Plan Review Details - Permit 07020666
Plan Review Stops For Permit 07020666
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2009-07-17 Cont ID  
Sent By jwitmer Date 2009-07-17 Time 13:01 Rev Time 0.55
Received By jwitmer Date 2009-07-17 Time 13:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2008-04-17 Cont ID  
Sent By jwitmer Date 2008-04-17 Time 14:24 Rev Time 1.33
Received By jwitmer Date 2008-04-17 Time 14:24 Sent To PC
Notes
2008-04-17 15:37:07BUILDING PLAN REVIEW
 PERMIT: 07020666
 ADD: 801 N DIXIE HWY
 CONT:EURO HOMES
 TEL: (561)655-5533
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION REVIEW
 ACTION: DENIED
  
 1)THE REVISION CAME IN UNDER THE MECHANICAL
 CONTRACTOR, THIS REVISION WOULD BE OUT OF THE SCOPE OF
 THEIR LICENSE. SEEFL S S 489.113. THIS REVISION
 SHOULD COME IN UNDER THE
 BUILDING CONTRACTORS PERMIT.
  
 2) THE ENGINEER ALEEN WIEDER HAS NOT PROVIDED ANY WIND
 INFORMATION ON THE DETAIL.
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1.BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
 2.WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. 3.
 WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
 4.THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 5.COMPONENTS AND CLADDING. THE DESIGN WIND
 PRESSURES IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE
 SELECTION OF EXTERIOR COMPONENTS AND CLADDING MATERIALS
 NOT SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 3) ENGINEER INDICATES THAT 2 1/2" # 12 SCREWS ARE TO BE
 SCREWED INTO THE RAFTERS. THE PLAN DOES NOT INDICATE
 THAT THE CURB ITSELF IS TO BE MADE OUT OF STEEL WITH
 BLOCKING ATTHE UPPER LIP.
 PLEASE CLARIFY THE CURB DETAIL, MATERIAL, IF METAL
 GAUGE OF METAL ETC. ALSO PROVIDE INFORMATION ON HOW THE
 DETAIL WILL BE FLASHEDWITH NO LIP ON THE TOP OF THE
 DETAIL PROVIDING A WATER STOP.
  
 4) THIS DETAIL WILL NEED TO BE REVIEWED BY THE DESIGNER
 OF RECORD FOR THE PROJECT. PLEASE SPANS OF RAFTERS AND
 THE WEIGHT OF THE MECHANICAL UNIT SO THE DESIGNER OF
 RECORD CAN CALCULATE
 THE LOADING OF THE EXISTING ROOF, SINCE THIS PLANS
 CLEARLY STATES NOT PART OF THIS REVIEW FOR LOADING.
  
 5)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES,
 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING
 REPORTS, MISSING REPORTS ARE AS FOLLOWS:
 TRUSS ANCHORS, WOOD CONNECTORS, ANCHORS 9B-72(31)(G)
  
 6) PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.)
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-04-09 Cont ID  
Sent By jwitmer Date 2008-04-09 Time 11:23 Rev Time 0.77
Received By jwitmer Date 2008-04-09 Time 11:23 Sent To PC
Notes
2008-04-09 11:24:33REVISION; SHEET S-3

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-02-05 Cont ID  
Sent By jwitmer Date 2008-02-05 Time 07:43 Rev Time 0.77
Received By jwitmer Date 2008-02-05 Time 07:43 Sent To PC
Notes
2008-02-05 07:54:19BUILDING PERMIT ISSUED WITHOUT ROOFING INFORMATION,
 FL617-R1 REPORT WAS SUBMITTED BUT NO SUB-SYSTEM WAS
 NOTED WHICH WOULD OF LED TO LOW PRESSURES REQUIRING RAS
 117 CALCULATIONS, TO BE SUBMITTED UNDER A SEPERATE
 ROOFING PERMIT WITH ASSOCIATED FEES, AND REVIEWS.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-11-21 Cont ID  
Sent By jwitmer Date 2007-11-21 Time 14:42 Rev Time 3.33
Received By jwitmer Date 2007-11-21 Time 14:42 Sent To  
Notes
2007-11-21 14:45:31BUILDING PROVISO: ROOFING PERMIT TO BE UNDER SEPERATE
 PERMIT WITH ASSOCIATED FEES AND REVIEW. ROOFING PRODUCT
 APPROVALS WERE SUBMITTED THE THIRD TIME AND NO
 SUB-SYSTEM WAS HIGHLIGHTED.
 THE LISTEDED SUB-SYSTMES ALL HAD LOW PRESSURES FOR
 ZONES 2 & 3 REQUIRING RAS 117 CALCULATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-10-19 Cont ID  
Sent By jjohnsto Date 2007-10-19 Time 16:33 Rev Time 3.00
Received By jjohnsto Date 2007-10-19 Time 16:33 Sent To  
Notes
2007-10-19 16:35:12CONSTRUCTION SERVICES DEPARTMENT
 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH,
 FLORIDA33401
 TEL:561-805-6713FAX:
 561-805-6731
  
 JAMES JOHNSTON, PERMIT NO 07020666 BUILDING
 PLAN EXAMINERII PROJECT ALTERATION
 E-MAIL:JJOHNSTON @WPB.ORG ADDRESS
 801 NORTH DIXIE HIGHWAY
  DATE OCTOBER 19, 2007
  
 BUILDINGPLANREVIEW
 ARCHITECT
 FLORIDA STATUE 481.219CERTIFICATION OF
 PARTNERSHIPS, LIMITED LIABILITY COMPANIES, AND
 CORPORATIONS.
 (1)THE PRACTICE OF OR THE OFFER TO PRACTICE
 ARCHITECTURE OR INTERIOR DESIGN BY LICENSEES THROUGH A
 CORPORATION, LIMITED LIABILITY COMPANY, OR PARTNERSHIP
 OFFERING ARCHITECTURAL OR INTERIOR DESIGN SERVICES TO
 THE PUBLIC, OR BY A CORPORATION, LIMITED LIABILITY
 COMPANY, OR PARTNERSHIP OFFERING ARCHITECTURAL OR
 INTERIOR DESIGN SERVICES TO THE PUBLIC THROUGH
 LICENSEES UNDER THIS PART AS AGENTS, EMPLOYEES,
 OFFICERS, OR PARTNERS, IS PERMITTED, SUBJECT TO THE
 PROVISIONS OF THIS SECTION.
 (2)FOR THE PURPOSES OF THIS SECTION, A CERTIFICATE OF
 AUTHORIZATION SHALL BE REQUIRED FOR A CORPORATION,
 LIMITED LIABILITY COMPANY, PARTNERSHIP, OR PERSON
 PRACTICING UNDER A FICTITIOUS NAME, OFFERING
 ARCHITECTURAL SERVICES TO THE PUBLIC JOINTLY OR
 SEPARATELY. HOWEVER, WHEN AN INDIVIDUAL IS PRACTICING
 ARCHITECTURE IN HER OR HIS OWN NAME, SHE OR HE SHALL
 NOT BE REQUIRED TO BE CERTIFIED UNDER THIS SECTION.
 CERTIFICATION UNDER THIS SUBSECTION TO OFFER
 ARCHITECTURAL SERVICES SHALL INCLUDE ALL THE RIGHTS AND
 PRIVILEGES OF CERTIFICATION UNDER SUBSECTION (3) TO
 OFFER INTERIOR DESIGN SERVICES.
 (10)EACH PARTNERSHIP, LIMITED LIABILITY COMPANY, AND
 CORPORATION CERTIFIED UNDER THIS SECTION SHALL NOTIFY
 THE DEPARTMENT WITHIN 30 DAYS OF ANY CHANGE IN THE
 INFORMATION CONTAINED IN THE APPLICATION UPON WHICH THE
 CERTIFICATION IS BASED. ANY REGISTERED ARCHITECT OR
 INTERIOR DESIGNER WHO QUALIFIES THE CORPORATION,
 LIMITED LIABILITY COMPANY, OR PARTNERSHIP AS PROVIDED
 IN SUBSECTION (7) SHALL BE RESPONSIBLE FOR ENSURING
 RESPONSIBLE SUPERVISING CONTROL OF PROJECTS OF THE
 ENTITY AND UPON TERMINATION OF HER OR HIS EMPLOYMENT
 WITH A PARTNERSHIP, LIMITED LIABILITY COMPANY, OR
 CORPORATION CERTIFIED UNDER THIS SECTION SHALL NOTIFY
 THE DEPARTMENT OF THE TERMINATION WITHIN 30 DAYS.
 COMMENT-THE CORPORATION SMITH AND MOORE ARCHITECTS,
 INC.MUST BE IN COMPLIANCE WITH THIS STATUE.
 A CERTIFICATE OF AUTHORIZATION IS REQUIRED. THE ADDRESS
 OF THE CORPORATION MUST BE LISTED WITH THIS
 CERTIFICATE.
  
  
  
  
 FLORIDA ADMINISTRATIVE CODE61G1-16.002DOCUMENTS
 SIGNED AND SEALED
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL
 AND BEING FILED FOR PUBLIC RECORD SHALL HAVE THE
 SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT WITH THE DATE.
 COMMENT-
 A. THE DESIGNER OF RECORD MUST SIGN AND SEAL THE
 STOREFRONT DRAWINGS PREPARED BY SMITH AND MOORE IN
 THEIR TITLE BLOCK.THE ACCEPTANCE REQUIREMENT WILL NOT
 BE NECESSARY AS THE DESIGNER AND PREPARER ARE THE
 SAME.
 B. THE FLORIDA PRODUCT APPROVAL FOR THE PANEL WALLS,
 STORE FRONT WAS SUBMITTED UNDER THE 2001 CODE. THE CODE
 BEING USED IS THE 2004.THE NOA MIAMI-DADE PRODUCT
 APPROVAL SUBMITTED WITH THIS PACKAGE HAS THE CORRECT
 CODE.I HAVE REPLACED THE 2001 FLORIDA PRODUCT
 APPROVALPANEL WALLS, STORE FRONTWITH THE 2004
 INFORMATION.
 PLEASE REVIEW THIS PRODUCT APPROVAL AND ACKNOWLEDGE
 ACCEPTANCE, IF APPLICABLE,ON BOTH COPIES.
  
  
 C PRODUCT APPROVALS REQUIRED
 FBC 1609.1.4 AND WPB ADMINISTRATIVE CODE 106.3
 REGULATED BY DCA RULE 9B-72FLORIDA PRODUCT APPROVALS
 SUBMIT TWO COPIES OF EACH APPROVAL ( 3 COPIES IF A
 THRESHOLD BUILDING ) WITH FLORIDA PRODUCT APPROVAL
 COVER SHEET THE ARCHITECT?S / ENGINEER?S SIGNATURE AS
 APPLICABLE, STATING ?TO THE BEST OF THEIR KNOWLEDGE THE
 PRODUCT APPROVAL COMPLIES WITH THE PLANS AND
 SPECIFICATIONS.SEE:WEB SITE
 WWW.FLORIDABUILDING.COM
  
 COMMENT-ARCHITECT MUST REVIEW THE PRODUCT APPROVALS
 SUBMITTED FOR COMPLIANCE WITH THE PROJECT
 AND PROVIDE THE STATEMENT ?TO THE BEST???..)
  
  
 D PROJECT INFORMATION
 FBC2004 FLORIDA BUILDING CODE BUILDING W/ 2005
 AND 6 REVISIONS
 FBC2004 ACCESSIBILITY CHAPTER11
 FBC2004 EXISTING BUILDING LEVEL OF ALTERATION II
 TYPE OF CONSTRUCTION V
 SPRINKLED / UN-SPRINKLED UN-SPRINKLED
 BASIC WIND SPEED ? MPH 140
 WIND EXPOSURE C
 WIND IMPORTANCE FACTOR I
 INTERNAL PRESSURE COEFFICIENT SEE 1609.6.2.1 TYPE OF
 OCCUPANCY A/B
 OCCUPANT LOAD-GROSS - NET 30
 COMMENT-NOTE THE FOLLOWING INFORMATION ON THE COVER
 SHEET
  
 D-1 SUBMIT A SURVEY OF THE EXISTING BUILDING WITH ALL
 PROPERTY LINES FOR REVIEW
  
  
 E FBC 713.1 GENERAL - FIRE RESISTANT JOINT SYSTEM
 JOINTS INSTALLED IN OR BETWEEN FIRE-RESISTANCE-RATED
 WALLS, FLOOR OR FLOOR/CEILING ASSEMBLIES AND ROOFS OR
 ROOF/CEILING ASSEMBLIES SHALL BE PROTECTED BY AN
 APPROVED FIRE-RESISTANT JOINT SYSTEM DESIGNED TO RESIST
 THE PASSAGE OF FIRE FOR A TIME PERIOD NOT LESS THAN THE
 REQUIRED FIRE-RESISTANCE RATING OF THE WALL, FLOOR OR
 ROOF IN OR BETWEEN WHICH IT IS INSTALLED.
 FIRE-RESISTANT JOINT SYSTEMS SHALL BE TESTED IN
 ACCORDANCE WITH SECTION 713.3 . THE VOID CREATED AT THE
 INTERSECTION OF A FLOOR/CEILING ASSEMBLY AND AN
 EXTERIOR CURTAIN WALL ASSEMBLY SHALL BE PROTECTED IN
 ACCORDANCE WITH SECTION 713.4 .
 COMMENT-DETAIL1-A3PLEASE PROVIDE THE SYSTEM
 THAT IS TO BE APPLIED TO THE JOINT LOCATED AT THE WALL
 ASSEMBLY CONNECTEDTO THE UNDERSIDE OF THE ROOF
  
  
  
  
 ENGINEER COMMENTS
  
 F FBC 2001 104.3 EXAMINATION OF DOCUMENTS
 104.3.1 PLAN REVIEW. THE BUILDING OFFICIAL SHALL
 EXAMINE OR CAUSE TO BE EXAMINED EACH APPLICATION FOR A
 PERMIT AND THE ACCOMPANYING DOCUMENTS, CONSISTING OF
 DRAWINGS, SPECIFICATIONS, COMPUTATIONS AND ADDITIONAL
 DATA, AND SHALL ASCERTAIN BY SUCH EXAMINATIONS WHETHER
 THE CONSTRUCTION INDICATED AND DESCRIBED IS IN
 ACCORDANCE WITH THE REQUIREMENTS OF THE TECHNICAL CODES
 AND ALL OTHER PERTINENT LAWS OR ORDINANCES. COMMENT
 PLEASE SEE INFORMATION REQUESTEDSECTION 1604.8.2
  
  
 G FBC 1604.8.2 CONCRETE AND MASONRY WALLS. CONCRETE AND
 MASONRY WALLS SHALL BE ANCHORED TO FLOORS, ROOFS AND
 OTHER STRUCTURAL ELEMENTS THAT PROVIDE LATERAL SUPPORT
 FOR THE WALL. SUCH ANCHORAGE SHALL PROVIDE A POSITIVE
 DIRECT CONNECTION CAPABLE OF RESISTING THE HORIZONTAL
 FORCES SPECIFIED IN THIS CHAPTER BUT NOT LESS THAN A
 MINIMUM STRENGTH DESIGN HORIZONTAL FORCE OF 280 PLF
 (4.10 KN/M) OF WALL, UNLESS THE LATERAL FORCE HAS
 OTHERWISE BEEN CALCULATED BY THE ENGINEER OF RECORD.
 WALLS SHALL BE DESIGNED TO RESIST BENDING BETWEEN
 ANCHORS WHERE THE ANCHOR SPACING EXCEEDS 4 FEET (1219
 MM). REQUIRED ANCHORS IN MASONRY WALLS OF HOLLOW UNITS
 OR CAVITY WALLS SHALL BE EMBEDDED IN A REINFORCED
 GROUTED STRUCTURAL ELEMENT OF THE WALL. SEE SECTIONS
 1609.6.5 FOR WIND DESIGN REQUIREMENTS. COMMENTS-SEE
 ITEMS LISTED BELOW
  
 H SHEET S-2PLACE DETAIL NUMBER OR SYMBOL AT EACH
 WINDOW AND DOOR OPENING.IDENTIFY THE ?TYPICAL?
 OPENINGS DRAWN ON SHEET S-2 ALSO WITH A NUMERICAL
 NUMBER OR SYMBOL.THIS WILL PROVIDE THE EXACT
 STRUCTURAL COMPONENT TO BE USED IN THE FIELD AND FOR
 THIS PLAN REVIEW.
  
 I SHEET S-2 IDENTIFY COLUMNS AT DETAIL 5-S1
  
 C SHEET S-2 DETAIL 2-S1PROVIDE A SECTION AS TO THE
 2? X 6?BLOCKING OR BRIDGING,
 GRADE OF LUMBER,SIZE OF EXISTING MEMBERS FOR
 ATTACHMENT, TYPE OF ATTACHMENTS, PURPOSE OF
 INSTALLATION.
  
  
 J SHEET S-2 DETAIL 2 S-1 AND 1 S-1PROVIDE
 INFORMATION AS TO THE EXTERIOR BEAM AT THIS LOCATION .
  
  
 K SHEET S-1 IDENTIFY ALL COLUMNS AND BEAMS ON THE
 PARTIAL FOUNDATION PLAN
  
  
 L SHEET S-1 IDENTIFY THE HILTI 500 SYSTEM TO BE USED
 FROM THE HILTI CHART AND NOTE ON PLAN
  
 M SHEET S-2STRUCTURAL NOTESPROVIDE THE CONCRETE
 DESIGN STRENGTH TO BE USED FOR THE FOUNDATION, BEAMS,
 COLUMNS.
 PROVIDE THE GRADE FOR THE REINFORCING STEEL
  
  
 N FBC1609.1.4 SUBMIT PRODUCT APPROVAL FOR THE
 TRUSS ANCHORS SIMPSON HG A-10
 COMMENTPLEASE FIND THE SIMPSON PRODUCT APPROVAL I
 RETRIEVED ON LINE.
 PLEASE REVIEW AND ACKNOWLEDGE ACCEPTANCE
  
  
  
 PLAN REVIEWER?S PREVIOUS COMMENTS ON 3/29/07NOT
 ADDRESSED
  
 4) DESIGN INFORMATION NOT COMPLETE
 COMMENTS-SEE THIS PLAN REVIEWER?S COMMENTD
  
 8) NEGATIVE AND POSITIVE DESIGN PRESSURES ARE TO BE PUT
 ON SHEET A-2ELEVATIONS
  
 9) WHERE IS THE PROPERTY LINES?
 COMMENTS-SEE THIS PLAN REVIEWER?S COMMENTD-1
  
 10) FLEXIBLE JOINT AT THE ROOF LINE OF THE TENANT
 SEPARATION WALL
 COMMENTS-SEE THIS PLAN REVIEWER?S COMMENTE

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-29 Cont ID  
Sent By jwitmer Date 2007-03-29 Time 16:26 Rev Time 2.22
Received By jwitmer Date 2007-03-29 Time 16:26 Sent To FIRE
Notes
2007-03-29 16:48:43BUILDING PLAN REVIEW
 PERMIT: 07020666
 ADD: 801 N DIXIE HWY
 CONT: EURO HOMES, INC
 TEL: (561)351-5850
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)THE DESCRIPTION OF WORK ON THE PLANS INDICATES
 DIVIDING A TENANT SPACE
 INTO TWO TENANT SPACES PLUS THE WORK ON THE EXTERIOR
 OF THE BUILDING NEW WINDOWS AND DOORS.
 PLEASE UPDATE THE PERMIT APPLICATION DESCRIPTION OF
 PROJECT.
  
 3)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 4) S-1 PLANS DO NOT INDICATE THE WIND DESIGN:
 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 5)FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EXTERIOR DOORS & SIDELIGHTSTO THE CURRENT 2004
 FBC
 B) STOREFRONT WINDOWS 2004 FBC
 C) MULLIONS IF NOT COVERED UNDER THE PRODUCT REPORT
 D) STORM SHUTTERS IF NOT LARGE MISSLE RATED GLASS
  
  
 6)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 7)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 8)SHEET A-2 INDICATE THE POSITIVE AND NEGATIVE
 PRESSURES OF OPENINGS.
  
 9)PLANS DO NOT INDICATE HOW THE NEW STUCCO CORNICE IS
 TO BE APPLIED?WHERE IN RELATIONSHIP IS THE PROPERTY
 LINE?
  
 10) PLEASE PROVIDE INFORMATION ON THE FLEXIBLE JOINT OF
 THE NEW TENANT SEPERATION WALL AT THE ROOFLINE?
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2009-07-23 Cont ID  
Sent By dpalmer Date 2009-07-23 Time 13:36 Rev Time 0.00
Received By dpalmer Date 2009-07-23 Time 13:36 Sent To PC
Notes
2009-07-23 13:37:06 
 ** PROVISO **
  
 ** BEFORE INSPECTIONS. ANY INSTALLATION OF NEW FIXTURES
 ON PLANS IS AT THE RISK OF CONTRACTOR TO INSTALL IF
 FIXTURES ARE OVER ALLOWANCES.
  
 1) NOTE: AS REVISIONS HAVE BEEN SUBMITTED REVISING
 LIGHTING FIXTURES, PLEASE KNOW THAT THE PREVIOUS
 ATTACHED LIGHTING PERFORMANCE CALCULATIONS WOULD BE
 REQUIRED TO BE UPDATED.
 AN EXAMPLE IS: THE PLANS SIMPLY STATE * RECESSED
 LIGHTS*, HOWEVER RECESSED LIGHTING FIXTURES COULD BE
 25W RATED, 50W RATED OR AS MUCH AS 1500W RATED. THE
 CALCULATIONS MY NOT USE A BULB WATTAGE OR RATING IT
 MUST BE BASED ON THE RATED FIXTURE. PLEASE SEE
 13-415.2.ABC.1.1, .1.2 UNDER THE 2004 FBC W/2006
 REVISIONS.
 PLEASE CALL TO GO OVER.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-01-11 Cont ID  
Sent By dpalmer Date 2008-01-11 Time 15:22 Rev Time 0.00
Received By dpalmer Date 2008-01-11 Time 15:22 Sent To  
Notes
2008-01-11 15:23:02LIGHTING CALCULATIONS ATTACHED TO E SHEET.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-12-24 Cont ID  
Sent By dpalmer Date 2007-12-24 Time 09:19 Rev Time 0.00
Received By dpalmer Date 2007-12-23 Time 19:32 Sent To PC
Notes
2007-12-24 09:28:49** DENIED4TH REVIEW **
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OFF ADDRESSING.
  
 ** PLEASE SEE THERE ARE NOW CHANGES ONCE AGAIN TO THE
 RISER WHICH WAS NEW ON PREVIOUS REVIEW WHICH HAS NOW
 GENERATED NEW COMMENTS.
  
 1) NOTE:THIS IS THE SAME COMMENT FROM PREVIOUS
 REVIEW. PLEASE SEE THERE ARE SEVERAL DEVICES/FIXTURES
 WITH NO CIRCUITING SHOWN.
 **PREVIOUS NOTE **
 PLEASE COMPLETE CIRCUITING FOR ALL NEW
 DEVICES/CIRCUITS BEING INSTALLED.
 PLEASE CORRELATE WITH A PANEL SCHEDULE TO BE SUBMITTED.
 PLEASE INDICATE THE MINIMUM CONDUCTOR SIZES, OVER
 CURRENT PROTECTION FOR NEW CIRCUITS AND PANEL. PLEASE
 BE SURE TO SEE 700.12F FOR CIRCUITING OF EMERGENCY AND
 EXIT LIGHT FIXTURES. (MUST BE CIRCUITED TO THE LOCAL
 LIGHTING BRANCH CIRCUIT IN AREA OF FIXTURE)
 240.4, 310.16, 408.4
 FBC 106.3.5.1.2
  
 2) NOTE: PLEASE SEE RISER HAS NOW BEEN CHANGED ONCE
 AGAIN TO ADDRESS PREVIOUS COMMENTS HOWEVER NEW COMMENT
 AND EXISTING COMMENT NEEDS TO BE ADDRESSED.
 RISER SHOWS AN EXISTING 200AMP METER MAIN COMBO, ALONG
 WITH A NEW 200AMP MDP. (IS NOT THE METER/MAIN PANEL THE
 MDP?)
 THE MDP SCHEDULE SHOWS A 200AMP BREAKER TO THE EXISTING
 PANEL *A* YET THIS SAME MDP SHOWS FEED-THRU LUGS?
 PLEASE CLARIFY.
 PLEASE SEE THE NEW MDP SCHEDULE NOW HAS A NEW 60AMP
 BREAKER FEEDING NEW PANEL *B* HOWEVER THE LOAD ON PANEL
 *B* IS SHOWING EXCEEDING THE RATING OF THE OVER CURRENT
 PROTECTION DEVICE. PLEASE ALSO VERIFY THE CONDUCTORS
 WHICH ARE SHOWN AS #2 INTO A 60AMP BREAKER.
 PLEASE SEE 110.3, 90.7, 240.4, 310.16, ETC
  
 3) NOTE: THIS COMMENT WAS FROM PREVIOUS REVIEW AND THE
 ONLY ITEM ADDED TO PLANS WAS A NOTE WHICH SAYS FOR
 LIGHTING TO MEET THE MAXIMUM LEVELS PER THE TABLE *C*.
 PLEASE KNOW THAT STATING THE CODE SECTION IN LIEU OF
 THE MINIMUM REQUIRED FOR CODE COMPLIANCE IN DESIGN MAY
 NOT BE USED.
 ** PREVIOUS NOTE**
 PLEASE KNOW AS PLANS APPEAR TO SHOW NEW LIGHTING BEING
 INSTALLED PLEASE PROVIDE LIGHTING POWER DENSITIES PER
 13-415.2
 ( ONLY FOR NEW).
  
  
  
 ** AS MENTIONED ON PREVIOUS REVIEW. PLEASE CALL TO GO
 OVER COMMENTS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
2007-12-23 19:32:472007-12-23 19:32:47
 IN ELEC FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-11-26 Cont ID  
Sent By dpalmer Date 2007-11-26 Time 14:09 Rev Time 0.00
Received By dpalmer Date 2007-11-26 Time 14:09 Sent To  
Notes
2007-11-26 14:10:08** DENIED 3RD REVIEW **
  
 ** THIS IS THE FIRST REVIEW OF ELECTRICAL PLANS ONLY
 NOW BEING SUBMITTED FOR REVIEW.
 THERE ARE NEW COMMENTS AS SOME INFORMATION NOW SHOWN ON
 PLANS FOR SCOPE OF WORK WAS NOT ON PREVIOUS PLANS.
  
 1) NOTE: PLEASE COMPLETE CIRCUITING FOR ALL NEW
 DEVICES/CIRCUITS BEING INSTALLED.
 PLEASE CORRELATE WITH A PANEL SCHEDULE TO BE SUBMITTED.
 PLEASE INDICATE THE MINIMUM CONDUCTOR SIZES, OVER
 CURRENT PROTECTION FOR NEW CIRCUITS AND PANEL. PLEASE
 BE SURE TO SEE 700.12F FOR CIRCUITING OF EMERGENCY AND
 EXIT LIGHT FIXTURES. (MUST BE CIRCUITED TO THE LOCAL
 LIGHTING BRANCH CIRCUIT IN AREA OF FIXTURE)
 240.4, 310.16, 408.4
 FBC 106.3.5.1.2
  
 2) NOTE: PLEASE SEE THE SIGN CIRCUIT AT DOOR LOCATION
 IS SHOWN AT 1200VA , HOWEVER THE LOAD CALCULATIONS ON
 PANEL *B* SHOW 2000VA.
 PLEASE ALSO KNOW 2000VA IS TOO HIGH FOR LOAD ON A
 SINGLE CIRCUIT.
 PLEASE KNOW THAT TWO SIGN CIRCUIT LOCATIONS REQUIRE TWO
 CIRCUITS.
 600.5, 220.
  
 3) NOTE: PLEASE SEE THERE IS NOW A NEW SUB-PANEL BEING
 FED FROM WHAT IS BEING SHOWN AS AN EXISTING 200AMP MCB
 METER MAIN COMBO WITH FEED-THRU LUGS.
 PLEASE SEE THE NEW SUB PANEL IS ONLY SHOWN RATED FOR
 125AMPS ALONG WITH THE CONDUCTORS.
 PLEASE ADJUST.
  
 4) NOTE: PLEASE KNOW AS PLANS APPEAR TO SHOW NEW
 LIGHTING BEING INSTALLED PLEASE PROVIDE LIGHTING POWER
 DENSITIES PER 13-415.2
 ( ONLY FOR NEW).
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-09-26 Cont ID  
Sent By dpalmer Date 2007-09-26 Time 13:11 Rev Time 0.00
Received By dpalmer Date 2007-09-26 Time 11:14 Sent To  
Notes
2007-09-26 13:11:33** DENIED**
  
 1) NOTE: PLEASE SEE COMMENTS FROM PREVIOUS REVIEW.
 COMMENTS 1, 2 AND 3.
 PLEASE KNOW THAT NO ELECTRICAL FOR PREVIOUS COMMENTS
 COULD BE LOCATED ON PLANS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-18 Cont ID  
Sent By dpalmer Date 2007-03-18 Time 08:46 Rev Time 0.00
Received By dpalmer Date 2007-03-18 Time 08:41 Sent To  
Notes
2007-03-18 08:46:50** UNSAT **
  
 1) NOTE: PLEASE PROVIDE THE NEW SHOW WINDOW RECEPTACLES
 ABOVE NEW WINDOW AREAS.
 PLEASE SHOW NEW OR EXISTING AT THE EXISTING WINDOWS
 ALSO.
 210.62.
 PLEASE INDICATE THE LOAD AND REQUIRED DEDICATED
 CIRCUITING PER 220.43A.
  
 2) NOTE: PLEASE INDICATE NEW OR EXISTING SIGN CIRCUIT
 PER 600.5.(1200VA MIN) IF NEW.
  
 3) NOTE: PLEASE BE SURE THE FOLLOWING CODES WHICH THIS
 PROJECT IS UNDER SHALL BE STATED ON THE PLANS.
 PLEASE KNOW THERE MAY BE OTHER CODES WHICH MAY BE
 MENTIONED BY OTHER TRADES.
 FBC 2004 W/2006 REVISIONS
 2005 NFPA-70
 FBC ADMIN SECTION 106.1.2, 110.1.2
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS/LAYOUT.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-11-29 Cont ID  
Sent By mwennerg Date 2007-11-29 Time 15:52 Rev Time 0.00
Received By mwennerg Date 2007-11-29 Time 15:52 Sent To  
Notes
2007-11-29 15:53:13FIRE EXTINGUISHERS SHALL BE 2A-10B,C RATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-10-23 Cont ID  
Sent By mwennerg Date 2007-10-23 Time 11:07 Rev Time 0.00
Received By mwennerg Date 2007-10-23 Time 11:07 Sent To  
Notes
2007-10-23 11:08:05***DENIED***
  
 COMMENTS WERE TAKEN DIRECTLY FROM FIRST FIRE PLAN
 REVIEW:
  
 1) IN ADDITION TO APPLICABLE BUILDING CODES, WORK TO
 COMPLY WITH NFPA 101, 2003 EDITION.
  
 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 3) PLEASE ILLUSTRATE EXIT SIGNS AND EMERGENCY LIGHTING
 EXISTING OR NEW.
  
 4) 2A-10-B,C RATED FIRE EXTINGUISHERS REQUIRED IF NOT
 ALREADY PROVIDED.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-03-30 Cont ID  
Sent By mwennerg Date 2007-03-30 Time 13:19 Rev Time 0.00
Received By mwennerg Date 2007-03-30 Time 13:19 Sent To  
Notes
2007-03-30 13:23:27***DENIED***
  
 1) IN ADDITION TO APPLICABLE BUILDING CODES, WORK TO
 COMPLY WITH NFPA 101, 2003 EDITION.
  
 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 3) PLEASE ILLUSTRATE EXIT SIGNS AND EMERGENCY LIGHTING
 EXISTING OR NEW.
  
 4) 2A-10-B,C RATED FIRE EXTINGUISHERS REQUIRED IF NOT
 ALREADY PROVIDED.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 7 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jwitmer Date 2009-06-25 Time 10:54 Sent To  
Notes
2009-06-25 10:54:53INCOMINGTO C45

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-04-17 Cont ID  
Sent By rregueir Date 2008-04-17 Time 09:44 Rev Time 0.00
Received By rregueir Date 2008-04-16 Time 09:43 Sent To B
Notes
2008-04-17 09:44:18ROUTED TO JIM WITMER

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-01-10 Cont ID  
Sent By spalmer Date 2008-01-10 Time 09:24 Rev Time 0.00
Received By spalmer Date 2008-01-10 Time 09:24 Sent To  
Notes
2008-01-10 09:25:31TO COMM BOARD # 22

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-12-19 Cont ID  
Sent By adarroug Date 2007-12-19 Time 14:44 Rev Time 0.00
Received By adarroug Date 2007-12-19 Time 14:44 Sent To  
Notes
2007-12-19 14:54:13TO "COMM" BD#33

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-11-07 Cont ID  
Sent By adarroug Date 2007-11-07 Time 14:00 Rev Time 0.00
Received By adarroug Date 2007-11-07 Time 14:00 Sent To  
Notes
2007-11-20 16:28:47TO "COMM" BD#26
2007-11-07 14:00:44WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-18 Cont ID  
Sent By adarroug Date 2007-09-18 Time 16:51 Rev Time 0.00
Received By adarroug Date 2007-09-18 Time 16:51 Sent To  
Notes
2007-09-26 13:24:23MOVED TO COMM BOARD SPACE #58. NOT A BOB BOARD PROJECT.
 DVP, RB.
2007-09-25 16:00:50TO "BOB"#2
2007-09-18 16:52:10WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-30 Cont ID  
Sent By mwennerg Date 2007-03-30 Time 13:26 Rev Time 0.00
Received By mwennerg Date 2007-02-27 Time 11:09 Sent To  
Notes
2007-03-02 09:53:01TO "COMM" BD#53
2007-02-27 11:09:29WAITING FOR "COMM" BD

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-02-04 Cont ID  
Sent By kstevens Date 2008-02-04 Time 16:51 Rev Time 0.00
Received By kstevens Date 2008-02-04 Time 16:51 Sent To  
Notes
2008-02-04 16:52:43PASSED/PROVISO--VENT OR AAV REQUIRED FOR THE
 DRINKING FOUNTAIN. SECTION 901.2.1.

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-21 Cont ID  
Sent By kstevens Date 2007-12-21 Time 08:14 Rev Time 0.00
Received By kstevens Date 2007-12-20 Time 18:54 Sent To  
Notes
2007-12-21 08:29:17DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. A DRINKING FOUNTAIN IS REQUIRED PER TABLE 403.1.
 PLEASE SHOW THE LOCATION AND SUBMIT A DETAIL SHOWING
 COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS AS
 WELL AS 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
  
 2. SHT A-3 INDICATES NEW PARAPETS. THIS WILL ADD TO THE
 SQUARE FOOTAGE TO BE DRAINED BY THE ROOF DRAINS. AS
 SUCH A ROOF PLAN SHALL BE SUBMITTED SHOWING ALL PRIMARY
 AND SECONDARY ROOF DRAINS OR EMERGENCY OVERFLOW
 SCUPPERS. SHOW THE LOCATION OF ALL ROOF DRAINS,
 EMERGENCY OVERFLOW SCUPPERS OR SECONDARY ROOF DRAINS.
 INDICATE THE SIZE OF THE ROOF DRAINS, SECONDARY ROOF
 DRAINS OR EMERGENCY OVERFLOW SCUPPERS. PLEASE SUBMIT
 CALCULATIONS FOR THE PRIMARY AND SECONDARY ROOF DRAINS
 OR EMERGENCY OVERFLOW SCUPPERS. INDICATE THE SQUARE
 FOOTAGE OF EACH AREA BEING DRAINED ALONG WITH 1/2 THE
 AREA OF ALL VERTICAL WALLS INCLUDING PARAPETS ADDED TO
 THE ROOF AREAS. SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS & TABLES.
  
 3. SHT P-1 PLUMBING NOTES #9 AIR CHAMBERS ARE NOT
 APPROVED. DELETE FROM REFERENCE. SECTION 604.9.
  
 4. SHT P-1 SANITARY RISER DIAGRAM INDICATES A DRY
 HORIZONTAL VENT PAST THE WATER CLOSET. THIS IS NOT
 APPROVED PER SECTIONS 905.3 & 905.4.--INDICATE
 WHERE THE SANITARY PIPING FOR THE NEW TOILET ROOM
 CONNECTS TO THE BUILDING DRAIN. SECTION 106.1.2.
  
 5. SUBMIT A WATER ISOMETRIC RISER DIAGRAM SHOWING ALL
 PIPE SIZES, VALVES ETC. INDICATE WHERE THE WATER PIPING
 CONNECTS TO THE WATER DISTRIBUTION SYSTEM IN THE
 BUILDING. SECTION 106.3.5.1.3.
  
 6. SHT P-1 SHOW COMPLIANCE FOR THE FOLLOWING:
 ___W/C:
 A. 11-4.16.5 FLUSH CONTROLS
 ___LAV:
 A. 11-4.19.4 EXPOSED PIPES & SURFACES
 B. 11-4.19.5 FAUCETS
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2007-12-02 Cont ID  
Sent By mflis Date 2007-12-02 Time 14:45 Rev Time 0.00
Received By mflis Date 2007-12-02 Time 14:45 Sent To  
Notes
2007-12-02 14:45:58ZONING REVIEW: PASSED
  
 * INTERIOR AND EXTERIOR RENOVATIONS TO EXISTING
 BUILDING
 * ZONING BP-5
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 2 Status P Date 2007-10-03 Cont ID  
Sent By mflis Date 2007-10-03 Time 11:07 Rev Time 0.00
Received By mflis Date 2007-10-03 Time 11:07 Sent To  
Notes
2007-10-03 11:08:00ZONING REVIEW: PASSED
  
 * INTERIOR RENOVATION AND EXTERIOR IMPROVEMENTS TO
 EXISTING STRUCTURE
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 1 Status P Date 2007-03-06 Cont ID  
Sent By mflis Date 2007-03-06 Time 14:21 Rev Time 0.00
Received By mflis Date 2007-03-06 Time 14:21 Sent To  
Notes
2007-03-06 14:22:45ZONING REVIEW: PASSED
  
 - REMODEL AND RENOVATION COMMERCIAL SPACE
  
 MATT FLIS - 822-1445