Plan Review Details - Permit 07020367
Plan Review Stops For Permit 07020367
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-02-21 Cont ID  
Sent By rmcdouga Date 2007-02-21 Time 06:56 Rev Time 0.00
Received By rmcdouga Date 2007-02-21 Time 06:35 Sent To  
Notes
2007-02-21 07:00:39CONTRACTOR HAS REMOVED THE FLAT ROOF FROM THE SCOPE OF
 WORK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-02-14 Cont ID  
Sent By rmcdouga Date 2007-02-14 Time 12:55 Rev Time 0.00
Received By rmcdouga Date 2007-02-14 Time 12:55 Sent To  
Notes
2007-02-14 14:18:42DENIED BY BUILDING
  
 1)THE COVERSHEET FOR THE FIRESTONE MODIFIED ROOF
 SYSTEM IS INCORRECT. THE ONE FOR THE 2004 FBC IS FL
 6760.
  
 2) SPECIFY THE MEAN ROOF HEIGHT OF THE STRUCTURE.
  
 3) SPECIFY WHICH ONE OF THE APPROVED SYSTEMS WILL BE
 INSTALLED. ALSO SPECIFY WHICH FASTENING OPTION AND
 MAXIMUM DESIGN PRESSURE WILL BE USED. CIRCLE THE
 APPROPRIATE ITEMS IN THE PRODUCT APPROVAL.
  
 4) IF ENHANCED FASTENING IS REQUIRED TO MEET THE HIGER
 UPLIFT PRESSURES OF THE PERIMETER AND CORNER AREAS,
 SUBMIT RAS 117 CALCULATIONS AS REQUIRED BY LIMITATION
 NUMBER 7 ON PAGE 34. THE PRESSURES FOR THE PERIMETER IS
 -59.2 AND FOR THE CORNERS IS -89 FOR UP TO 30' IN
 EXPOSURE CATEGORY B.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  