Plan Review Details - Permit 07020542
Plan Review Stops For Permit 07020542
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-09-13 Cont ID  
Sent By jwitmer Date 2007-09-13 Time 11:39 Rev Time 1.11
Received By jwitmer Date 2007-09-13 Time 11:39 Sent To PC
Notes
2007-09-13 11:40:59ISSUE PERMIT FOR 2 TWO FOUNDATIONS STAIRS AND
 ACCESSIBLE RAMPS FOR 2 MODULAR BUILDINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-09-10 Cont ID  
Sent By jwitmer Date 2007-09-10 Time 11:02 Rev Time 1.11
Received By jwitmer Date 2007-09-10 Time 11:02 Sent To  
Notes
2007-09-10 11:31:00BUILDING PLAN REVIEW
 PERMIT: 07020542
 ADD: 6600 N JOG RD
 CONT: HOLT CONTRACTORS
 TEL: (561)212-9099
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) COMPLIED, NOC NOT REQUIRED FOR SOLID WASTE
 AUTHORITY
  
 3) THE PERMIT APPLICATION DESCRIPTION OF PROJECT IN
 DETAIL "REMOVE & REPLACE TWO TEMPORARY OFFICE MODULAR
 BUILDINGS" , INDICATES A TEMPORARY OFFICE USAGE BY
 DEFINITION THIS IS LESS THAN 180 DAYS SEE
 ADMINISTRATIVE CODE 107.1*.THIS OFFICE DISCUSSED THE
 REQUIREMENTS FOR DRY STACK FOUNDATIONS TO BE USED FOR A
 PERMANENT INSTALLATION WITH THE DESIGNERS, SINCE THAT
 TIME THIS OFFICE HAD CONCERNS WITH THIS TYPE OF
 INSTALLATION AND TO GET A GENERAL CONSENSUSWE LOOKED
 AT THE FAQ ON THE DCA WEBSITE FOR INFORMATION ON
 MANUFACTURED BUILDINGS FOR NON-RESIDENTIAL USE. THERE
 WAS
 NO INFORMATION AS TO COMMERCIAL ASPECTS FOR FOUNDATIONS
 BUT FOR RESIDENTIAL UNITS:FIND THE FOLLOWING
 STATEMENT ABOUT MODULAR HOMES WHICH ARE DESIGNED TO
 FBC, AS OPPOSED TO MOBILE HOMES WHICH ARE DESIGNED TO
 HUD STANDARDS.BOTH TYPES ARE CLASSIFIED AS
 MANUFACTURED BUILDINGS.THE FOLLOWING EXTRACT IS
 SPECIFIC TO MODULAR HOMES (UNDER FBC):
  
 EXTRACT FROM:
 WWW.DCA.STATE.FL.US/FBC/MANUFACTURED_BUILDINGS/MOBILE_V
 S_MODULAR_HOMES_REV.PDF
  
  
 MODULAR HOMES?ARE DESIGNED, BUILT, PERMITTED AND
 INSPECTED TO THE FLORIDA BUILDING CODE (FBC), AND MUST
 BE INSTALLED ON PERMANENT FOUNDATIONS (E.G., POURED
 FOOTERS, STEM WALLS & POURED PIERS OR ENGINEERED SLABS,
 JUST LIKE SITE BUILT HOMES) THAT ARE DESIGNED AND BUILT
 SPECIFICALLY FOR THAT HOME BY A CONTRACTOR LICENSED BY
 THE DEPARTMENT OF BUSINESS & PROFESSIONAL REGULATION
 (DBPR). IT IS A VIOLATION OF FLORIDA STATUTES FOR A
 MOBILE HOME INSTALLER TO INSTALL A MODULAR HOME. TO BE
 ACCEPTABLE IN FLORIDA, A MODULAR HOME MUST BEAR THE
 INSIGNIA OF THE FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS
 (DCA) ON THE INSIDE OF THE COVER OF THE HOME?S
 ELECTRICAL PANEL. THEY ARE CONSIDERED REAL PROPERTY
 WHEN INSTALLED ON A PERMANENT FOUNDATION, AND INSURED
 AS SUCH.
 NOTE: A FEW MODULAR MANUFACTURERS CONTINUE TO PRODUCE
 THEIR HOMES ON A MOBILE HOME TYPE CHASSIS (CALLED
 ?ON-FRAME? CONSTRUCTION, WHICH IS ALLOWED IN THE FBC)
 AND TRANSPORT THEM ON WHEELS AND AXLES JUST LIKE MOBILE
 HOMES; AS OPPOSED TO MOST WHO CONSTRUCT [WITHOUT THE
 CHASSIS] ON TYPICAL FLOOR JOIST TYPE CONSTRUCTION AND
 TRANSPORT THE MODULES ON A FLAT BED TRAILER, LIFTING
 THEM INTO PLACE ONSITE WITH A CRANE. NO MATTER THE
 METHOD OF CONSTRUCTION, THE MODULAR HOME MUST BE
 INSTALLED BY A LICENSED CONTRACTOR ON A PERMANENT
 FOUNDATION, AS SPECIFIED IN CHAPTER 428.4 FBC.
  
  
 THESE ARE SPECIFICALLY FOR RESIDENTIAL USE BUT THE
 PRINCIPLE IS THE SAME.AMONG THE MULTIPLE REFERENCES
 TO "PERMANENT FOUNDATIONS", THE DCA GIVE EXAMPLES AS
 "POURED FOOTERS, STEM WALLS & POURED PIERS OR
 ENGINEERED SLABS, JUST LIKE SITE BUILT HOMES".
  
 WEDNESDAY JUNE 20/2007 THIS SAME QUESTION WAS ASKED TO
 THE BUILDING CODE ADVISORY BOARD OF PALM BEACH COUNTY,
 IN THE CASE OF BUILDINGS TO BE INSTALLED AS A PERMANENT
 INSTALLATION
 ( GREATER THAN 180 DAYS) THERE WAS AN AGREEMEENT THAT
 SOME TYPE OF PERMANENT FOUNDATION WOULD BE REQUIRED, AS
 HOW THIS WOULD BE DETAILED WOULD DEPEND ON THE
 INTERPRETATION OF THE JHA.
  
 SEE ATTACHED HUD TYPE FOUNDATION EXTRACT FROM:
 WWW.DCA.STATE.FL.US/FBC/MANUFACTURED_BUILDINGS/Q_AND_%2
 0AV2.PDF
  
 11. CAN A MODULAR RESIDENCE BE INSTALLED ON A HUD TYPE
 (15C) FOUNDATION WITH PADS, DRY STACKED BLOCKS AND
 TIE-DOWNS?
 ANSWER. THIS IS A SITE RELATED ISSUE, SUBJECT TO CODE
 INTERPRETATION AND ENFORCEMENT BY THE LOCAL BUILDING
 OFFICIAL. CHAPTER 428.4, FBC STATES: "IF THE PLANS ARE
 FOR A RESIDENTIAL MANUFACTURED (MODULAR) BUILDING,
 CERTIFICATION FROM THE DESIGN PROFESSIONAL RESPONSIBLE
 FOR THE PLANS THAT THE STRUCTURE HAS BEEN DESIGNED ONLY
 FOR ERECTION OR INSTALLATION ON A SITE BUILT PERMANENT
 FOUNDATION AND IS NOT DESIGNED TO BE MOVED ONCE SO
 ERECTED".
 NOTE: THE INSTALLATION OF A MODULAR HOME ON A HUD TYPE
 FOUNDATION MAY PRECLUDE THE CLASSIFICATION OF THE
 RESIDENCE AS ?REAL PROPERTY? BY THE LOCAL PROPERTY
 APPRAISER?S OFFICE AND TRIGGER HIGHER INSURANCE RATES
 THAT TYPICALLY APPLY TO HUD TYPE HOMES, OFTEN
 CLASSIFIED AS ?PERSONAL PROPERTY?.
  
 AS OF THIS MORNING (6-21-07) MEETING WITH THE ASSIT.
 BUILING OFFICIAL ROBERT BROWN AND THE BUILDING OFFICIAL
 NEIL MELICK AND REVIEWING THE FINDINGS OF THE BCAB
 BOARD THIS OFFICE FEELS THE NEED FOR A PERMANENT
 FOUNDATION WILL BE REQUIRED ALONG WITH TIE-DOWN
 INFORMATION TO TIE THE STRUCTURE DOWN THROUGH TO THE
 FOUNDATION. THE TAC THAT GAVE A RECOMMENDATION
 INDICATED THAT A BINDING INTERPRETATION WOULD NEED TO
 BE A DECLARATORY STATMENT, THE BUILDING
 OFFICIALS INTERPRETATION STANDS UNTIL A DEC STATEMENT
 IS DECLARED OR YOU GO FOR A VARIANCE IN DISAGREEMENT OF
 THE BUILDING OFFICIALS INTERPRETATION.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-06-21 Cont ID  
Sent By jwitmer Date 2007-06-21 Time 15:12 Rev Time 3.33
Received By jwitmer Date 2007-06-21 Time 15:11 Sent To  
Notes
2007-09-10 11:15:47BUILDING PLAN REVIEW
 PERMIT: 07020542
 ADD: 6600 N JOG RD
 CONT: HOLT CONTRACTORS
 TEL: (561)212-9099
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) COMPLIED, SOLID WASTE AUTHORITY DOES NOT NEED NOC.
  
 3) 2ND REQUEST,THE PERMIT APPLICATION DESCRIPTION OF
 PROJECT IN DETAIL "REMOVE & REPLACE TWO TEMPORARY
 OFFICE MODULAR BUILDINGS" , INDICATES A TEMPORARY
 OFFICE USAGE BY DEFINITION THIS IS LESS THAN 180 DAYS
 SEE ADMINISTRATIVE CODE 107.1*.THIS OFFICE DISCUSSED
 THE REQUIREMENTS FOR DRY STACK FOUNDATIONS TO BE USED
 FOR A PERMANENT INSTALLATION WITH THE DESIGNERS, SINCE
 THAT TIME THIS OFFICE HAD CONCERNS WITH THIS TYPE OF
 INSTALLATION AND TO GET A GENERAL CONSENSUSWE LOOKED
 AT THE FAQ ON THE DCA WEBSITE FOR INFORMATION ON
 MANUFACTURED BUILDINGS FOR NON-RESIDENTIAL USE. THERE
 WAS
 NO INFORMATION AS TO COMMERCIAL ASPECTS FOR FOUNDATIONS
 BUT FOR RESIDENTIAL UNITS:FIND THE FOLLOWING
 STATEMENT ABOUT MODULAR HOMES WHICH ARE DESIGNED TO
 FBC, AS OPPOSED TO MOBILE HOMES WHICH ARE DESIGNED TO
 HUD STANDARDS.BOTH TYPES ARE CLASSIFIED AS
 MANUFACTURED BUILDINGS.THE FOLLOWING EXTRACT IS
 SPECIFIC TO MODULAR HOMES (UNDER FBC):
  
 EXTRACT FROM:
 WWW.DCA.STATE.FL.US/FBC/MANUFACTURED_BUILDINGS/MOBILE_V
 S_MODULAR_HOMES_REV.PDF
  
  
 MODULAR HOMESARE DESIGNED, BUILT, PERMITTED AND
 INSPECTED TO THE FLORIDA BUILDING CODE (FBC), AND MUST
 BE INSTALLED ON PERMANENT FOUNDATIONS (E.G., POURED
 FOOTERS, STEM WALLS & POURED PIERS OR ENGINEERED SLABS,
 JUST LIKE SITE BUILT HOMES) THAT ARE DESIGNED AND BUILT
 SPECIFICALLY FOR THAT HOME BY A CONTRACTOR LICENSED BY
 THE DEPARTMENT OF BUSINESS & PROFESSIONAL REGULATION
 (DBPR). IT IS A VIOLATION OF FLORIDA STATUTES FOR A
 MOBILE HOME INSTALLER TO INSTALL A MODULAR HOME. TO BE
 ACCEPTABLE IN FLORIDA, A MODULAR HOME MUST BEAR THE
 INSIGNIA OF THE FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS
 (DCA) ON THE INSIDE OF THE COVER OF THE HOME?S
 ELECTRICAL PANEL. THEY ARE CONSIDERED REAL PROPERTY
 WHEN INSTALLED ON A PERMANENT FOUNDATION, AND INSURED
 AS SUCH.
 NOTE: A FEW MODULAR MANUFACTURERS CONTINUE TO PRODUCE
 THEIR HOMES ON A MOBILE HOME TYPE CHASSIS (CALLED
 ?ON-FRAME? CONSTRUCTION, WHICH IS ALLOWED IN THE FBC)
 AND TRANSPORT THEM ON WHEELS AND AXLES JUST LIKE MOBILE
 HOMES; AS OPPOSED TO MOST WHO CONSTRUCT [WITHOUT THE
 CHASSIS] ON TYPICAL FLOOR JOIST TYPE CONSTRUCTION AND
 TRANSPORT THE MODULES ON A FLAT BED TRAILER, LIFTING
 THEM INTO PLACE ONSITE WITH A CRANE. NO MATTER THE
 METHOD OF CONSTRUCTION, THE MODULAR HOME MUST BE
 INSTALLED BY A LICENSED CONTRACTOR ON A PERMANENT
 FOUNDATION, AS SPECIFIED IN CHAPTER 428.4 FBC.
  
  
 THESE ARE SPECIFICALLY FOR RESIDENTIAL USE BUT THE
 PRINCIPLE IS THE SAME.AMONG THE MULTIPLE REFERENCES
 TO "PERMANENT FOUNDATIONS", THE DCA GIVE EXAMPLES AS
 "POURED FOOTERS, STEM WALLS & POURED PIERS OR
 ENGINEERED SLABS, JUST LIKE SITE BUILT HOMES".
  
 WEDNESDAY JUNE 20/2007 THIS SAME QUESTION WAS ASKED TO
 THE BUILDING CODE ADVISORY BOARD OF PALM BEACH COUNTY,
 IN THE CASE OF BUILDINGS TO BE INSTALLED AS A PERMANENT
 INSTALLATION
 ( GREATER THAN 180 DAYS) THERE WAS AN AGREEMEENT THAT
 SOME TYPE OF PERMANENT FOUNDATION WOULD BE REQUIRED, AS
 HOW THIS WOULD BE DETAILED WOULD DEPEND ON THE
 INTERPRETATION OF THE JHA.
  
 SEE ATTACHED HUD TYPE FOUNDATION EXTRACT FROM:
 WWW.DCA.STATE.FL.US/FBC/MANUFACTURED_BUILDINGS/Q_AND_%2
 0AV2.PDF
  
 11. CAN A MODULAR RESIDENCE BE INSTALLED ON A HUD TYPE
 (15C) FOUNDATION WITH PADS, DRY STACKED BLOCKS AND
 TIE-DOWNS?
 ANSWER. THIS IS A SITE RELATED ISSUE, SUBJECT TO CODE
 INTERPRETATION AND ENFORCEMENT BY THE LOCAL BUILDING
 OFFICIAL. CHAPTER 428.4, FBC STATES: "IF THE PLANS ARE
 FOR A RESIDENTIAL MANUFACTURED (MODULAR) BUILDING,
 CERTIFICATION FROM THE DESIGN PROFESSIONAL RESPONSIBLE
 FOR THE PLANS THAT THE STRUCTURE HAS BEEN DESIGNED ONLY
 FOR ERECTION OR INSTALLATION ON A SITE BUILT PERMANENT
 FOUNDATION AND IS NOT DESIGNED TO BE MOVED ONCE SO
 ERECTED".
 NOTE: THE INSTALLATION OF A MODULAR HOME ON A HUD TYPE
 FOUNDATION MAY PRECLUDE THE CLASSIFICATION OF THE
 RESIDENCE AS ?REAL PROPERTY? BY THE LOCAL PROPERTY
 APPRAISER?S OFFICE AND TRIGGER HIGHER INSURANCE RATES
 THAT TYPICALLY APPLY TO HUD TYPE HOMES, OFTEN
 CLASSIFIED AS "PERSONAL PROPERTY".
  
 AS OF THIS MORNING (6-21-07) MEETING WITH THE ASSIT.
 BUILING OFFICIAL ROBERT BROWN AND THE BUILDING OFFICIAL
 NEIL MELICK AND REVIEWING THE FINDINGS OF THE BCAB
 BOARD THIS OFFICE FEELS THE NEED FOR A PERMANENT
 FOUNDATION WILL BE REQUIRED ALONG WITH TIE-DOWN
 INFORMATION TO TIE THE STRUCTURE DOWN THROUGH TO THE
 FOUNDATION. THE RECOMENDATIONS FROM THE TAC ARE AT BEST
 RECOOMMENDATIONS IT WILL TAKE A DECLATORY STATEMENT TO
 REVERSE THE BUILDING OFFICIALS INTERPRETATION OR GO FOR
 A VARIANCE FROM THE BUILDING BOARD OF ADJUSTMENT AND
 APPEAL DISSAGREEING THE WITH THE BUILDING OFFICIALS
 INTERPRETATION.
  
 4-9 COMPLIED.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
2007-06-21 15:45:19BUILDING PLAN REVIEW
 PERMIT: 07020542
 ADD: 6600 N JOG RD
 CONT: HOLT CONTRACTORS
 TEL: (561)212-9099
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) THE PERMIT APPLICATION DESCRIPTION OF PROJECT IN
 DETAIL "REMOVE & REPLACE TWO TEMPORARY OFFICE MODULAR
 BUILDINGS" , INDICATES A TEMPORARY OFFICE USAGE BY
 DEFINITION THIS IS LESS THAN 180 DAYS SEE
 ADMINISTRATIVE CODE 107.1*.THIS OFFICE DISCUSSED THE
 REQUIREMENTS FOR DRY STACK FOUNDATIONS TO BE USED FOR A
 PERMANENT INSTALLATION WITH THE DESIGNERS, SINCE THAT
 TIME THIS OFFICE HAD CONCERNS WITH THIS TYPE OF
 INSTALLATION AND TO GET A GENERAL CONSENSUSWE LOOKED
 AT THE FAQ ON THE DCA WEBSITE FOR INFORMATION ON
 MANUFACTURED BUILDINGS FOR NON-RESIDENTIAL USE. THERE
 WAS
 NO INFORMATION AS TO COMMERCIAL ASPECTS FOR FOUNDATIONS
 BUT FOR RESIDENTIAL UNITS:FIND THE FOLLOWING
 STATEMENT ABOUT MODULAR HOMES WHICH ARE DESIGNED TO
 FBC, AS OPPOSED TO MOBILE HOMES WHICH ARE DESIGNED TO
 HUD STANDARDS.BOTH TYPES ARE CLASSIFIED AS
 MANUFACTURED BUILDINGS.THE FOLLOWING EXTRACT IS
 SPECIFIC TO MODULAR HOMES (UNDER FBC):
  
 EXTRACT FROM:
 WWW.DCA.STATE.FL.US/FBC/MANUFACTURED_BUILDINGS/MOBILE_V
 S_MODULAR_HOMES_REV.PDF
  
  
 MODULAR HOMES?ARE DESIGNED, BUILT, PERMITTED AND
 INSPECTED TO THE FLORIDA BUILDING CODE (FBC), AND MUST
 BE INSTALLED ON PERMANENT FOUNDATIONS (E.G., POURED
 FOOTERS, STEM WALLS & POURED PIERS OR ENGINEERED SLABS,
 JUST LIKE SITE BUILT HOMES) THAT ARE DESIGNED AND BUILT
 SPECIFICALLY FOR THAT HOME BY A CONTRACTOR LICENSED BY
 THE DEPARTMENT OF BUSINESS & PROFESSIONAL REGULATION
 (DBPR). IT IS A VIOLATION OF FLORIDA STATUTES FOR A
 MOBILE HOME INSTALLER TO INSTALL A MODULAR HOME. TO BE
 ACCEPTABLE IN FLORIDA, A MODULAR HOME MUST BEAR THE
 INSIGNIA OF THE FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS
 (DCA) ON THE INSIDE OF THE COVER OF THE HOME?S
 ELECTRICAL PANEL. THEY ARE CONSIDERED REAL PROPERTY
 WHEN INSTALLED ON A PERMANENT FOUNDATION, AND INSURED
 AS SUCH.
 NOTE: A FEW MODULAR MANUFACTURERS CONTINUE TO PRODUCE
 THEIR HOMES ON A MOBILE HOME TYPE CHASSIS (CALLED
 ?ON-FRAME? CONSTRUCTION, WHICH IS ALLOWED IN THE FBC)
 AND TRANSPORT THEM ON WHEELS AND AXLES JUST LIKE MOBILE
 HOMES; AS OPPOSED TO MOST WHO CONSTRUCT [WITHOUT THE
 CHASSIS] ON TYPICAL FLOOR JOIST TYPE CONSTRUCTION AND
 TRANSPORT THE MODULES ON A FLAT BED TRAILER, LIFTING
 THEM INTO PLACE ONSITE WITH A CRANE. NO MATTER THE
 METHOD OF CONSTRUCTION, THE MODULAR HOME MUST BE
 INSTALLED BY A LICENSED CONTRACTOR ON A PERMANENT
 FOUNDATION, AS SPECIFIED IN CHAPTER 428.4 FBC.
  
  
 THESE ARE SPECIFICALLY FOR RESIDENTIAL USE BUT THE
 PRINCIPLE IS THE SAME.AMONG THE MULTIPLE REFERENCES
 TO "PERMANENT FOUNDATIONS", THE DCA GIVE EXAMPLES AS
 "POURED FOOTERS, STEM WALLS & POURED PIERS OR
 ENGINEERED SLABS, JUST LIKE SITE BUILT HOMES".
  
 WEDNESDAY JUNE 20/2007 THIS SAME QUESTION WAS ASKED TO
 THE BUILDING CODE ADVISORY BOARD OF PALM BEACH COUNTY,
 IN THE CASE OF BUILDINGS TO BE INSTALLED AS A PERMANENT
 INSTALLATION
 ( GREATER THAN 180 DAYS) THERE WAS AN AGREEMEENT THAT
 SOME TYPE OF PERMANENT FOUNDATION WOULD BE REQUIRED, AS
 HOW THIS WOULD BE DETAILED WOULD DEPEND ON THE
 INTERPRETATION OF THE JHA.
  
 SEE ATTACHED HUD TYPE FOUNDATION EXTRACT FROM:
 WWW.DCA.STATE.FL.US/FBC/MANUFACTURED_BUILDINGS/Q_AND_%2
 0AV2.PDF
  
 11. CAN A MODULAR RESIDENCE BE INSTALLED ON A HUD TYPE
 (15C) FOUNDATION WITH PADS, DRY STACKED BLOCKS AND
 TIE-DOWNS?
 ANSWER. THIS IS A SITE RELATED ISSUE, SUBJECT TO CODE
 INTERPRETATION AND ENFORCEMENT BY THE LOCAL BUILDING
 OFFICIAL. CHAPTER 428.4, FBC STATES: "IF THE PLANS ARE
 FOR A RESIDENTIAL MANUFACTURED (MODULAR) BUILDING,
 CERTIFICATION FROM THE DESIGN PROFESSIONAL RESPONSIBLE
 FOR THE PLANS THAT THE STRUCTURE HAS BEEN DESIGNED ONLY
 FOR ERECTION OR INSTALLATION ON A SITE BUILT PERMANENT
 FOUNDATION AND IS NOT DESIGNED TO BE MOVED ONCE SO
 ERECTED".
 NOTE: THE INSTALLATION OF A MODULAR HOME ON A HUD TYPE
 FOUNDATION MAY PRECLUDE THE CLASSIFICATION OF THE
 RESIDENCE AS ?REAL PROPERTY? BY THE LOCAL PROPERTY
 APPRAISER?S OFFICE AND TRIGGER HIGHER INSURANCE RATES
 THAT TYPICALLY APPLY TO HUD TYPE HOMES, OFTEN
 CLASSIFIED AS ?PERSONAL PROPERTY?.
  
 AS OF THIS MORNING MEETING WITH THE ASSIT. BUILING
 OFFICIAL ROBERT BROWN AND THE BUILDING OFFICIAL NEIL
 MELICK AND REVIEWING THE FINDINGS OF THE BCAB BOARD
 THIS OFFICE FEELS THE NEED FOR A PERMANENT FOUNDATION
 WILL BE REQUIRED ALONG WITH TIE-DOWN INFORMATION TO TIE
 THE STRUCTURE DOWN THROUGH TO THE FOUNDATION.
  
 4) COMPLIED.
  
 5-8)COMPLIED.
  
 9)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 10-11)COMPLIED.
  
 12) A FULL FOUNDATION WILL BE REQUIRED AS STATED IN
 COMMENT # 3.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-29 Cont ID  
Sent By jwitmer Date 2007-03-29 Time 12:29 Rev Time 2.22
Received By jwitmer Date 2007-03-29 Time 12:29 Sent To  
Notes
2007-03-29 14:24:58BUILDING PLAN REVIEW
 PERMIT: 07020542
 ADD: 6600 N JOG RD
 CONT: HOLT CONTRACTORS
 TEL: (561)212-9099
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) THE PERMIT APPLICATION DESCRIPTION OF PROJECT IN
 DETAIL "REMOVE & REPLACE TWO TEMPORARY OFFICE MODULAR
 BUILDINGS" , INDICATES A TEMPORARY OFFICE USAGE BY
 DEFINITION THIS IS LESS THAN 180 DAYS SEE
 ADMINISTRATIVE CODE 107.1*. THE CONCERN IS IF THE OTHER
 UNITS THAT ARE BEING PULLED OUT WERE THEY CONSIDERED
 "TEMPORARY"?IF THESE UNITS ARE TO BE USED FOR MORE
 THAN 180 DAYS THE UNITS WILL NEED TO MEET THE
 REQUIREMENTS OF 1805.2 MINIMUM DEPTH OF THE FOOTING/
 FOUNDATIONBEING 12" BELOW GRADE, NOT THE BLOCK LAID
 AT GRADE LEVEL. THIS CONCERN WOULD BE
 FOR BOTH UNITS THAT ARE APPLIED FOR UNDER THIS PREMIT.
  
 4)THERE IS NO SITE PLAN SHOWING THE LOCATION OF THE
 STRUCTURES, THIS MAY REQUIRE A ADDRESSING STOP IN THE
 NEXT REVIEW, ALSO NOT SHOWING THE LOCATION THERE MAYBE
 ISSUES WITH
 FLOODZONES.
  
 5) THE STATE APPROVED PLAN HWC PLAN# 1954-8043F DOES
 HAVE A STATE APPROVAL NUMBER OF 21369, IN REVIEWING THE
 PLAN ON LINE AS WELL AS THE STATE APPROVED PLAN
 SUBMITTED
 THE SITE INSTALLED ITEMS ARE MISSING INFORMATION: A)
 FOUNDATION (TERMPORARY180 OR LESS)OR 1805.2
 REQUIREMENTS.
 B) ACCESSIBLE RAMPS, AND GENERAL ACCESS TO THE
 STRUCTURE THRU STAIRS.
 C) ACCESSIBLE PARKING LOT.
 D) 9/11EXTERIOR GLAZING PROTECTION, STORM SHUTTERS E)
 17 WINDOW AND DOOR COVERINGS IF REQUIRED- HIGH WIND
 DEBRIS REGION . 110 MPH.
  
 6)FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 STORM SHUTTERS
  
 7) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 8)) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 9)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 10) PLANS INTERNATIONAL ENGINEERING ASSOCIATES, INC.
 ARE COPIES NOT ORIGINALS, PLEASE PROVIDE ORIGINALS.
  
 11) PLANS INDICATE THE USE OF PREFAB ACCESSIBLE RAMP
 PROVIDE ADDITIONAL INFORMATION, IT APPEARS TO BE A
 HIGHER THAN 30"
  
 12)MODULAR BUILDING BY UNITED MODULAR THE 3 BAY UNIT
 UNTIL THE LETTER IS SUBMITTED INDICATING THE TEMPORARY
 USE IS LESS THAN 180 DAYS
 WE CAN'T DETERMINE IF THE DRY STACK BLOCK OR A FULL
 FOUNDATION EMBEDDED 12" BELOW THE SURFACE WILL BE
 REQUIRED.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-09-04 Cont ID  
Sent By dpalmer Date 2007-09-04 Time 16:32 Rev Time 0.00
Received By dpalmer Date 2007-09-04 Time 16:32 Sent To  
Notes
2007-09-04 16:34:30SHEET WITH ELECTRICAL SERVICE RISER(S) ARE FOR FEEDIGN
 THE TWO STATE APPROVED PLANS FOR MANUFATCURED
 BUILDINGS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-06-04 Cont ID  
Sent By dpalmer Date 2007-06-04 Time 17:02 Rev Time 0.00
Received By dpalmer Date 2007-06-04 Time 12:41 Sent To  
Notes
2007-06-04 17:03:29** UNSAT **
  
  
 1) NOTE: PLEASE SEE THE COMMENTS FROM THE PREVIOUS
 REVIEW WHICH MENTIONS THE ENERGY CALCULATIONS CONTAIN A
 RAISED SEAL OVER A PHOTO-COPIED SIGNATURE WHICH IS NOT
 PERMITTED PER FLORIDA STATUTES 471.023, FAC
 61G15-23.002 AND FBC 13-103.1.1.1
 PLEASE SEE THE ENERGY CALCULATIONS ARE NOT COMPLETE AS
 NO INTERIOR LIGHTING IS FIGURED INTO THE CALCULATIONS.
 PLEASE COORDINATE ALL LIGHTING ON PLANS WITH ENERGY
 CALCULATIONS.
  
 2) NOTE: PLEASE SEE RISER INDICATES ONLY A 100AMP FEED
 TO PANEL *B* WHICH ACTUALLY CONTAINS A LOAD HIGHER THAN
 100AMPS.
 THIS EXCEEDS THE RATING OF CONDUCTORS AND BREAKER.
 240.4, 310.16, 408, ETC.
  
 3) NOTE: PLEASE SEE THE EXISTING PANEL FOR THE TWO
 TRAILERS IS BEING SHOWN A MLO WITH TWO BREAKERS FOR
 EACH TRAILER, PLEASE SEE 230.70/71 AS NO MORE THAN
 6SPACES IS PERMITTED IN SERVICE EQUIPMENT. PLEASE
 CLARIFY WHERE THE SINGLE MAIN IS LOCATED OR WILL A MCB
 BE INSTALLED IN THIS PANEL?
  
 4) NOTE: PLEASE SEE THE ENTIRE PACKAGE SUBMITTED
 APPEARS THAT ONE SET OF PLANS IS FOR AN OLDER
 TRAILER(3UNITS) WHICH IS NOT BEING BROUGHT UP TO CODE
 AND ONE (2 TRAILERS) WHICH IS BEING BROUGHT UP TO
 CODE?
 PLEASE SEE PREVIOUS REVIEW NOTES WHICH REQUESTED *ALL*
 OLD/ VOIDED SHEETS TO BE COMPLETELY REMOVED AND FOR
 ONLY NEW SHEETS TO BE INSERTED INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING. HOWEVER THE OLD/VOIDED SHEETS
 WERE LEFT IN SETS.
 PLEASE SEE COMMENTS FROM OTHER TRADES WITH RESPECT TO
 THE SETS AND PERMITTING.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-04 Cont ID  
Sent By dpalmer Date 2007-03-04 Time 13:03 Rev Time 0.00
Received By dpalmer Date 2007-03-04 Time 12:35 Sent To  
Notes
2007-03-04 13:04:15** UNSAT**
  
  
 1) NOTE: PLEASE SEE THAT THE SCOPE OF WORK IS NOT
 COMPLETELY CLEAR AT THIS TIME. THE PLANS APPEAR TO SHOW
 TWO BUILDINGS ALONG WITH PERMIT APPLICATION WHICH ALSO
 MENTIONS TWO BUILDINGS TO BE DONE.
 PLEASE SEE THE ONE SET OF TRAILERS TO MAKE ONE BUILDING
 DO NOT SEEM TO SHOW THESE AS STATE APPROVED. PLEASE
 ALSO SEE THE PLANS WHICH WERE SUBMITTED FOR THE OTHER
 BUILDING WITH THREE TRAILERS SHALL BEAR THE ORIGINAL
 STAMP FROM THE STATE. THESE PLANS ARE PHOTO-COPIES OF
 STATE STAMPED PLANS. THIS OFFICE IS AWARE THAT THE
 PLANS DO NOT REQUIRE AN ORIGINAL SIGNATURE, DATE AND
 SEAL FROM THE DESIGNER PROFESSIONAL. THE STATE STAMP IS
 REQUIRED FOR ALL SHEETS AND IS REQUIRED TO BE
 ORIGINAL.
 PLEASE SEE THE FLORIDA ENERGY CALCULATIONS WERE
 SUBMITTED FOR THE TWO TRAILER BUILDING CONTAIN RAISED
 SEALS OVER A PHOTO-COPIED SIGNATURE WHICH IS REQUIRED
 TO BE ORIGINAL. FS 471.025, FAC 61G15-23.002
 PLEASE CLARIFY WHERE THE INTERIOR LIGHTING ALLOWANCES
 ARE SHOWN? ONLY EXTERIOR INPUT IS COULD BE LOCATED ON
 SHEETS SUBMITTED. PLEASE CLARIFY 13-415.2
 THIS IS THE ONLY WAY THAT VERIFICATION CAN BE MADE THAT
 NO CHANGES HAVE BEEN MADE TO THE STATE APPROVED PLANS.
 FBC 106.1.2 ADMIN SECTION.
 FS 553.79
  
 2) NOTE: PLEASE CLARIFY THE ELECTRICAL RISER AND PLANS
 AS SUBMITTED FOR SHEET 1OF 2. PLEASE SEE PLANS INDICATE
 NEW METERS, YET PLANS DO NOT SHOW THIS?
 PLEASE VERIFY WHERE THE SERVICE COMES FROM? IS THIS
 FEED FROM FPL? MAIN DISCONNECT IS BEING SHOWN ON THE
 LINE SIDE OF METERING DEVICES.
 PLEASE SEE NO METERS ON RISER?
 PLEASE SEE PANELS ON RISER DO NOT INDICATE BEING MCB?
 PLEASE CLARIFY.
 PLEASE CLARIFY IF THE TWO PANELS WHICH ARE SHOWN AS
 EXISTING ON THE TWO TRAILER BUILDINGS CONTAIN
 DISCONNECTS?
 250.32, 215.5, 225.31-39 ETC.
  
 3) NOTE: PLEASE SEE THAT THE FOLLOWING CODES SHALL BE
 STATED ON PLANS.
 NFPA-70 2005.
  
 4) NOTE: PLEASE SUBMIT THE AIC RATINGS FOR ALL SERVICE
 EQUIPMENT.
 110.9.
 FBC 106.1.2
  
 5) NOTE: PLEASE CLARIFY WHAT TYPE OF LIGHTING AND
 LEVELS ARE PROVIDED FOR EGRESS OF STAIRS AND PATHS OUT
 AND AWAY FROM THESE BUILDINGS.
 LS 101 7.8.1.3, 7.9.2.2
  
 '* ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-09-11 Cont ID  
Sent By mawillia Date 2007-09-11 Time 11:52 Rev Time 0.00
Received By mawillia Date 2007-09-11 Time 11:52 Sent To  
Notes
2007-09-11 11:52:39*****APPROVED*****
  
  
 PLAN SHEETS (MODULAR 2 OF 4) AND 2 OF 5 WERE STAMPED,
 INTIALED, AND DATED.
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-06-05 Cont ID  
Sent By mawillia Date 2007-06-05 Time 16:02 Rev Time 0.00
Received By mawillia Date 2007-06-05 Time 15:35 Sent To  
Notes
2007-06-05 15:39:48*****DENIED*****
  
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.THE REMOVAL AND(OR) REPLACEMENT OF THE MODULAR
 BUILDINGS SHALL NOT INTERFERE OR HINDER EMERGENCY
 RESPONSE ACCESS TO OR EGRESS FROM THE PROPERTY OR
 VICINITY THEREOF (INCLUDING FIRE LANES).
  
 3.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED. FOR EXAMPLE SEE SHEET FD1 UNDER STATE
 CODES.
  
 4.ALL SUBMITTED PLAN SHEETS SHALL HAVE THE ADDRESS OF
 WHERE THE SCOPE OF WORK WILL BE CONDUCTED IN THE TITLE
 BLOCK.
  
 5.PLEASE PROVIDE A SITE PLAN SHOWING THE HOW THE
 STRUCTURES RELATES TO STREETS, HYDRANTS, BUILDINGS,
 ETC. IN THE IMMEDIATE AREA.
  
 6.DISPLAY 2A:10BC RATED FIRE EXTINGUISHER(S) LOCATION
 IN THE PROPOSED STRUCTURES.
  
 7.WILL THESE PROPOSED STRUCTURES HAVE A FIRE ALARM
 AND/OR FIRE SPRINKLER SYSTEM IN ITS MAKEUP?
  
 8. PLEASE BE ADVISED THAT IF IT IS DETERMINED THAT AN
 INDEPENDENT NUMERICAL ADDRESS IS REQUIRED, THOSE
 NUMBERS SHALL BE NO LESS THE 6" IN HEIGHT AND NO LESS
 THAN 1" IN WIDTH.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-03-30 Cont ID  
Sent By mawillia Date 2007-03-30 Time 18:41 Rev Time 0.00
Received By mawillia Date 2007-03-30 Time 17:58 Sent To  
Notes
2007-03-30 18:40:51*****DENIED*****
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.THE REMOVAL AND(OR) REPLACEMENT OF THE MODULAR
 BUILDINGS SHALL NOT INTERFERE OR HINDER EMERGENCY
 RESPONSE ACCESS TO OR EGRESS FROM THE PROPERTY OR
 VICINITY THEREOF (INCLUDING FIRE LANES).
  
 3.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 4.ALL SUBMITTED PLAN SHEETS SHALL HAVE THE ADDRESS OF
 WHERE THE SCOPE OF WORK WILL BE CONDUCTED IN THE TITLE
 BLOCK.
  
 5.PLEASE PROVIDE A SITE PLAN SHOWING THE HOW THE
 STRUCTURES RELATES TO STREETS, HYDRANTS, BUILDINGS,
 ETC. IN THE IMMEDIATE AREA.
  
 6.DISPLAY 2A:10BC RATED FIRE EXTINGUISHER(S) LOCATION
 IN THE PROPOSED STRUCTURES.
  
 7.WILL THESE PROPOSED STRUCTURES HAVE A FIRE ALARM
 AND/OR FIRE SPRINKLER SYSTEM IN ITS MAKEUP?
  
 8. PLEASE BE ADVISED THAT IF IT IS DETERMINED THAT AN
 INDEPENDENT NUMERICAL ADDRESS IS REQUIRED, THOSE
 NUMBERS SHALL BE NO LESS THE 6" IN HEIGHT AND NO LESS
 THAN 1" IN WIDTH.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-31 Cont ID  
Sent By adarroug Date 2007-08-31 Time 16:54 Rev Time 0.00
Received By adarroug Date 2007-08-31 Time 16:54 Sent To  
Notes
2007-09-04 11:58:13TO "COMM" BD#44--EXPEDITED
2007-08-31 16:54:32WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-07 Cont ID  
Sent By adarroug Date 2007-05-07 Time 15:55 Rev Time 0.00
Received By adarroug Date 2007-05-07 Time 15:55 Sent To  
Notes
2007-05-17 09:46:07TO "COMM" BD#64
2007-05-07 15:55:23WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-30 Cont ID  
Sent By mawillia Date 2007-03-30 Time 17:54 Rev Time 0.00
Received By mawillia Date 2007-02-22 Time 13:09 Sent To  
Notes
2007-02-26 14:05:32TO "COMM" BD#8
2007-02-22 13:09:49WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-03-15 Cont ID  
Sent By rregueir Date 2007-03-15 Time 15:23 Rev Time 0.00
Received By rregueir Date 2007-03-15 Time 15:13 Sent To  
Notes
2007-03-15 15:23:58NO PERMITTED MECHANICAL WORK RELATED TO THIS PROJECT.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-09-10 Cont ID  
Sent By kstevens Date 2007-09-10 Time 18:12 Rev Time 0.00
Received By kstevens Date 2007-09-10 Time 17:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-06-18 Cont ID  
Sent By kstevens Date 2007-06-18 Time 10:14 Rev Time 0.00
Received By kstevens Date 2007-06-18 Time 10:14 Sent To  
Notes
2007-06-18 10:37:28DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. PLANS WILL BE APPROVED IF THE BUILDINGS IN QUESTION
 MAINTAIN THEIR APPROVAL THRU THE FLA. DEPT. OF
 COMMUNITY AFFAIRS WITH THE ALTERATIONS INDICATED. IF
 THE BUILDING/BUILDINGS LOSE THIS APPROVAL AND MUST
 COMPLY WITH THE FBC-2004 THEN SOME NEW ISSUES FOR
 PLUMBING AND ACCESSIBILITY MAY BE BROUGHT UP.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-03-14 Cont ID  
Sent By kstevens Date 2007-03-14 Time 17:05 Rev Time 0.00
Received By kstevens Date 2007-03-14 Time 17:05 Sent To  
Notes
2007-03-14 17:06:33PLUMBING OK--SEE CONCERNS EXPRESSED IN THE
 ELECTRICAL PLAN REVIEW COMMENT #1

Review Stop Z ZONING
Rev No 2 Status P Date 2007-05-25 Cont ID  
Sent By eschneid Date 2007-05-25 Time 14:22 Rev Time 0.00
Received By eschneid Date 2007-05-25 Time 14:22 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-03-01 Cont ID  
Sent By eschneid Date 2007-03-01 Time 14:30 Rev Time 0.00
Received By eschneid Date 2007-03-01 Time 14:30 Sent To  
Notes
2007-03-01 14:46:01FAILED
  
 1) A SITE PLAN OR SURVEY SHOWING THE LOCATION OF THE
 REPLACED BUILDINGS, INCLUDING SURROUNDING BUILDINGS AND
 FEATURES, IS REQUIRED.THE SITE PLAN OR SURVEY SHALL
 SHOW THE LOCATION OF WORK WITHIN THE CONTEXT OF THE
 LOCATION MAP SHOWN ON THE COVER OF THE PLANS.
  
 2) A LANDSCAPE PLAN, MEETING THE FOUNDATION PLANTING
 REQUIREMENTS OF SECTION 94-443(E), IS REQUIRED.
  
 CONTACT ERIC SCHNEIDER @ 822-1435.