Plan Review Details - Permit 07020672
| Plan Review Stops For Permit 07020672 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2007-03-09 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-03-09 |
Time |
08:52 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2007-03-09 |
Time |
08:40 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-02-28 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-02-28 |
Time |
11:56 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2007-02-28 |
Time |
11:20 |
Sent To |
I |
|
| Notes |
| 2007-02-28 11:56:37 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW | | | | | | 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL | | | COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY | | | INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL | | | CONSTRUCTION COST ANALYSIS SERVICES PER108.3 FBC AS | | | AMENDED. EVEN IF YOU PROVIDE LABOR AS AN OWNER/BUILDER, | | | THE VALUE OF THE APPLICATION MUST BE AT THE SAME RATE A | | | CONTRACTOR WOULD CHARGE. THIS IS FOR REPORT PURPOSES. | | | | | | 2} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT | | | SIZE AND TYPE, GROUNDING DETAILS. 215.5. | | | | | | 3} PER 110.9 AND 110.10: OBTAIN THE | | | AVAILABLE FAULT CURRENT AT THE UTILITY | | | AND CALCULATE THE SAME AT THE EQUIPMENT. | | | INDICATE THE AIC RATING FOR THE | | | EQUIPMENT IS EQUAL TO OR GREATER THAN | | | THE AVAILABLE FAULT. | | | | | | 4} PLEASE PROVIDE A PANEL SCHEDULE SO THAT | | | BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVER CURRENT | | | PROTECTION COMPLIANCE MAY BE REVIEWED PER 106.3.5.4 FBC | | | AS AMENDED. ALSO SEE 408.4 NEC. ALL PANELS BEING | | | ADDED. | | | | | | 5} REGARDING THE RANGE AND DRYER WIRING, AN EQUIPMENT | | | GROUND IS REQUIRED PER 250.134-138. 2 WIRE AND 3 WIRE | | | ROMEX IS LISTED ON THE PLAN. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-02-28 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-02-28 |
Time |
11:57 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-02-27 |
Time |
16:12 |
Sent To |
PC |
|
| Notes |
| 2007-02-27 16:12:26 | TO "E" BOX |
|
|
|