Plan Review Details - Permit 07020671
Plan Review Stops For Permit 07020671
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-28 Cont ID  
Sent By tgordon Date 2007-02-28 Time 14:24 Rev Time 0.00
Received By tgordon Date 2007-02-27 Time 16:12 Sent To  
Notes
2007-02-27 16:12:59TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-03-09 Cont ID  
Sent By tgordon Date 2007-03-09 Time 08:38 Rev Time 0.25
Received By tgordon Date 2007-03-09 Time 08:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-02-28 Cont ID  
Sent By tgordon Date 2007-02-28 Time 14:05 Rev Time 0.45
Received By tgordon Date 2007-02-28 Time 14:05 Sent To  
Notes
2007-02-28 14:24:20*** DENIED ***
 1) MECHANICAL PLANS HAVE TO MUCH FLOOR PLAN INFORMATION
 ON THEM AND ARE DIFFICULT TO READ THE A/C DUCT DESIGN.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY.
 PER 2004 FBC 106.1.1.
  
 2) THE VALUE ON THE PERMIT APPLICATION NEEDS TO BE THE
 FAIR MARKET VALUE. VALUE ENTERED ON APPLICATION WAS TO
 LOW AND WAS ADJUSTED USING MARSHALL & SWIFT TO OBTAIN
 THE REPLACEMENT VALUE, PER 2004 FBC WPB AMEND. 108.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  
  
 .