Plan Review Details - Permit 07020482
Plan Review Stops For Permit 07020482
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-07-06 Cont ID  
Sent By jwitmer Date 2007-07-06 Time 10:38 Rev Time 1.11
Received By jwitmer Date 2007-07-06 Time 10:38 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-06-26 Cont ID  
Sent By jwitmer Date 2007-06-26 Time 15:04 Rev Time 1.33
Received By jwitmer Date 2007-06-26 Time 15:04 Sent To  
Notes
2007-06-26 15:38:25BUILDING PLAN REVIEW
 PERMIT: 07020482
 ADD: 1501 PRESIDENTIAL WAY
 CONT: GRUBER HALL CORP
 TEL: (561)666-3377
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS
 NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE
 OF COMMENCEMENT
 AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) SHEET A-1 DOES NOT INDICATE THE MINIMUM BUILDING
 TYPE. THE LIST BELOW IS REQUIRED TO BE ON THE PLAN,
 110.2 FBC CODE, INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PROJECT WAS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 THE PLANS ARE NOT CONSISTANT THE GENERAL INFO LISTING
 THE ABOVE REQUIEMENTS STATES THIS IS A TYPE VB BUILDING
 (NOTE C) , NOTE E INDICATES FIRE SPRINKLERS ARE PRESENT
 AND AREA INCREASES WERE TAKEN.
 THIS IS WHERE THERE IS A DISCREPANCY AT THE BOTTOM LEFT
 OF SHEET A1 GENERAL SPECS NOTE 21THIS NOTE INDICATES
 "NO FRONTAGE OR FIRE SPRINKLER INCREASES MADE".
 THE DESIGNER OF RECORD NEEDS TO MAKE CORRECTIONS TO THE
 PLAN, THE LETTER SIZE REPONSE CAN NOT BE PART OF THE
 LEGAL DOCUMENTS SINCE IT IS NOT SIGNED NOR SEALED.
  
 COMMENT # 3FROM THE 2ND REVIEW: FROM THE PREVIOUS
 REVIEW:SHEET A-1 PLANS INDICATED THIS IS A TYPE II
 BUILDING,? THIS IS TO BE A MINIMUM BUILDING TYPE! THE
 PLAN NOW INDICATE IT TO BE A TYPE V CONSTRUCTION.
 THE PLANS ALSO STATE THAT THE TOTAL SQUAREFOOTAGE
 FORTHE BUILDING TO BE 24,963 SQUARE FEET WHICH IS OVER
 THE LIMIT OF 9,000 SQUARE FEET FOR A TYPE VB BUILDING.
 FURTHER IN THE REVIEW I MENTIONED THAT IF THERE WERE
 FIRE SPINKLERS INCREASES COULD BE TAKEN , AND THE
 RESPONSE WAS THERE WERE NONE. I ALSO INDICATED THAT
 FRONTAGE INCREASES COULD BE TAKEN, NONE WERE TAKEN. IF
 THE FRONTAGE INCREASES WERE TAKEN I BELIEVE THE FIGURES
 WOULD DECLARE FOR A MINIUM BUILDING TYPE THIS WOULD BE
 A TYPE III-B BUILDING. PLEASE CORRECT THE MINIUM
 BUILDING TYPE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-06-14 Cont ID  
Sent By jwitmer Date 2007-06-14 Time 17:41 Rev Time 0.77
Received By jwitmer Date 2007-06-14 Time 17:41 Sent To PC
Notes
2007-06-14 17:43:22BUILDING PLAN REVIEW
 PERMIT: 07020482
 ADD: 1501 PRESIDENTIAL WAY
 CONT: GRUBER HALL CORP
 TEL: (561)666-3377
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS
 NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE
 OF COMMENCEMENT
 AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) COMMENT # 4 FROM THE PREVIOUS REVIEW:SHEET A-1
 PLANS INDICATED THIS IS A TYPE II BUILDING,? THIS IS TO
 BE A MINIMUM BUILDING TYPE! THE PLAN NOW INDICATE IT TO
 BE A TYPE V CONSTRUCTION.
 THE PLANS ALSO STATE THAT THE TOTAL SQUAREFOOTAGE
 FORTHE BUILDING TO BE 24,963 SQUARE FEET WHICH IS OVER
 THE LIMIT OF 9,000 SQUARE FEET FOR A TYPE VB BUILDING.
 FURTHER IN THE REVIEW I MENTIONED THAT IF THERE WERE
 FIRE SPINKLERS INCREASES COULD BE TAKEN , AND THE
 RESPONSE WAS THERE WERE NONE. I ALSO INDICATED THAT
 FRONTAGE INCREASES COULD BE TAKEN, NONE WERE TAKEN. IF
 THE FRONTAGE INCREASES WERE TAKEN I BELIEVE THE FIGURES
 WOULD DECLARE FOR A MINIUM BUILDING TYPE THIS WOULD BE
 A TYPE III-B BUILDING. PLEASE CORRECT THE MINIUM
 BUILDING TYPE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-16 Cont ID  
Sent By jwitmer Date 2007-03-16 Time 06:35 Rev Time 3.33
Received By jwitmer Date 2007-03-16 Time 06:35 Sent To  
Notes
2007-03-16 07:03:35BUILDING PLAN REVIEW
 PERMIT: 07020482
 ADD: 1501 PRESIDENTIAL WAY
 CONT: GRUBER HALL CORP
 TEL: (561)666-3377
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS
 NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE
 OF COMMENCEMENT
 AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)A-1 PLANS FAIL TO INDICATE COMPLIANCE WITH BREAK
 ROOM SINK:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES
 (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4
 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD
 APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN
 ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19
 INCHES (485 MM) UNDERNEATH THE SINK
  
 4) SHEET A-1 PLANS INDICATE THIS IS A TYPE II BUILDING,
 AOR B? THIS IS TO BE A MINIMUM BUILDING TYPE!
  
 5)PLANS FAIL TO PROVIDE THE ACTUAL TOTAL SQUARE
 FOOTAGE (FOOTPRINT) OF THE BUILDING?
  
 6) IF FRONTAGE INCREASES WERE TAKEN, OR IF FIRE
 SPRINKLER INCREASES WERE TAKEN?
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-08-22 Cont ID  
Sent By dpalmer Date 2007-08-22 Time 17:58 Rev Time 0.00
Received By dpalmer Date 2007-08-22 Time 17:44 Sent To PC
Notes
2007-08-22 17:59:50REVISED,
  
 REDLINED NOTE FOR NEC 517.13 (A)(B) FOR TYPE OF
 CONDUITS AND REDUNDANT GROUNDING REQUIRED.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-06-26 Cont ID  
Sent By dpalmer Date 2007-06-26 Time 12:33 Rev Time 0.00
Received By dpalmer Date 2007-06-26 Time 12:09 Sent To  
Notes
2007-06-26 12:38:21***** PLANS REDLINED ****
  
 **THE ENERGY CALCULATIONS FROM PREVIOUS REVIEW ARE THE
 SAME ONES WITH NOTES FROM PRIOR REVIEW. (FORM D AND
 FROM OF THE 2001 CODE).
 AS PLANS INDICATE A NOTE ON SHEET A-1 THAT NO NEW A/C
 EQUIPMENT IS BEING INSTALLED,ENERGY CALCULATIONS ARE
 NOT NEEDED.
 THE LIGHTING PERFORMANCE CALCULATIONS ARE ON THE
 E-SHEETS. NO NEW A/C EQUIPMENT MAY BE INSTALLED UNLESS
 SUBMITTING NEW ENERGY CALCULATIONS WHICH COMPLY WITH
 THE 2004 FBC. THIS WAS REDLINED ON PLANS.
  
 ELECTRICAL SHEETS STAMPED OK FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-04-24 Cont ID  
Sent By dpalmer Date 2007-04-24 Time 17:32 Rev Time 0.00
Received By dpalmer Date 2007-04-24 Time 16:54 Sent To  
Notes
2007-04-24 17:32:25** UNSAT2ND REVIEW**
  
 ** PLEASE SEE THERE ARE NOTES FROM THE PREVIOUS REVIEW
 WHICH STILL NEED TO BE ADDRESSED ALONG WITH TWO NEW
 NOTES.
  
  
 1) NOTE: THIS IS THE SAME COMMENT. PLEASE KNOW THAT
 STATING THE LATEST ADOPTED EDITION ETC IS NOT
 PERMITTED.
 PLEASE BE SURE ALL PLANS REFLECT THE LATEST ADOPTED
 CODES PER THE STATE OF FLORIDA. PLEASE SEE THE
 FOLLOWING WHICH ARE CURRENTLY ADOPTED AS OF DECEMBER
 8TH, 2006.
 2004 FBC W/ 2006 REVISIONS. THIS WILL AFFECT PLANS
 SUBMITTED
 2005 NFPA-70 (NEC). THIS WILL AFFECT PLANS SUBMITTED.
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE SEE OTHER CODES WHICH MAY BE REQUIRED TO BE
 STATED ON PLANS BY OTHER TRADES WHICH MAY NOT BE STATED
 IN THIS REVIEWER(S) COMMENTS.
  
 2) NOTE: PLEASE CLARIFY THE GROUNDING ETC AND USE OF
 ANY OF THESE ITEMS FOR ANY STORAGE OR PROCEDURES. THIS
 MAY ELABORATED IN NOTES, UNLESS SOME OF THESE ITEMS ARE
 INDEED IN USE, THEN ELECTRICAL PLANS WILL NEED TO BE
 ADJUSTED TO SHOWCLASS/ AND DIVISION LOCATIONS WHERE
 APPLICABLE.
 PLEASE 517.12, 517.13, 517.60, 517.62 AND OTHER PARTS
 OF 517. PLEASE SPECIFY AREAS AND USE IN THESE AREAS.
 PLEASE SPECIFY ANY USE OF ANESTHETIZING LOCATIONS IF
 THIS APPLIES TO THIS OFFICE AND USE. PLEASE BE SURE TO
 PLACE NOTES FOR TYPE OF WIRING METHODS AND GROUNDING AS
 REQUIRED PER SECTIONS STATED.
  
 3) NOTE: PLEASE CORRELATE PANEL SCHEDULE AND ALL
 CIRCUITING ON PLANS. PLEASE SEE THE COMPLETED PANEL
 SCHEDULE(S) SO THAT ALL ITEMS ON PANEL SCHEDULE ARE
 SPECIFIC TO AREAS AND ROOMS IN WHICH THEY FEED. PLEASE
 SEE COMMENTARY BELOW EXTRACTED FROM THE CODE. *SECTION
 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE THAT THE
 IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.
  
 4) NOTE:PLEASE SEE 700.12E FOR EMERGENCY AND EXIT
 LIGHTS. PLEASE SEE HALLWAY EMERGENCY/EXIT LIGHT WHICH
 IS CIRCUITED TO OFFICE #1 AND NOT HALL.
 THESE ARE REQUIRED TO BE CIRCUITED TO LOCAL LIGHTING
 BRANCH CIRCUIT.
 THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE
 THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES.
  
 5) NOTE: PLEASE SEE PLEASE SHOW PER, 220.14,220.44 WHEN
 A RECEPTACLE LOAD IS KNOWN, THE HIGHER OF THE TWO SHALL
 BE SHOWN..
  
 6) NOTE: PLEASE SEE COMPLIANCE WITH THE 2004 FBC
 CHAPTER 13 FOR CONTROL OF LIGHTING PER 13-415.1ABC.1.1,
 .1.2 AND .1.3 FOR NEW INSTALLATIONS AS REQUIRED PER
 13.101
 PLEASE SEE BY DEFINITION THIS SPACE IS IN A BUILDING
 GREATER THAN 5K SQ FT.
 PLEASE SHOW COMPLIANCE WITH THIS AND IF THERE ARE ANY
 QUESTIONS, PLEASE CALL TO GO OVER THIS.
 PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED ARE SHOWN
 AS A METHOD D? PLEASE SEE 13-415.1.AB.1.1,13-415.1.A,
 13-415.1.B, 13-415.1.C, 13-415.2 FOR LIGHTING
 PERFORMANCE CALCULATIONS.
 PLEASE ALSO SEE THE SHEETS SUBMITTED CONTAIN HAND DRAWN
 ITEMS AND WHITE OUT ON SHEETS WHICH ARE SIGNED, DATED
 AND SEALED BY AN ARCHITECT WHICH IS NOT PERMITTED. FS
 481.221
 PLEASE CALL TO GO OVER THESE REQUIREMENTS FROM FBC
 CHAPTER 13, 2004 FBC W/ THE 2006 REVISIONS.
  
 PLEASE SEE THAT THE FIXTURE SCHEDULE SHALL BE SPECIFIC
 FOR FIXTURES TO BE INSTALLED AND COORDINATION WITH THE
 LPD/CALCULATIONS IS REVIEWED FOR COMPLIANCE.
 PLEASE BE SURE TO INDICATE THE TYPE OF FIXTURE, WATTAGE
 AND NUMBER OF LAMPS PER FIXTURE.
  
 7) NOTE: PLEASE SEE THE ELECTRICAL CLOSET WHERE
 ELECTRICAL PANEL AND EQUIPMENT IS SHOWN DOES NOT MEET
 110.26 FOR MINIMUM CLEARANCES. PLEASE ALSO SEE PLANS
 APPEAR TO SHOW A SHELF ABOVE THE ELECTRICAL PANEL(S)
 AND EQUIPMENT.
 PLEASE SEE THERE ARE SEVERAL LIFE SAFETY AND FIRE
 HAZARDS WHICH ARE PRESENT.
 PLEASE SEE 110.26, 422.17, 408.7, 240.24.
 PLEASE RELOCATED OR ADJUST WALLS/DOORS/OPENINGS AND
 REMOVAL OF SHELVING.
  
 8) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME AS SOME OF THE SAME COMMENTS
 ARE REPEATED FROM PREVIOUS REVIEW.
 ** AS STATED IN PREVIOUS REVIEW, PLEASE CALL TO GO OVER
 COMMENTS. THIS WILL HELP TO AVOID DELAYS ETC WITH
 PROJECT.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-02-28 Cont ID  
Sent By dpalmer Date 2007-02-28 Time 07:39 Rev Time 0.00
Received By dpalmer Date 2007-02-28 Time 06:52 Sent To  
Notes
2007-02-28 07:39:55** UNSAT **
  
 ** PLEASE SEE OF THERE IS A SUITE TO THIS UNIT, PLEASE
 STATE ON PLANS. THIS IS TO VERIFIED WITH OUR ADDRESSING
 REVIEWER.
  
 1) NOTE: PLEASE BE SURE ALL PLANS REFLECT THE LATEST
 ADOPTED CODES PER THE STATE OF FLORIDA. PLEASE SEE THE
 FOLLOWING WHICH ARE CURRENTLY ADOPTED AS OF DECEMBER
 8TH, 2006.
 2004 FBC W/ 2006 REVISIONS. THIS WILL AFFECT PLANS
 SUBMITTED
 2005 NFPA-70 (NEC). THIS WILL AFFECT PLANS SUBMITTED.
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE SEE OTHER CODES WHICH MAY BE REQUIRED TO BE
 STATED ON PLANS BY OTHER TRADES WHICH MAY NOT BE STATED
 IN THIS REVIEWER(S) COMMENTS.
  
 2) NOTE:PLEASE SHOW ALL CIRCUITING ON PLANS AND
 CORRELATE WITH PANEL SCHEDULE(S).
 PLEASE SEE THERE ARE A FEW ITEMS ON PLANS WHICH STILL
 DO NOT SHOW THE CIRCUITING.
 PLEASE SEE ALL CIRCUITS WHICH REFLECT TO A PANEL AND
 CIRCUITS WHICH ARE NOT PART OF THE SUBMITTED PANEL
 SCHEDULES SUBMITTED.
 PLEASE ALSO SEE WATER FOUNTAIN HAS BEEN ADDED TO PLANS;
 HOWEVER PLANS DO NOT INDICATE ANY ELECTRICAL
 RECEPTACLES FOR THIS UNIT.
 PLEASE CORRELATE AND COORDINATE ALL.
 FBC 106.1.2, 106.3.5.1.2
  
 3) NOTE: PLEASE 517.12, 517.13, 517.60, 517.62 AND
 OTHER PARTS OF 517. PLEASE SPECIFY AREAS AND USE IN
 THESE AREAS. PLEASE SPECIFY ANY USE OF ANESTHETIZING
 LOCATIONS IF THIS APPLIES TO THIS OFFICE AND USE.
 PLEASE BE SURE TO PLACE NOTES FOR TYPE OF WIRING
 METHODS AND GROUNDING AS REQUIRED PER SECTIONS STATED.
  
 4) NOTE: PLEASE CORRELATE PANEL SCHEDULE AND COMPLETE
 PANEL SCHEDULE(S) SO THAT ALL ITEMS ON PANEL SCHEDULE
 ARE SPECIFIC TO AREAS AND ROOMS IN WHICH THEY FEED.
 PLEASE SEE COMMENTARY BELOW EXTRACTED FROM THE CODE.
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.
  
 5) PLEASE SEE 700.12E FOR EMERGENCY AND EXIT LIGHTS.
 PLEASE KNOW AS CIRCUITING IS NOT SHOWN AT THIS TIME,
 COMPLIANCE FOR THIS CAN NOT BE VERIFIED. THESE SHALL BE
 CIRCUITED TO LOCAL LIGHTING BRANCH CIRCUIT.
 THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE
 THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES.
  
 6) NOTE: PLEASE SHOW LOAD CALCULATIONS, PLEASE SHOW
 PER, 220.12, 220.14, 220.42, 220.44 ETC.
 PLEASE ALSO SHOW ALL CONTINUOUS LOADS AT 125% PER
 215.3, AND 230.42
 PLEASE INDICATE THE SIZE OF WHAT IS BEING SHOWN FOR THE
 EXISTING PANEL AND LOAD ON PANEL ALONG WITH NEW LOADS.
  
 7) NOTE: PLEASE SEE COMPLIANCE WITH THE 2004 FBC
 CHAPTER 13 FOR CONTROL OF LIGHTING PER 13-415.1ABC.1.1,
 .1.2 AND .1.3.
 PLEASE SEE BY DEFINITION THIS SPACE IS IN A BUILDING
 GREATER THAN 5K SQ FT.
 PLEASE SHOW COMPLIANCE WITH THIS AND IF THERE ARE ANY
 QUESTIONS, PLEASE CALL TO GO OVER THIS.
 PLEASE SUBMIT LIGHTING POWER DENSITIES PER THE 2004 FBC
 W/ 2006 REVISION. PLEASE SEE 13-415.1.AB.1.1, 13-415.2
 FOR LIGHTING PERFORMANCE CALCULATIONS ALONG WITH ENERGY
 CALCULATIONS.
 PLEASE SEE THAT THE FIXTURE SCHEDULE SHALL BE SPECIFIC
 FOR FIXTURES TO BE INSTALLED AND COORDINATION WITH THE
 LPD/CALCULATIONS IS REVIEWED FOR COMPLIANCE.
 * PLEASE KNOW AS THE COMPLETE SCOPE OF WORK SEEMS TO BE
 MORE THAN APPLIED FOR ON PERMIT APPLICATION, ENERGY
 CALCULATIONS MAY ALSO BE REQUIRED FOR SPECIFIC
 USE/AREA.
 PLEASE BE SURE TO HAVE THE DESIGNER OF RECORD FOR THE
 ENERGY CALCULATIONS SIGN, DATE AND SEAL THESE AS
 REQUIRED PER 13-103.1.1.1
 *PLEASE SEE NOTES ON PLANS MENTIONS SOME OF THESE AREAS
 AS EXISTING FOR NO WORK, YET PLANS INDICATE WORK BEING
 DONE IN THESE AREAS.
  
 8) NOTE: PLEASE SEE PLAN WHERE WHAT SEEMS TO BE A WATER
 HEATER IN THE EQUIPMENT CLOSET WITH A RECEPTACLE TO
 *PLUG-IN* THIS UNIT? PLEASE SEE 422.30, 422.31 FOR THIS
 UNIT TO BE HARDWIRED AT A MINIMUM. MAY CONTAIN
 DISCONNECT AS NOTED, HOWEVER BREAKER IN PANEL MAY ALSO
 BE USED IF INDEED LOCATED IN PANEL ADJACENT TO UNIT.
 PLEASE CLARIFY.
  
 9) NOTE: PLEASE SEE THAT FIVE (5) SETS OF PLANS WERE
 SUBMITTED FOR REVIEW WHERE-AS ONLY TWO SETS ARE NEEDED
 FOR PERMITTING AND REVIEW. PLEASE KNOW THAT IF
 ADDITIONAL COPIES (UP TO THREE TOTAL) ARE REQUESTED TO
 BE STAMPED BY THE CITY, THEN PLEASE BE SURE THE
 ADDITIONAL THIRD SET IS SIGNED, DATED AND SEALED BY THE
 DESIGNER OF RECORD AS SHOWNON THE OTHER TWO SETS. FS
 481.221.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-07-06 Cont ID  
Sent By mawillia Date 2007-06-28 Time 11:47 Rev Time 0.00
Received By rbrown Date 2007-06-28 Time 10:53 Sent To  
Notes
2007-06-28 11:47:36*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;PLAN SHEET E-1 STAMPED, INITIALED, AND
 DATED
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-05-07 Cont ID  
Sent By mawillia Date 2007-05-07 Time 15:46 Rev Time 0.00
Received By mawillia Date 2007-05-07 Time 15:34 Sent To  
Notes
2007-05-07 15:43:03*****DENIED*****
  
 WITH THE EXCEPTION OF #1, THE FOLLOWING COMMENTS TAKEN
 FROM THE PREVIOUS FIRE PLAN REVIEW STILL NEED TO BE
 ADDRESSED:
  
  
  
 2.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 5.IF THE BUILDING OR PORTIONS OF THE BUILDING ARE TO
 BE OCCUPIED DURING THE INTERIOR RENOVATION, THIS SHALL
 BE PERMITTED ONLY WHERE THE REQUIRED MEANS OF EGRESS
 AND REQUIRED FIRE PROTECTION FEATURES ARE IN PLACE AND
 CONTINUOUSLY MAINTAINED.
  
 6.PLEASE INDICATE THE MINIMUM INTERIOR FINISH
 CLASSIFICATIONS FOR THE NEW CEILING TILES IN TERMS OF
 CLASS A, CLASS B, OR CLASS C.
  
 7.WILL THE REMOVAL AND/OR RELOCATION OF SOME OF THE
 INTERIOR PARTITIONS IMPACT THE FIRE SPRINKLER HEADS? IF
 SO, SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 FIRE SPRINKLER REMODEL.
  
 8.SHOW THE LOCATION OF THE FIRE EXTINGUISHER(S) IN
 THIS OFFICE SPACE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-03-31 Cont ID  
Sent By mawillia Date 2007-03-31 Time 16:20 Rev Time 0.00
Received By mawillia Date 2007-03-31 Time 15:34 Sent To  
Notes
2007-03-31 15:49:35*****DENIED*****
  
  
 1.IN ADDITION TO THE NUMERICAL ADDRESS, THE SUITE
 NUMBER SHALL BE INCLUDED IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 2.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 5.IF THE BUILDING OR PORTIONS OF THE BUILDING ARE TO
 BE OCCUPIED DURING THE INTERIOR RENOVATION, THIS SHALL
 BE PERMITTED ONLY WHERE THE REQUIRED MEANS OF EGRESS
 AND REQUIRED FIRE PROTECTION FEATURES ARE IN PLACE AND
 CONTINUOUSLY MAINTAINED.
  
 6.PLEASE INDICATE THE MINIMUM INTERIOR FINISH
 CLASSIFICATIONS FOR THE NEW CEILING TILES IN TERMS OF
 CLASS A, CLASS B, OR CLASS C.
  
 7.WILL THE REMOVAL AND/OR RELOCATION OF SOME OF THE
 INTERIOR PARTITIONS IMPACT THE FIRE SPRINKLER HEADS? IF
 SO, SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 FIRE SPRINKLER REMODEL.
  
 8.SHOW THE LOCATION OF THE FIRE EXTINGUISHER(S) IN
 THIS OFFICE SPACE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-08-15 Cont ID  
Sent By adarroug Date 2007-08-15 Time 08:37 Rev Time 0.00
Received By adarroug Date 2007-08-15 Time 08:37 Sent To E
Notes
2007-08-15 08:38:07TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-07-03 Cont ID  
Sent By adarroug Date 2007-07-03 Time 16:33 Rev Time 0.00
Received By adarroug Date 2007-07-03 Time 16:33 Sent To B
Notes
2007-07-03 16:34:02TO "JWITMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-06-22 Cont ID  
Sent By adarroug Date 2007-06-22 Time 14:57 Rev Time 0.00
Received By adarroug Date 2007-06-22 Time 14:49 Sent To  
Notes
2007-06-26 11:53:29TO "COMM" BD#63--EXPEDITED PERMIT--
2007-06-22 14:58:11WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-19 Cont ID  
Sent By adarroug Date 2007-04-19 Time 15:20 Rev Time 0.00
Received By adarroug Date 2007-04-19 Time 15:20 Sent To  
Notes
2007-04-19 15:23:31TO "COMM" BD#3

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-31 Cont ID  
Sent By mawillia Date 2007-03-31 Time 15:34 Rev Time 0.00
Received By mawillia Date 2007-02-21 Time 09:52 Sent To  
Notes
2007-02-26 13:40:32TO "COMM" BD#61
2007-02-21 09:52:16WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2007-05-09 Cont ID  
Sent By rregueir Date 2007-05-09 Time 13:30 Rev Time 0.00
Received By rregueir Date 2007-05-09 Time 13:10 Sent To  
Notes
2007-05-09 13:29:30NO MECHANICAL WORK SHOWN ON PLANS. SEPARATE MECHANICAL
 PERMIT APPLICATION WITH REQUIRED DOCUMENTATION NEEDED
 AT TIME OF APPLICATION. A MECHANICAL PERMIT IS
 REQUIRED.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-03-14 Cont ID  
Sent By rregueir Date 2007-03-14 Time 09:27 Rev Time 0.00
Received By rregueir Date 2007-03-14 Time 09:27 Sent To  
Notes
2007-03-14 09:32:01NO INFORMATION PROVIDED REGARDING EXTENT OR NATURE OF
 MODIFICATIONS TO A/C SYSTEM. ANY MODIFICATIONS TO THE
 EXISTING SYSTEM AS WELL AS THE ADDITION OF EXHAUST FANS
 REQUIRES A MECHANICAL PERMIT. PLEASE SUBMIT ALL
 NECESSARY DOCUMENTATION PER FBC 106.1 AND 106.3.5.1.4
 AT TIME OF APPLICATION.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-06-28 Cont ID  
Sent By kstevens Date 2007-06-28 Time 16:49 Rev Time 0.00
Received By kstevens Date 2007-06-28 Time 16:48 Sent To  
Notes
2007-06-28 16:52:27 
  
  
  
  
  
 PASSED/PROVISO
  
 THE HEIGHT OF THE ACCESSIBLE W/C SHALL BE 17" TO 19"
 MEASURED TO THE TOP OF THE TOILET SEAT. SECTION
 11-4.16.3--THE GRAB BAR BEHIND THE W/C SHALL BE
 3'0" MINIMUM. SECTION 11-4.16.4.
  
  
  
  
  
 .

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-05-30 Cont ID  
Sent By kstevens Date 2007-05-30 Time 11:06 Rev Time 0.00
Received By kstevens Date 2007-05-30 Time 11:06 Sent To  
Notes
2007-05-30 11:25:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
  
 ****FROM PREVIOUS REVIEW:
  
  
 1. SUBMIT A DETAIL FOR THE NEW TOILET ROOMS, (TOILET
 ROOMS 2 & 4). SHOW COMPLIANCE FOR THE FOLLOWING: FOR
 W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE - NOT ADDRESSED, NO
 RESPONSE
 B. 11-4.16.3 HEIGHT - NOT ADDRESSED, NO RESPONSEC.
 11-4.16.4 GRAB BARS - NO GRAB BAR BEHIND THE WATER
 CLOSET INDICATED.
 D. 11-4.16.5 FLUSH CONTROLS - NOT ADDRESSED, NO
 RESPONSE
 E. 11-4.16.6- OK
 FOR THE LAVS:
 A. 11-4.19.2- OK
 B. 11-4.19.3- OK
 C. 11-4.19.4 EXPOSED PIPES & SURFACES - NOT ADDRESSED,
 NO RESPONSE
 D. 11-4.19.5 FAUCETS - NOT ADDRESSED, NO RESPONSEE.
 11-4.19.6- OK
 FOR THE TOILET ROOMS:
 A.- OK
  
 2. SUBMIT A DETAIL FOR THE BREAK ROOM SINK. SHOW
 COMPLIANCE FOR THE FOLLOWING:
 A. 11-4.24.2- OK
 B. 11-4.24.3 KNEE CLEARANCE- NOT ADDRESSED, NO
 RESPONSE
 C. 11-4.24.4- OK
 D. 11-4.24.5- OK
 E. 11-4.24.6 EXPOSED PIPES & SURFACES- NOT
 ADDRESSED, NO RESPONSE
 F. 11-4.24.7 FAUCETS- NOT ADDRESSED, NO RESPONSE
  
 3. SUBMIT A WATER RISER DIAGRAM. SHOW ALL PIPE SIZES,
 VALVES,& IF QUICK CLOSING VALVES ARE INSTALLED, WATER
 HAMMER ARRESTORS PER SECTION 604.9, LOCATED NEAR THE
 FIXTURE, IN AN "EFFECTIVE RAGE", (NOT IN THE CEILING),
 PER PDI-WH 201 AND MANUF. INSTALLATION INSTRUCTIONS.
 SECTION 106.3.5.1.3(3)(10)(13).
 ****RESPONSE NOTED, BUT A WATER HAMMER ARRESTOR IS
 REQUIRED ON THE SUPPLY LINE TO THE ICE MAKER IN THE
 REFRIG.--WATER RISER DIAGRAM FOR EXAM ROOM #1 AND
 TOILET ROOM #2 MISLABELED.--THE SINK IN EXAM ROOM
 #4 IS NOT SHOWN ON THE RISER DIAGRAM.
  
 4. A DRINKING FOUNTAIN IS REQUIRED PER TABLE 403.1.
 ****RESPONSE NOTED, BUT A DRINKING FOUNTAIN IS REQUIRED
 PER TABLE 403.1 AND A BOTTLED WATER COOLER CAN NOT BE
 SUBSTITUTED FOR MORE THAN 50% OF THE REQUIRED DRINKING
 FOUNTAINS. IF ONE IS REQUIRED, THEN IT SHALL BE A
 DRINKING FOUNTAIN.
  
 5. OK
 6. OK
  
 ************NEW COMMENTS************
  
 1B. A TURNING AREA IS REQUIRED IN THE ACCESSIBLE TOILET
 ROOMS. SECTION 11-4.22.3.
  
 2B. SEE ATTACHED SHEET CONCERNING THE DESIGN
 PROFESSIONAL AND FS 533.80(2)(B). THIS IS GIVEN AS A
 ONE TIME NOTICE AS SOME OF THE COMMENTS ARE THE SAME AS
 THE PREVIOUS REVIEW.
  
 3. TWO COMPLETE SETS OF PLANS SHALL BE SUBMITTED.
 PLEASE ADD ALL SHEETS FROM THE FIRST REVIEW THAT WILL
 NOT BE CHANGED TO THE NEW SHEETS FROM THE SECOND
 REVIEW. (SEE D-1). SECTION 106.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 ****NOT ADDRESSED
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL KSTEVENS@
 WPB.ORG

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-03-14 Cont ID  
Sent By kstevens Date 2007-03-14 Time 11:56 Rev Time 0.00
Received By kstevens Date 2007-03-14 Time 11:56 Sent To  
Notes
2007-03-14 12:31:31DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
  
  
 1. SUBMIT A DETAIL FOR THE NEW TOILET ROOMS, (TOILET
 ROOMS 2 & 4). SHOW COMPLIANCE FOR THE FOLLOWING: FOR
 W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.3 HEIGHT
 C. 11-4.16.4 GRAB BARS
 D. 11-4.16.5 FLUSH CONTROLS
 E. 11-4.16.6 DISPENSERS
 FOR THE LAVS:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 D. 11-4.19.5 FAUCETS
 E. 11-4.19.6 MIRRORS
 FOR THE TOILET ROOMS:
 A. THE DOORS SHALL NOT SWING INTO THE CLEAR FLOOR
 SPACE REQUIRED FOR ANY FIXTURE. SECTION 11-4.22.2.
  
 2. SUBMIT A DETAIL FOR THE BREAK ROOM SINK. SHOW
 COMPLIANCE FOR THE FOLLOWING:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.4 SINK DEPTH
 D. 11-4.24.5 CLEAR FLOOR SPACE - FORWARD APPROACH
 REQUIRED. - NO CABINET DOORS ALLOWED
 E. 11-4.24.6 EXPOSED PIPES & SURFACES
 F. 11-4.24.7 FAUCETS
  
 3. SUBMIT A WATER RISER DIAGRAM. SHOW ALL PIPE SIZES,
 VALVES,& IF QUICK CLOSING VALVES ARE INSTALLED, WATER
 HAMMER ARRESTORS PER SECTION 604.9, LOCATED NEAR THE
 FIXTURE, IN AN "EFFECTIVE RAGE", (NOT IN THE CEILING),
 PER PDI-WH 201 AND MANUF. INSTALLATION INSTRUCTIONS.
 SECTION 106.3.5.1.3(3)(10)(13).
  
 4. A DRINKING FOUNTAIN IS REQUIRED PER TABLE 403.1.
  
 5. SHT A-1 ROOM FINISH SCHEDULE INDICATES DRYWALL FOR
 THE WALLS IN THE TOILET ROOMS.PER SECTION 1210.2,
 WALLS WITHIN 2FT OF URINALS AND WATER CLOSETS SHALL
 HAVE A SMOOTH, HARD, NONABSORBENT SURFACE, TO A HEIGHT
 OF 4' ABOVE THE FLOOR. DRYWALL DOES NOT MEET THESE
 REQUIREMENTS. PLEASE INDICATE HOW THIS REQUIREMENT WILL
 BE ADDRESSED.
  
 6. SHT A-1 THE PLUMBING RISER DIAGRAM DOES NOT REFLECT
 THE FLOOR PLAN, NOR DOES IT MEET CODE REQUIREMENTS.--
 THE SINK IN EXAM ROOM #1 SHALL DISCHARGE DOWNSTREAM OF
 THE FIXTURES IN TOILET ROOM #2 PER SECTION 909.1.--
 THE SINK IN EXAM ROOM #2 IS INDICATED AS EXISTING ON
 THE FLOOR PLAN, BUT INDICATED AS NEW ON THE SANT RISER
 DIAGRAM.--THE NEW BREAK ROOM SINK IS NOT INDICATED
 ON THE RISER DIAGRAM.--THE NEW TOILET ROOM #4 IS
 NOT INDICATED ON THE SANT RISER DIAGRAM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved