CAUSES THE DOOR TO BE INOPERABLE. |
| | THE MINIMUM TEST SIZES AND MINIMUM DESIGN PRESSURES |
| | SHALL BE AS INDICATED IN TABLE 1714.5.3 . |
| | |
| | 71) A3.08 & A3.30 DETAIL# 1 BOTH INDICATE THE |
| | INSTALLATION OF FABRIC AWNINGS ON STEEL TUBING, AWNINGS |
| | ARE TO BE COVERED UNDER A SEPARATE PERMIT IF THE |
| | FOLLOWING INFORMATION IS NOT INCLUDED IN THIS PACKAGE: |
| | |
| | |
| | 3105.4.1 |
| | DESIGN OF THE FRAMING MEMBERS SHALL NOT BE BASED ON |
| | REMOVAL OR REPOSITIONING OF PARTS, OR THE WHOLE, DURING |
| | PERIODS OF 75 MPH WIND VELOCITY. |
| | |
| | 3105.4.2 |
| | DESIGN OF THE STRUCTURAL FRAMING MEMBERS SHALL BE BASED |
| | ON RATIONAL ANALYSIS, USING THE APPLICABLE WIND LOADS |
| | OF CHAPTER 16 AS SHOWN BELOW: |
| | |
| | 3105.4.2.1 |
| | THE WIND DESIGN LOADS FOR ANY FABRIC OR |
| | MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK |
| | REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC AT WIND |
| | VELOCITIES OF 75 MPH, SHALL BE BASED ON THE FOLLOWING |
| | CRITERIA: |
| | 1.MINIMUM WIND VELOCITY OF 3-SECOND WIND GUST 90 |
| | MPH |
| | 2.IMPORTANCE FACTOR BASED ON LOW HAZARD TO HUMAN |
| | LIFE OF 0.77. |
| | 3.EXPOSURE CATEGORY B FOR OR C AS DEFINED IN |
| | CHAPTER 16 . |
| | |
| | 3105.4.2.2 |
| | THE WIND DESIGN LOADS FOR ANY FABRIC OR MEMBRANE |
| | COVERED STRUCTURE DESIGNED WITH A PERMANENT OR |
| | NONREMOVABLE FABRIC OR MEMBRANE, SHALL BE BASED ON THE |
| | FOLLOWING CRITERIA: |
| | 1.MINIMUM WIND VELOCITY AS REQUIRED IN CHAPTER 16 |
| | . |
| | 2.IMPORTANCE FACTOR BASED ON LOW HAZARD TO HUMAN |
| | LIFE OF 0.77. |
| | 3.EXPOSURE CATEGORY B OR C AS DEFINED IN CHAPTER |
| | 16 . |
| | |
| | 3105.4.2 |
| | THE FABRIC PORTIONS OF AWNINGS FABRIC COVERED FRAMES |
| | SHALL BE SECURELY LACED, TIED OR OTHERWISE FASTENED TO |
| | THE FRAME; NO RAFTER OR FRONT BAR WILL BE PERMITTED IN |
| | POCKETS; AND IN NO CASE SHALL A ROLLING CURTAIN BE |
| | CAUSED TO OPERATE OVER A CANOPY FRAME. |
| | |
| | 72) A3.30 DETAILS 3 & 4 BOTH INDICATE A RIGID OR SOLID |
| | ROOF SYSTEM, PLANS DO NOT INDICATE WHAT TYPE OF |
| | MATERIALS WILL BE USED. PLEASE PROVIDE DETAIL WITH TYPE |
| | OF FRAMING MEMBERS |
| | TYPE OF FACIA FINISH, CEILING AND TYPE OF ATTACHMENTS? |
| | 106.1.2 ADD INFO REQUIRED. |
| | |
| | 73) A4.01 DETAIL# 4 INDICATES THE USE OF PLYWOOD AS |
| | ROOF SHEATHING AS PART OF THE CABANA ROOFSYSTEM? |
| | TABLE 601. |
| | |
| | 74) A40.01 CUT SECTION OF THE CABANA, PLEASE PROVIDE A |
| | DETAIL INDICATING THE HEIGHT OF THE SINK AT THE BAR |
| | AREA? |
| | |
| | 75) A7.01 & A7.02 STAIR 1 & 2FIRST FLOOR BENEATH THE |
| | STAIRS TO COMPLY WITH FAIR HOUSING ANSI 307.4 REDUCED |
| | VERTICAL CLEARANCE WHEN HEADROOM IS LESS THAN 80?. |
| | |
| | 76) A7.09 DETAIL# 5 REFUSE CHUTE ROOFING DETAIL |
| | INDICATES THE USE OF PLYWOOD SHEATHING, SEE TABLE 601. |
| | |
| | 77)A8.03 DETAIL 6 PLEASE CORRECT THE CODE REFERENCE |
| | TO THE CODE SECTION FOR FIRE TREATED WOOD AND THE CODE |
| | REFERENCE. |
| | |
| | 78) A8.03 DETAILS 3,4,5,8&9 ALL REQUIRE FIRE RETARDANT |
| | TREATED PLYWOOD: 803.4.2 SET-OUT CONSTRUCTION. WHERE |
| | WALLS AND CEILINGS ARE REQUIRED TO BE OF |
| | FIRE-RESISTANCE-RATED OR NONCOMBUSTIBLE CONSTRUCTION |
| | AND WALLS ARE SET OUT OR CEILINGS ARE DROPPED DISTANCES |
| | GREATER THAN SPECIFIED IN SECTION 803.4.1 , CLASS A |
| | FINISH MATERIALS SHALL BE USED EXCEPT WHERE INTERIOR |
| | FINISH MATERIALS ARE PROTECTED ON BOTH SIDES BY AN |
| | AUTOMATIC SPRINKLER SYSTEM OR ATTACHED TO |
| | NONCOMBUSTIBLE BACKING OR FURRING STRIPS INSTALLED AS |
| | SPECIFIED IN SECTION 803.4.1 . THE HANGERS AND ASSEMBLY |
| | MEMBERS OF SUCH DROPPED CEILINGS THAT ARE BELOW THE |
| | MAIN CEILING LINE SHALL BE OF NONCOMBUSTIBLE MATERIALS, |
| | EXCEPT THAT IN TYPE III AND V CONSTRUCTION, |
| | FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED. THE |
| | CONSTRUCTION OF EACH SET-OUT WALL SHALL BE OF |
| | FIRE-RESISTANCE-RATED CONSTRUCTION AS REQUIRED |
| | ELSEWHERE IN THIS CODE. |
| | |
| | 79)A8.05 EXTERIOR SOFFITS, VARIOUS DETAILS INDICATE |
| | THE SOFFIT OR DROPPED CEILING, THERE IS NO INFORMATION |
| | ON THE TYPE OF STUDS, SPACING, ATTACHMENT TO DECK ABOVE |
| | OR TYPE OF LATH AND SPACING OF HORIZONTAL FRAMING |
| | MEMBERS IS THE WIRE LATH TIED UP OR SCREWED IN PLACE? |
| | 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 80) A8.06 DETAIL# 11 INDICATES THE USE OF 5V METAL |
| | CRIMP SIDING DIRECTLY APPLIED TO THE METAL FRAMING, |
| | WHAT TYPE OF BRACING IS TO BE USED? PLEASE PROVIDE THE |
| | PRODUCT APPROVAL |
| | INDICATING THIS IS STRUCTURAL SHEATHING NO SHEATHING |
| | REQUIRED. |
| | |
| | 81) A8.06 DETAIL# 10 DETAIL INDICATES THE USE OF |
| | PLYWOOD NOT FIRE RATED! |
| | |
| | 82A)A9.01 VARIOUS DETAILS INDICATE A DESIGN SOUND |
| | TEST NUMBER, PLEASE INDICATE THE SOUND TRANSMISSION |
| | CLASS NUMERICALLY, 1207.2 AIR-BORNE SOUND. WALLS, |
| | PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| | AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| | 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION ASSEMBLIES |
| | FOR PIPING; ELECTRICAL DEVICES; RECESSED CABINETS; |
| | BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR EXHAUST |
| | DUCTS SHALL BE SEALED, LINED, INSULATED OR OTHERWISE |
| | TREATED TO MAINTAIN THE REQUIRED RATINGS. THIS |
| | REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT ENTRANCE |
| | DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT FITTING TO |
| | THE FRAME AND SILL. |
| | |
| | 82B) PLEASE PROVIDE COMPLIANCE WITH SOUND TRANSFERENCE |
| | THROUGH THE FLOOR SYSTEM? |
| | 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 83)A9.01 NOTE # 2 USE OF CEMENTITITOUS BACKER BOARD, |
| | PLEASE PROVIDE THE MANUFACTURERS SPEC THAT A VAPOR |
| | BARRIER WOULD NOT BE REQUIRED? |
| | |
| | 84) DISCREPANCY BETWEEN A9.01 NOTE# 2 USE OF |
| | CEMENTITITOUS BACKER BOARD AND A2.71 NOTE# 2 FIBERGLASS |
| | BACKER BOARD? PLEASE CORRECT. |
| | |
| | 85)SHEET A4.01 CABANA RESTROOMS FINISH SCHEDULE IS |
| | ELUSIVE NOTE 5 INDICATES SCHEDULE TO BE ON A2.71 WHICH |
| | IS FOR UNITS ONLY, A2.70 IS THE FINISH SCHEDULE FOR THE |
| | COMMON AREAS BUT THE FINISH SCHEDULE IS NOT FOUND THERE |
| | EITHER. NOTE 8 INDICATES REFERS TO THE INTERIOR DESIGN |
| | PACKAGE, WHERE? |
| | 85A) WALL TYPES & THICKNESS |
| | 85B) CEILING TYPES & THICKNESS |
| | 85C) ARETHE CEILINGS DROPPED IN ANY AREAS |
| | NOTE:2509.1 WET AREAS. |
| | SHOWERS AND PUBLIC TOILET WALLS SHALL CONFORM TO |
| | SECTIONS 1210.2 AND 1210.3 . |
| | 2509.3 LIMITATIONS. |
| | WATER-RESISTANT GYPSUM BACKING BOARD SHALL NOT BE USED |
| | IN THE FOLLOWING LOCATIONS: |
| | 1.OVER A VAPOR RETARDER IN SHOWER OR BATHTUB |
| | COMPARTMENTS. |
| | 2.WHERE THERE WILL BE DIRECT EXPOSURE TO WATER OR |
| | IN AREAS SUBJECT TO CONTINUOUS HIGH HUMIDITY. |
| | 3.ON CEILINGS WHERE FRAME SPACING EXCEEDS 12 |
| | INCHES (305 MM) O.C. FOR ?-INCH-THICK (12.7 MM) |
| | WATER-RESISTANT GYPSUM BACKING BOARD AND MORE THAN 16 |
| | INCHES (406 MM) O.C. FOR 5 / 8 -INCH-THICK (15.9 MM) |
| | WATER-RESISTANT GYPSUM BACKING BOARD. |
| | |
| | 86) S-1 INDICATES THAT FOUNDATION WORK IN AREAS WILL |
| | COME UP TO THE PROPERTY LINE, SHOW COMPLIANCE WITH |
| | 3307.1 PROTECTION OF ADJACENT PROPERTY. |
| | |
| | 87) ADJACENT TO EXCAVATIONS. |
| | EVERY EXCAVATION ON A SITE LOCATED 5 FEET (1524 MM) OR |
| | LESS FROM THE STREET LOT LINE SHALL BE ENCLOSED WITH A |
| | BARRIER NOT LESS THAN 6 FEET (1829 MM) HIGH. WHERE |
| | LOCATED MORE THAN 5 FEET (1524 MM) FROM THE STREET LOT |
| | LINE, A BARRIER SHALL BE ERECTED WHEN REQUIRED BY THE |
| | BUILDING OFFICIAL. BARRIERS SHALL BE OF ADEQUATE |
| | STRENGTH TO RESIST WIND PRESSURE AS SPECIFIED IN |
| | CHAPTER 16 . |
| | |
| | |
| | 88) WHILE UNDER CONSTRUCTION A STANDPIPE SHALL MEET THE |
| | REQUIREMENTS OF: 3311.1 WHERE REQUIRED.BUILDINGS FOUR |
| | STORIES OR MORE IN HEIGHT SHALL BE PROVIDED WITH NOT |
| | LESS THAN ONE STANDPIPE FOR USE DURING CONSTRUCTION. |
| | SUCH STANDPIPES SHALL BE INSTALLED WHERE THE PROGRESS |
| | OF CONSTRUCTION IS NOT MORE THAN 40 FEET (12 192 MM) IN |
| | HEIGHT ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT |
| | ACCESS. SUCH STANDPIPE SHALL BE PROVIDED WITH FIRE |
| | DEPARTMENT HOSE CONNECTIONS AT ACCESSIBLE LOCATIONS |
| | ADJACENT TO USABLE STAIRS. SUCH STANDPIPES SHALL BE |
| | EXTENDED AS CONSTRUCTION PROGRESSES TO WITHIN ONE FLOOR |
| | OF THE HIGHEST POINT OF CONSTRUCTION HAVING SECURED |
| | DECKING OR FLOORING. |
| | |
| | 89) S-8 INDICATES A TABLE OF CONCRETE COVERAGE HOW DOES |
| | THIS TABLE COMPLY WITH TABLE |
| | 601 THE HOUR RATINGS FOR STRUCTURAL FRAMES COLUMNS, |
| | GIRDERS OR BEAMS, FLOOR AND ROOF SLABS? |
| | |
| | 90) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, |
| | IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE |
| | ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| | REQUIREMENT, THE SPECIFIC |
| | REQUIREMENT SHALL BE APPLICABLE. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |