Review Stop AD ADDRESSING
Rev No 2 Status F Date 2007-06-26 Cont ID  
Sent By lursu Date 2007-06-26 Time 10:23 Rev Time 0.00
Received By lursu Date 2007-06-26 Time 10:23 Sent To  
Notes
2007-06-26 10:36:23THE ADDRESS USED AS 255 EVERNIA ST WITH THE UNITMU4
 IS NOT CITY STANDARD .THIS UNIT HAS THE MAIN ENTRANCE
 FROM THE STREET AND IT IS NECESESSARY TO RECEIVE A
 UNIQUE SITE ADDRESS .PLEASE CONTACT ME FOR A NEW
 ADDRESS AND ALSO PLEASE SUPPLY THE LOCATION MAP FOR
 THIS UNIT.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 1 Status P Date 2007-03-07 Cont ID  
Sent By mjacobs Date 2007-03-07 Time 12:04 Rev Time 0.00
Received By lursu Date 2007-03-07 Time 12:04 Sent To  
Notes
2007-03-07 12:04:57SITE ADDRESS IS CORRECT .
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]
2007-03-04 08:27:23NEEDS

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status F Date 2008-03-12 Cont ID  
Sent By mjacobs Date 2008-03-12 Time 12:38 Rev Time 0.00
Received By mjacobs Date 2008-03-12 Time 11:07 Sent To PC
Notes
2008-03-12 12:38:04BUILDING PLAN REVIEW
 PERMIT: 07020610
 ADD: 255 EVERNIA ST MU-4
 CONT: DC CONSTRUCTION
 TEL: (561)988-8505
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: REVISION
 ACTION: DENIED
  
 1)THE LETTER SUBMITTED FROM THE ENGINEER IS FOR
 DRILLING SEVERAL TWO INCH DIAMETER HOLES INTO THE STEEL
 BEAM. THE LETTER NEEDS TO BE SPECIFIC WITH THE SIZE,
 LOCATION AND NUMBER OF HOLES TO BE DRILLED INTO THE
 STEEL. THE PLANS INDICATE THE DIAMETER OF THE HOLES TO
 BE SIX INCHES WHERE AS, THE LETTER STATES TWO INCH
 DIAMETER HOLES; WHICH IS IT? THE INFORMATION IN THE
 LETTER NEEDS TO CORRELATE WITH THE PLANS. SUBMIT
 ENGINEERED DRAWINGS OF THE STEEL BEAN SHOWING THE SIZE
 AND LOCATION OF THE PROPOSED HOLES. THE SEAL AND
 SIGNATURE ON THE DRAWINGS SHALL BE IN CONFORMANCE WITH
 FAC 61G15-23.002 AND 61G1-16.004
  
 NOTE: THE SHOP DRAWINGS ON FILE FOR THE STRUCTURAL
 BEAMS AND COLUMN WERE DESIGN WITHOUT ANY HOLES
 THEREFORE, ENGINEERED DRAWINGS IS REQUIRED SHOWING THE
 MODIFICATIONS TO THE W10 BEAMS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 FAX (561)805-6676
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2008-02-19 Cont ID  
Sent By mjacobs Date 2008-02-19 Time 07:50 Rev Time 0.00
Received By mjacobs Date 2008-02-15 Time 14:22 Sent To PC
Notes
2008-02-19 07:50:45BUILDING PLAN REVIEW
 PERMIT: 07020610
 ADD: 255 EVERNIA ST. MU-4
 CONT: DC CONSTRUCTION ASSOC. INC
 TEL: (561)988-8505
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: REVISION 2-19-08
 ACTION: DENIED
  
 1)A STRUCTURAL ENGINEER WILL HAVE TO APPROVED AND
 DESIGN ANY ALTERATION TO THE STRUCTURAL STEEL JOIST,
 BEAMS OR GIRDER. SUBMIT ENGINEERED DRAWINGS FOR THE
 STRUCTURAL CHANGES. THE DRAWINGS SHALL BE IN
 CONFORMANCE WITH FAC 61G15-23.002 AND 61G1-16.004. THE
 HOLES NEED THE APPROVAL OF A STRUCTURAL ENGINEER.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 PHONE (561)805-6726
 FAX (561)805-6676
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-11-05 Cont ID  
Sent By   Date 2007-11-05 Time   Rev Time 0.00
Received By mjacobs Date 2007-11-05 Time 11:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-11-05 Cont ID  
Sent By mjacobs Date 2007-11-05 Time 11:54 Rev Time 0.00
Received By mjacobs Date 2007-11-05 Time 11:06 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-10-03 Cont ID  
Sent By mjacobs Date 2007-10-03 Time 10:07 Rev Time 0.00
Received By mjacobs Date 2007-10-03 Time 07:44 Sent To PC
Notes
2007-10-03 10:07:23BUILDING PLAN REVIEW
 PERMIT: 07020610
 ADD: 255 EVERNIA STREET
 CONT: DC CONSTRUCTION ASSO.
 TEL: (561)988-8505
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 4TH
 ACTION: DENIED
  
 1)OK
  
 2)FL.S.S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6) THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)OK,
 4)OK
 5)OK
 6)OK
 7)OK,
  
 **NO RESPONSE**
 8)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 9)OK
  
 10) OK
  
 11)OK
  
 12)OK
  
 NEW*************
  
 13)OK
  
 14)OK
  
 15)OK
  
 16)OK
  
 17)OK
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-09-17 Cont ID  
Sent By mjacobs Date 2007-09-17 Time 12:03 Rev Time 0.00
Received By mjacobs Date 2007-09-15 Time 13:40 Sent To  
Notes
2007-09-17 12:03:44BUILDING PLAN REVIEW
 PERMIT: 07020610
 ADD: 255 EVERNIA STREET
 CONT: DC CONSTRUCTION ASSO.
 TEL: (561)988-8505
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 3RD
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGE AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)FL.S.S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6) THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)OK,
 4)OK
 5)OK
 6)OK
 7)OK, HOWEVER, OPENING GUARDS SHALL HAVE BALUSTERS OR
 ORNAMENTAL PATTERNS SUCH THAT A 4 INCH DIAMETER SPHERE
 CANNOT PASS THROUGH. FBC 1012.3
  
 **NO RESPONSE**
 8)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 9)GUARDRAILS SHALL BE IN CONFORMANCE WITH FBC
 SEC.1607.7 AND FBC. SEC. 1012. INDICATE HOW THE
 GUARDRAIL WILL BE ATTATCHED,
 **NO RESPONSE**
  
 10) SUBMIT THE SHOP DRAWINGS FOR THE STAIRS FOR REVIEW
 AS NOTED ON THE DRAWINGS.
 **NOTED** HOWEVER, THE SHOP DRAWINGS SHALL HAVE AN
 APPROVAL STAMP BY THE ENGINEER OR ARCHITECT OR RECORD.
 SEE SHEET S-3 SUBMITTAL NOTE #1.
  
 11)PROVIDE A STRUCTURAL STEEL SCHEDULE FOR THE STEEL
 COLUMNS AND BEAMS INDICATING ALL DIMENTIONS. SEE SHEET
 S-2 IS MISSING THE DIMENTIONS OF THE STRUCTURAL COLUMNS
 AND BEAMS. ALSO INDICATE THE SIZE OF THE HOLES, THE
 TYPE OF BOLTS. SHOW THE DESIGN BEARING LOAD OF THE
 BEAMS AND COLUMNS.
  
 12)OK
  
 NEW*************
  
 13)OK
  
 14)OK
  
 15)OK
  
 16)NOTE:WALL WITHIN 2FEET OF URINALS AND WATER
 CLOSETS SHALL HAVE A SMOOTH, HARD, NONABOORBENT SURFACE
 TO A HEIGHT OF 4 FEET ABOVE THE FLOOR. EPOXY PAINT ON
 DRYWALL IS NOT CONSIDERED A HARD SURFACE. FBC 1210.2
  
 17)INDICATE WHICH TABLE WAS USED TO CALCULATE THE
 OCCUPANT LOAD OF THE BUILDING. SEE TABLE 1004.1.2.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-06-29 Cont ID  
Sent By mjacobs Date 2007-06-29 Time 11:07 Rev Time 0.00
Received By mjacobs Date 2007-06-29 Time 06:54 Sent To  
Notes
2007-06-29 11:07:23BUILDING PLAN REVIEW
 PERMIT: 07020610
 ADD: 255 EVERNIA STREET
 CONT: DC CONSTRUCTION ASSO.
 TEL: (561)988-8505
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)OK, HOWEVER,THERE WERE SOME ELECTRICAL ISSUES.
  
 4)OK
  
 5)OK
  
 6)OK
  
 7)1009.11.5 HANDRAIL EXTENSIONS.
 HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING
 SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN
 ADJACENT STAIR FLIGHT. WHERE HANDRAILS ARE NOT
 CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL EXTEND
 HORIZONTALLY AT LEAST 12 INCHES (305 MM) BEYOND THE TOP
 RISER AND CONTINUE TO SLOPE FOR THE DEPTH OF ONE TREAD
 BEYOND THE BOTTOM RISER.
  
  
 8)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 9)GUARDRAILS SHALL BE IN CONFORMANCE WITH FBC
 SEC.1607.7 AND FBC. SEC. 1012. INDICATE HOW THE
 GUARDRAIL WILL BE ATTATCHED,
  
 10) SUBMIT THE SHOP DRAWINGS FOR THE STAIRS FOR REVIEW
 AS NOTED ON THE DRAWINGS.
  
 11)PROVIDE A STRUCTURAL STEEL SCHEDULE FOR THE STEEL
 COLUMNS AND BEAMS INDICATING ALL DIMENTIONS. SEE SHEET
 S-2 IS MISSING THE DIMENTIONS OF THE STRUCTURAL COLUMNS
 AND BEAMS. ALSO INDICATE THE SIZE OF THE HOLES, THE
 TYPE OF BOLTS. SHOW THE DESIGN BEARING LOAD OF THE
 BEAMS AND COLUMNS.
  
 12)OK
  
 NEW*************
  
 13)1603.1.1 FLOOR LIVE LOAD . MEZZANINE
 THE UNIFORMLY DISTRIBUTED, CONCENTRATED AND IMPACT
 FLOOR LIVE LOAD USED IN THE DESIGN SHALL BE INDICATED
 FOR FLOOR AREAS. LIVE LOAD REDUCTION OF THE UNIFORMLY
 DISTRIBUTED FLOOR LIVE LOADS, IF USED IN THE DESIGN,
 SHALL BE INDICATED.
  
 14)1603.4
 CONSTRUCTION DOCUMENTS FOR OTHER THAN RESIDENTIAL
 BUILDINGS FILED WITH THE BUILDING OFFICIAL WITH
 APPLICATIONS FOR PERMITS SHALL SHOW ON EACH DRAWING THE
 LIVE LOADS PER SQUARE FOOT (M 2 ) OF AREA COVERED FOR
 WHICH THE BUILDING IS DESIGNED. OCCUPANCY PERMITS FOR
 BUILDINGS HEREAFTER ERECTED SHALL NOT BE ISSUED UNTIL
 THE FLOOR LOAD SIGNS, REQUIRED BY SECTION 1603.3 , HAVE
 BEEN INSTALLED. FOR STAIRS LOAD SEE FBC 1607.1
  
 15)NOTE: THE DOORS IN FRONT OF THE SINK SHALL BE
 REMOVED TO MEET THE REQUIREMENTS OF FBC.SEC.11-4.24
  
  
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-06 Cont ID  
Sent By mjacobs Date 2007-03-06 Time 10:31 Rev Time 0.00
Received By mjacobs Date 2007-03-06 Time 07:45 Sent To  
Notes
2007-03-06 10:32:46BUILDING PLAN REVIEW
 PERMIT: 07020610
 ADD: 255 EVERNIA STREET
 CONT: DC CONSTRUCTION ASSO.
 TEL: (561)988-8505
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 4)2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 5)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 -------------------------------------
 ) NUMBER OF UNITS
 ) NUMBER OF FLOORS
 ) NUMBER OF ROOMS
 ) SQ. FT. FOOTPRINT
 ) SQ. FT. UNDER ROOF (TOTAL)
 ) OCCUPANT LOAD
 ) FLOOD ZONE
 ) FLOOD ELEVATION
 )L.O.M.R.
  
 6)110.4.3.SIGNS REQUIRED. IN EVERY
 BUILDING OR PART OF A BUILDING USED FOR
 STORAGE, INDUSTRIAL OR HAZARDOUS PUR-
 POSES, THE SAFE FLOOR LOADS, AS REVIEWED
 BY THE BUILDING OFFICIAL ON THE PLAN,
 SHALL BE MARKED ON PLATES OF APPROVED DE
 SIGN WHICH SHALL BE SUPPLIED & SECURELY
 AFFIXED BY THE OWNER OF THE BUILDING IN
 A CONSPICUOUS PLACE IN EACH STORY TO
 WHICH THEY RELATE. SUCH PLATES SHALL NOT
 BE REMOVEDOR DEFACED, & IF LOST,
 REMOVED THE OWNER OF THE BUILDING SHALL
 REPLACE THEM.
  
 7)1009.11.5 HANDRAIL EXTENSIONS.
 HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING
 SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN
 ADJACENT STAIR FLIGHT. WHERE HANDRAILS ARE NOT
 CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL EXTEND
 HORIZONTALLY AT LEAST 12 INCHES (305 MM) BEYOND THE TOP
 RISER AND CONTINUE TO SLOPE FOR THE DEPTH OF ONE TREAD
 BEYOND THE BOTTOM RISER.
  
  
 8)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 9)GUARDRAILS SHALL BE IN CONFORMANCE WITH FBC
 SEC.1607.7 AND FBC. SEC. 1012. INDICATE HOW THE
 GUARDRAIL WILL BE ATTATCHED,
  
 10) SUBMIT THE SHOP DRAWINGS FOR THE STAIRS FOR REVIEW
 AS NOTED ON THE DRAWINGS.
  
 11)PROVIDE A STRUCTURAL STEEL SCHEDULE FOR THE STEEL
 COLUMNS AND BEAMS INDICATING ALL DIMENTIONS. SEE SHEET
 S-2 IS MISSING THE DIMENTIONS OF THE STRUCTURAL COLUMNS
 AND BEAMS. ALSO INDICATE THE SIZE OF THE HOLES, THE
 TYPE OF BOLTS. SHOW THE DESIGN BEARING LOAD OF THE
 BEAMS AND COLUMNS.
  
 12)61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-10-08 Cont ID  
Sent By btrobaug Date 2008-10-08 Time 15:35 Rev Time 0.00
Received By btrobaug Date 2008-10-08 Time 15:13 Sent To PC
Notes
2008-10-08 15:36:30 
  
 REVISION (DELTA #3) TO CHANGE A/C SYSTEM, ADDED A
 MICROWAVE RECEPTACLE./WRT.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-10-01 Cont ID  
Sent By dpalmer Date 2007-10-01 Time 17:37 Rev Time 0.00
Received By dpalmer Date 2007-10-01 Time 15:06 Sent To  
Notes
2007-10-01 17:38:19 
  
 REDLINED CD LEVELS FOR STROBE DEVICES TO MEET FBC
 11-4.28.3(4)

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-09-08 Cont ID  
Sent By dpalmer Date 2007-09-08 Time 16:47 Rev Time 0.00
Received By dpalmer Date 2007-09-08 Time 15:40 Sent To  
Notes
2007-09-08 16:47:382007-09-08 16:47:38
  
 ** DENIED 3RD REVIEW **
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
 ** PLEASE SEE THE NOTES BELOW ARE THE SAME AS PREVIOUS
 REVIEW AS THE SAME PLANS WERE SUBMITTED BACK FOR
 REVIEW.
 A RESPONSE LETTER WAS SUBMITTED WHICH MENTIONS MANY OF
 THESE ITEMS WERE DONE HOWEVER AS THE SAME PLANS WERE
 SUBMITTED THIS IS NOT POSSIBLE.
  
 1) NOTE: RESPONSE TO NOTE #1 FROM PREVIOUS REVIEW
 MENTIONS TO SEE REVISED SHEET A-1, HOWEVER AS THE SAME
 PLANS WERE SUBMITTED THIS IS NOT POSSIBLE. NOTE
 REMAINS.
  
 2) NOTE: RESPONSE MENTIONS THE ENERGY CALCULATIONS WERE
 REVISED. THIS IS INDEED CORRECT HOWEVER PLEASE SEE THE
 ENERGY CALCULATIONS AS SUBMITTED STILL NEED TO
 COORDINATE ALL FIXTURE/LUMINARIES ON PLANS WITH THE
 INPUT DATA REPORT. THE SHEETS ARE SIGNED AND SEALED SO
 THE PART OF THE PREVIOUS NOTE #2 WHICH REQUESTS THE
 SHEETS TO BE SIGNED DATED AND SEALED DOES NOT APPLY.
 PLEASE BE SURE WHEN RESUBMITTED THESE THAT THE SAME IS
 DONE.
 13-415.1.A, 13-415.2
  
 3) NOTE: RESPONSE TO NOTE #3 MENTIONS THE CLOSET WAS
 CHANGED TO AN ELECTRICAL ROOM, BUT THIS WAS NOT DONE ON
 PLANS. NOTE REMAINS.
  
 4) NOTE: RESPONSE TO NOTE #4 OK. THE ADDRESS WAS
 CONFIRMED WITH THE ADDRESSING REVIEWER.
  
 5) NOTE: RESPONSE TO NOTE #5 MENTIONS NORMAL AND
 EMERGENCY LEVELS WERE SHOWN ON SHEET A-1 AND SHEET
 A-1.1 HOWEVER THIS WAS NOT DONE. ONLY LEVELS ON A-1 OF
 SOME KIND WERE SHOWN. NO PHOTO-METRICS WERE SHOWN ON
 A-1.1.
 NO REVISED ELECTRICAL SHEETS SO, THE NOTE REMAINS.
  
 6) NOTE: RESPONSE TO NOTE #6 MENTIONS TO SEE REVISED
 RISER AND THE BREAKER WAS REDUCED. PLEASE KNOW BASED ON
 THE RESPONSE LETTER WHICH MENTIONS 80AMP OVER CURRENT
 PROTECTION THIS WOULD STILL BE TOO HIGH WITH THE FEEDER
 SIZE AS SHOWN ON RISER.
 PLEASE ALSO SEE 450.3 AS THE OCP IS STILL TOO HIGH.
 (MAX 125%).
 THE GROUND DETAIL WAS NOT SUBMITTED. (MAY NOT QUOTE THE
 CODE)
 THE LOAD CALCULATIONS WERE NOT REVISED.
  
  
 7) NOTE: RESPONSE TO NOTE #7 MENTIONS EQUIPMENT IS
 INDICATED ON PLANS HOWEVER THIS WAS NOT DONE. RESPONSE
 ALSO MENTIONS TO SEE SHEET E-3 HOWEVER NOT SHEET E-3
 WAS SUBMITTED OR IN EITHER OF THE THREE SETS
 SUBMITTED.
  
 8) NOTE: RESPONSE TO NOTE #8 MENTIONS THIS WAS
 ADDRESSED IN A NOTE #1 ON E-1, HOWEVER NOTE #1 DOES NOT
 MENTION AND INDICATE ANY MINIMUM LEVELS FOR ADA
 DEVICES.
  
 9) NOTE: RESPONSE TO PREVIOUS NOTE #9 WAS *NOTED*.
 PLEASE KNOW AS THESE COMMENTS HAVE NOW BEEN REPEATED
 FOR THE SAME COMMENTS A FEE AS REQUIRED PER FS
 553.80(2)(B) HAS NOW BEEN ASSESSED.
 THIS FEE IS DUE BEFORE PLANS ARE RESUBMITTED FOR THE
 FOLLOWING REVIEW.
 PLEASE ALSO KNOW ONE COPY OF EACH SET OF ELECTRICAL
 PLANS AND ENERGY CALCULATIONS ARE NOW BEING RETAINED BY
 THIS OFFICE.
 THIS FEE OF $2700.00 IS DUE BEFORE PLANS MAY BE
 RESUBMITTED FOR THE NEXT REVIEW. IT IS RECOMMENDED THAT
 IF THERE ARE ANY QUESTIONS ON THE COMMENTS AS TYPED TO
 PLEASE CALL TO GO OVER NOTES. THIS WAS STATED ON BOTH
 OF THE PREVIOUS REVIEW COMMENTS.
 PLEASE SEE THE NOTES BELOW WHICH WERE TRANSFERRED FROM
 PREVIOUS REVIEW.
 AS NOTED ABOVE SOME OF THESE ITEMS ARE NOW OK, HOWEVER
 MOST STILL NEED ADDRESSING.
  
 ** AS STATED ON THE PREVIOUS REVIEW, IF THERE ARE
 COMMENTS OR QUESTIONS WHICH CAN BE GONE OVER ON THE
 PHONE, PLEASE CALL.
 THIS WOULD ALLEVIATE THE BACK AND FORTH ON PLANS ON ANY
 ITEMS NOT CLEAR AND PERHAPS NOT UNDERSTOOD OR NOT TYPED
 IN ANY MANOR.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
  
 ********** THESE NOTES FROM BELOW ARE EXACTLY AS STATED
 ON PREVIOUS REVIEW ***
  
 ** PLEASE SEE THERE ARE SOME COMMENTS FROM PREVIOUS
 REVIEW WHICH ARE IN NEED OF ADDRESSING ALONG WITH NEW
 COMMENTS BASED ON REVISIONS AND CHANGES TO THE PLANS.
 PLEASE SEE NEW COMMENTS ALSO BASED ON INFORMATION NOW
 SHOWN WHICH WAS NOT ON PREVIOUS PLANS.
  
  
  
 1) NOTE:PLEASE SEE THE ARCHITECTURAL COVER SHEET
 WHICH CONTAINS A 2005 NFPA-72, WHICH SHOULD BE 2002.
 THIS COULD BE REDLINED HOWEVER AS THIS SHEET WILL
 REQUIRE REVISIONS FOR OTHER COMMENTS THIS SHOULD BE
 ADJUSTED AT THIS TIME.
  
 2) NOTE: PLEASE SEE THIS NOTE REMAINS THE SAME FROM
 PREVIOUS REVIEW.
 PLEASE SEE THE ENERGY CALCULATIONS DO NOT CORRELATE
 WITH THE PLANS.
 PLEASE SEE THE INFORMATION ON THE INPUT DATA REPORT FOR
 THE TYPE OF LUMINARIES, THE NUMBER OF LUMINARIES, AND
 THE WATTAGE AS SHOWN ON LUMINARIES.
 PLEASE SEE THESE DO NOT CORRELATE AT THIS TIME. PLEASE
 SEE THE FIXTURE SCHEDULE NEEDS TO BE COMPLETED WITH
 FIXTURE INFORMATION. THESE CAN ALWAYS BE REVISED AT A
 LATER DATE.
 PLEASE SEE THE SIGNATURE, DATE AND RAISED SEAL IS
 REQUIRED ON CERTIFICATION SHEETS. 13-103.1.1.1 PLEASE
 SEE ONLY THE SIGNATURE AND DATE ARE PRESENT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE ENERGY CALCULATIONS DO NOT CORRELATE
 WITH THE PLANS. PLEASE SEE THE LIGHTING, WATTAGE,
 NUMBER OF FIXTURES ETC.
 PLEASE BE SURE THE FIXTURE LEGEND STATES THE TYPE OF
 FIXTURE SPECIFIED AND COORDINATE THIS WITH THE ENERGY
 CALCULATIONS.
 THESE DO NOT CORRELATE AT ALL AT THIS TIME.
 PLEASE SEE MAXIMUM LIGHTING POWER DENSITIES WHICH HAS
 NOT BEEN STATED ON PLANS, OR CORRELATE IN ENERGY
 CALCULATIONS.
 PLEASE BE SURE THESES CONTAIN A RAISED SEAL, DATE AND
 SIGNATURE OF THE DESIGNER OF RECORD ON SHEET(S) WHICH
 CONTAIN THE TITLE BLOCKS FOR THE DESIGNER OF RECORD.
 THE SHEET CONTAINS THE LOCATION OF THE PRINTED NAME FOR
 THE DESIGNER HOWEVER THIS SHEET WAS NOT SIGNED, DATED
 OR SEALED.
 PLEASE BE SURE ONCE THE METHOD OF CONTROLS IS FIGURED
 FOR THE PLANS TO BE SURE TO CORRELATE CONTROL METHODS
 ON THE ENERGY CALCULATIONS.
 PLEASE SEE FBC 2004 W/ 2006 REVISIONS. 13-103.1.1.1,
 13-415.1.ABC.1.1, .1.2, .1.3, 13-415.1.AB.1.1,
 13-415.2, 13-415.2.ABC.1.2 (3) FOR TRACK LIGHTING.
  
 3) NOTE: PLEASE SEE THE LOCATION OF THE ELECTRICAL
 PANEL IS NOT PERMITTED IN CLOSET.110.26, 408.7, 240.24
 ETC
 PLEASE SEE COMMENTS WITH RESPECT TO THE NEW RISER AS
 OTHER ELECTRICAL EQUIPMENT IS NOT SHOWN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE ELECTRICAL PLANS DO NOT INDICATE A
 SCALE IN WHICH PLANS ARE UNDER, HOWEVER IT IS BEING
 ASSUMED THAT THE SCALE IS THAT OF THE ARCHITECTURAL
 PLANS AT 3/16THS.
 PLEASE SEE THE LOCATION AND MINIMUM CLEARANCES FOR THE
 ELECTRICAL PANEL *A* DO NOT SEEM TO MEET 110.26. PLEASE
 ALSO SEE 408.7 AND 240.24 FOR LOCATION OF EASILY
 IGNITABLE MATERIALS AND CLOSE PROXIMITY OF COMBUSTIBLES
 WITH OVER CURRENT PROTECTION DEVICES.
 PLEASE ADJUST PLANS.
  
 4) NOTE:PLEASE KNOW THE SUITE/UNIT # MAY BE ADJUSTED
 BY THE ADDRESSING REVIEWER. ON SHEETS WHICH DO NOT
 REQUIRE REVISIONS THE ADDRESS FOR SUITE/UNIT NUMBER MAY
 BE CHANGED BY HAND.
 THIS COMMENT WILL REMAIN AS THE INFORMATION FOR THIS
 HAS BEEN FORWARDED TO ADDRESSING.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE THE ADDRESS ON THE PLANS FOR THE
 LOCATION OF THE SCOPE OF WORK. PLEASE ALSO KNOW THIS
 WILL BE SENT TO ADDRESSING FOR THE NEW SUITE NUMBER
 WHICH WILL BE ASSIGNED.
  
 5) NOTE: PLEASE SEE THE PHOTO-METRICS ON SHEET A-1 DOES
 NOT INDICATE THE COMPLIANCE AS PREVIOUSLY NOTED. PLEASE
 SHOW LEVELS UNDER NORMAL AND UNDER EMERGENCY. AS THE
 LIGHTING PLANS DO NOT INDICATE THE EMERGENCY LIGHT
 FIXTURES NEEDED FOR THIS EGRESS PATH IT DOES NOT SEEM
 THE MINIMUM LEVELS CAN BE MET BASED ON THE PLANS
 SUBMITTED.
 PLEASE SUBMIT THE COMPLETED INFORMATION FOR REVIEW.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE PROVIDE THE PHOTO-METRIC LEVELS FOR STAIRS PER
 NFPA-101 2003 7.8.1.3, 7.9.2.2.
  
 6) NOTE: PLEASE SEE THE PLANS NOW INCLUDE A NEW
 ELECTRICAL RISER WHICH CONTAINS THE FOLLOWING
 COMMENTS.
 A) PLEASE SEE THE OCP FOR THE TRANSFORMER IS SET TOO
 HIGH PER 450.3.
 B) PLEASE SEE THE CONDUCTOR SIZES ARE NOT SUFFICIENT
 SIZE FOR THE 100AMP OCP AS SHOWN ON MAIN DISCONNECT.
 PLEASE SEE 6A ABOVE AS THE OCP WILL BE
 CHANGING.240.4,310.16,ETC.
 C) PLEASE SEE INDICATE THE GROUNDING ATTACHMENT FOR
 TRANSFORMER. 250.50,250.20,250.30 ETC.
 D) PLEASE SEE THE NEW LOAD CALCULATIONS NEED TO BE
 ADJUSTED TO COORDINATE WITH ALL ELECTRICAL AND
 DEDICATED LOADS ON PANEL SCHEDULE. THERE ARE SEVERAL
 DEDICATE CIRCUIT LOADS ON PANEL WHICH ARE NOT SHOWN IN
 LOAD CALCULATIONS. THESE MAY NOT BE PART OF THE GENERAL
 LIGHTING/RECEPTACLE LOADS.
 PLEASE SEE WATER HEATERS UNDER 422.13 WHICH IS REQUIRED
 AT 125% (NEW CODE CHANGE FOR 05). PLEASE SEE OTHER
 SECTIONS IN THE 2005 NEC 220.
  
 7) NOTE: PLEASE SHOW LOCATION OF ALL SERVICE EQUIPMENT
 INCLUDING THE NEW TRANSFORMER NOT SHOWN. PLEASE SEE
 110.26,408.7,240.24,450.9,450.13 ETC.
  
 8) NOTE:PLEASE SEE PLANS INDICATE THE DEVICES AS
 PREVIOUSLY REQUESTED AND IT IS KNOWN THAT THE FA
 DEVICES WILL BE UNDER A SEPARATE PERMIT HOWEVER THE
 MINIMUM LEVELS FOR ADA COMPLIANCE NEEDS TO BE STATED ON
 PLANS. THIS CAN BE ON THE SYMBOL LEGEND.
 PLEASE SEE THE LEVELS AS REQUIRED IN CODE STATED IN
 PREVIOUS NOTES. QUOTING THE CODE IN LIEU OF SPECIFIC
 INFORMATION IS NOT PERMITTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW AS THIS BUILDING ISFULLY SPRINKLED AND
 CONTAINS A FIRE ALARM SYSTEM, PLEASE KNOW THE BASE
 PLANS SHALL INDICATE THE BASE PROTECTION EVEN THOUGH
 ANY FIRE SPRINKLER AND FIRE ALARM WORK WILL BE UNDER A
 SEPARATE PERMIT. FBC ADMIN SECTION 106.3.5.1.2 PLEASE
 PROVIDE THE MINIMUM LEVELS FOR ALL HORN AND STROBE
 DEVICES PER FBC 11-4.28.1, .2 AND .3(4). THIS IS
 REQUIRED ON THE PLANS AT THIS TIME.
  
 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS. THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
 ******************************************************
 * *****

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-06-25 Cont ID  
Sent By dpalmer Date 2007-06-25 Time 14:33 Rev Time 0.00
Received By dpalmer Date 2007-06-25 Time 08:14 Sent To  
Notes
2007-06-25 14:33:47 
  
 *** UNSAT 2ND REVIEW ***
  
 ** PLEASE SEE THERE ARE SOME COMMENTS FROM PREVIOUS
 REVIEW WHICH ARE IN NEED OF ADDRESSING ALONG WITH NEW
 COMMENTS BASED ON REVISIONS AND CHANGES TO THE PLANS.
 PLEASE SEE NEW COMMENTS ALSO BASED ON INFORMATION NOW
 SHOWN WHICH WAS NOT ON PREVIOUS PLANS.
  
  
  
 1) NOTE:PLEASE SEE THE ARCHITECTURAL COVER SHEET
 WHICH CONTAINS A 2005 NFPA-72, WHICH SHOULD BE 2002.
 THIS COULD BE REDLINED HOWEVER AS THIS SHEET WILL
 REQUIRE REVISIONS FOR OTHER COMMENTS THIS SHOULD BE
 ADJUSTED AT THIS TIME.
  
 2) NOTE: PLEASE SEE THIS NOTE REMAINS THE SAME FROM
 PREVIOUS REVIEW.
 PLEASE SEE THE ENERGY CALCULATIONS DO NOT CORRELATE
 WITH THE PLANS.
 PLEASE SEE THE INFORMATION ON THE INPUT DATA REPORT FOR
 THE TYPE OF LUMINARIES, THE NUMBER OF LUMINARIES, AND
 THE WATTAGE AS SHOWN ON LUMINARIES.
 PLEASE SEE THESE DO NOT CORRELATE AT THIS TIME. PLEASE
 SEE THE FIXTURE SCHEDULE NEEDS TO BE COMPLETED WITH
 FIXTURE INFORMATION. THESE CAN ALWAYS BE REVISED AT A
 LATER DATE.
 PLEASE SEE THE SIGNATURE, DATE AND RAISED SEAL IS
 REQUIRED ON CERTIFICATION SHEETS. 13-103.1.1.1 PLEASE
 SEE ONLY THE SIGNATURE AND DATE ARE PRESENT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE ENERGY CALCULATIONS DO NOT CORRELATE
 WITH THE PLANS. PLEASE SEE THE LIGHTING, WATTAGE,
 NUMBER OF FIXTURES ETC.
 PLEASE BE SURE THE FIXTURE LEGEND STATES THE TYPE OF
 FIXTURE SPECIFIED AND COORDINATE THIS WITH THE ENERGY
 CALCULATIONS.
 THESE DO NOT CORRELATE AT ALL AT THIS TIME.
 PLEASE SEE MAXIMUM LIGHTING POWER DENSITIES WHICH HAS
 NOT BEEN STATED ON PLANS, OR CORRELATE IN ENERGY
 CALCULATIONS.
 PLEASE BE SURE THESES CONTAIN A RAISED SEAL, DATE AND
 SIGNATURE OF THE DESIGNER OF RECORD ON SHEET(S) WHICH
 CONTAIN THE TITLE BLOCKS FOR THE DESIGNER OF RECORD.
 THE SHEET CONTAINS THE LOCATION OF THE PRINTED NAME FOR
 THE DESIGNER HOWEVER THIS SHEET WAS NOT SIGNED, DATED
 OR SEALED.
 PLEASE BE SURE ONCE THE METHOD OF CONTROLS IS FIGURED
 FOR THE PLANS TO BE SURE TO CORRELATE CONTROL METHODS
 ON THE ENERGY CALCULATIONS.
 PLEASE SEE FBC 2004 W/ 2006 REVISIONS. 13-103.1.1.1,
 13-415.1.ABC.1.1, .1.2, .1.3, 13-415.1.AB.1.1,
 13-415.2, 13-415.2.ABC.1.2 (3) FOR TRACK LIGHTING.
  
 3) NOTE: PLEASE SEE THE LOCATION OF THE ELECTRICAL
 PANEL IS NOT PERMITTED IN CLOSET.110.26, 408.7, 240.24
 ETC
 PLEASE SEE COMMENTS WITH RESPECT TO THE NEW RISER AS
 OTHER ELECTRICAL EQUIPMENT IS NOT SHOWN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE ELECTRICAL PLANS DO NOT INDICATE A
 SCALE IN WHICH PLANS ARE UNDER, HOWEVER IT IS BEING
 ASSUMED THAT THE SCALE IS THAT OF THE ARCHITECTURAL
 PLANS AT 3/16THS.
 PLEASE SEE THE LOCATION AND MINIMUM CLEARANCES FOR THE
 ELECTRICAL PANEL *A* DO NOT SEEM TO MEET 110.26. PLEASE
 ALSO SEE 408.7 AND 240.24 FOR LOCATION OF EASILY
 IGNITABLE MATERIALS AND CLOSE PROXIMITY OF COMBUSTIBLES
 WITH OVER CURRENT PROTECTION DEVICES.
 PLEASE ADJUST PLANS.
  
 4) NOTE:PLEASE KNOW THE SUITE/UNIT # MAY BE ADJUSTED
 BY THE ADDRESSING REVIEWER. ON SHEETS WHICH DO NOT
 REQUIRE REVISIONS THE ADDRESS FOR SUITE/UNIT NUMBER MAY
 BE CHANGED BY HAND.
 THIS COMMENT WILL REMAIN AS THE INFORMATION FOR THIS
 HAS BEEN FORWARDED TO ADDRESSING.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE THE ADDRESS ON THE PLANS FOR THE
 LOCATION OF THE SCOPE OF WORK. PLEASE ALSO KNOW THIS
 WILL BE SENT TO ADDRESSING FOR THE NEW SUITE NUMBER
 WHICH WILL BE ASSIGNED.
  
 5) NOTE: PLEASE SEE THE PHOTO-METRICS ON SHEET A-1 DOES
 NOT INDICATE THE COMPLIANCE AS PREVIOUSLY NOTED. PLEASE
 SHOW LEVELS UNDER NORMAL AND UNDER EMERGENCY. AS THE
 LIGHTING PLANS DO NOT INDICATE THE EMERGENCY LIGHT
 FIXTURES NEEDED FOR THIS EGRESS PATH IT DOES NOT SEEM
 THE MINIMUM LEVELS CAN BE MET BASED ON THE PLANS
 SUBMITTED.
 PLEASE SUBMIT THE COMPLETED INFORMATION FOR REVIEW.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE PROVIDE THE PHOTO-METRIC LEVELS FOR STAIRS PER
 NFPA-101 2003 7.8.1.3, 7.9.2.2.
  
 6) NOTE: PLEASE SEE THE PLANS NOW INCLUDE A NEW
 ELECTRICAL RISER WHICH CONTAINS THE FOLLOWING
 COMMENTS.
 A) PLEASE SEE THE OCP FOR THE TRANSFORMER IS SET TOO
 HIGH PER 450.3.
 B) PLEASE SEE THE CONDUCTOR SIZES ARE NOT SUFFICIENT
 SIZE FOR THE 100AMP OCP AS SHOWN ON MAIN DISCONNECT.
 PLEASE SEE 6A ABOVE AS THE OCP WILL BE
 CHANGING.240.4,310.16,ETC.
 C) PLEASE SEE INDICATE THE GROUNDING ATTACHMENT FOR
 TRANSFORMER. 250.50,250.20,250.30 ETC.
 D) PLEASE SEE THE NEW LOAD CALCULATIONS NEED TO BE
 ADJUSTED TO COORDINATE WITH ALL ELECTRICAL AND
 DEDICATED LOADS ON PANEL SCHEDULE. THERE ARE SEVERAL
 DEDICATE CIRCUIT LOADS ON PANEL WHICH ARE NOT SHOWN IN
 LOAD CALCULATIONS. THESE MAY NOT BE PART OF THE GENERAL
 LIGHTING/RECEPTACLE LOADS.
 PLEASE SEE WATER HEATERS UNDER 422.13 WHICH IS REQUIRED
 AT 125% (NEW CODE CHANGE FOR 05). PLEASE SEE OTHER
 SECTIONS IN THE 2005 NEC 220.
  
 7) NOTE: PLEASE SHOW LOCATION OF ALL SERVICE EQUIPMENT
 INCLUDING THE NEW TRANSFORMER NOT SHOWN. PLEASE SEE
 110.26,408.7,240.24,450.9,450.13 ETC.
  
 8) NOTE:PLEASE SEE PLANS INDICATE THE DEVICES AS
 PREVIOUSLY REQUESTED AND IT IS KNOWN THAT THE FA
 DEVICES WILL BE UNDER A SEPARATE PERMIT HOWEVER THE
 MINIMUM LEVELS FOR ADA COMPLIANCE NEEDS TO BE STATED ON
 PLANS. THIS CAN BE ON THE SYMBOL LEGEND.
 PLEASE SEE THE LEVELS AS REQUIRED IN CODE STATED IN
 PREVIOUS NOTES. QUOTING THE CODE IN LIEU OF SPECIFIC
 INFORMATION IS NOT PERMITTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW AS THIS BUILDING ISFULLY SPRINKLED AND
 CONTAINS A FIRE ALARM SYSTEM, PLEASE KNOW THE BASE
 PLANS SHALL INDICATE THE BASE PROTECTION EVEN THOUGH
 ANY FIRE SPRINKLER AND FIRE ALARM WORK WILL BE UNDER A
 SEPARATE PERMIT. FBC ADMIN SECTION 106.3.5.1.2 PLEASE
 PROVIDE THE MINIMUM LEVELS FOR ALL HORN AND STROBE
 DEVICES PER FBC 11-4.28.1, .2 AND .3(4). THIS IS
 REQUIRED ON THE PLANS AT THIS TIME.
  
 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS. THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-04 Cont ID  
Sent By dpalmer Date 2007-03-04 Time 08:40 Rev Time 0.00
Received By dpalmer Date 2007-03-04 Time 07:20 Sent To  
Notes
2007-03-04 08:41:06*** UNSAT ***
  
 1) NOTE: PLEASE KNOW THAT PERMIT APPLICATION HAS BEEN
 SUBMITTED AFTER DECEMBER 8TH, 2006 WHICH PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGE SIN THE FBC WHICH WILL
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE ALSO SEE ELECTRICAL CHANGES UNDER THE 2005
 INCLUDING ANY SECTIONS OF CODES WHICH ARE REFLECTED ON
 PLANS FROM THE PREVIOUS 2002 NEC.
 PLEASE LIST THE FOLLOWING FOR THIS REVIEWER AT A
 MINIMUM.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE THE ENERGY CALCULATIONS DO NOT
 CORRELATE WITH THE PLANS. PLEASE SEE THE LIGHTING,
 WATTAGE, NUMBER OF FIXTURES ETC.
 PLEASE BE SURE THE FIXTURE LEGEND STATES THE TYPE OF
 FIXTURE SPECIFIED AND COORDINATE THIS WITH THE ENERGY
 CALCULATIONS.
 THESE DO NOT CORRELATE AT ALL AT THIS TIME.
 PLEASE SEE MAXIMUM LIGHTING POWER DENSITIES WHICH HAS
 NOT BEEN STATED ON PLANS, OR CORRELATE IN ENERGY
 CALCULATIONS.
 PLEASE BE SURE THESES CONTAIN A RAISED SEAL, DATE AND
 SIGNATURE OF THE DESIGNER OF RECORD ON SHEET(S) WHICH
 CONTAIN THE TITLE BLOCKS FOR THE DESIGNER OF RECORD.
 THE SHEET CONTAINS THE LOCATION OF THE PRINTED NAME FOR
 THE DESIGNER HOWEVER THIS SHEET WAS NOT SIGNED, DATED
 OR SEALED.
 PLEASE BE SURE ONCE THE METHOD OF CONTROLS IS FIGURED
 FOR THE PLANS TO BE SURE TO CORRELATE CONTROL METHODS
 ON THE ENERGY CALCULATIONS.
 PLEASE SEE FBC 2004 W/ 2006 REVISIONS. 13-103.1.1.1,
 13-415.1.ABC.1.1, .1.2, .1.3, 13-415.1.AB.1.1,
 13-415.2, 13-415.2.ABC.1.2 (3) FOR TRACK LIGHTING.
  
 3) NOTE: PLEASE SEE THAT PLANS DO NOT INDICATE ANY
 METHODS FOR THE REQUIRED AUTOMATED CONTROLS PER FBC
 2004 W/2006 REVISIONS.
 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 4) NOTE: PLEASE SEE THE ELECTRICAL PLANS DO NOT
 INDICATE A SCALE IN WHICH PLANS ARE UNDER, HOWEVER IT
 IS BEING ASSUMED THAT THE SCALE IS THAT OF THE
 ARCHITECTURAL PLANS AT 3/16THS.
 PLEASE SEE THE LOCATION AND MINIMUM CLEARANCES FOR THE
 ELECTRICAL PANEL *A* DO NOT SEEM TO MEET 110.26. PLEASE
 ALSO SEE 408.7 AND 240.24 FOR LOCATION OF EASILY
 IGNITABLE MATERIALS AND CLOSE PROXIMITY OF COMBUSTIBLES
 WITH OVER CURRENT PROTECTION DEVICES.
 PLEASE ADJUST PLANS.
  
 5) NOTE: PLEASE PROVIDE THE ADDRESS ON THE PLANS FOR
 THE LOCATION OF THE SCOPE OF WORK. PLEASE ALSO KNOW
 THIS WILL BE SENT TO ADDRESSING FOR THE NEW SUITE
 NUMBER WHICH WILL BE ASSIGNED.
  
 6) NOTE: PLEASE PROVIDE THE PHOTO-METRIC LEVELS FOR
 STAIRS PER NFPA-101 2003 7.8.1.3, 7.9.2.2.
  
 7) NOTE: PLEASE SEE THAT NO INFORMATION IS BEING
 PROVIDED FOR THE NEW ELECTRICAL PANEL. WHERE IS IT FED
 FROM? FEEDERS? METER? MAIN? ETC.
 THIS IS A NEW BUILD OUT AND THE PANEL DOES NOT EXIST.
 215.5, 310.16, 230.70, 240.4, 250.110, ETC.
 FBC 106.1.2, 106.3.5.1.2
  
 8) NOTE: PLEASE KNOW AS THIS BUILDING ISFULLY
 SPRINKLED AND CONTAINS A FIRE ALARM SYSTEM, PLEASE KNOW
 THE BASE PLANS SHALL INDICATE THE BASE PROTECTION EVEN
 THOUGH ANY FIRE SPRINKLER AND FIRE ALARM WORK WILL BE
 UNDER A SEPARATE PERMIT. FBC ADMIN SECTION 106.3.5.1.2
 PLEASE PROVIDE THE MINIMUM LEVELS FOR ALL HORN AND
 STROBE DEVICES PER FBC 11-4.28.1, .2 AND .3(4). THIS IS
 REQUIRED ON THE PLANS AT THIS TIME.
  
 9) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS
 FOR ENGINEERING FIRM FOR THE *S* SHEETS. PLEASE SEE THE
 FAC 61G15-23.002 AND FS 471.023.
 PLEASE KNOW THAT THE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER IS MISSING AT THIS TIME. **THIS IS
 REQUIRED FOR THESE SHEETS WHETHER OR NOT COMMENT IS
 MADE BY OTHER TRADE(S)/REVIEWER(S).
  
  
 ***PLEASE KNOW AS THERE WAS MISSING INFORMATION WHICH
 IS REQUIRED FOR REVIEW AT THIS TIME FOR MANY ITEMS,
 THERE MAY BE COMMENTS ONCE INFORMATION IS PROVIDED THAT
 CAN NOT BE REVIEWED FOR CODE COMPLIANCE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-07-06 Cont ID  
Sent By mwennerg Date 2007-07-06 Time 14:51 Rev Time 0.00
Received By mwennerg Date 2007-07-06 Time 14:51 Sent To  
Notes
2007-07-06 14:57:12***PROVISO***
  
 #9) IT IS UNDERSTOOD THAT SHOP DRAWINGS WILL BE
 PROVIDED. PLEASE PROVIDE BASE FIRE SPRINKLER LAYOUT
 (REMODEL) FOR REVIEW.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-03-16 Cont ID  
Sent By mawillia Date 2007-03-16 Time 00:43 Rev Time 0.00
Received By mawillia Date 2007-03-15 Time 23:58 Sent To  
Notes
2007-03-16 00:41:47***DENIED*****
  
  
 01.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE
 PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED.
  
 02. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 03.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 04.THE COMPLETE ADDRESS OF WHERE THE SCOPE OF WORK
 WILL BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 05.DISPLAY THE TENANT SPACE NUMBER FOR THIS SITE SO
 THAT IT IS DISTINGUISHABLE FROM OTHER TENANT SPACES. AS
 PER WEST PALM BEACH CODE, THOSE NUMBERS SHALL BE NO
 LESS THAN 3" IN HEIGHT.
  
 06.THE REAR DOOR SHOULD HAVE AN EXIT SIGN LIGHT.
  
 07.WHAT IS INTERIOR FINISH CLASSIFICATION FOR THE
 WALLS AND CEILINGS IN THE EXITS, EXIT ACCESS CORRIDORS,
 AND IN ALL OTHER AREAS?
  
 08.PROVIDE A LIFE SAFETY PLAN SHEET WHICH INDICATES
 THE TRAVEL DISTANCE TO THE EXIT(S).ALSO ON THIS
 SHEET, INDICATE THE LOCATION OFFIRE EXTINGUISHER(S)
 AT DISTANCES TO SATISFY THE 75' TRAVEL DISTANCE
 REQUIREMENT.
  
 09.PROVIDE A LAYOUT OF THE FIRE SPRINKLER SYSTEM FOR
 THIS TENANT SPACE.
  
 10.IF SO EQUIPPED WITH A FIRE ALARM SYSTEM, WILL IT
 BE INDEPENDENT OR WILL IT BE TIED INTO THE STRAND'S
 SYSTEM.
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED ON THE PLAN.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-11-12 Cont ID  
Sent By adarroug Date 2008-11-12 Time 10:45 Rev Time 0.00
Received By adarroug Date 2008-11-12 Time 10:45 Sent To  
Notes
2008-11-12 10:47:53TO "BOB"#4

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-10-02 Cont ID  
Sent By adarroug Date 2008-10-02 Time 09:49 Rev Time 0.00
Received By adarroug Date 2008-10-02 Time 09:49 Sent To  
Notes
2008-10-02 09:52:18TO "COMM" BD#19
  

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-04-23 Cont ID  
Sent By adarroug Date 2008-04-23 Time 14:39 Rev Time 0.00
Received By adarroug Date 2008-04-23 Time 14:39 Sent To M
Notes
2008-04-23 14:39:41TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-03-06 Cont ID  
Sent By adarroug Date 2008-03-06 Time 12:41 Rev Time 0.00
Received By adarroug Date 2008-03-06 Time 12:41 Sent To B
Notes
2008-03-06 12:41:50TO "MJACOBS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-02-14 Cont ID  
Sent By adarroug Date 2008-02-14 Time 14:16 Rev Time 0.00
Received By adarroug Date 2008-02-14 Time 14:16 Sent To M
Notes
2008-02-14 14:16:25TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-10-31 Cont ID  
Sent By adarroug Date 2007-10-31 Time 12:42 Rev Time 0.00
Received By adarroug Date 2007-10-31 Time 12:42 Sent To B
Notes
2007-10-31 12:42:25TO "MJACOBS" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-09-20 Cont ID  
Sent By adarroug Date 2007-09-20 Time 15:57 Rev Time 0.00
Received By adarroug Date 2007-09-20 Time 15:57 Sent To  
Notes
2007-10-01 14:33:37TO "BOB" #3
2007-09-20 15:57:55WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-29 Cont ID  
Sent By adarroug Date 2007-08-29 Time 16:16 Rev Time 0.00
Received By adarroug Date 2007-08-29 Time 16:16 Sent To  
Notes
2007-09-08 15:40:52TO BOB BOARD SPACE #16
2007-08-29 16:17:03WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-24 Cont ID  
Sent By adarroug Date 2007-06-24 Time 13:40 Rev Time 0.00
Received By adarroug Date 2007-06-24 Time 13:40 Sent To  
Notes
2007-06-24 17:34:22TO "BOB"#18
2007-06-24 13:40:44WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-15 Cont ID  
Sent By mawillia Date 2007-03-15 Time 23:58 Rev Time 0.00
Received By mawillia Date 2007-02-26 Time 10:16 Sent To  
Notes
2007-02-26 10:25:05TO "BOB"#15

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2008-11-13 Cont ID  
Sent By tgordon Date 2008-11-13 Time 09:32 Rev Time 0.45
Received By tgordon Date 2008-11-13 Time 09:32 Sent To  
Notes
2008-11-13 09:33:26REVISION TO MECHANICAL PLANS M-1, M-2 AND E-CAL'S.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2008-10-02 Cont ID  
Sent By tgordon Date 2008-10-02 Time 16:32 Rev Time 1.20
Received By tgordon Date 2008-10-02 Time 16:32 Sent To  
Notes
2008-10-02 16:41:05PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO MECHANICAL PLAN M-1 AND M-2.
 *** DENIED ***
  
 1) A/C SYSTEM MODEL NUMBERS LISTED ON THE A/C EQUIPMENT
 SCHEDULE COULD NOT BE FOUND ON THE ARI DIRECTORY
 WEB-SITE, PLEASE SUBMIT MANUFACTURES SPEC'S OR ARI
 CERTIFICATE, PER 2004 FBC 13-407.1.ABC.3.1.1.
  
 2) THE MECHANICAL REVISION WILL NEED TO PASS A ZONING
 REVIEW DUE TO THE OUTDOOR CONDENSER UNITS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-04-23 Cont ID  
Sent By tgordon Date 2008-04-23 Time 16:45 Rev Time 0.40
Received By tgordon Date 2008-04-23 Time 16:45 Sent To  
Notes
2008-04-23 16:45:50REVISION TO MECH. PLANS PAGES M-1 AND M-2.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-02-15 Cont ID  
Sent By tgordon Date 2008-02-15 Time 12:16 Rev Time 0.30
Received By tgordon Date 2008-02-15 Time 12:16 Sent To B
Notes
2008-02-15 12:17:35REVISION TO MECH. PLANS PAGES M-1 AND M-2.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-06-25 Cont ID  
Sent By tgordon Date 2007-06-25 Time 15:20 Rev Time 0.25
Received By tgordon Date 2007-06-25 Time 15:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-03-05 Cont ID  
Sent By tgordon Date 2007-03-05 Time 16:20 Rev Time 0.35
Received By tgordon Date 2007-03-05 Time 16:20 Sent To  
Notes
2007-03-05 16:39:20*** DENIED ***
 1) SEE ENERGY CALCULATIONS PAGE 2 NEED TO BE SIGNED BY
 PREPARER AND OWNER/AGENT.
  
 2) JOB ADDRESS NEEDS TO BE IN THE TITLE BLOCK.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-09-15 Cont ID  
Sent By jleech Date 2007-09-15 Time 09:08 Rev Time 0.00
Received By jleech Date 2007-09-15 Time 09:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-07-05 Cont ID  
Sent By jleech Date 2007-07-05 Time 14:30 Rev Time 0.00
Received By jleech Date 2007-07-05 Time 14:26 Sent To  
Notes
2007-07-05 14:38:02DENIED;
 NO DOORS PERMITED UNDER BREAK ROOM SINK. FBC-2004
 BUILDING SECTION 11-4.23.3 CLEAR KNEE SPACE REQUIRED
 UNDER BREAK SINK, 19" DEEP. DOORS ARE NOT PERMITED TO
 SWING INTO THE CLEAR FLOOR SPACE OF THE SINK.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-03-10 Cont ID  
Sent By jleech Date 2007-03-10 Time 07:17 Rev Time 0.00
Received By jleech Date 2007-03-10 Time 07:17 Sent To  
Notes
2007-03-10 07:25:01DENIED;
  
 1. SHOW COMPIANCE TO FBC-2004 PLUMBING TABLE 403.1.
 TYPE OF BUSINESS SQ. FT., AND NUMBER OF EMPLOYEES.
 2. HOT WATER REQUIRED FOR SERVICE SINK IN BATHROOM
 CLOSET. SECTION 607.1.
 3. PAGE A-4 KITCHEN ELEVATION; ADD NOTE, NO DOORS OR
 BASE UNDER SINK FOR FRONTAL APPROACH.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status N Date 2008-10-03 Cont ID  
Sent By mflis Date 2008-10-03 Time 10:47 Rev Time 0.00
Received By mflis Date 2008-10-03 Time 10:47 Sent To  
Notes
***NONE***