Plan Review Details - Permit 07020355
| Plan Review Stops For Permit 07020355 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2007-07-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-07-11 |
Time |
10:07 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-07-10 |
Time |
16:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-05-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-05-07 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-05-07 |
Time |
10:19 |
Sent To |
|
|
| Notes |
| 2007-05-07 11:23:26 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC | | | FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | ***PLAN CHECK ONLY*** | | | | | | 1-5.)ADDRESSED. | | | | | | 6.)PLATFORM DETAIL EL X-1,2, V13, NO GUARDS SHOWN | | | FBC1012.THIS COMMENT APPLIES TO OTHER SHEETS SUCH AS | | | EL X-3,4.NOTE THAT THE "HANDRAIL" PLAN DOES NOT HAVE | | | CROSS SECTIONS REFERRING TO THESE ELEVATIONS SO I | | | CANNOT DETERMINE IF THE HANDRAIL (WHICH MAY ALSO SERVE | | | AS GUARDRAILS?) IS TO BE INSTALLED IN THIS LOCATION AND | | | WAS OMITTED FOR CLARITY, OR IF THE DESIGN INTENT IS FOR | | | THE PLATFORM OPEN SIDES.SEE FBC1012.1, FBC1028. | | | | | | 2ND REVIEW - A NOTE WAS ADDED STATING THAT PLATFORMS | | | OVER 48" IN HEIGHT WILL HAVE HANDDRAILS.SEE | | | FBC1012.1, GUARDS REQUIRED (IN ADDITION TO OTHER | | | LOCATIONS WHICH MAY BE APPLICABLE) ON INDUSTRIAL | | | EQUIPMENT PLATFORMS OVER 30 INCHES ABOVE THE FLOOR. | | | PLEASE NOTE THAT THERE IS A DIFFERENCE BETWEEN A | | | HANDRAIL AND A GUARDRAIL FBC1002. FBC1015.2 | | | ADDRESSES MECHANICAL EQUIPMENT PLATFORMS SPECIFICALLY. | | | | | | 7.)SHOW ALL REQUIRED GUARDS ON THE PLAN.FOR | | | INSTANCE, SEE ELEVATIONS X-3,4.SEE FBC1012, 1028. | | | | | | 2ND REVIEW - A PLAN WAS PROVIDED BUT THE NOTE (48" HIGH | | | PLATFORMS) CONFLICTS WITH CODE REQUIREMENTS OF 30". | | | PLEASE REVISE THE NOTE AND REVISE HANDRAIL/GUARDRAIL | | | PLAN AS REQUIRED. | | | | | | 8.)1ST REVIEW - ARE ALL HANDRAILS SHOWN ON L1 TO ALSO | | | SERVE AS GUARDRAILS?THEY APPEAR TO BE AT PLATFORM | | | AREAS; HANDRAILS ARE NOT REQUIRED FOR PLATFORMS BUT | | | GUARDS (GUARDRAILS) ARE.SEE OTHER COMMENTS. | | | | | | 2ND REVIEW - THE RESPONSE, "THIS SAFETY RAIL IS FOR | | | MAINTENANCE PURPOSES OF THE CONVEYOR ONLY" DOES NOT | | | ADDRESS THE COMMENT.THE GUARDRAILS ARE REQUIRED, | | | HANDRAIL REQUIREMENTS ARE NOT CLEAR.SEE OTHER | | | COMMENTS. | | | | | | 9.)1ST REVIEW - SEE ELEVATIONS X-1,2, SECTION DETAIL | | | V7, 3.1. THIS DETAIL IS TOO SMALL TO READ.THE SHEETS | | | ARE LABELED BUT NOT NUMBERED.DOES THIS REFER TO SHEET | | | 3.1 (NO 3.1 IN THE SET)?ARCHITECTURAL STANDARDS ARE | | | FOR DETAIL AND SECTION INDICATORS TO REFER TO DETAIL | | | AND PAGE, BUT THE DETAILS PROVIDED REFER TO SHEETS | | | WHICH ARE NOT IN THE PACKAGE.PLEASE EITHER PROVIDE | | | STANDARD DETAIL AND SECTION INDICATORS OR ADVISE AS TO | | | HOW I COULD BEST UNDERSTAND THE PLAN. | | | | | | 2ND REVIEW - THE SHEET PROVIDED DOES NOT HAVE A TITLE | | | BLOCK AND IS NOT SEALED.PLEASE INCORPORATE ALL | | | NECESSARY DETAILS INTO THE PLAN AND REMOVE UNNECESSARY | | | DETAILS.OTHER SHEETS HAVE SMALL ILLEGIBLE DETAILS. | | | EITHER REMOVE FROM THE PLAN OR ENLARGE SO THAT THEY ARE | | | LEGIBLE. | | | | | | 10.) ADDRESSED, BUT PLEASE SEE ELECTRIC COMMENTS. | | | | | | 11.) THE PREVIOUS COMMENT REQUESTED CLARIFICATION FOR | | | THE PURPOSE OF THE WALKS AND LANDINGS.THE PLAN NOW | | | STATES IN GENERAL NOTES THAT "ALL PLATFORMS ARE FOR | | | MAINTENANCE PURPOSES ONLY."PLEASE FURTHER DESCRIBE | | | THE USE OF THE LANDINGS AND WALKS."MAINTENANCE ONLY"; | | | IS THIS TO OCCUR ON OCCASION SUCH AS ONCE A MONTH, OR | | | SEVERAL TIMES IN THE DAY?COMPLIANCE WITH VERTICAL | | | ACCESSIBILITY (EXCEPTION) APPEARS TO BE CLEAR, BUT | | | EGRESS REQUIREMENTS ARE NOT CLEAR. | | | | | | PLEASE INCORPORATE THIS INFORMATION ON THE ISO SHEET | | | WHICH MAKES IT APPEAR THAT THE LANDINGS ARE WORK | | | AREAS. | | | | | | | | | NEW COMMENTS; | | | | | | 12.)CLEARLY INDICATE ALL CHANGES TO THE PLAN WITH | | | CLOUDS AND REVISION NUMBERS. SEVERAL SHEETS CHANGED | | | WITH NO REVISIONS SHOWN. | | | | | | 13.)SHEET A, ELEVATIONS X-1, 2 HAS A DETAIL V7 3.1 | | | WHICH IS TOO SMALL TO BE LEGIBLE.ALL INFORMATION ON | | | THE PLAN IS TO BE LEGIBLE.CHECK ALL SHEETS, ALL | | | DETAILS. | | | | | | 14.)THE GENERAL NOTES REFER TO THE CONVEYOR SAFETY | | | CABLE RAIL LOCATIONS.REQUIRED GUARDS ARE TO COMPLY | | | WITH FBC1012, FBC1607.7.PLEASE STATE STRUCTURAL | | | DESIGN CRITERIA ON THE PLAN AND PROVIDE A DETAIL | | | SHOWING COMPLIANCE WITH FBC1012.THE DETAIL AS DRAWN | | | IS NOT TALL ENOUGH AND THE OPENINGS ARE TOO LARGE TO | | | REJECT A 21" OBJECT.CODE COMPLIANCE IS NOT CLEAR. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-04-03 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-04-03 |
Time |
08:43 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-04-02 |
Time |
17:49 |
Sent To |
|
|
| Notes |
| 2007-04-03 08:00:26 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC | | | FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.)ALL INFORMATION REQUIRED BY FAC61G1-16-23.002, 003 | | | AND FAC61G15-23.002 ARE TO BE ON EACH SHEET. | | | | | | 2.)ALL SHEETS ARE TO BE SIGNED, SEALED, DATED, FS471, | | | FS481 WHEN SUBMITTED FOR PUBLIC RECORD. | | | | | | 3.)DECLARE GOVERNING CODE. | | | | | | 4.)INFORMATIONAL ONLY; THIS IS A PLAN CHECK.PERMIT | | | APPLICATON REQUIRED.REVIEW WILL REMAIN IN "F" | | | STATUS. | | | | | | 5.)L3, SHOW TRAVEL DISTANCES AND PROVIDE A CODE | | | SUMMARY (BUILDING TYPE, OCCUPANCY, TRAVEL DISTANCE, | | | BUILDING AREA, OCCUPANT LOAD). | | | | | | 6.)PLATFORM DETAIL EL X-1,2, V13, NO GUARDS SHOWN | | | FBC1012.THIS COMMENT APPLIES TO OTHER SHEETS SUCH AS | | | EL X-3,4.NOTE THAT THE "HANDRAIL" PLAN DOES NOT HAVE | | | CROSS SECTIONS REFERRING TO THESE ELEVATIONS SO I | | | CANNOT DETERMINE IF THE HANDRAIL (WHICH MAY ALSO SERVE | | | AS GUARDRAILS?) IS TO BE INSTALLED IN THIS LOCATION AND | | | WAS OMITTED FOR CLARITY, OR IF THE DESIGN INTENT IS FOR | | | THE PLATFORM OPEN SIDES.SEE FBC1012.1, FBC1028. | | | | | | 7.)SHOW ALL REQUIRED GUARDS ON THE PLAN.FOR | | | INSTANCE, SEE ELEVATIONS X-3,4.SEE FBC1012, 1028. | | | | | | 8.)ARE ALL HANDRAILS SHOWN ON L1 TO ALSO SERVE AS | | | GUARDRAILS?THEY APPEAR TO BE AT PLATFORM AREAS; | | | HANDRAILS ARE NOT REQUIRED FOR PLATFORMS BUT GUARDS | | | (GUARDRAILS) ARE.SEE OTHER COMMENTS. | | | | | | 9.)SEE ELEVATIONS X-1,2, SECTION DETAIL V7, 3.1. THIS | | | DETAIL IS TOO SMALL TO READ.THE SHEETS ARE LABELED | | | BUT NOT NUMBERED.DOES THIS REFER TO SHEET 3.1 (NO 3.1 | | | IN THE SET)?ARCHITECTURAL STANDARDS ARE FOR DETAIL | | | AND SECTION INDICATORS TO REFER TO DETAIL AND PAGE, BUT | | | THE DETAILS PROVIDED REFER TO SHEETS WHICH ARE NOT IN | | | THE PACKAGE.PLEASE EITHER PROVIDE STANDARD DETAIL AND | | | SECTION INDICATORS OR ADVISE AS TO HOW I COULD BEST | | | UNDERSTAND THE PLAN. | | | | | | 10.) CONTRACTOR HAS DECLARED VALUE OF $45,000.THIS IS | | | TO INCLUDE ALL MATERIALS AND LABOR, FBC*108.3. | | | | | | 11.)PLEASE CLARIFY THE PURPOSE OF THE WALKS AND | | | LANDINGS.FROM ISO AND ELEVATIONS THIS APPEARS TO BE | | | AN OCCUPIABLE WORK AREA, BUT DOES NOT MEET GENERAL | | | EGRESS REQUIREMENTS OF FBC10 OR ACCESSIBILITY FBC11 | | | (VERTICAL ACCESSIBILITY, HANDRAILS, EGRESS, ETC.).SEE | | | ALSO FBC11-4.1.3(5)(3) IF APPLICABLE. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2007-08-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-08-10 |
Time |
11:21 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-08-08 |
Time |
12:48 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2007-06-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-06-23 |
Time |
19:00 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-06-23 |
Time |
18:36 |
Sent To |
|
|
| Notes |
| 2007-06-23 19:00:50 | *** UNSAT 3RD REVIEW *** | | | | | | | | | 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW WITH | | | RESPECT TO PLANS ONLY BEING SUBMITTED FOR *PLAN | | | REVIEW*. | | | PLEASE KNOW THAT PLANS ARE STILL NOT SUBMITTED FOR | | | PERMIT AND WILL BE PLACED INTO A FAILED STATUS EVEN | | | WHEN ALL CODE COMMENTS ARE ADDRESSED. | | | VERIFICATION OF LICENSE INFORMATION, PERMIT VALUATION, | | | CONTRACTING LICENSING AND CODES IN EFFECT AT THE TIME | | | OF APPLICATION WILL ALL STILL NEED TO BE VERIFIED. IF | | | THERE ARE ANY CODE CHANGES WHICH ARE ADOPTED BY THE | | | STATE AND THE PERMIT APPLICATION HAS NOT BEEN MADE, | | | THEN PLANS WILL FALL UNDER THE NEW CODES ADOPTED BY THE | | | STATE WHICH MAY REQUIRE DESIGN CHANGES. | | | ALL OF THESE ITEMS CAN NOT BE VERIFIED AT THIS TIME. | | | | | | 2) NOTE:PLEASE SEE AS STATED ON PREVIOUS REVIEWS; | | | PLEASE BE SURE ALL INFORMATION IN TITLE BLOCKS IS | | | CORRECT.PLEASE SEE THERE IS NOW A DESIGNER OF RECORD | | | CHANGE. PLEASE SEE THE ATTACHED PRINT OUT FROM THE | | | DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION AS | | | THE INFORMATION FOR THE ENGINEER OF RECORD ON TITLE | | | BLOCKS DOES NOT MATCH THE STATE WEBSITE. | | | PLEASE ADJUST AS THIS INFORMATION MUST MATCH. | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-04-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-04-25 |
Time |
14:28 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-04-25 |
Time |
14:10 |
Sent To |
|
|
| Notes |
| 2007-04-25 14:28:32 | | | | | | | ** UNSAT2ND REVIEW** | | | | | | | | | | | | 1) NOTE: PLEASE SEE THAT PLANS ARE STILL ONLY BEING | | | SUBMITTED FOR *PLAN REVIEW* ONLY AND HAVE NOT BEEN | | | SUBMITTED FOR PERMIT APPLICATION. PLEASE KNOW THAT EVEN | | | IF ELECTRICAL WAS OK, THE PLANS WOULD STILL REMAIN IN A | | | *F* STATUS UNTIL THE TIME THAT THE PERMIT APPLICATION, | | | CONTRACTOR, VALUATION ETC CAN BE REVIEWED ALONG WITH | | | FINAL DOCUMENTS. | | | | | | 2) NOTE: PLEASE SEEINFORMATION ON TITLE BLOCKS FOR | | | BOTH OF THE ENGINEER AND ARCHITECT AS REQUIRED UNDER | | | FLORIDA ADMINISTRATIVE CODES 61G15-23.002, 61G1-16.004. | | | PLEASE ALSO SEE FLORIDA STATUTES 471.023 AND 481.219 | | | WHERE APPLICABLE FOR REQUIRED FIRM LICENSE NUMBER(S). | | | PLEASE SEE MISSING THE REQUIRED PRINTED NAME AND | | | PRINTED LICENSE NUMBER OF DESIGNERS. | | | PRINTED NAMES ARE REUIRED FOR ALL TITLE BLOCKS FOR | | | ARCHITECT AND ENGINEER. | | | ** REVIEW OF TITLE BLOCKS AND INFORMATION REQUIRED ON | | | TITLE BLOCKS CAN NOT BE DONE AT THIS TIME. | | | PLANS NOW CONTAIN TITLE BLOCKS, HOWEVER NOT COMPLETE | | | WITH ALL INFORMATION AS REQUIRED. | | | | | | 3) NOTE: PLEASE SEE MOST OF THE SEALS ON THE SHEETS FOR | | | THE MEP ARE NOT CLEAR AND VISIBLE WITH ALL INFORMATION | | | ON RAISED SEAL ESAILY READ. | | | FAC 61G15-23.001. | | | | | | 4) NOTE:THE VALUE IN RESPONSE LETTER MENTIONS WHEN | | | APPLIED FOR PERMIT THE VALUE WILL BE 180K, HOWEVER | | | PLEASE KNOW THAT THE VALUE SHALL INCLUDE ALL LABOR TO | | | INSTALL AND VALUE FOR EQUIPMENT EVEN IF EQUIPMENT IS | | | OWNER SUPPLIED. THIS VALUE SHOWN IS LOW FOR THIS | | | SYSTEM. | | | PLEASE KNOW THAT THE VALUE FOR THE COMPLETE SCOPE OF | | | WORK FOR THE CONVEYOR SYSTEM, ELECTRICAL, ETC SHALL | | | INCLUDE ALL LABOR AND MATERIALS EVEN IF EQUIPMENT, | | | ELECTRICAL PANELS ETC ARE OWNER SUPPLIED. PLEASE ADJUST | | | THE APPLIED VALUE FOR ALL WORK AS SHOWN. FBC 108.3 | | | ADMIN SECTION. | | | | | | 5) NOTE: PLEASE PROVIDE MORE INFORMATION ON ELECTRICAL | | | SYSTEM(S). PLEASE PROVIDE INFORMATION ON LISTINGS OF | | | CONTROL BOARDS/PANELS FROM A NRTL. | | | PLEASE KNOW THAT THE INFORMATION AS SHOWN ON BASE | | | BUILDING FOR SUPPLY DOES NOT PROVIDE ENOUGH INFORMATION | | | FOR THIS SYSTEM. | | | 110.3, 90.7. | | | PLEASE LIST ON RECORD SET OF PLANS WHERE POWER ETC IS | | | COMING FROM. THIS SHOULD CORRELATE WITH THE MAIN | | | BUILDING PLANS SHOWING CIRCUITING ETC. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-03-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-03-04 |
Time |
15:38 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-03-04 |
Time |
15:07 |
Sent To |
|
|
| Notes |
| 2007-03-04 15:40:41 | ** UNSAT ** | | | | | | 1) NOTE: PLEASE KNOW THAT PLANS HAVE ONLY BEEN | | | SUBMITTED FOR *PLAN REVIEW* ONLY AND HAVE NOT BEEN | | | SUBMITTED FOR PERMIT APPLICATION. PLEASE KNOW THAT EVEN | | | IF ELECTRICAL WAS OK, THE PLANS WOULD STILL REMAIN IN A | | | *F* STATUS UNTIL THE TIME THAT THE PERMIT APPLICATION, | | | CONTRACTOR, VALUATION ETC CAN BE REVIEWED ALONG WITH | | | FINAL DOCUMENTS. | | | | | | 2) NOTE: PLEASE KNOW THAT PERMIT APPLICATION HAS BEEN | | | SUBMITTED AFTER DECEMBER 8TH, 2006 WHICH PLACES | | | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. | | | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO | | | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. | | | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH WILL | | | AFFECT DESIGNS FOR ALL TRADES | | | | | | 3) NOTE: PLEASE SEE MISSING TITLE BLOCKS FOR BOTH OF | | | THE ENGINEER AND ARCHITECT AS REQUIRED UNDER FLORIDA | | | ADMINISTRATIVE CODES 61G15-23.002, 61G1-16.004. PLEASE | | | ALSO SEE FLORIDA STATUTES 471.023 AND 481.219 WHERE | | | APPLICABLE FOR REQUIRED FIRM LICENSE NUMBER(S). PLEASE | | | SEE MISSING THE REQUIRED PRINTED NAME AND PRINTED | | | LICENSE NUMBER OF DESIGNERS. | | | ** REVIEW OF TITLE BLOCKS AND INFORMATION REQUIRED ON | | | TITLE BLOCKS CAN NOT BE DONE AT THIS TIME. | | | | | | 4) NOTE: PLEASE BE SURE ALL SEALS ARE CLEAR AND VISIBLE | | | WITH ALL INFORMATION ON SAID SEAL. THE PE SEAL IS VERY | | | FAINT AND INFORMATION IS NOT EASILY READ. 61G15-23.001 | | | | | | 5) NOTE: ***IMPORTANT*** | | | PLEASE SEE ATTACHED DOCUMENTATION FROM THE DEPARTMENT | | | OF BUSINESS AND PROFESSIONAL REGULATION / STATE'S | | | WEBSITE WHICH SHOWS THE LICENSE FOR JAMES PURDY, PE # | | | 14240 AS *DELINQUENT*/ EXPIRED. | | | ONE SET OF PLANS TO BE RETAINED. | | | | | | 6) NOTE: PLEASE KNOW THAT THE VALUE FOR THE COMPLETE | | | SCOPE OF WORK FOR THE CONVEYOR SYSTEM, ELECTRICAL, ETC | | | SHALL INCLUDE ALL LABOR AND MATERIALS EVEN IF | | | EQUIPMENT, ELECTRICAL PANELS ETC ARE OWNER SUPPLIED. | | | PLEASE ADJUST THE APPLIED VALUE FOR ALL WORK AS SHOWN. | | | FBC 108.3 ADMIN SECTION. | | | | | | 7) NOTE: PLEASE PROVIDE MORE INFORMATION ON ELECTRICAL | | | SYSTEM(S). PLEASE PROVIDE INFORMATION ON LISTINGS OF | | | CONTROL BOARDS/PANELS FROM A NRTL. | | | 110.3, 90.7. | | | PLEASE LIST ON RECORD SET OF PLANS WHERE POWER ETC IS | | | COMING FROM. THIS SHOULD CORRELATE WITH THE MAIN | | | BUILDING PLANS SHOWING CIRCUITING ETC. | | | | | | 8) NOTE: PLEASE SEE ANY COMMENTS FROM OTHER TRADES | | | WHICH MAY AFFECT ELECTRICAL PLANS. | | | | | | 9) NOTE: PLEASE SEE SEVERAL SHEETS FROM THE ARCHITECT | | | IN EACH SET ARE NOT SIGNED, DATED AND SEALED AS | | | REQUIRED. PLEASE SEE SOME SHEETS WHERE IT APPEARS THE | | | DESIGNER STARTED TO SIGN PLANS AND STOPPED MID-POINT? | | | 481.221. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2007-07-24 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-07-24 |
Time |
13:32 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-07-24 |
Time |
12:41 |
Sent To |
|
|
| Notes |
| 2007-07-24 13:02:45 | *****APPROVED***** | | | | | | ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE | | | BEEN ADDRESSED;PLAN SHEET A1.3 STAMPED,INITIALED, AND | | | DATED. | | | | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2007-05-08 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-05-08 |
Time |
13:31 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-05-08 |
Time |
13:01 |
Sent To |
|
|
| Notes |
| 2007-05-08 13:21:17 | *****DENIED***** | | | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE | | | PLAN REVIEW STILL NEED TO BE ADDRESSED: | | | | | | 1. THE ACTUAL ADDRESS OF WHERE THE SCOPE OF WORK WILL | | | BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH | | | SUBMITTED PLAN SHEET. | | | | | | 2.THE CONVEYOR SYSTEM SHALL NOT OBSTRUCT EXITS, | | | ACCESS THERETO, EGRESS THEREFROM, OR VISIBILITY | | | THEREOF. | | | | | | 4.INDUSTRIAL EQUIPMENT ACCESS STAIRS THAT SERVE AS A | | | COMPONENT OF THE MEANS OF EGRESS FROM THE INVOLVED | | | EQUIPMENT SHALL BE PERMITTED IN ACCORDANCE WITH TABLE | | | 40.2.5.2.1 OF NFPA101. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-03-30 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-03-30 |
Time |
17:43 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-03-30 |
Time |
16:19 |
Sent To |
|
|
| Notes |
| 2007-03-30 17:42:57 | *****DENIED***** | | | | | | | | | 1. THE ACTUAL ADDRESS OF WHERE THE SCOPE OF WORK WILL | | | BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH | | | SUBMITTED PLAN SHEET. | | | | | | 2.THE CONVEYOR SYSTEM SHALL NOT OBSTRUCT EXITS, | | | ACCESS THERETO, EGRESS THEREFROM, OR VISIBILITY | | | THEREOF. | | | | | | 3.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 4.INDUSTRIAL EQUIPMENT ACCESS STAIRS THAT SERVE AS A | | | COMPONENT OF THE MEANS OF EGRESS FROM THE INVOLVED | | | EQUIPMENT SHALL BE PERMITTED IN ACCORDANCE WITH TABLE | | | 40.2.5.2.1 OF NFPA101. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-08-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-08-02 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-08-02 |
Time |
14:14 |
Sent To |
E |
|
| Notes |
| 2007-08-02 14:14:36 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-06-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-11 |
Time |
08:35 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-11 |
Time |
08:35 |
Sent To |
|
|
| Notes |
| 2007-06-22 16:34:37 | TO "COMM" BD#43 | | 2007-06-11 08:35:59 | WAITING FOR"COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-04-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-04-23 |
Time |
12:02 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-04-23 |
Time |
12:02 |
Sent To |
|
|
| Notes |
| 2007-04-25 08:57:14 | TO "COMM" BD#52/PLANS ON RACK--1 ROLL | | 2007-04-23 12:02:24 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-04-03 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-04-03 |
Time |
08:59 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-02-15 |
Time |
14:19 |
Sent To |
|
|
| Notes |
| 2007-02-26 11:51:02 | TO "COMM" BD#45 | | 2007-02-15 14:20:05 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2007-02-28 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2007-02-28 |
Time |
17:08 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2007-02-28 |
Time |
17:08 |
Sent To |
|
|
| Notes |
|
|
|