Plan Review Details - Permit 07020324
Plan Review Stops For Permit 07020324
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-10-24 Cont ID  
Sent By jgomez Date 2007-10-24 Time 13:47 Rev Time 0.00
Received By jgomez Date 2007-10-24 Time 12:38 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-06-19 Cont ID  
Sent By jgomez Date 2007-06-19 Time 11:40 Rev Time 0.00
Received By jgomez Date 2007-06-19 Time 11:40 Sent To PC
Notes
2007-06-19 13:18:13BUILDING REVIEW 3RD CHECKLIST:
 1- NOTICE OF COMMENCEMENT IS EXPIRED AFTER 90 DAYS IF
 WORK IS NOT STARTED. NEED TO RE-RECORD NOTICE OF
 COMMENCEMENT.
  
 2- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) PRECAST LINTELS.NOA 03-0605.05 SUBMITTED
 EXPIRED ON 05/21/06. NEED CURRENT ONE.
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
 PRODUCT APPROVALS HAVE AN APPROVED AND REVIEWED STAMP
 BUT IT LACKS THE MOST IMPORTANT INFORMATION. WHO
 REVIEWED AND APPROVED IT?.NEED TO PROVIDE THE NAME
 OF THE ENGINEER WHO REVIEWED AND APPROVED THE PRODUCT
 APPROVALS.
 ALSO,ENGINEER SIGNATUREIS NOT THESAME AS SHOWN ON
 FLOOR PLANS.
  
 4- HURRICANE SHUTTERS:
 A) PROVIDE COMPLETE AND CORRECT INSTALLATION
 SCHEDULE. INFORMATION SUBMITTED IS INCORRECT.USE
 CLEAN COPY. SEE ATTACHED CLEAN COPY. TRACO SECURITY
 WINDOWS IS NOT THE PRODUCT APPROVAL MANUFACTURER.
 COORDINATE SIZE OF OPENINGS AND DESIGN PRESSURES WITH
 FLOOR PLANS. REVISE SIZE TYPE AND SPACING OF ANCHORS.
 PROVIDE INFORMATION FOR TOP AND BOTTOM ANCHORS. WHAT'S
 #5 SHOWN ON CENTER BOLTS OR REINFORCING BARS COLUMN?.
  
 SEE ENGINEERED DRAWINGS FOR STORM SHUTTERS AND MARK
 SPECIFIC MOUNTING CONDITIONS (EG: WALL MOUNT) AND
 SPECIFIC TYPE OF ANCHOR AND SPACING TO BE USED
 ACCORDING TO THE DESIGN PRESSURES, PANEL SPAN,EDGE
 DISTANCE, CONNECTION TYPE AND STRUCTURE TO BE ATTACHED
 TO ( CONCRETE BLOCK).SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 5- ENGINEER TO PROVIDE ACTUAL CALCULATIONS FOR OPENING
 DESIGN PRESSURES. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.DESIGN PRESSURES SHOWN ON OPENINGS ARE LOW
 COMPARED TO REVISED TABLE 1609.6.2.1(2) OF FBC 2004 AND
 ACTUAL OPENING LOCATION, END OR INTERIOR ZONE.
  
 6- ENGINEER TO SPECIFYALL LOADS INCLUDING ATTIC LIVE
 LOADS AS REQUIRED BY SEC. R301 AND TABLE R301.5 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 7- INFORMATION SUBMITTED FOR EMERGENCY EGRESS WINDOWS
 IS INCORRECT.SEC. R301 AND TABLE R301.5HAVE NOTHING
 TO DO WITH EMERGENCY EGRESS. REVISE AS REQUIRED. SEE
 2004 FLORIDA RESIDENTIAL CODE FOR CORRECT CODE SECTION
 FOR EGRESS WINDOWS AND REVISE ALL INFORMATION AS
 REQUIRED.
 ALSO, NET CLEAR OPENING: 20".THIS IS NET CLEAR
 OPENING IN WHAT DIRECTION? WIDTH?.
  
 8-REVISE INFORMATION GIVEN ON WIND INFORMATION - 2004
 FBC.SEEFBC 2004 INCLUDING THE REVISIONSAND
 SPECIFY CORRECT SECTIONS OF THE CODE.
 PROVIDE COMPLETE AND CORRECT SPECIFICATIONS FOR SIZE OF
 REINFORCING STEEL ANGLE TO SUPPORT EXISTING TIE BEAM.
 SPECIFICATIONS SUBMITTED ARE INCOMPLETE.SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 9- COORDINATE LIVE AND DEAD LOADS SHOWN ON WIND
 INFORMATION - 2004 FBC AND STRUCTURAL LOADS INFORMATION
 GIVEN ON THE SAME SHEET.INFORMATION SHOWN DOESN'T
 MATCH.
  
 10- ROOF SHEATHING INFORMATION SHOWN ON PLYWOOD
 SHEATHING FASTENER SCHEDULE AND TYPICAL EXTERIOR WALL
 SECTION DOESN'T MATCH. REVISE AS REQUIRED.SEE SEC.
 R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE FOR CORRECT
 TYPE AND FASTENER SPACING FOR INTERIOR ZONES AND ZONE
 3.
  
 11- ENGINEER TO SEE ATTACHED COPY OF FLORIDA STATUTE
 553.80(2)(B) REGARDING PLAN REVIEW FEES FORDESIGN
 PROFESSIONAL DOCUMENTS AND CONTINUOUS FAILURES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-05-09 Cont ID  
Sent By jgomez Date 2007-05-09 Time 10:49 Rev Time 0.00
Received By jgomez Date 2007-05-09 Time 10:49 Sent To PC
Notes
2007-05-09 10:52:58BUILDING REVIEW SECOND CHECKLIST:
 1- PROPERTY IS LOCATED ON FLOOD ZONE A9 (ELEVATION 13).
 MINIMUM FLOOR ELEVATION REQUIRED FOR FINISH FLOOR
 ELEVATION AND ANY EQUIPMENTIS 13'-6" AS REQUIRED BY
 CITY ORDINANCE.PLANS TO INDICATE THIS MINIMUM
 ELEVATION.
 ALSO,SINCE PROPERTY IS LOCATED IN A FLOOD ZONE AREA,
 THEOWNER IS REQUIRED TO PROVIDE AN ELEVATION
 CERTIFICATE.
  
 2- NOTICE OF COMMENCEMENT WAS RECORDED ON 2/13/07.
 NOTICE OF COMMENCEMENT EXPIRES AFTER 90 DAYS OF
 RECORDING IF WORK IS NOT STARTED.THEREFORE, MAY NEED
 TO PROVIDE RE-RECORDED NOTICE OF COMMENCEMENT.
  
 3- AFTER PLANS ARE REVISED, BRING TEHM TO PALM BEACH
 COUNTY TO PAY THE IMPACT FEES (2300 N. JOG RD.
 (561)233-5115).BRING BACK TO THIS OFFICESTAMPED
 PLANS AND COPY OF PAID RECEIPT IF ADDITIONAL FEES ARE
 DUE.
  
 4- ENGINEER NEEDS TO UPDATE HIS LICENSE WITH THE STATE
 PRIOR TO RESUBMITTAL OF PLANS TO THIS OFFICE.
  
 5- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) WINDOW MULLIONS.
  
 B) PRECAST LINTELS.
  
 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 OF CITY AMENDMENTS TO FBC
 2004.
 ***NOTE: INDICATE NAME OF ENGINEER APPROVING THE
 PRODUCT APPROVALS.INFORMATION WAS NOT PROVIDED ON
 APPROVED PRODUCT APPROVALS.
  
 7- HURRICANE SHUTTERS:
 A) PROVIDE COMPLETE APPROVED PRODUCT APPROVAL.
 INFORMATION SUBMITTED IS NOT AN APPROVED PRODUCT
 APPROVAL AS REQUIRED BY DCA.
  
 B) ENGINEER OF RECORD TO REVIEW AND APPROVE IN
 WRITING PRODUCT APPROVAL.
  
 C) PROVIDE KEY PLAN AND CORRECT INSTALLATION
 SCHEDULE. CHECK OPENING SIZE AND LOCATION, DESIGN
 PRESSURES, ANCHOR SPECIFIED,SHUTTER GLASS SEPARATION,
 EDGE DISTANCE VS PANEL SPAN,ANCHOR SPACING TOP AND
 BOTTOM, CENTER BOLTS REINFORCING, ETC. SEE PRODUCT
 APPROVAL TO FIND CORRECT INFORMATION AND REVISE AS
 REQUIRED.
  
 8- ENGINEER TO REVISE DESIGN PRESSURES FOR DOOR AND
 WINDOW OPENINGS ACCORDING TO SIZE AND LOCATION. END OR
 INTERIOR.SEEREVISED TABLE 1609.6.2.1(2) OF 2004 FBC
 AND REVISE DESIGN PRESSURES AS REQUIRED.OTHERWISE,
 PROVIDE COMPLETE ENGINEERING CALCULATIONS SHOWING
 CALCULATED VALUES. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 9- OWES $654.54 FOR UPDATED BUILDING PERMIT VALUATION
 AND RADON FEES.
  
 10- SHEET A1:
 A) SPECIFY ALL DESIGN LOADSAS REQUIRED BY SEC.
 R301 AND TABLE R301.5 OF 2004 FLORIDA RESIDENTIAL CODE.
 INFORMATION SUBMITTED IS INCORRECT.
  
 B) REVISE EGRESS WINDOW NOTES:MIN. TOTAL AREA IS
 FOR MIN. TOTAL OPENING AREA, NOT GLASS AREA. REVISE AS
 REQUIRED.
  
 11- SHEET A2:
 A) DEMOLITION REAR KITCHEN DETAIL:
 * SPECIFY IF EXISTING BEAM IS A POURED TIE BEAM OR BOND
 BEAM.PROPOSED FLOOR PLAN CALLS FOR TIE BEAM, WHILE
 THIS DETAIL CALLS FORBOND BEAM. THERE IS A BIG
 DIFFERENCE BETWEEN BOTH. REVISE/CLARIFY AS REQUIRED.
  
 ** HOW IS THE BEAM REINFORCED TO SUPPORT THE ADDITIONAL
 ROOF LOAD CONSIDERING THAT EXISTING POURED CONCRETE
 COLUMN WILL BE REMOVED. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 *** OPENING DIMENSION SHOWN ON THIS DETAIL DOESN'T
 MATCH OPENING DIMENSION SHOWN ON PROPOSED FLOOR PLAN.
  
 12- SHEETA3:
 A) ROOF PLAN:
 * REVISE NUMBER AND TYPE OF FASTENER SPECIFIED FOR
 SIMPSON HETA20 ANCHOR. SEE CURRENT CATALOG AND REVISE
 AS REQUIRED. OTHERWISE, PROVIDE COMPLETE ENGINEERING
 ANALYSIS FOR TYPE AND NUMBER OF FASTENERS THAT DIFFER
 FROM THOSE TESTED AND PUBLISHED BY THE MANUFACTURER.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 ** CLARIFY WHAT'S UA= 1805. THERE IS NOT ABREVIATION
 LEGEND TO IDENTIFY THIS ABREVIATION.
  
 *** WHAT'S W/14-DX1 1/2?. REVISE AS REQUIRED.
  
 B) ROOF SHEATHING DETAIL:
 * REVISE ROOF SHEATHING SPECIFICATIONS FOR TYPE OF NAIL
 TO BE USED. SEE SEC. R803..2.3.1 OF 2004 FLORIDA
 RESIDENTIAL CODEFOR TYPE OF NAIL TO BE USED.
  
 ** PLYWOOD THICKNESS DOESN'T MATCH SPECS ON TYP. EXT.
 WALL SECTION. REVISE AS REQUIRED.
  
 *** SPECIFICATIONS FOR ROOF SHEATHING SHOWN ON ROOF
 SHEATHING DETAIL AND TYP. WALL SECTION DON'T MATCH.
 REVISE AS REQUIRED AND CLEARLY IDENTIFY END ZONES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-28 Cont ID  
Sent By jgomez Date 2007-03-28 Time 17:14 Rev Time 0.00
Received By jgomez Date 2007-03-28 Time 17:14 Sent To  
Notes
2007-03-28 17:50:30BUILDING REVIEW CHECKLIST:
  
 1- PROVIDE 2 COPIES OF EVERYTHING.
  
 2- PROVIDE NOC AS REQUIRED BY SEC. 713.13 FLORIDA
 STATUTE.
  
 3- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH
 COUNTY TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE
 DUE.
  
 4- ENGINEER TO CHECK WITH DBPR TO UPDATE HIS LICENSE
 STATUS.
  
 5- ENGINEER'S SEAL IS NOT LEGIBLE. UNABLE TO DETERMINE
 IF USING UPDATED SEAL.
  
 6- PROVIDE PRODUCT APPROVAL (TWO COPIES)AS REQUIRED
 BY RULE 9B-72 FOR:
 A) WINDOW MULLIONS.
  
 B) TRUSS CONNECTORS SPECIFIED ON PLANS AND DETAILS.
  
 7- ENGINEER TO REVIEW AND APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 8- HURRICANE SHUTTERS:
 A) PROVIDE PRODUCT APPROVAL (REVIEWED AND APPROVED
 BY THE ENGINEER).
  
 B) PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE
 ATTACHED SAMPLE OF INSTALLATION SCHEDULE. COMPLETE ALL
 THE INFORMATION.
  
 9- PROVIDE CALCULATIONS FOR DESIGN PRESSURES AT DOORS
 AND WINDOWS. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
 THEY ARE TOO LOW COMPARED TOZONE LOCATION AND TABLE
 R301.2(2) OF 2004 FLORIDARESIDENTIAL CODE.
  
 10- VALUE DECLARED ON THE PERMIT APPLICATION IS TOO
 LOW. IT WAS UPDATED TO $64,000 AS REQUIRED BY SEC.
 108.3 CITY AMENDMENTS TO FBC 2004. THEREFORE, OWES
 $654.54FOR ADDITIONAL PERMIT FEES AND RADON FEES.
  
 11- SPECIFY ATTIC ACCESS AS REQUIRED BY SEC. R807 OF
 2004 FLORIDA RESIDENTIAL CODE.
  
 12- SHEET A1:
 A) SPECIFY ALL DESIGN LOADS INCLUDING LIVE AND DEAD
 LOADS AS REQUIRED BY SEC. R301 AND TABLE R301.5 OF 2004
 FLORIDA RESIDENTIAL CODE. INFORMATION SUBMITTED IS
 INCOMPLETE AND NEED TO ADDRESS PROPER CODE.
  
 B) REVISE EMERGENCY EGRESS INFORMATION. SEE SEC.
 R310 OF 2004 FLORIDA RESIDENTIALCODE FOR PROPER CODE
 SECTIONS..
  
 C) AREA CALCULATIONS DON'T ADD UP.REVISE AS
 REQUIRED.
  
 D) CLARIFY WHY SHOWING VERTICAL REINFORCEMENT
 COLUMNS ON EXISTING SLAB. THIS NEEDS TO BE SHOWN ON
 FOUNDATION PLAN.
  
 E) SEE REDLINED COMMENTS ON ALL PLANS AND RETURN
 REVIEWED SET AFTER ALL CORRECTIONS ARE DONE TO EXPEDITE
 REVIEW PROCESS.
  
 13- SHEET A2:
 A) IF CLOSING EXISTING BATHROOM WINDOW, THEN NEED TO
 PROVIDE MECHANICAL VENTILATION.
  
 B) NEED TO PROVIDE COMPLETE DETAILS/ SECTIONS AND
 SPECS FOR NEW OPENING AT EXISTING BEARING WALL BY
 KITCHEN AREA. SPECIFY COLUMNS, BEAM, ETC. AND SHORING.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 14- SHEET A3:
 A) SPECIFY CALCULATED UPLIFT LOADS ON ROOF FRAMING
 PLAN TO VERIFY CONNECTORS COMPLIANCE. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 B) REVISE NUMBER AND TYPE OF FASTENER SPECIFIED FOR
 TRUSS CONNECTORS. SEE CURRENT CATALOG.SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 C) FASTENER SCHEDULE AND CALCULATIONS HAS NOTHING TO
 DO WITH ROOF PLAN SHOWN. REVISE/CLARIFY AS REQUIRED.
 PROVIDE ONLY THE INFORMATION THAT IS RELEVANT TO THIS
 PROJECT. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 D) INFORMATION ON BEAM SCHEDULE, LINTEL SCHEDULE,
 TYPICAL WALL SECTION AND TYP BEAM DETAIL A-A-4 TO
 MATCH. REVISE AS REQUIRED. SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004.
  
 E) REVISE PLYWOOD SHEATHING FASTENER SCHEDULE AND
 ROOF SHEATHING DETAIL AND TYPICAL WALL SECTION.SEE
 SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 15- SHEET A4:
 A) INFORMATION ON TYP. WALL SECTION REGARDING
 CONCRETE STRENGTH DOESN'TMATCH INFORMATION SHOWN ON
 FOUNDATION PLAN. REVISE AS REQUIRED.
  
 B) ROOF SHOWN ON ELEVATIONS DON'T MATCH ROOF FRAMING
 PLAN. REVISE AS REQUIRED. SEE AREA OF NEW ROOF MEETING
 EXISTING ROOF.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-10-12 Cont ID  
Sent By btrobaug Date 2007-10-12 Time 11:05 Rev Time 0.00
Received By btrobaug Date 2007-10-12 Time 09:24 Sent To P
Notes
2007-10-12 11:05:18 
  
 PROVISO
  
 THE WATER HEATER LOCATION CREATES A VIOLATION OF THE
 CLEARANCE REQUIREMENTS OF 110.26 FOR ELECTRICAL
 EQUIPMENT
 AND CANNOT BE LOCATED AS SHOWN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-06-06 Cont ID  
Sent By btrobaug Date 2007-06-06 Time 07:29 Rev Time 0.50
Received By btrobaug Date 2007-06-06 Time 06:43 Sent To P
Notes
2007-06-06 07:29:20 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE LOAD CALCULATIONS SHOULD BE PER 220.83(B) SINCE
 A/C SYSTEM IS BEING ADDED.
  
 2} THE HEAT LOAD IN THE PANEL SCHEDULE DOES NOT
 CORRELATE WITH THE LOAD OF 8000W ON THE MECHANICAL
 SHEET.
  
 3} THE TANKLESS WATER HEATER SHOWN ON THE PLAN IS NOT
 ON THE SCHEDULE OR IN THE LOAD CALCULATIONS.
  
 4} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI.
  
 5} BATH CIRCUIT IS REQUIRED , LOCATED PER 210.52(D),
 AND BE GFI PROTECTED PER 210.8(A) (1), FOR THE EXISTING
 BATH. EXISTING BUILDING CODE, SECTION 608.1.
  
 PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH
 CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM
 SEPARATELY TO EXPEDITE THE REVIEW PROCESS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-05-02 Cont ID  
Sent By btrobaug Date 2007-05-02 Time 10:48 Rev Time 1.00
Received By btrobaug Date 2007-05-02 Time 07:49 Sent To P
Notes
2007-05-02 10:46:28 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE PLAN INDICATES A METER AND MAIN DISCONNECT ON
 THE STRUCTURE, THE RISER ONLY INDICATES A MAIN ONLY.
 PLEASE CORRELATE TO SHOW ACTUAL CONDITIONS.
  
 2} THE TANKLESS WATER HEATER APPEARS IN THE LOAD
 CALCULATIONS AS 8500 VA AND ON THE PANEL SCHEDULE AS
 4500 VA, PLEASE CORRECT., INCLUDE CORRECT OCP AND
 CONDUCTOR SIZE.
  
 3} THE BATHROOM AND "OUTSIDE" GFI CIRCUITS ARE NOT
 REQUIRED IN THE LOAD CALCULATIONS AS THEY ARE INCLUDED
 IN THE GENERAL LIGHTING CALCULATION. SEE 220.14(J),
 2005 NEC.
  
 4} THE AHU LOAD IN THE CALCULATION AND ON THE SCHEDULE
 ARE NOT THE SAME, THEREFORE THE OCP AND WIRE SIZES ARE
 INCORRECT. 310.16 PLEASE CORRELATE.
  
 5} THE WASHER AND DRYER ON THE PLAN APPEAR TO BE A
 STACKED UNIT, BUT ARE ON SEPARATE CIRCUITS IN THE
 SCHEDULE. PLEASE CORRECT TO INTENDED CONDITIONS.
  
 6} THE LOAD CALCULATIONS ARE DUPLICATED IN THE PANEL
 SCHEDULE AND IN THE LOAD CALCULATION
 SCHEDULE/WORKSHEET. THE PANEL SCHEDULE INDICATES
 CONNECTED LOAD AND THE CALC SHEET THE DEMAND LOAD.
 THERE IS NO NEED TOCALCULATE THE CONNECTED LOAD IN
 THE PANEL SCHEDULE. THE CONNECTED LOAD SHOULD BE SHOWN
 FOR CONDUCTOR AND OCP SIZE ONLY. PLEASE KEEP THIS IN
 MIND FOR FUTURE PLANS AS WELL AS THIS RESUB. THE
 REFERENCE TO 220.30 IS INCORRECT. SEE ARTICLE 220 IN
 THE 2005 NEC, ADOPTED DECEMBER 8, 2006.
  
 7} THE BATH CIRCUIT PER 210.11(C)(3) IS REQUIRED IN THE
 SCHEDULE.
  
 8} BOTH BATH RECEPTACLES (MASTER) MUST BE GFI PER 210.8
 (A)(1).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-02-27 Cont ID  
Sent By btrobaug Date 2007-02-27 Time 09:33 Rev Time 1.00
Received By btrobaug Date 2007-02-27 Time 07:54 Sent To M
Notes
2007-02-27 09:33:40 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} INDICATE WHETHER THE SERVICE IS NEW OR EXISTING.
 NOTE: IF NEW OR RELOCATED THERE MAY BE ADDITIONAL
 COMMENTS REGARDING DISCONNECTING MEANS, OCP, GROUNDING
 AND AIC RATINGS PER 225, 230, 250 AND 110.
  
 2}PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 3} PROVIDE A PANEL SCHEDULE PER 408.4. PLEASE SEE NEW
 VERBAGE FOR 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS."
  
 4} A RECEPTACLE MUST BE ADDED IN THE MASTER BECROOM TO
 COMPLY WITH 210.52(A)(1).
  
 5} THE RECEPTACLES IN THE BATHROOM MUST INDICATE
 COMPLIANCE WITH 210.8(A)(1) GFI PROTECTED.
  
 6} A GFI RECEPTACLE MUST BE INSTALLED OUTSIDE IN THE
 BACK PER 210.52(E).
  
 7} A RECEPTACLE MUST BE ADDED WITHIN 25' OF THE A/C
 CONDENSER, IF NONE EXISTS.
  
 8} REFERENCES TO THE 2001 BUILDING CODE ARE INCORRECT
 AND MUST BE CHANGED TO 2004. THE REASON FOR THAT
 COMMENT IN AN ELECTRICAL REVIEW IS TO CLARIFY THAT THE
 2005 NEC IS CURRENTLY ADOPTED, WHICH IS REFERENCED IN
 THE 2004 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-10-10 Cont ID  
Sent By adarroug Date 2007-10-10 Time 10:57 Rev Time 0.00
Received By adarroug Date 2007-10-10 Time 10:57 Sent To Z
Notes
2007-10-10 10:58:06TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-06-01 Cont ID  
Sent By adarroug Date 2007-06-01 Time 08:31 Rev Time 0.00
Received By adarroug Date 2007-06-01 Time 08:31 Sent To E
Notes
2007-06-01 08:31:51TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-05-24 Cont ID  
Sent By adarroug Date 2007-05-24 Time 15:55 Rev Time 0.00
Received By adarroug Date 2007-05-24 Time 15:55 Sent To Z
Notes
2007-05-24 15:55:25TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-05-01 Cont ID  
Sent By adarroug Date 2007-05-01 Time 10:21 Rev Time 0.00
Received By adarroug Date 2007-05-01 Time 10:21 Sent To E
Notes
2007-05-01 10:21:18TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-04-30 Cont ID  
Sent By adarroug Date 2007-04-30 Time 10:17 Rev Time 0.00
Received By adarroug Date 2007-04-30 Time 10:17 Sent To  
Notes
2007-04-30 10:19:25TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-26 Cont ID  
Sent By adarroug Date 2007-02-26 Time 08:37 Rev Time 0.00
Received By adarroug Date 2007-02-26 Time 08:37 Sent To E
Notes
2007-02-26 08:37:25TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-28 Cont ID  
Sent By jgomez Date 2007-03-28 Time 17:14 Rev Time 0.00
Received By jgomez Date 2007-02-15 Time 13:41 Sent To  
Notes
2007-02-15 13:41:44TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-10-23 Cont ID  
Sent By tgordon Date 2007-10-23 Time 15:45 Rev Time 0.45
Received By tgordon Date 2007-10-23 Time 15:45 Sent To B
Notes
2007-10-23 15:54:48*** PROVISO ***
 1) EQUIPMENT SCHEDULE WILL NEED TO BE REVISED BEFORE
 ROUGH MECHANICAL INSPECTION TO SHOW A THREE TON SYSTEM
 AS COOLING LOAD CALCULATIONS VERIFY THAT A THREE TON
 WOULD BE THE CORRECT SIZE SYSTEM, SEE 2004 FBC
 13-607.1.ABC.1.1.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-06-18 Cont ID  
Sent By tgordon Date 2007-06-18 Time 08:28 Rev Time 0.30
Received By tgordon Date 2007-06-18 Time 08:28 Sent To B
Notes
2007-06-18 08:49:23*** DENIED ***
 1) INFORMATION ON PLANS MAY NOT BE DONE IN PEN, AS
 PLANS MAY BE ALTERED AFTER THE FACT.
  
 2) PLEASE SHOW THE CFM'S AT ALL SUPPLY AIR GRILLS.
  
 3) ENERGY CALCULATIONS LINE 11 (A) ARE SHOWING THE
 SUPPLY AIR DUCTS IN A CONDITIONED SPACE AS THE SUPPLY
 DUCTS ARE IN THE ATTIC THAT WOULD BE AN UNCONDITIONED
 SPACE, PLEASE CORRECT ENERGY CALCULATIONS.
  
 4) COOLING LOAD CALCULATIONS (MANUAL J) ARE SHOWING THE
 CEILING HEIGHT AT 10 FT. THE PLANS PAGE A-4 SHOW THE
 CEILING HEIGHT AT 8 FT. PLEASE RE-CALCULATE THE COOLING
 LOAD CALCULATIONS AT 8 FT..
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-05-07 Cont ID  
Sent By tgordon Date 2007-05-07 Time 09:19 Rev Time 0.30
Received By tgordon Date 2007-05-07 Time 09:19 Sent To B
Notes
2007-05-07 09:34:09*** DENIED ***
 1) THE ENGINEER LUIS LOPEZ LICENSE EXPIRED 2-28-07,
 PLEASE CORRECT.
  
 2) SEE PLANS PAGE A-1 (A/C DUCT LAY-OUT). CHANGES MAY
 NOT BE MADE BY HAND TO SIGNED AND SEALED PLANS.
  
 3) THE DUCT LAY-OUT IS FOR THE EXISTING PART OF THE
 HOUSE, YOU ONLY NEED TO SHOW THIS IF THAT DUCT-WORK IS
 TO BE REPLACED.
  
 4) PLEASE SUBMIT A DUCT LAY-OUT FOR THE NEW ADDITION
 AND EQUIPMENT LISTING FOR THE NEW EQUIPMENT (A/C).
  
 5) NEED TO SUBMIT TWO COPY'S OF THE MECHANICAL (A/C)
 PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-02-27 Cont ID  
Sent By tgordon Date 2007-02-27 Time 16:25 Rev Time 0.25
Received By tgordon Date 2007-02-27 Time 16:25 Sent To P
Notes
2007-02-27 16:29:51*** DENIED ***
 1) NEED TO SUBMIT TWO COPIES OF THE ENERGY CALCULATIONS
 AND MANUAL J CALCULATIONS (ONLY ONE COPY WAS
 SUBMITTED).
  
 2) NO MECHANICAL PLANS WERE SUBMITTED FOR REVIEW.
 PLEASE SUBMIT MECHANICAL PLANS FOR REVIEW, PER 2004 FBC
 WPB AMEND. 106.3.5.4 (10).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-10-23 Cont ID  
Sent By mperson Date 2007-10-23 Time 14:00 Rev Time 0.00
Received By mperson Date 2007-10-23 Time 14:00 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-06-15 Cont ID  
Sent By mperson Date 2007-06-15 Time 14:12 Rev Time 0.33
Received By mperson Date 2007-06-15 Time 14:12 Sent To M
Notes
2007-06-15 14:30:09DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET A1 PLEASE CLEARLY INDICATE IF THE PROPOSED
 TANKLESS WATER HEATER IS GAS OR ELECTRIC ON THE
 RESUBMITTAL.
  
 2. SHEET A2 PLUMBING RISER: PLEASE CORRECT THE
 FOLLOWING ON THE SANITARY ISOMETRIC PLUMBING RISER
 DIAGRAM.
 A} PLEASE CORRECT THE LOCATION OF THE TRAP AND
 STANDPIPE FOR THE WASHING MACHINE TO BE BELOW THE
 CLEANOUT 4' A.F.F.
 B} PLEASE DELETE THE 4" CLEANOUT BETWEEN THE
 PROPOSED TUB AND LAVS.
 C} PLEASE INDENTIFY THE CLEANOUT AT THE JUNCTION
 OF THE BUILDING SEWER AND BUILDING DRAIN AS A TWO-WAY
 CLEANOUT, PER FBC-2004 PLUMBING, SECTION 708.3.5.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS REVIEWER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-05-07 Cont ID  
Sent By mperson Date 2007-05-07 Time 08:11 Rev Time 0.33
Received By mperson Date 2007-05-07 Time 08:11 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-03-09 Cont ID  
Sent By mperson Date 2007-03-09 Time 08:23 Rev Time 1.00
Received By mperson Date 2007-03-09 Time 08:23 Sent To B
Notes
2007-03-09 09:16:40DENIED
 REFERENCE: FBC-2004 PLUMBING; FBC-2004 CHAPTER 1, CITY
 OF WEST PALM BEACH AMENDMENTS;
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE CODE COMPLIANCE:
  
 1. SHEET A2 ISOMETRIC SANITARY RISER DIAGRAM: THE
 SANITARY RISER DIAGRAM DOES NOT REFLECT THE FLOOR PLAN.
 PLEASE REFERENCE THE ATTACHED SANITARY RISER DIAGRAM TO
 THE PLUMBING COMMENTS THAT REFLECTS THE FLOOR PLAN AND
 IS CODE COMPLIANT.
  
 2. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4(9)
 RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING
 ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT
 LOCATIONS.
 NOTE: NOT ALL PIPES ARE SIZED AND NOT ALL CLEANOUTS ARE
 LOCATED.
  
 3. THE FOLLOWING IS REQUIRED FOR THE WASHING MACHINE:
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING
 NOTE: PLEASE INDICATE THE STANDPIPE ON THE
 RESUBMITTAL.
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 NOTE: CLEANOUT FOR WASHING MACHINE SHALL BE THREE INCH
 (3"). PLEASE INDICATE THIS ON THE RESUBMITTAL.
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 NOTE: CLEANOUT FOR WASHING MACHINE SHALL BE LOCATED AT
 FOUR FEET ABOVE FINNISH FLOOR (4' A.F.F.). PLEASE
 INDICATE THIS ON THE RESUBMITTAL.
  
 4. SHEET A4 ISOMETRIC SANITARY RISER DIAGRAM DOES NOT
 INDICATE THE FOLLOWING CLEANOUT. ITS HARD TO TELL ON
 THE RISER DIAGRAM WHERE THE SANITARY PIPING LEAVES THE
 BUILDING. IF THE WASHING MACHINE AND THE MASTER BATH
 BOTH EXIT THE BUILDING THEY WILL BOTH NEED TWO-WAY
 CLEANOUTS. PLEASE CLARIFY AND CORRECT ON THE
 RESUBMITTAL.
 (B) 708.3.5 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION. THERE SHALL BE A
 CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER.
  
 5. SHEET A1 PLUMBING NOTES NUMBER 1: PLEASE DELETE "
 MINIMUM SLOPE SHALL BE 1/8" PER FOOT." AND ADD THE
 FOLLOWING IN ITS PLACE " SLOPE SHALL BE PER FBC-2004
 PLUMBING, TABLE 704.1."
  
 ******IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL. PLEASE REFERENCE THE ATTACHED CORRECTED
 ISOMETRIC SANITARY RISER DIAGRAM TO THE PLUMBING
 COMMENTS FOR THE RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  

Review Stop Z ZONING
Rev No 4 Status P Date 2007-10-11 Cont ID  
Sent By eschneid Date 2007-10-11 Time 10:59 Rev Time 0.00
Received By ADAVILA Date 2007-10-11 Time 11:00 Sent To E
Notes
2007-10-11 11:00:09PER ERIC SCHNEIDER, PRINCIPAL PLANNER.

Review Stop Z ZONING
Rev No 3 Status P Date 2007-05-25 Cont ID  
Sent By adavila Date 2007-05-25 Time 12:39 Rev Time 0.00
Received By adavila Date 2007-05-25 Time 12:38 Sent To I
Notes
2007-05-25 12:39:26PER ERIC SCHNEIDER, PRINCIPAL PLANNER.

Review Stop Z ZONING
Rev No 2 Status P Date 2007-04-30 Cont ID  
Sent By adavila Date 2007-04-30 Time 15:45 Rev Time 0.00
Received By adavila Date 2007-04-30 Time 15:44 Sent To I
Notes
2007-04-30 15:45:29PER ERIC SCHNEIDER, PRINCIPAL PLANNER.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-02-22 Cont ID  
Sent By adavila Date 2007-02-22 Time 12:56 Rev Time 0.00
Received By adavila Date 2007-02-22 Time 12:55 Sent To I
Notes
2007-02-22 13:01:32PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. PLEASE PROVIDE RESPONSE TO COMMENTS IN WRITING.
  
 2. PROVIDE TWO (2) SIGNED AND SEALED SURVEYS LESS THAN
 A YEAR OLD.
  
 3. PROVIDE ALL SETBACK DIMENSIONS FROM PROPERTY LINE.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.