 |
Plan Review Details - Permit 07020482
| Plan Review Stops For Permit 07020482 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2007-07-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-07-06 |
Time |
10:38 |
Rev Time |
1.11 |
| Received By |
jwitmer |
Date |
2007-07-06 |
Time |
10:38 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2007-06-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-06-26 |
Time |
15:04 |
Rev Time |
1.33 |
| Received By |
jwitmer |
Date |
2007-06-26 |
Time |
15:04 |
Sent To |
|
|
| Notes |
| 2007-06-26 15:38:25 | BUILDING PLAN REVIEW | | | PERMIT: 07020482 | | | ADD: 1501 PRESIDENTIAL WAY | | | CONT: GRUBER HALL CORP | | | TEL: (561)666-3377 | | | | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 3RDREVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF | | | THE COURT. | | | NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS | | | NOT ACTUALLY | | | COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF, | | | SUCH NOTICE IS | | | NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE | | | OF COMMENCEMENT | | | AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 3) SHEET A-1 DOES NOT INDICATE THE MINIMUM BUILDING | | | TYPE. THE LIST BELOW IS REQUIRED TO BE ON THE PLAN, | | | 110.2 FBC CODE, INFORMATION THAT IS REQUIRED FOR RECORD | | | KEEPING & FOR CERTIFICATE OF | | | OCCUPANCY: | | | A) THE EDITION OFTHE CODE UNDER WHICH | | | THE PROJECT WAS DESIGNED. | | | B) THE USE AND OCCUPANCY, IN ACCORDANCE | | | WITH THE PROVISIONS OF CHAPTER 3. | | | C) THE TYPE OF CONSTRUCTION AS DEFINED | | | IN CHAPTER 6, TABLE 601. | | | D) THE DESIGN OCCUPANT LOAD, SEE 1004. | | | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS | | | PROVIDED, WHETHER THE SPRINKLER SYSTEM | | | IS REQUIRED. | | | F) ANY SPECIAL STIPULATIONS & CONDITIONS | | | OF THE BUILDING PERMIT. | | | | | | THE PLANS ARE NOT CONSISTANT THE GENERAL INFO LISTING | | | THE ABOVE REQUIEMENTS STATES THIS IS A TYPE VB BUILDING | | | (NOTE C) , NOTE E INDICATES FIRE SPRINKLERS ARE PRESENT | | | AND AREA INCREASES WERE TAKEN. | | | THIS IS WHERE THERE IS A DISCREPANCY AT THE BOTTOM LEFT | | | OF SHEET A1 GENERAL SPECS NOTE 21THIS NOTE INDICATES | | | "NO FRONTAGE OR FIRE SPRINKLER INCREASES MADE". | | | THE DESIGNER OF RECORD NEEDS TO MAKE CORRECTIONS TO THE | | | PLAN, THE LETTER SIZE REPONSE CAN NOT BE PART OF THE | | | LEGAL DOCUMENTS SINCE IT IS NOT SIGNED NOR SEALED. | | | | | | COMMENT # 3FROM THE 2ND REVIEW: FROM THE PREVIOUS | | | REVIEW:SHEET A-1 PLANS INDICATED THIS IS A TYPE II | | | BUILDING,? THIS IS TO BE A MINIMUM BUILDING TYPE! THE | | | PLAN NOW INDICATE IT TO BE A TYPE V CONSTRUCTION. | | | THE PLANS ALSO STATE THAT THE TOTAL SQUAREFOOTAGE | | | FORTHE BUILDING TO BE 24,963 SQUARE FEET WHICH IS OVER | | | THE LIMIT OF 9,000 SQUARE FEET FOR A TYPE VB BUILDING. | | | FURTHER IN THE REVIEW I MENTIONED THAT IF THERE WERE | | | FIRE SPINKLERS INCREASES COULD BE TAKEN , AND THE | | | RESPONSE WAS THERE WERE NONE. I ALSO INDICATED THAT | | | FRONTAGE INCREASES COULD BE TAKEN, NONE WERE TAKEN. IF | | | THE FRONTAGE INCREASES WERE TAKEN I BELIEVE THE FIGURES | | | WOULD DECLARE FOR A MINIUM BUILDING TYPE THIS WOULD BE | | | A TYPE III-B BUILDING. PLEASE CORRECT THE MINIUM | | | BUILDING TYPE. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-06-14 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-06-14 |
Time |
17:41 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2007-06-14 |
Time |
17:41 |
Sent To |
PC |
|
| Notes |
| 2007-06-14 17:43:22 | BUILDING PLAN REVIEW | | | PERMIT: 07020482 | | | ADD: 1501 PRESIDENTIAL WAY | | | CONT: GRUBER HALL CORP | | | TEL: (561)666-3377 | | | | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2NDREVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF | | | THE COURT. | | | NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS | | | NOT ACTUALLY | | | COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF, | | | SUCH NOTICE IS | | | NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE | | | OF COMMENCEMENT | | | AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 3) COMMENT # 4 FROM THE PREVIOUS REVIEW:SHEET A-1 | | | PLANS INDICATED THIS IS A TYPE II BUILDING,? THIS IS TO | | | BE A MINIMUM BUILDING TYPE! THE PLAN NOW INDICATE IT TO | | | BE A TYPE V CONSTRUCTION. | | | THE PLANS ALSO STATE THAT THE TOTAL SQUAREFOOTAGE | | | FORTHE BUILDING TO BE 24,963 SQUARE FEET WHICH IS OVER | | | THE LIMIT OF 9,000 SQUARE FEET FOR A TYPE VB BUILDING. | | | FURTHER IN THE REVIEW I MENTIONED THAT IF THERE WERE | | | FIRE SPINKLERS INCREASES COULD BE TAKEN , AND THE | | | RESPONSE WAS THERE WERE NONE. I ALSO INDICATED THAT | | | FRONTAGE INCREASES COULD BE TAKEN, NONE WERE TAKEN. IF | | | THE FRONTAGE INCREASES WERE TAKEN I BELIEVE THE FIGURES | | | WOULD DECLARE FOR A MINIUM BUILDING TYPE THIS WOULD BE | | | A TYPE III-B BUILDING. PLEASE CORRECT THE MINIUM | | | BUILDING TYPE. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-03-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-03-16 |
Time |
06:35 |
Rev Time |
3.33 |
| Received By |
jwitmer |
Date |
2007-03-16 |
Time |
06:35 |
Sent To |
|
|
| Notes |
| 2007-03-16 07:03:35 | BUILDING PLAN REVIEW | | | PERMIT: 07020482 | | | ADD: 1501 PRESIDENTIAL WAY | | | CONT: GRUBER HALL CORP | | | TEL: (561)666-3377 | | | | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF | | | THE COURT. | | | NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS | | | NOT ACTUALLY | | | COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF, | | | SUCH NOTICE IS | | | NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE | | | OF COMMENCEMENT | | | AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 3)A-1 PLANS FAIL TO INDICATE COMPLIANCE WITH BREAK | | | ROOM SINK: | | | 11-4.24.2 SINKS, HEIGHT. SINKS SHALL | | | BE MOUNTED WITH THE COUNTER NO HIGHER | | | THAN 34" ABOVE THE FINISH FLOOR. | | | 11-4.24.3 KNEE CLEARANCE THAT IS AT | | | LEAST 27" HIGH 30" WIDE, AND 19" DEEP | | | SHALL BE PROVIDED UNDERNEATH SINKS. | | | 11-4.24.5 CLEAR FLOOR SPACE. | | | A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES | | | (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4 | | | SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD | | | APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN | | | ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19 | | | INCHES (485 MM) UNDERNEATH THE SINK | | | | | | 4) SHEET A-1 PLANS INDICATE THIS IS A TYPE II BUILDING, | | | AOR B? THIS IS TO BE A MINIMUM BUILDING TYPE! | | | | | | 5)PLANS FAIL TO PROVIDE THE ACTUAL TOTAL SQUARE | | | FOOTAGE (FOOTPRINT) OF THE BUILDING? | | | | | | 6) IF FRONTAGE INCREASES WERE TAKEN, OR IF FIRE | | | SPRINKLER INCREASES WERE TAKEN? | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2007-08-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-08-22 |
Time |
17:58 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-08-22 |
Time |
17:44 |
Sent To |
PC |
|
| Notes |
| 2007-08-22 17:59:50 | REVISED, | | | | | | REDLINED NOTE FOR NEC 517.13 (A)(B) FOR TYPE OF | | | CONDUITS AND REDUNDANT GROUNDING REQUIRED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2007-06-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-06-26 |
Time |
12:33 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-06-26 |
Time |
12:09 |
Sent To |
|
|
| Notes |
| 2007-06-26 12:38:21 | ***** PLANS REDLINED **** | | | | | | **THE ENERGY CALCULATIONS FROM PREVIOUS REVIEW ARE THE | | | SAME ONES WITH NOTES FROM PRIOR REVIEW. (FORM D AND | | | FROM OF THE 2001 CODE). | | | AS PLANS INDICATE A NOTE ON SHEET A-1 THAT NO NEW A/C | | | EQUIPMENT IS BEING INSTALLED,ENERGY CALCULATIONS ARE | | | NOT NEEDED. | | | THE LIGHTING PERFORMANCE CALCULATIONS ARE ON THE | | | E-SHEETS. NO NEW A/C EQUIPMENT MAY BE INSTALLED UNLESS | | | SUBMITTING NEW ENERGY CALCULATIONS WHICH COMPLY WITH | | | THE 2004 FBC. THIS WAS REDLINED ON PLANS. | | | | | | ELECTRICAL SHEETS STAMPED OK FOR REVIEW. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-04-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-04-24 |
Time |
17:32 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-04-24 |
Time |
16:54 |
Sent To |
|
|
| Notes |
| 2007-04-24 17:32:25 | ** UNSAT2ND REVIEW** | | | | | | ** PLEASE SEE THERE ARE NOTES FROM THE PREVIOUS REVIEW | | | WHICH STILL NEED TO BE ADDRESSED ALONG WITH TWO NEW | | | NOTES. | | | | | | | | | 1) NOTE: THIS IS THE SAME COMMENT. PLEASE KNOW THAT | | | STATING THE LATEST ADOPTED EDITION ETC IS NOT | | | PERMITTED. | | | PLEASE BE SURE ALL PLANS REFLECT THE LATEST ADOPTED | | | CODES PER THE STATE OF FLORIDA. PLEASE SEE THE | | | FOLLOWING WHICH ARE CURRENTLY ADOPTED AS OF DECEMBER | | | 8TH, 2006. | | | 2004 FBC W/ 2006 REVISIONS. THIS WILL AFFECT PLANS | | | SUBMITTED | | | 2005 NFPA-70 (NEC). THIS WILL AFFECT PLANS SUBMITTED. | | | 2002 NFPA-72 | | | 2003 NFPA-101 | | | | | | ** PLEASE SEE OTHER CODES WHICH MAY BE REQUIRED TO BE | | | STATED ON PLANS BY OTHER TRADES WHICH MAY NOT BE STATED | | | IN THIS REVIEWER(S) COMMENTS. | | | | | | 2) NOTE: PLEASE CLARIFY THE GROUNDING ETC AND USE OF | | | ANY OF THESE ITEMS FOR ANY STORAGE OR PROCEDURES. THIS | | | MAY ELABORATED IN NOTES, UNLESS SOME OF THESE ITEMS ARE | | | INDEED IN USE, THEN ELECTRICAL PLANS WILL NEED TO BE | | | ADJUSTED TO SHOWCLASS/ AND DIVISION LOCATIONS WHERE | | | APPLICABLE. | | | PLEASE 517.12, 517.13, 517.60, 517.62 AND OTHER PARTS | | | OF 517. PLEASE SPECIFY AREAS AND USE IN THESE AREAS. | | | PLEASE SPECIFY ANY USE OF ANESTHETIZING LOCATIONS IF | | | THIS APPLIES TO THIS OFFICE AND USE. PLEASE BE SURE TO | | | PLACE NOTES FOR TYPE OF WIRING METHODS AND GROUNDING AS | | | REQUIRED PER SECTIONS STATED. | | | | | | 3) NOTE: PLEASE CORRELATE PANEL SCHEDULE AND ALL | | | CIRCUITING ON PLANS. PLEASE SEE THE COMPLETED PANEL | | | SCHEDULE(S) SO THAT ALL ITEMS ON PANEL SCHEDULE ARE | | | SPECIFIC TO AREAS AND ROOMS IN WHICH THEY FEED. PLEASE | | | SEE COMMENTARY BELOW EXTRACTED FROM THE CODE. *SECTION | | | 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE THAT THE | | | IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A | | | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE | | | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. | | | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED | | | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE | | | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, | | | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE | | | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT | | | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS | | | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR | | | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT | | | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE | | | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT | | | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS | | | SECTION. | | | | | | 4) NOTE:PLEASE SEE 700.12E FOR EMERGENCY AND EXIT | | | LIGHTS. PLEASE SEE HALLWAY EMERGENCY/EXIT LIGHT WHICH | | | IS CIRCUITED TO OFFICE #1 AND NOT HALL. | | | THESE ARE REQUIRED TO BE CIRCUITED TO LOCAL LIGHTING | | | BRANCH CIRCUIT. | | | THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE | | | THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL | | | LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL | | | SWITCHES. | | | | | | 5) NOTE: PLEASE SEE PLEASE SHOW PER, 220.14,220.44 WHEN | | | A RECEPTACLE LOAD IS KNOWN, THE HIGHER OF THE TWO SHALL | | | BE SHOWN.. | | | | | | 6) NOTE: PLEASE SEE COMPLIANCE WITH THE 2004 FBC | | | CHAPTER 13 FOR CONTROL OF LIGHTING PER 13-415.1ABC.1.1, | | | .1.2 AND .1.3 FOR NEW INSTALLATIONS AS REQUIRED PER | | | 13.101 | | | PLEASE SEE BY DEFINITION THIS SPACE IS IN A BUILDING | | | GREATER THAN 5K SQ FT. | | | PLEASE SHOW COMPLIANCE WITH THIS AND IF THERE ARE ANY | | | QUESTIONS, PLEASE CALL TO GO OVER THIS. | | | PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED ARE SHOWN | | | AS A METHOD D? PLEASE SEE 13-415.1.AB.1.1,13-415.1.A, | | | 13-415.1.B, 13-415.1.C, 13-415.2 FOR LIGHTING | | | PERFORMANCE CALCULATIONS. | | | PLEASE ALSO SEE THE SHEETS SUBMITTED CONTAIN HAND DRAWN | | | ITEMS AND WHITE OUT ON SHEETS WHICH ARE SIGNED, DATED | | | AND SEALED BY AN ARCHITECT WHICH IS NOT PERMITTED. FS | | | 481.221 | | | PLEASE CALL TO GO OVER THESE REQUIREMENTS FROM FBC | | | CHAPTER 13, 2004 FBC W/ THE 2006 REVISIONS. | | | | | | PLEASE SEE THAT THE FIXTURE SCHEDULE SHALL BE SPECIFIC | | | FOR FIXTURES TO BE INSTALLED AND COORDINATION WITH THE | | | LPD/CALCULATIONS IS REVIEWED FOR COMPLIANCE. | | | PLEASE BE SURE TO INDICATE THE TYPE OF FIXTURE, WATTAGE | | | AND NUMBER OF LAMPS PER FIXTURE. | | | | | | 7) NOTE: PLEASE SEE THE ELECTRICAL CLOSET WHERE | | | ELECTRICAL PANEL AND EQUIPMENT IS SHOWN DOES NOT MEET | | | 110.26 FOR MINIMUM CLEARANCES. PLEASE ALSO SEE PLANS | | | APPEAR TO SHOW A SHELF ABOVE THE ELECTRICAL PANEL(S) | | | AND EQUIPMENT. | | | PLEASE SEE THERE ARE SEVERAL LIFE SAFETY AND FIRE | | | HAZARDS WHICH ARE PRESENT. | | | PLEASE SEE 110.26, 422.17, 408.7, 240.24. | | | PLEASE RELOCATED OR ADJUST WALLS/DOORS/OPENINGS AND | | | REMOVAL OF SHELVING. | | | | | | 8) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO | | | REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A | | | NOTICE GIVEN AT THIS TIME AS SOME OF THE SAME COMMENTS | | | ARE REPEATED FROM PREVIOUS REVIEW. | | | ** AS STATED IN PREVIOUS REVIEW, PLEASE CALL TO GO OVER | | | COMMENTS. THIS WILL HELP TO AVOID DELAYS ETC WITH | | | PROJECT. | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-02-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-02-28 |
Time |
07:39 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-02-28 |
Time |
06:52 |
Sent To |
|
|
| Notes |
| 2007-02-28 07:39:55 | ** UNSAT ** | | | | | | ** PLEASE SEE OF THERE IS A SUITE TO THIS UNIT, PLEASE | | | STATE ON PLANS. THIS IS TO VERIFIED WITH OUR ADDRESSING | | | REVIEWER. | | | | | | 1) NOTE: PLEASE BE SURE ALL PLANS REFLECT THE LATEST | | | ADOPTED CODES PER THE STATE OF FLORIDA. PLEASE SEE THE | | | FOLLOWING WHICH ARE CURRENTLY ADOPTED AS OF DECEMBER | | | 8TH, 2006. | | | 2004 FBC W/ 2006 REVISIONS. THIS WILL AFFECT PLANS | | | SUBMITTED | | | 2005 NFPA-70 (NEC). THIS WILL AFFECT PLANS SUBMITTED. | | | 2002 NFPA-72 | | | 2003 NFPA-101 | | | | | | ** PLEASE SEE OTHER CODES WHICH MAY BE REQUIRED TO BE | | | STATED ON PLANS BY OTHER TRADES WHICH MAY NOT BE STATED | | | IN THIS REVIEWER(S) COMMENTS. | | | | | | 2) NOTE:PLEASE SHOW ALL CIRCUITING ON PLANS AND | | | CORRELATE WITH PANEL SCHEDULE(S). | | | PLEASE SEE THERE ARE A FEW ITEMS ON PLANS WHICH STILL | | | DO NOT SHOW THE CIRCUITING. | | | PLEASE SEE ALL CIRCUITS WHICH REFLECT TO A PANEL AND | | | CIRCUITS WHICH ARE NOT PART OF THE SUBMITTED PANEL | | | SCHEDULES SUBMITTED. | | | PLEASE ALSO SEE WATER FOUNTAIN HAS BEEN ADDED TO PLANS; | | | HOWEVER PLANS DO NOT INDICATE ANY ELECTRICAL | | | RECEPTACLES FOR THIS UNIT. | | | PLEASE CORRELATE AND COORDINATE ALL. | | | FBC 106.1.2, 106.3.5.1.2 | | | | | | 3) NOTE: PLEASE 517.12, 517.13, 517.60, 517.62 AND | | | OTHER PARTS OF 517. PLEASE SPECIFY AREAS AND USE IN | | | THESE AREAS. PLEASE SPECIFY ANY USE OF ANESTHETIZING | | | LOCATIONS IF THIS APPLIES TO THIS OFFICE AND USE. | | | PLEASE BE SURE TO PLACE NOTES FOR TYPE OF WIRING | | | METHODS AND GROUNDING AS REQUIRED PER SECTIONS STATED. | | | | | | 4) NOTE: PLEASE CORRELATE PANEL SCHEDULE AND COMPLETE | | | PANEL SCHEDULE(S) SO THAT ALL ITEMS ON PANEL SCHEDULE | | | ARE SPECIFIC TO AREAS AND ROOMS IN WHICH THEY FEED. | | | PLEASE SEE COMMENTARY BELOW EXTRACTED FROM THE CODE. | | | *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE | | | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A | | | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE | | | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. | | | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED | | | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE | | | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, | | | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE | | | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT | | | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS | | | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR | | | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT | | | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE | | | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT | | | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS | | | SECTION. | | | | | | 5) PLEASE SEE 700.12E FOR EMERGENCY AND EXIT LIGHTS. | | | PLEASE KNOW AS CIRCUITING IS NOT SHOWN AT THIS TIME, | | | COMPLIANCE FOR THIS CAN NOT BE VERIFIED. THESE SHALL BE | | | CIRCUITED TO LOCAL LIGHTING BRANCH CIRCUIT. | | | THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE | | | THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL | | | LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL | | | SWITCHES. | | | | | | 6) NOTE: PLEASE SHOW LOAD CALCULATIONS, PLEASE SHOW | | | PER, 220.12, 220.14, 220.42, 220.44 ETC. | | | PLEASE ALSO SHOW ALL CONTINUOUS LOADS AT 125% PER | | | 215.3, AND 230.42 | | | PLEASE INDICATE THE SIZE OF WHAT IS BEING SHOWN FOR THE | | | EXISTING PANEL AND LOAD ON PANEL ALONG WITH NEW LOADS. | | | | | | 7) NOTE: PLEASE SEE COMPLIANCE WITH THE 2004 FBC | | | CHAPTER 13 FOR CONTROL OF LIGHTING PER 13-415.1ABC.1.1, | | | .1.2 AND .1.3. | | | PLEASE SEE BY DEFINITION THIS SPACE IS IN A BUILDING | | | GREATER THAN 5K SQ FT. | | | PLEASE SHOW COMPLIANCE WITH THIS AND IF THERE ARE ANY | | | QUESTIONS, PLEASE CALL TO GO OVER THIS. | | | PLEASE SUBMIT LIGHTING POWER DENSITIES PER THE 2004 FBC | | | W/ 2006 REVISION. PLEASE SEE 13-415.1.AB.1.1, 13-415.2 | | | FOR LIGHTING PERFORMANCE CALCULATIONS ALONG WITH ENERGY | | | CALCULATIONS. | | | PLEASE SEE THAT THE FIXTURE SCHEDULE SHALL BE SPECIFIC | | | FOR FIXTURES TO BE INSTALLED AND COORDINATION WITH THE | | | LPD/CALCULATIONS IS REVIEWED FOR COMPLIANCE. | | | * PLEASE KNOW AS THE COMPLETE SCOPE OF WORK SEEMS TO BE | | | MORE THAN APPLIED FOR ON PERMIT APPLICATION, ENERGY | | | CALCULATIONS MAY ALSO BE REQUIRED FOR SPECIFIC | | | USE/AREA. | | | PLEASE BE SURE TO HAVE THE DESIGNER OF RECORD FOR THE | | | ENERGY CALCULATIONS SIGN, DATE AND SEAL THESE AS | | | REQUIRED PER 13-103.1.1.1 | | | *PLEASE SEE NOTES ON PLANS MENTIONS SOME OF THESE AREAS | | | AS EXISTING FOR NO WORK, YET PLANS INDICATE WORK BEING | | | DONE IN THESE AREAS. | | | | | | 8) NOTE: PLEASE SEE PLAN WHERE WHAT SEEMS TO BE A WATER | | | HEATER IN THE EQUIPMENT CLOSET WITH A RECEPTACLE TO | | | *PLUG-IN* THIS UNIT? PLEASE SEE 422.30, 422.31 FOR THIS | | | UNIT TO BE HARDWIRED AT A MINIMUM. MAY CONTAIN | | | DISCONNECT AS NOTED, HOWEVER BREAKER IN PANEL MAY ALSO | | | BE USED IF INDEED LOCATED IN PANEL ADJACENT TO UNIT. | | | PLEASE CLARIFY. | | | | | | 9) NOTE: PLEASE SEE THAT FIVE (5) SETS OF PLANS WERE | | | SUBMITTED FOR REVIEW WHERE-AS ONLY TWO SETS ARE NEEDED | | | FOR PERMITTING AND REVIEW. PLEASE KNOW THAT IF | | | ADDITIONAL COPIES (UP TO THREE TOTAL) ARE REQUESTED TO | | | BE STAMPED BY THE CITY, THEN PLEASE BE SURE THE | | | ADDITIONAL THIRD SET IS SIGNED, DATED AND SEALED BY THE | | | DESIGNER OF RECORD AS SHOWNON THE OTHER TWO SETS. FS | | | 481.221. | | | | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2007-07-06 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-06-28 |
Time |
11:47 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2007-06-28 |
Time |
10:53 |
Sent To |
|
|
| Notes |
| 2007-06-28 11:47:36 | *****APPROVED***** | | | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE | | | BEEN ADDRESSED;PLAN SHEET E-1 STAMPED, INITIALED, AND | | | DATED | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2007-05-07 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-05-07 |
Time |
15:46 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-05-07 |
Time |
15:34 |
Sent To |
|
|
| Notes |
| 2007-05-07 15:43:03 | *****DENIED***** | | | | | | WITH THE EXCEPTION OF #1, THE FOLLOWING COMMENTS TAKEN | | | FROM THE PREVIOUS FIRE PLAN REVIEW STILL NEED TO BE | | | ADDRESSED: | | | | | | | | | | | | 2.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR | | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | | | 5.IF THE BUILDING OR PORTIONS OF THE BUILDING ARE TO | | | BE OCCUPIED DURING THE INTERIOR RENOVATION, THIS SHALL | | | BE PERMITTED ONLY WHERE THE REQUIRED MEANS OF EGRESS | | | AND REQUIRED FIRE PROTECTION FEATURES ARE IN PLACE AND | | | CONTINUOUSLY MAINTAINED. | | | | | | 6.PLEASE INDICATE THE MINIMUM INTERIOR FINISH | | | CLASSIFICATIONS FOR THE NEW CEILING TILES IN TERMS OF | | | CLASS A, CLASS B, OR CLASS C. | | | | | | 7.WILL THE REMOVAL AND/OR RELOCATION OF SOME OF THE | | | INTERIOR PARTITIONS IMPACT THE FIRE SPRINKLER HEADS? IF | | | SO, SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE | | | FIRE SPRINKLER REMODEL. | | | | | | 8.SHOW THE LOCATION OF THE FIRE EXTINGUISHER(S) IN | | | THIS OFFICE SPACE. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-03-31 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-03-31 |
Time |
16:20 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-03-31 |
Time |
15:34 |
Sent To |
|
|
| Notes |
| 2007-03-31 15:49:35 | *****DENIED***** | | | | | | | | | 1.IN ADDITION TO THE NUMERICAL ADDRESS, THE SUITE | | | NUMBER SHALL BE INCLUDED IN THE TITLE BLOCK OF EACH | | | SUBMITTED PLAN SHEET. | | | | | | 2.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR | | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | | | 5.IF THE BUILDING OR PORTIONS OF THE BUILDING ARE TO | | | BE OCCUPIED DURING THE INTERIOR RENOVATION, THIS SHALL | | | BE PERMITTED ONLY WHERE THE REQUIRED MEANS OF EGRESS | | | AND REQUIRED FIRE PROTECTION FEATURES ARE IN PLACE AND | | | CONTINUOUSLY MAINTAINED. | | | | | | 6.PLEASE INDICATE THE MINIMUM INTERIOR FINISH | | | CLASSIFICATIONS FOR THE NEW CEILING TILES IN TERMS OF | | | CLASS A, CLASS B, OR CLASS C. | | | | | | 7.WILL THE REMOVAL AND/OR RELOCATION OF SOME OF THE | | | INTERIOR PARTITIONS IMPACT THE FIRE SPRINKLER HEADS? IF | | | SO, SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE | | | FIRE SPRINKLER REMODEL. | | | | | | 8.SHOW THE LOCATION OF THE FIRE EXTINGUISHER(S) IN | | | THIS OFFICE SPACE. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2007-08-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-08-15 |
Time |
08:37 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-08-15 |
Time |
08:37 |
Sent To |
E |
|
| Notes |
| 2007-08-15 08:38:07 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-07-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-07-03 |
Time |
16:33 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-03 |
Time |
16:33 |
Sent To |
B |
|
| Notes |
| 2007-07-03 16:34:02 | TO "JWITMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-06-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-22 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-22 |
Time |
14:49 |
Sent To |
|
|
| Notes |
| 2007-06-26 11:53:29 | TO "COMM" BD#63--EXPEDITED PERMIT-- | | 2007-06-22 14:58:11 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-04-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-04-19 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-04-19 |
Time |
15:20 |
Sent To |
|
|
| Notes |
| 2007-04-19 15:23:31 | TO "COMM" BD#3 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-03-31 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-03-31 |
Time |
15:34 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-02-21 |
Time |
09:52 |
Sent To |
|
|
| Notes |
| 2007-02-26 13:40:32 | TO "COMM" BD#61 | | 2007-02-21 09:52:16 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2007-05-09 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-05-09 |
Time |
13:30 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-05-09 |
Time |
13:10 |
Sent To |
|
|
| Notes |
| 2007-05-09 13:29:30 | NO MECHANICAL WORK SHOWN ON PLANS. SEPARATE MECHANICAL | | | PERMIT APPLICATION WITH REQUIRED DOCUMENTATION NEEDED | | | AT TIME OF APPLICATION. A MECHANICAL PERMIT IS | | | REQUIRED. | | | | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-03-14 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-03-14 |
Time |
09:27 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-03-14 |
Time |
09:27 |
Sent To |
|
|
| Notes |
| 2007-03-14 09:32:01 | NO INFORMATION PROVIDED REGARDING EXTENT OR NATURE OF | | | MODIFICATIONS TO A/C SYSTEM. ANY MODIFICATIONS TO THE | | | EXISTING SYSTEM AS WELL AS THE ADDITION OF EXHAUST FANS | | | REQUIRES A MECHANICAL PERMIT. PLEASE SUBMIT ALL | | | NECESSARY DOCUMENTATION PER FBC 106.1 AND 106.3.5.1.4 | | | AT TIME OF APPLICATION. | | | | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2007-06-28 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-06-28 |
Time |
16:49 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-06-28 |
Time |
16:48 |
Sent To |
|
|
| Notes |
| 2007-06-28 16:52:27 | | | | | | | | | | | | | | | | | | | PASSED/PROVISO | | | | | | THE HEIGHT OF THE ACCESSIBLE W/C SHALL BE 17" TO 19" | | | MEASURED TO THE TOP OF THE TOILET SEAT. SECTION | | | 11-4.16.3--THE GRAB BAR BEHIND THE W/C SHALL BE | | | 3'0" MINIMUM. SECTION 11-4.16.4. | | | | | | | | | | | | | | | | | | . |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2007-05-30 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-05-30 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-05-30 |
Time |
11:06 |
Sent To |
|
|
| Notes |
| 2007-05-30 11:25:00 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FBC-2004 BUILDING | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | | | | 1. SUBMIT A DETAIL FOR THE NEW TOILET ROOMS, (TOILET | | | ROOMS 2 & 4). SHOW COMPLIANCE FOR THE FOLLOWING: FOR | | | W/C'S: | | | A. 11-4.16.2 CLEAR FLOOR SPACE - NOT ADDRESSED, NO | | | RESPONSE | | | B. 11-4.16.3 HEIGHT - NOT ADDRESSED, NO RESPONSEC. | | | 11-4.16.4 GRAB BARS - NO GRAB BAR BEHIND THE WATER | | | CLOSET INDICATED. | | | D. 11-4.16.5 FLUSH CONTROLS - NOT ADDRESSED, NO | | | RESPONSE | | | E. 11-4.16.6- OK | | | FOR THE LAVS: | | | A. 11-4.19.2- OK | | | B. 11-4.19.3- OK | | | C. 11-4.19.4 EXPOSED PIPES & SURFACES - NOT ADDRESSED, | | | NO RESPONSE | | | D. 11-4.19.5 FAUCETS - NOT ADDRESSED, NO RESPONSEE. | | | 11-4.19.6- OK | | | FOR THE TOILET ROOMS: | | | A.- OK | | | | | | 2. SUBMIT A DETAIL FOR THE BREAK ROOM SINK. SHOW | | | COMPLIANCE FOR THE FOLLOWING: | | | A. 11-4.24.2- OK | | | B. 11-4.24.3 KNEE CLEARANCE- NOT ADDRESSED, NO | | | RESPONSE | | | C. 11-4.24.4- OK | | | D. 11-4.24.5- OK | | | E. 11-4.24.6 EXPOSED PIPES & SURFACES- NOT | | | ADDRESSED, NO RESPONSE | | | F. 11-4.24.7 FAUCETS- NOT ADDRESSED, NO RESPONSE | | | | | | 3. SUBMIT A WATER RISER DIAGRAM. SHOW ALL PIPE SIZES, | | | VALVES,& IF QUICK CLOSING VALVES ARE INSTALLED, WATER | | | HAMMER ARRESTORS PER SECTION 604.9, LOCATED NEAR THE | | | FIXTURE, IN AN "EFFECTIVE RAGE", (NOT IN THE CEILING), | | | PER PDI-WH 201 AND MANUF. INSTALLATION INSTRUCTIONS. | | | SECTION 106.3.5.1.3(3)(10)(13). | | | ****RESPONSE NOTED, BUT A WATER HAMMER ARRESTOR IS | | | REQUIRED ON THE SUPPLY LINE TO THE ICE MAKER IN THE | | | REFRIG.--WATER RISER DIAGRAM FOR EXAM ROOM #1 AND | | | TOILET ROOM #2 MISLABELED.--THE SINK IN EXAM ROOM | | | #4 IS NOT SHOWN ON THE RISER DIAGRAM. | | | | | | 4. A DRINKING FOUNTAIN IS REQUIRED PER TABLE 403.1. | | | ****RESPONSE NOTED, BUT A DRINKING FOUNTAIN IS REQUIRED | | | PER TABLE 403.1 AND A BOTTLED WATER COOLER CAN NOT BE | | | SUBSTITUTED FOR MORE THAN 50% OF THE REQUIRED DRINKING | | | FOUNTAINS. IF ONE IS REQUIRED, THEN IT SHALL BE A | | | DRINKING FOUNTAIN. | | | | | | 5. OK | | | 6. OK | | | | | | ************NEW COMMENTS************ | | | | | | 1B. A TURNING AREA IS REQUIRED IN THE ACCESSIBLE TOILET | | | ROOMS. SECTION 11-4.22.3. | | | | | | 2B. SEE ATTACHED SHEET CONCERNING THE DESIGN | | | PROFESSIONAL AND FS 533.80(2)(B). THIS IS GIVEN AS A | | | ONE TIME NOTICE AS SOME OF THE COMMENTS ARE THE SAME AS | | | THE PREVIOUS REVIEW. | | | | | | 3. TWO COMPLETE SETS OF PLANS SHALL BE SUBMITTED. | | | PLEASE ADD ALL SHEETS FROM THE FIRST REVIEW THAT WILL | | | NOT BE CHANGED TO THE NEW SHEETS FROM THE SECOND | | | REVIEW. (SEE D-1). SECTION 106.1. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | ****NOT ADDRESSED | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL KSTEVENS@ | | | WPB.ORG |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-03-14 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-03-14 |
Time |
11:56 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-03-14 |
Time |
11:56 |
Sent To |
|
|
| Notes |
| 2007-03-14 12:31:31 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FBC-2004 BUILDING | | | | | | | | | 1. SUBMIT A DETAIL FOR THE NEW TOILET ROOMS, (TOILET | | | ROOMS 2 & 4). SHOW COMPLIANCE FOR THE FOLLOWING: FOR | | | W/C'S: | | | A. 11-4.16.2 CLEAR FLOOR SPACE | | | B. 11-4.16.3 HEIGHT | | | C. 11-4.16.4 GRAB BARS | | | D. 11-4.16.5 FLUSH CONTROLS | | | E. 11-4.16.6 DISPENSERS | | | FOR THE LAVS: | | | A. 11-4.19.2 HEIGHT & CLEARANCES | | | B. 11-4.19.3 CLEAR FLOOR SPACE | | | C. 11-4.19.4 EXPOSED PIPES & SURFACES | | | D. 11-4.19.5 FAUCETS | | | E. 11-4.19.6 MIRRORS | | | FOR THE TOILET ROOMS: | | | A. THE DOORS SHALL NOT SWING INTO THE CLEAR FLOOR | | | SPACE REQUIRED FOR ANY FIXTURE. SECTION 11-4.22.2. | | | | | | 2. SUBMIT A DETAIL FOR THE BREAK ROOM SINK. SHOW | | | COMPLIANCE FOR THE FOLLOWING: | | | A. 11-4.24.2 HEIGHT | | | B. 11-4.24.3 KNEE CLEARANCE | | | C. 11-4.24.4 SINK DEPTH | | | D. 11-4.24.5 CLEAR FLOOR SPACE - FORWARD APPROACH | | | REQUIRED. - NO CABINET DOORS ALLOWED | | | E. 11-4.24.6 EXPOSED PIPES & SURFACES | | | F. 11-4.24.7 FAUCETS | | | | | | 3. SUBMIT A WATER RISER DIAGRAM. SHOW ALL PIPE SIZES, | | | VALVES,& IF QUICK CLOSING VALVES ARE INSTALLED, WATER | | | HAMMER ARRESTORS PER SECTION 604.9, LOCATED NEAR THE | | | FIXTURE, IN AN "EFFECTIVE RAGE", (NOT IN THE CEILING), | | | PER PDI-WH 201 AND MANUF. INSTALLATION INSTRUCTIONS. | | | SECTION 106.3.5.1.3(3)(10)(13). | | | | | | 4. A DRINKING FOUNTAIN IS REQUIRED PER TABLE 403.1. | | | | | | 5. SHT A-1 ROOM FINISH SCHEDULE INDICATES DRYWALL FOR | | | THE WALLS IN THE TOILET ROOMS.PER SECTION 1210.2, | | | WALLS WITHIN 2FT OF URINALS AND WATER CLOSETS SHALL | | | HAVE A SMOOTH, HARD, NONABSORBENT SURFACE, TO A HEIGHT | | | OF 4' ABOVE THE FLOOR. DRYWALL DOES NOT MEET THESE | | | REQUIREMENTS. PLEASE INDICATE HOW THIS REQUIREMENT WILL | | | BE ADDRESSED. | | | | | | 6. SHT A-1 THE PLUMBING RISER DIAGRAM DOES NOT REFLECT | | | THE FLOOR PLAN, NOR DOES IT MEET CODE REQUIREMENTS.-- | | | THE SINK IN EXAM ROOM #1 SHALL DISCHARGE DOWNSTREAM OF | | | THE FIXTURES IN TOILET ROOM #2 PER SECTION 909.1.-- | | | THE SINK IN EXAM ROOM #2 IS INDICATED AS EXISTING ON | | | THE FLOOR PLAN, BUT INDICATED AS NEW ON THE SANT RISER | | | DIAGRAM.--THE NEW BREAK ROOM SINK IS NOT INDICATED | | | ON THE RISER DIAGRAM.--THE NEW TOILET ROOM #4 IS | | | NOT INDICATED ON THE SANT RISER DIAGRAM. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |