Plan Review Details - Permit 07020578
Plan Review Stops For Permit 07020578
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-04-13 Cont ID  
Sent By mjacobs Date 2007-04-13 Time 14:45 Rev Time 0.00
Received By mjacobs Date 2007-04-13 Time 13:34 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-04-24 Cont ID  
Sent By dpalmer Date 2007-04-24 Time 15:26 Rev Time 0.00
Received By dpalmer Date 2007-04-24 Time 15:14 Sent To P
Notes
2007-04-24 15:26:40AS PREVIOUSLY REQUESTED, OLD/VOIDED SHEETS WERE TO BE
 REMOVED BEFORE INSERTING NEW SHEETS. NEITHER WAS DONE.
 THE OLD SHEETS WERE REMOVED BY STAFF AND NEW SHEETS
 INSERTED CORRECTLY INTO TWO COMPLETE SETS.
 AS OLD SHEETS 3 AND 4 CONTAINED REDLINES FROM THE
 PLUMBING REVIEWER, AND NEW SHEETS 3 AND 4 WERE
 SUBMITTED, PLANS WERE ROUTED TO PLUMBING REVIEWER FOR
 REVIEW.
  
 *** ALL ELECTRICAL IS EXISTING FROM EXISTING ELECTRICAL
 PANEL PER ENGINEER AND ELECTRICAL CONTRACTOR. ALL
 CONDUCTOR SIZES AND BREAKER SIZES SHALL BE VIF. 310.16,
 240.4

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-30 Cont ID  
Sent By dpalmer Date 2007-03-30 Time 10:54 Rev Time 0.00
Received By dpalmer Date 2007-03-30 Time 10:54 Sent To  
Notes
2007-03-30 10:54:33****** UNSAT *****
  
 ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1
 IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE
 ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY
 THE CITY OF WEST PALM BEACH.
  
 ** PLEASE KNOW AS THE PLANS ARE NOT COMPLETE WITH SOME
 INFORMATION AS NEEDED FOR REVIEW, ONLY A REVIEW OF
 SUBMITTED PLANS COULD BE DONE.
  
 1) NOTE: PLEASE PROVIDE ELECTRICAL DETAIL FOR L ANY NEW
 LOADS, IF EXISTING PLEASE INDICATE HOW THESE ARE BEING
 FED. PLEASE INDICATE THE BREAKER AND CONDUCTOR SIZES
 WHICH ARE NEW OR EXISITNG. IF NO NEW LODAS ARE BEING
 ADDED, THEN PLEASE INDICATE.
 PLEASE SUBMIT A DETAIL FOR ANY NEW WIRING OF THE SPA
 AND ASSOCIATED EQUIPMENT.
 NEED TO VERIFY WIRING, SIZE, LOAD, OVER CURRENT
 PROTECTION ETC.
 240.4, 408.4, 310.16
  
 FBC 106.3.5.1.2
  
 2) NOTE: PLEASE SEE MISSING DETAIL FOR NEW LIGHT, HOW
 IS THIS BEING FED? IS THIS LOW VOLTAGE, SIZE OF
 TRANSFORMER, NEW OR EXISTING AND SIZE OF THE NEW
 CONDUCTORS BEING ADDED.
  
 3) NOTE: PLEASE SEE MISSING EQUIPOTENTIAL BONDING GRID
 PER 680.26
  
 ** PLEASE KNOW THAT ANY ADDITIONAL PANEL SCHEDULE, WIHT
 BREAKER INFORMATION AND WIRING ON PANEL SCHEDULE MAY BE
 DONE BY THE ELECTRICAL CONTRACTOR WHICH HAS ALREADY
 BEEN IN CONTACT WITH THIS OFFICE.
 PLEASE SEE THAT THE COMMENTS FOR 2 AND 3 NEEDS TO BE
 DONE BY THE ENGINEERING FIRM.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-04-19 Cont ID  
Sent By adarroug Date 2007-04-19 Time 09:29 Rev Time 0.00
Received By adarroug Date 2007-04-19 Time 09:29 Sent To E
Notes
2007-04-19 09:29:25TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-29 Cont ID  
Sent By dpalmer Date 2007-03-29 Time 08:45 Rev Time 0.00
Received By dpalmer Date 2007-03-29 Time 08:45 Sent To  
Notes
2007-03-29 08:46:15TO COMM BOARD #30

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-22 Cont ID  
Sent By bpowell Date 2007-03-27 Time 15:11 Rev Time 0.00
Received By adarroug Date 2007-03-22 Time 16:35 Sent To Z
Notes
2007-03-22 16:35:42TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-03-08 Time   Rev Time 0.00
Received By adarroug Date 2007-02-23 Time 15:54 Sent To  
Notes
2007-02-23 15:54:54TO "Z" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-04-26 Cont ID  
Sent By kstevens Date 2007-04-26 Time 14:32 Rev Time 0.00
Received By kstevens Date 2007-04-26 Time 14:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-04-09 Cont ID  
Sent By kstevens Date 2007-04-09 Time 10:40 Rev Time 0.00
Received By kstevens Date 2007-04-09 Time 10:40 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2007-03-27 Cont ID  
Sent By bpowell Date 2007-03-27 Time 15:02 Rev Time 0.00
Received By bpowell Date 2007-03-27 Time 15:02 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-03-08 Cont ID  
Sent By bpowell Date 2007-03-08 Time 16:48 Rev Time 0.00
Received By bpowell Date 2007-03-08 Time 16:54 Sent To  
Notes
2007-03-08 16:52:28A SURVEY SHALL BE PROVIDED SHOWING THE LOCATION OF THE
 SPA AND THE DIMENSIONS/SETBACKS FROM THE PROPERTY
 LINES.
  
 BOBBY POWELL, PLANNER, (561) 822-1435