| 2007-06-28 15:07:07 | |
| | |
| | *** UNSAT 2ND REVIEW *** |
| | |
| | |
| | 1) NOTE: PLEASE SEE SPECIFICALLY THE PREVIOUS REVIEW |
| | NOTED **IMPORTANT** WHICH REQUESTED ALL OF THE |
| | OLD/VOIDED SHEETS TO BE REMOVED FROM SETS AND TO SUBMIT |
| | THEM SEPARATELY. |
| | THIS WAS NOT DONE, PLEASE SEE THE SAME REQUEST STANDS. |
| | |
| | 2) NOTE:SAME NOTE AS PREVIOUS REVIEW. |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SUPPLY MORE INFORMATION FOR ELECTRICAL, WHERE IT |
| | IS BEING FROM? HOW AND WHERE ARE DISCONNECTING MEANS> |
| | (SPECIFIC DISTANCES ETC). |
| | PLEASE SEE COMMENTS WHICH WERE GIVEN TO OWNER?S |
| | REPRESENTATIVE FOR REQUIRE INFORMATION SHOWING ALL |
| | CLASS AND DIVISION LOCATIONS. |
| | PLEASE SEE 514.11 ETC. |
| | FBC 106.1.2 (ADMIN SECTION FOR ADDITIONAL |
| | INFORMATION). |
| | |
| | 3) NOTE: SAME NOTE. PLEASE SEE THE REQUIRED LICENSE |
| | INFORMATION WAS NOT PLACED ON TITLE BLOCKS AS |
| | REQUIRED. |
| | PLEASE SEE THE TITLE BLOCKS NOW CONTAIN A NEW ENGINEER |
| | WHICH ADDRESSING AND INFORMATION ON TITLE BLOCKS DOES |
| | NOT COORDINATE WITH THE STATE WEBSITE. |
| | PLEASE KNOW PLANS MAY BE RETAINED AND FORWARDED TO THE |
| | FLORIDA BOARD OF PROFESSIONAL ENGINEERS. |
| | FAC 61G15-23.002, FS 471.023 |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE SEE MISSING INFORMATION FOR TITLE BLOCKS FOR |
| | BOTH OFTHE ENGINEERING FIRMS AS REQUIRED UNDER |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.002 AND FLORIDA |
| | STATUTES 471.023. |
| | PLEASE SEE MISSING THE REQUIRED PRINTED NAME AND |
| | PRINTED LICENSE NUMBER OF THE PE. |
| | PLEASE ALSO SEE MISSING THE CERTIFICATE OF |
| | AUTHORIZATION NUMBER. |
| | ** PLEASE SEE THE INFORMATION AS LISTED ON THE STATE OF |
| | FLORIDA'S WEBSITE DOES NOT CORRELATE WITH PLANS FOR |
| | "CORE STATES ENGINEERING". |
| | ** PLEASE KNOW THAT ONE SET OF PLANS WILL BE RETAINED |
| | BY THIS OFFICE. |
| | |
| | 4) NOTE: PLEASE COORDINATE APPLICATIONS AND D SCOPE OF |
| | WORK AS APPLIED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE KNOW THAT AT THIS TIME THE PERMIT APPLICATION IS |
| | BEING MADE UNDER A CBC LICENSE FOR A FUEL PERMIT WHICH |
| | IS TO BE VERIFIED FOR SCOPE AND WHETHER OR NOT THIS |
| | TYPE OF PERMIT CAN BE APPLIED FOR UNDER THE CBC LICENSE |
| | AND SCOPE AS SHOWN ON PLANS. PLEASE KNOW OTHER SUB WORK |
| | WILL REQUIRE ADDITIONAL PERMIT APPLICATIONS FOR SUB |
| | SCOPE OF WORK. ONCE MAIN PERMIT IS ISSUED AND THOSE SUB |
| | TRADE REVIEWS ARE PASSED, THEN THE SUB CONTRACTOR CAN |
| | SIMPLY APPLY FOR PERMIT, REFERENCE THE MAIN PLANS AND |
| | PAY SUB PERMIT FEE AND BE ISSUED A PERMIT THE SAME |
| | DAY/TIME. |
| | |
| | 5) NOTE: SAME NOTE. THE VALUE ISLOW AND A VALUE WILL |
| | MAY BE ASSESSED BY THIS OFFICE. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE KNOW THAT THE COMPLETE SCOPE OF WORK FOR THE |
| | FUEL TANK, PUMPS, ELECTRICAL, ETC SHALL INCLUDE ALL |
| | LABOR AND MATERIALS EVEN IF EQUIPMENT, PUMPS TANK(S) |
| | ETC ARE OWNER SUPPLIED. |
| | PLEASE ADJUST THE APPLIED VALUE FOR ALL WORK AS SHOWN. |
| | |
| | 6) NOTE:PLEASE SEE THE PLANS NOW CONTAIN AS NEW |
| | ENGINEER OF RECORD. PLEASE SEE THE SEAL IS NOT CLEAR |
| | AND VISIBLE WITH ALL INFORMATION ON SAID SEAL AS |
| | REQUIRE PER FAC 61G15-23.001. |
| | PLEASE SEE THE PLANS ALSO APPEAR TO BE SIGNED WITH |
| | *INITIALS*, IF THIS IS INDEED THE LEGAL SIGNATURE OF |
| | THE DESIGNER OF RECORD PLEASE SUBMIT A SIGNED, DATED, |
| | SEALED AND NOTARIZED LETTER FOR SIGNATURE VERIFICATION. |
| | THIS WILL BE PLACED IN OUR SIGNATURE FILE FOR FUTURE |
| | REFERENCE. |
| | FS 471.025 |
| | |
| | 7) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENT FOR CODE COMPLIANCE AS SOME OF THE NOTES |
| | FORM PREVIOUS REVIEW STILL REMAIN. |
| | PLEASE SEE THIS IS ONLY A NOTICE GIVEN AT THIS TIME. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |