Plan Review Details - Permit 07020689
Plan Review Stops For Permit 07020689
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-07-23 Cont ID  
Sent By mjacobs Date 2007-07-23 Time 13:28 Rev Time 0.00
Received By mjacobs Date 2007-07-23 Time 13:15 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-04-03 Cont ID  
Sent By mjacobs Date 2007-04-03 Time 07:32 Rev Time 0.00
Received By mjacobs Date 2007-04-03 Time 06:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-07 Cont ID  
Sent By mjacobs Date 2007-03-07 Time 14:58 Rev Time 0.00
Received By mjacobs Date 2007-03-06 Time 17:21 Sent To  
Notes
2007-03-06 18:59:22BUILDING PLAN REVIEW
 PERMIT: 07020689
 ADD: 1616 N. FLORIDA MANGO RD
 CONT: JASO AND ASSOC. INC.
 TEL: (561)347-0673
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 ) NUMBER OF UNITS
 ) NUMBER OF FLOORS
 ) NUMBER OF ROOMS
 ) SQ. FT. FOOTPRINT
 ) SQ. FT. UNDER ROOF (TOTAL)
 ) OCCUPANT LOAD
 ) FLOOD ZONE
  
 4)INDICATE CLEARLY ON THE DRAWINGW THE PROPOSED WORK
 AREAAND DESCRIBE IN DETAIL WHAT WORK WILL BE CARRIED
 OUT. SHOW ON THE DRAWINGS WHICH WALLS ARE EXISTING AND
 WHICH ONES ARE NEW. IF THERE WILL BE ANY DEMOLITION
 INDICATE ON THE PLANS. WILL THE BATHROOMS FIXTURES BE
 REPLACE ETC. THIS INFORMATION IS VERY IMPORTANT FOR
 PLAN REVIEW. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE
  
 5)WPB AMENDMENTS 108.3*THE VALUE IS TO LOW. IF IN
 THE OPINION OF THE BUILDING OFFICIAL, THE CLAIMED
 VALUATION OF THE BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION, THE PERMIT
 SHALL BE DENIED. FOR PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT
 VALUE OF THE PROJECT.
  
 6)PROVIDE THE EXISTING AND PROPOSED FLOOR PLAN OF THE
 PROJECT.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-05-22 Cont ID  
Sent By btrobaug Date 2007-05-22 Time 12:04 Rev Time 0.50
Received By btrobaug Date 2007-05-22 Time 11:44 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-05-03 Cont ID  
Sent By btrobaug Date 2007-05-03 Time 14:40 Rev Time 0.75
Received By btrobaug Date 2007-04-30 Time 07:06 Sent To PC
Notes
2007-05-03 14:39:53 
  
 REVISION DENIED
  
 THIS WAS A PROVISO ON THE PERMITTED SET AND FAILED TO
 GET ADDRESSED ON THE REVISION.
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1}INDICATE COMPLIANCE WITH 13-415.1ABC.1.2, FBC FOR
 SPACE CONTROLS FOR LIGHTING." STANDARD"SWITCHES ARE
 SHOWN ON THE PLAN. THE SUBMITTALS WERE RECEIVED IN THE
 RESUB PACKAGE, BUT THE SENSORS NEED TO BE LOCATED ON
 THE PLAN.SHOW COMPLIANCE ON THE DRAWING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-04-05 Cont ID  
Sent By btrobaug Date 2007-04-05 Time 15:14 Rev Time 0.75
Received By btrobaug Date 2007-04-05 Time 13:19 Sent To  
Notes
2007-04-05 15:14:06 
  
 PROVISO
  
 THIS PERMIT IS BEING ISSUED TO
 FACILITATE THE REPAIR OF THIS BUILDING
 THE PLANS HOWEVER ARE INCOMPLETE. PLEASE
 RESUBMIT A REVISION SHOWING ACTUAL
 CONDITIONS PRIOR TO CALLING ROUGH
 ELECTRICAL INSPECTION.
 THE REVIEWED PLAN MUST BE ON THE JOB
 SITE AT TIME OF INSPECTION. ALLOW AT
 LEAST ONE WEEK (PER TRADE) FOR PLAN
 REVIEW.
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1}INDICATE COMPLIANCE WITH 13-415.1ABC.1.2, FBC FOR
 SPACE CONTROLS FOR LIGHTING." STANDARD"SWITCHES ARE
 SHOWN ON THE PLAN. THE SUBMITTALS WERE RECEIVED IN THE
 RESUB PACKAGE, BUT THE SENSORS NEED TO BE LOCATED ON
 THE PLAN.SHOW COMPLIANCE ON THE DRAWING.
  
 2} THE DISCONNECT LOCATIONS FOR THE CONDENSING UNITS DO
 NOT COMPLY WITH THE 3' CLEARANCE REQUIREMENTS OF
 110.26, NEC.
  
 3} THE UTILITY RECEPTACLE CIRCUIT (#PA-20) FOR THE
 CONDENSING UNITS WAS OMITTED FROM THE PANEL SCHEDULE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-06 Cont ID  
Sent By btrobaug Date 2007-03-06 Time 09:06 Rev Time 2.00
Received By btrobaug Date 2007-03-02 Time 07:25 Sent To  
Notes
2007-03-05 13:45:41 
 DENIED/INCOMPLETE INFORMATION
  
 THIS REVIEWING IS BASED ON THE OPINION THAT ALL THE
 ELECTRICAL SYSTEMS AND EQUIPMENT ON THE PLAN IS NEW AS
 THERE IS NOTHING IN THE DESCRIPTION ON THE APPLICATION,
 OR NOTES ON THE PLAN INDICATING OTHERWISE.
  
 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
 THE PANELS ARE MARKED "MLO", INDICATE THE LOCATION OF
 THE DISCONNECTING MEANS. SEE 408.36.
  
 2}PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT
 SIZE AND TYPE, GROUNDING DETAILS PER 215.5.. THE "ONE
 LINE "DIAGRAM SUBMITTED DOES NOT HAVE ENOUGH
 INFORMATION.
  
 3} GIVE AMPERE RATING FOR THE PANELS. 215.5
  
 4} THE PANEL SCHEDULES ARE LABELED "PA AND "PC", THE
 PANELS AND CIRCUITS ARE LABELED "PA" AND "PB". PLEASE
 CORRELATE.
  
 5} THE LIGHTING CIRCUIT IN SUITE 1, OFFICE 105, IS
 MISMARKED "PB-18"
  
 6} THE WATER COOLERS SHOWN IN BOTH SUITES ON SHEET E1,
 ARE NOT LISTED ON THE PANEL SCHEDULES. SEE 210.23(A)(2)
 FOR REQUIREMENTS.
  
 7} PLEASE COMPLETE NOTE #7 , OR USE AS A CONTINUATION
 OF NOTE #6.
  
 8} CONDENSER #1, CIRCUIT 5,7 AND #2, CIRCUIT 8,10,
 PANEL "PA" INDICATE A 10 AMP LOAD (2500 WATTS)
 PROTECTED BY A 60 AMP BREAKER. THIS EXCEEDS THE
 PARAMETERS OF 440.22 FOR OCP.
  
 9} THE AHU CIRCUITS IN PANEL "PA" ARE IN VIOLATION OF
 424.3(B). SEE ALSO 240.4, REFERENCED IN SAME. THE
 WATTAGE OF THESE UNITS DOES NOT CORRESPOND TO THE
 SPECIFICATIONS ON SHEET M1. PLEASE CORRELATE
  
 10} SHOW THE LOCATION REQUIRED DISCONNECTS PER 440.14,
 ANDRECEPTACLE PER 210.63 FOR THE CONDENSING UNT,
 SHEET E1.
  
 11}THE PANEL LABELED "PC", CIRCUIT PB 4,6 AT THE
 RECEPTACLE, INDICATES A 60 AMP OCP FOR A 3300 WATT A/C
 LOAD IN VIOLATION OF 240.4.
  
 12}INDICATE COMPLIANCE WITH 13-415.1ABC.1.2, FBC FOR
 SPACE CONTROLS FOR LIGHTING." STANDARD SWITCHES ARE
 SHOWN ON THE PLAN.SHOW COMPLIANCE ON THE DRAWING.
  
 13} INDICATE COMPLIANCE WITH 13-415.2ABC.1, PERFORMANCE
 CALCULATION PROCEDURES. SUBMIT FORMS WITH 13-415.2B OR
 13-415.2.C.1 DENSITIES.
  
 NOTE: IF THERE ARE ANY QUESTIONS REGARDING THE
 REQUIREMENT TO COMPLY, PLEASE SEE 13.400.0.C.4, SECOND
 PARAGRAPH.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-04-03 Cont ID  
Sent By mwennerg Date 2007-04-03 Time 10:39 Rev Time 0.00
Received By mwennerg Date 2007-04-03 Time 10:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-03-08 Cont ID  
Sent By mawillia Date 2007-03-08 Time 11:40 Rev Time 0.00
Received By mawillia Date 2007-03-08 Time 10:57 Sent To  
Notes
2007-03-08 11:39:42******DENIED*****
  
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.COMBUSTIBLE WASTE MATERIALS SHALL BE REMOVED FROM
 THE SITE AT THE END OF EACH SHIFT OR MORE FREQUENTLY AS
 NECESSARY FOR SAFE OPERATION.
  
 3.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF
 NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE
 OR HINDER WITH EMERGENCY RESPONSE ACCESSTO THE
 STRUCTURE OR THE VICINITY THEREOF (INCLUDING FIRE
 LANES).
  
 4.IT IS STATED ON SHEET A2 THAT THE MEANS OF EGRESS
 FACTORS IS/ARE BASED ON NFPA 101 - 2006, HOWEVER , NFPA
 101- 2003 EDITION SHALL BE REFERENCED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEM
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-07-30 Cont ID  
Sent By adarroug Date 2007-07-30 Time 09:17 Rev Time 0.00
Received By adarroug Date 2007-07-30 Time 09:17 Sent To B
Notes
2007-07-30 09:17:35TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-07-23 Cont ID  
Sent By adarroug Date 2007-07-23 Time 09:21 Rev Time 0.00
Received By adarroug Date 2007-07-23 Time 09:21 Sent To P
Notes
2007-07-23 09:22:13TO "PSCHMITZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-05-14 Cont ID  
Sent By adarroug Date 2007-05-14 Time 14:50 Rev Time 0.00
Received By adarroug Date 2007-05-14 Time 14:50 Sent To E
Notes
2007-05-14 14:50:40TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-04-23 Cont ID  
Sent By adarroug Date 2007-04-23 Time 11:39 Rev Time 0.00
Received By adarroug Date 2007-04-23 Time 11:39 Sent To E
Notes
2007-04-23 11:39:49TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-28 Cont ID  
Sent By spalmer Date 2007-03-28 Time 18:17 Rev Time 0.00
Received By spalmer Date 2007-03-28 Time 18:17 Sent To  
Notes
2007-03-28 18:18:07TO BOB # 8

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-08 Cont ID  
Sent By mawillia Date 2007-03-08 Time 10:57 Rev Time 0.00
Received By mawillia Date 2007-02-27 Time 17:31 Sent To  
Notes
2007-02-27 17:32:06TO "BOB"#4

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-03-29 Cont ID  
Sent By tgordon Date 2007-03-29 Time 13:35 Rev Time 0.25
Received By tgordon Date 2007-03-29 Time 13:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-03-02 Cont ID  
Sent By tgordon Date 2007-03-02 Time 13:40 Rev Time 0.30
Received By tgordon Date 2007-03-02 Time 13:40 Sent To  
Notes
2007-03-02 13:46:55*** DENIED ***
 1) PROVIDE FRESH AIR CALCULATIONS, PER 2004 FBC/M
 403.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-07-23 Cont ID  
Sent By pschmitz Date 2007-07-23 Time 09:28 Rev Time 0.00
Received By pschmitz Date 2007-07-23 Time 09:28 Sent To B
Notes
2007-07-23 09:44:01AAV IN PLACE OF VTR

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-03-31 Cont ID  
Sent By jleech Date 2007-03-31 Time 09:15 Rev Time 0.00
Received By jleech Date 2007-03-31 Time 09:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-03-03 Cont ID  
Sent By jleech Date 2007-03-03 Time 12:46 Rev Time 0.00
Received By jleech Date 2007-03-03 Time 12:46 Sent To  
Notes
2007-03-03 13:06:24DENIED;
 BOTTLED WATER COOLER MUST BE A DRINKING FOUNTAIN SEE
 FBC-2004 PLUMBING SECTION 410.1.
 PLUMBING PLAN REVIEW BY;