| Plan Review Stops For Permit 07020528 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2007-03-03 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-03-03 |
Time |
16:57 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-03-03 |
Time |
16:33 |
Sent To |
|
|
| Notes |
| 2007-03-03 17:25:21 | ******APPROVED*****W/REMINDER | | | | | | | | | | | | A TWO-HOUR PRESSURE TEST AT 200 PSI WILL BE REQUIRED | | | SINCE THE MODIFICATION TO THE EXISTING SYSTEM AFFECTED | | | MORE THAN 20 SPRINKLERS.HOWEVER, IF THE MODIFICATIONS | | | CAN NOT BE ISOLATED, THIS OFFICE WILL REQUIRE THE | | | FOLLOWING INFORMATION ON YOUR LETTERHEAD:(1) THE | | | APPROPIATE CODE REFERENCE AND LANGUAGE,(2) THE | | | COMPLETE ADDRESS OF THE JOB SITE,AND (3) THE PERMIT | | | NUMBER.THE LETTER SHALL BE ENCLOSED AT TIME OF | | | INSPECTION TO BE FILED IN THE WPB FIRE PREVENTION | | | BUREAU. | | | | | | | | | PLAN SHEET FP-1 STAMPED, INITIALED, AND DATED.READY | | | FOR PERMIT ISSUANCE. |
|
|