| 2007-03-04 14:24:16 | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE KNOW THAT PERMIT APPLICATION HAS BEEN |
| | SUBMITTED AFTER DECEMBER 8TH, 2006 WHICH PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGE SIN THE FBC WHICH WILL |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE ALSO SEE ELECTRICAL CHANGES UNDER THE 2005 |
| | INCLUDING ANY SECTIONS OF CODES WHICH ARE REFLECTED ON |
| | PLANS FROM THE PREVIOUS 2002 NEC. |
| | PLEASE LIST THE FOLLOWING FOR THIS REVIEWER AT A |
| | MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | 2) NOTE:PLEASE SUBMIT ENERGY/PERFORMANCE CALCULATIONS |
| | FOR NEW LIGHTING. |
| | PLEASE KNOW THAT ALL NEW SHALL COMPLY WITH THE CHAPTER |
| | 13 REQUIREMENTS. |
| | PLEASE BE SURE ONCE THE METHOD OF CONTROLS IS FIGURED |
| | FOR THE PLANS TO BE SURE TO CORRELATE CONTROL METHODS |
| | ON THE ENERGY CALCULATIONS/PERFORMANCE CALCULATIONS. |
| | PLEASE SEE FBC 2004 W/ 2006 REVISIONS. 13-103.1.1.1, |
| | 13-415.1.ABC.1.1, .1.2, .1.3, 13-415.1.AB.1.1, |
| | 13-415.2. |
| | |
| | 3) NOTE: PLEASE SEE THAT PLANS DO NOT INDICATE ANY |
| | METHODS FOR THE REQUIRED AUTOMATED CONTROLS PER FBC |
| | 2004 W/2006 REVISIONS. ANY NEW AREAS, LIGHTING AND |
| | CONTROLS. |
| | THE SCOPE OF WORK AS NOTED AND SHOWN ON PLANS WILL |
| | REQUIRE CHAPTER 13 COMPLIANCE FOR CONTROLS AND |
| | LIGHTING. |
| | 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | |
| | 4) NOTE: PLEASE PROVIDE LOCATIONS FOR ELECTRICAL PANELS |
| | WHETHER NEW OR EXISTING ALONG WITH TRANSFORMER |
| | LOCATION. |
| | PLEASE KNOW AT THIS TIME ONE PANEL IS BEING NOTED AS |
| | BEING PLACED IN A STORAGE ROOM WHICH IS NOT PERMITTED. |
| | PLEASE SEE THE LOCATION AND MINIMUM CLEARANCES FOR THE |
| | ELECTRICAL PANEL(S) NEED TO MEET 110.26. |
| | PLEASE ALSO SEE 408.7 AND 240.24 FOR LOCATION OF EASILY |
| | IGNITABLE MATERIALS AND CLOSE PROXIMITY OF COMBUSTIBLES |
| | WITH OVER CURRENT PROTECTION DEVICES. |
| | PLEASE ADJUST PLANS. |
| | PLEASE SEE 450.9, 450.13, 450.21 FOR TRANSFORMER |
| | LOCATIONS. |
| | |
| | 5) NOTE:PLEASE SEE PANELS SEEMS TO BE NOTED AS |
| | EXISTING; HOWEVER THE RISER DOES NOT SEEM TO SHOW WHAT |
| | IS EXISTING OR WHAT IS NEW. |
| | PLEASE CLARIFY. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 6) NOTE: PLEASE KNOW WHETHER NEW OR EXISTING THE PANEL |
| | ON THE SECONDARY SIDE OF THE TRANSFORMER WILL REQUIRE A |
| | MCB IF NOT EXISTING. |
| | PLEASE ALSO SEE THE TAP CONDUCTOR RULES AS STATED IN |
| | 240.21C |
| | PLEASE ALSO SEE 408.16 |
| | |
| | 7) NOTE: PLEASE SEE PLANS MENTIONS TO REMOVE ALL HORNS |
| | AND STROBES, PLEASE BE SURE TO NOTE ON PLANS THAT ANY |
| | NEW DEVICES BEING RE-INSTALLED SHALL MEET FBC |
| | 11-4.28.1,.2 AND .3(4). PLEASE STATE LEVELS FOR THESE |
| | DEVICES FOR ADA COMPLIANCE. |
| | PLEASE KNOW ANY OLD DEVICES WHICH MAY NOT MEET CODE |
| | WILL NOT BE PERMITTED TO BE RE-INSTALLED. NEW DEVICES |
| | WILL BE REQUIRED. |
| | |
| | 8) NOTE: PLEASE CLARIFY THE RECEPTACLE DEVICES IN |
| | KITCHEN/FOOD AREAS MEETING 210.8B3 |
| | |
| | 9) NOTE: PLEASE CLARIFY THE NOTE ON PANEL *PB* WHICH |
| | MENTIONS 2-POLE 40AMP BREAKER ON #10 CONDUCTORS ALONG |
| | WITH 6 ADDITIONAL #10 CONDUCTORS IN ONE SINGLE 1/2 INCH |
| | CONDUIT. PLEASE SEE TABLES IN CHAPTER 9 AS PIPE FILL IS |
| | EXCEEDED. (C.1) |
| | |
| | 10) NOTE: PLEASE KNOW IF THE SCOPE OF ELECTRICAL WORK |
| | IS THE INSTALLATION OF THE SERVICE EQUIPMENT AS SHOWN |
| | ON RISER AND ALL SERVICE EQUIPMENT DOES NOT EXIST AT |
| | PRESENT AND IS NEW, THEN THE PLANS WILL BE REQUIRED TO |
| | BE SIGNED, DATED AND SEALED BY A PE. FS |
| | 471.003(2)(H)(2A) |
| | |
| | 11) NOTE: PLEASE SHOW GROUNDING ATTACHMENT FOR THE |
| | TRANSFORMER IF NEW. |
| | 250.20, 250.30, 250.66 |
| | |
| | 12) NOTE: PLEASE NOTE IF EM/EXT LTS ARE WIRED PER |
| | 700.12E (LOCAL LIGHTING BRANCH CIRCUIT). |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |