Plan Review Details - Permit 07020609
Plan Review Stops For Permit 07020609
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-02 Cont ID  
Sent By mjacobs Date 2007-03-02 Time 10:11 Rev Time 0.00
Received By mjacobs Date 2007-03-01 Time 16:39 Sent To  
Notes
2007-03-01 17:29:21BUILDING PLAN REVIEW
 PERMIT: 07020609
 ADD:255 EVERNIA STREET
 CONT: DC CONSTRUCTION ASSOC. INC.
 TEL: (561)988-8505
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST.
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 4)2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 5)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 -------------------------------------
 ) NUMBER OF UNITS
 ) NUMBER OF FLOORS
 ) NUMBER OF ROOMS
 ) SQ. FT. FOOTPRINT
 ) SQ. FT. UNDER ROOF (TOTAL)
 ) OCCUPANT LOAD
 ) FLOOD ZONE
 ) FLOOD ELEVATION
 )L.O.M.R.
  
 6)110.4.3.SIGNS REQUIRED. IN EVERY
 BUILDING OR PART OF A BUILDING USED FOR
 STORAGE, INDUSTRIAL OR HAZARDOUS PUR-
 POSES, THE SAFE FLOOR LOADS, AS REVIEWED
 BY THE BUILDING OFFICIAL ON THE PLAN,
 SHALL BE MARKED ON PLATES OF APPROVED DE
 SIGN WHICH SHALL BE SUPPLIED & SECURELY
 AFFIXED BY THE OWNER OF THE BUILDING IN
 A CONSPICUOUS PLACE IN EACH STORY TO
 WHICH THEY RELATE. SUCH PLATES SHALL NOT
 BE REMOVEDOR DEFACED, & IF LOST,
 REMOVED THE OWNER OF THE BUILDING SHALL
 REPLACE THEM.
  
 7)SUBMIT DETAIL ELEVATION DRAWINGWS OF THE INTERIOR
 EAST / WEST/ NORTH AND SOUTH ELEVATIONS.
  
 8)DETAIL #1 ON SHEET A-3 SHOW THE OPPOSITE SECTION OF
 THE WALL AS THE EXTERIOR, HOWEVER, ON SHEET A-1, THAT
 WALL SHOWS THAT IT IS PART OF THE INTERIOR STRUCTURE.
 CLARIFY.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIEN CLARITY TO
 INDICATE THE NATURE / LOCATION AND EXTENT OF WORK. FBC.
 106.1.1.
  
 9)GUARDRAILS SHALL BE IN CONFORMANCE WITH FBC
 SEC.1607.7 AND FBC. SEC. 1012. INDICATE HOW THE
 GUARDRAIL WILL BE ATTATCHED,
  
 10) SUBMIT THE SHOP DRAWINGS FOR THE STAIRS FOR REVIEW
 AS NOTED ON THE DRAWINGS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-02-26 Cont ID  
Sent By btrobaug Date 2007-02-26 Time 12:54 Rev Time 1.00
Received By btrobaug Date 2007-02-26 Time 12:02 Sent To  
Notes
2007-02-26 12:29:39 
  
  
 DENIED/INCOMPLETE INFORMATION.
  
 1} INDICATE COMPLIANCE WITH 13-415.1ABC.1.2, FBC FOR
 SPACE CONTROLS FOR LIGHTING." STANDARD SWITCHES ARE
 SHOWN ON THE PLAN. SHEET #2 OF THE ENERGY GAUGE ONLY
 LISTS 1 FLUORESCENT, AND NOTE THAT ALTHOUGH A MANUAL
 CONTROL IS LISTED, IT MUST AUTOMATICALLY TURN LIGHTS
 OFF WITHIN 30 MINUTES OF ALL OCCUPANTS LEAVING THE
 SPACE. DESIGNATE WHICH MANUFACTURER AND MODELS ARE
 BEING SPECIFIED FOTR THIS PROJECT BY THE ENGINEER.
  
 2} INDICATE COMPLIANCE WITH 13-415.2ABC.1, PERFORMANCE
 CALCULATION PROCEDURES. SUBMIT FORMS WITH 13-415.2B OR
 13-415.2.C.1 TABLE DENSITIES.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-03-06 Cont ID  
Sent By mawillia Date 2007-03-06 Time 14:22 Rev Time 0.00
Received By mawillia Date 2007-03-06 Time 13:09 Sent To  
Notes
2007-03-06 13:46:14*****DENIED*****
  
  
 01.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE
 PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED.
  
 02. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 03.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 04.THE COMPLETE ADDRESS OF WHERE THE SCOPE OF WORK
 WILL BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 05.DISPLAY THE TENANT SPACE NUMBER FOR THIS SITE SO
 THAT IT IS DISTINGUISHABLE FROM OTHER TENANT SPACES. AS
 PER WEST PALM BEACH CODE, THOSE NUMBERS SHALL BE NO
 LESS THAN 3" IN HEIGHT.
  
 06.THE REAR DOOR SHOULD HAVE AN EXIT SIGN LIGHT.
  
 07.WHAT IS INTERIOR FINISH CLASSIFICATION FOR THE
 WALLS AND CEILINGS IN THE EXITS, EXIT ACCESS CORRIDORS,
 AND IN ALL OTHER AREAS?
  
 08.PROVIDE A LIFE SAFETY PLAN SHEET WHICH INDICATES
 THE TRAVEL DISTANCE TO THE EXIT(S).ALSO ON THIS
 SHEET, INDICATE THE LOCATION OFFIRE EXTINGUISHER(S)
 AT DISTANCES TO SATISFY THE 75' TRAVEL DISTANCE
 REQUIREMENT.
  
 09.PROVIDE A LAYOUT OF THE FIRE SPRINKLER SYSTEM FOR
 THIS TENANT SPACE.
  
 10.IF SO EQUIPPED WITH A FIRE ALARM SYSTEM, WILL IT
 BE INDEPENDENT OR WILL IT BE TIED INTO THE STRAND'S
 SYSTEM.
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED ON THE PLAN.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-06 Cont ID  
Sent By mawillia Date 2007-03-06 Time 13:09 Rev Time 0.00
Received By mawillia Date 2007-02-26 Time 10:04 Sent To  
Notes
2007-02-26 10:10:26TO "BOB"#5

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-02-26 Cont ID  
Sent By tgordon Date 2007-02-26 Time 15:58 Rev Time 0.30
Received By tgordon Date 2007-02-26 Time 15:58 Sent To  
Notes
2007-02-26 16:19:03*** DENIED ***
 1) PLEASE SHOW THE JOB ADDRESS IN THE TITLE BLOCK, SEE
 2004 FBC WPB AMEND. 106.1.1.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-03-03 Cont ID  
Sent By jleech Date 2007-03-03 Time 10:15 Rev Time 0.00
Received By jleech Date 2007-03-03 Time 10:15 Sent To  
Notes
2007-03-03 10:29:44DENIED;
 1. WATER RISER; WATER HAMMER ARRESTOR IS REQUIRED AT
 BREAK SINK FOR REFIGERATOR WATER PLEASE SPEC. TYPE AND
 MANUFATURE.
 2. PAGE A-3 KITCHEN ELEVATIONS FRONTAL CLEAR FLOOR
 SPACE REQUIRED WITH KNEE CLEARANCE OF 19" DEEP. DOORS
 AND 4" BASE MUST BE REMOVED. SECTION 11-4.24.3
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695