Plan Review Details - Permit 07020506
Plan Review Stops For Permit 07020506
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2007-05-14 Cont ID  
Sent By mperson Date 2007-05-14 Time 10:04 Rev Time 0.45
Received By mperson Date 2007-05-14 Time 10:04 Sent To PC
Notes
2007-05-14 10:12:57REVISION: NEW LAYOUT WITH ALL NEW PIPING DUE TO DAMAGED
 EXISTING.
  
 ****************PROVISO****************
 IF DRYER ROOM IS A CONFINED SPACE, OPEN-
 INGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
 A} PER FBC-2004 FUEL GAS, SECTION 404.13.3AN
 INSULATED COPPER TRACER WIRE SHALL BE INSTALLED
 ADJACENT TO UNDERGROUND NONMETALLIC GAS PIPING. THE
 TRACER WIRE SIZE SHALL NOT BE LESS THAN 18 AWG AND THE
 INSULATION TYPE SHALL BE SUITABLE FOR DIRECT BURIAL.
  
 B} FBC-2004 FUEL GAS SEC. 404.12 OUTLET
 CLOSURES: GAS OUTLETS THAT DO NOT CON-
 NECT TO APPLIANCES SHALL BE CAPPED GAS
 TIGHT.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-04-17 Cont ID  
Sent By mperson Date 2007-04-17 Time 15:38 Rev Time 0.45
Received By mperson Date 2007-04-17 Time 15:38 Sent To PC
Notes
2007-04-17 15:52:12REVISION DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS REVISION PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. CLEARLY INDICATE ON THE RESUBMITTED REVISION THE
 EXISTING PIPING AND THE NEW PIPING.
  
 2. PLEASE INDICATE THE FOLLOWING FOR THE FUTURE
 GRILL:
  
 A} BTU LOAD FOR THE FUTURE GRILL.
 B} PIPE SIZES FOR THE FUTURE GRILL.
 C} PLEASE INDICATE THE PIPING FOR THE FUTURE GRILL AS
 NEW BECAUSE THERE IS NO INDICATION OF A GRILL ON THE
 PERMITTED FILE COPY PRINT.
  
 3. PLEASE CORRECT THE TOTAL BTU LOAD TO REFLECT THE
 ADDED BTU LOAD OF THE FUTURE GRILL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2007-02-27 Cont ID  
Sent By mperson Date 2007-02-27 Time 08:26 Rev Time 0.45
Received By mperson Date 2007-02-27 Time 08:26 Sent To PC
Notes
2007-02-27 08:44:15 
 IF DRYER ROOM IS A CONFINED SPACE, OPEN-
 INGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,500 CUBIC FEET REQUIRED.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-05-04 Cont ID  
Sent By adarroug Date 2007-05-04 Time 13:20 Rev Time 0.00
Received By adarroug Date 2007-05-04 Time 13:20 Sent To G
Notes
2007-05-04 13:20:24TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-03 Cont ID  
Sent By spalmer Date 2007-04-03 Time 17:08 Rev Time 0.00
Received By spalmer Date 2007-04-03 Time 17:08 Sent To G
Notes
2007-04-03 17:08:39TO MIKE PERSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-27 Cont ID  
Sent By mperson Date 2007-02-27 Time 08:27 Rev Time 0.00
Received By mperson Date 2007-02-22 Time 13:41 Sent To  
Notes
2007-02-22 13:41:28TO "G" BOX