| 2007-03-20 20:02:30 | RECEPTS W/IN 6FT OF LUNDRY SINKS. GFI 210.8A7 INCLUDING |
| | WASHING MACHINES |
| 2007-02-23 10:28:37 | *** UNSAT *** |
| | |
| | 6700 FOX HOLLOW |
| | |
| | |
| | 1) NOTE: PLEASE BE SURE ALL PLANS REFLECT THE LATEST |
| | ADOPTED CODES PER THE STATE OF FLORIDA. PLEASE SEE THE |
| | FOLLOWING WHICH ARE CURRENTLY ADOPTED AS OF DECEMBER |
| | 8TH, 2006. |
| | 2004 FBC W/ 2006 REVISION. (THIS WILL AFFECT PLANS |
| | SUBMITTED). |
| | 2005 NFPA-70 (NEC). |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | ** THESE CODES ARE REQUIRED AT A MINIMUM FOR THIS TRADE |
| | REVIEWER; OTHERS MAY BE REQUIRED PER OTHER TRADES OR |
| | REVIEWER(S). |
| | PLEASE SEE THERE ARE MANY AREAS ON THE PLANS WHICH |
| | REFERENCE OLDER CODES FROM PREVIOUS CODES, THESE SHOULD |
| | BE REVISED ACCORDINGLY. |
| | |
| | 2) NOTE: PLEASE SEE 2004 FBC W/2006 FOR NOTE REQUIRED |
| | FOR TYPE OF RECESSED LIGHTING FIXTURES PER |
| | 13-606.1.ABC.1.2.4 |
| | |
| | 3) NOTE: PLEASE SEE REAR THAT THE REAR PORCH WILL |
| | REQUIRE A LIGHT W/ A SWITCH FROM THE MASTER BEDROOM OR |
| | A 3-WAY FOR THE FLOOD LIGHTS WHICH ARE BEING SHOWN FOR |
| | EGRESS LIGHTING FROM FAMILY ROOM. OTHER OPTIONS MAY |
| | ALSO BE DONE, HOWEVER PLEASE SHOW MINIMUM LIGHT(S) FOR |
| | EGRESS. A LIGHT FIXTURE OF SOME TYPE WILL BE REQUIRED |
| | FOR ILLUMINATION OF THE REAR AREA. (FLOODS AS SHOWN ARE |
| | OK) |
| | 210.70, LS 101 7.8 |
| | |
| | 4) NOTE: PLEASE SEE THE COMPRESSOR FOR THE A/C CU IS |
| | BEING SHOWN WITH A LOAD OF 9.8KW; PLEASE VERIFY THIS AS |
| | THIS LOAD EXCEED THAT OF THE RATING OF THE CIRCUIT |
| | BREAKER. |
| | THIS WAS REDLINED ON PREVIOUS PLANS ON MANY OCCASIONS |
| | BUT TO DATE NO CHANGES HAVE BEEN MADE. |
| | |
| | 5) NOTE: PLEASE KNOW THAT A MEETING WAS HELD AT THE |
| | SOUTHERN SECTION MEETING IN OCT 06 WHERE WE WERE |
| | DIRECTLY INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE |
| | DETECTORS ON PLANS FOR RESIDENTIAL HOMES IS NOT |
| | ACCEPTABLE WHEN THESE DEVICES ANY ACTUALLY FALL UNDER |
| | THE DEFINITIONS OF SMOKE ALARMS WHICH WOULD BE SHOWN AS |
| | SA/SMOKE ALARMS. |
| | THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE |
| | OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED. |
| | BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE |
| | DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL |
| | NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY |
| | HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF |
| | SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS |
| | SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS |
| | SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS |
| | FOR OTHER NEW HOMES. |
| | ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC |
| | RESIDENTIAL CODE/ FBC AND IN NFPA-72. |
| | IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |