Plan Review Details - Permit 07020316
Plan Review Stops For Permit 07020316
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-04-20 Cont ID  
Sent By mjacobs Date 2007-04-20 Time 15:51 Rev Time 0.00
Received By mjacobs Date 2007-04-20 Time 15:42 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-04-12 Cont ID  
Sent By mjacobs Date 2007-04-12 Time 12:46 Rev Time 0.00
Received By mjacobs Date 2007-04-12 Time 11:30 Sent To  
Notes
2007-04-12 12:46:00BUILDING PLAN REVIEW
 PERMIT:07020316
 ADD: 250 S. AUSTRALIAN AVE #300
 CONT:ITASCA CONST.
 TEL: (561)241-4999
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)THE APPLICATION STATES THE WORK WILL CARRIED OUT ON
 THE 3RD FLOOR ONLY,HOWEVER, THE DRAWINGS SHOW WORK ON
 THE 2ND AND 3RD FLOORS. EITHER REMOVE THE INFORMATION
 REGARDING THE SECOND FLOOR FROM THE PACKAGE OR INCLUDE
 IT ON THE APPLICATION. IF THIS APPLICATION IS FOR
 DEMOLITION ONLY, THEN, ONLY THE DEMOLITION DRAWINGS
 SHALL BE SUBMITTED AT THIS TIME. REMOVE ALL OTHER
 DRAWINGS FROM THE PACKAGE.
 PARTIALLY
 ADDRESSED.*********************************************
 *********************
  
 3)106.1 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICAATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THE CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL (SEE ALSO SECTION
 106.3.5)
  
 4)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. IF IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATEDON THE APPLICATION, THE PERMIT
 SHALL BE DENIED. FOR PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALLBE THE TOTAL REPLACEMENT
 COST EXCLUDING LAND VALUE.OUR VALUATION REFERENCE IS
 ICC (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS
 SERVICES PER 108.3 FBC*
 NOT
 ADDRESSED**********************************************
 *****************
  
 5)FBC 2004 (EXISTING) INDICATE THE LEVEL OF
 ALTERATION. SEE CH. 3. FOR MORE INFORMATION.
 NOT
 ADDRESSED**********************************************
 *******************
  
 6)THE APPLICATION IS FOR THE DEMOLITION ONLY. REMOVE
 ALL OTHER DRAWINGS WHICH DOES NOT PERTAIN TO THE
 DEMOLITION OF THE PROJECT.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-02-20 Cont ID  
Sent By mjacobs Date 2007-02-20 Time 18:04 Rev Time 0.00
Received By mjacobs Date 2007-02-20 Time 16:14 Sent To  
Notes
2007-02-20 17:59:15BUILDING PLAN REVIEW
 PERMIT:07020316
 ADD: 250 S. AUSTRALIAN AVE #300
 CONT:ITASCA CONST.
 TEL: (561)241-4999
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)THE APPLICATION STATES THE WORK WILL CARRIED OUT ON
 THE 3RD FLOOR ONLY,HOWEVER, THE DRAWINGS SHOW WORK ON
 THE 2ND AND 3RD FLOORS. EITHER REMOVE THE INFORMATION
 REGARDING THE SECOND FLOOR FROM THE PACKAGE OR INCLUDE
 IT ON THE APPLICATION. IF THIS APPLICATION IS FOR
 DEMOLITION ONLY, THEN, ONLY THE DEMOLITION DRAWINGS
 SHALL BE SUBMITTED AT THIS TIME. REMOVE ALL OTHER
 DRAWINGS FROM THE PACKAGE.
  
 3)106.1 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICAATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THE CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL (SEE ALSO SECTION
 106.3.5)
  
 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL OF BUILDINGS AND SYSTEMS
 SHALL BE THE TOTAL REPLACEMENT COST EXCLUDING LAND
 VALUE.OUR VALUATION REFERENCE IS ICC (BVD),
 MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES PER
 108.3 FBC*
  
 4)FBC 2004 (EXISTING) INDICATE THE LEVEL OF
 ALTERATION. SEE CH. 3. FOR MORE INFORMATION.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-04-18 Cont ID  
Sent By dpalmer Date 2007-04-17 Time 12:55 Rev Time 0.00
Received By dpalmer Date 2007-04-17 Time 12:54 Sent To  
Notes
2007-04-17 13:25:38VALUE TO BE VERIFIED AND ADJUSTED AS PREVIOUSLY STATED
 W/ BUILDING REVIEWER.
 FBC 108.3,

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-04-08 Cont ID  
Sent By dpalmer Date 2007-04-08 Time 09:35 Rev Time 0.00
Received By dpalmer Date 2007-04-08 Time 09:32 Sent To  
Notes
2007-04-08 09:38:14** UNSAT **
  
 1) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF
 WORK BEING SHOWN ON PLANS FOR BOTH WORK ON THE 2ND AND
 3RD FLOOR IS LOW. IT WAS REQUESTED ON PREVIOUS REVIEW
 TO ADJUST AS THE VALUE WAS LOW FOR ALL TRADES AND
 WORK.
 PLEASE SEE FBC 108.3
 A VALUE MAY BE ACCESSED BY REVIEWER(S).
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-02-15 Cont ID  
Sent By dpalmer Date 2007-02-15 Time 08:02 Rev Time 0.00
Received By dpalmer Date 2007-02-15 Time 07:47 Sent To  
Notes
2007-02-15 08:02:20**** UNSAT ****
  
 1) NOTE: PLEASE SEE THE PERMIT APPLICATION IS FOR DEMO
 WORK ON THE 3RD FLOOR; HOWEVER THE PLANS INDICATE DEMO
 WORK ALSO ON THE 2ND FLOOR.
 WILL WORK ON EACH FLOOR BE UNDER SEPARATE PERMITS?
 PLEASE SEE THE VALUE FOR THE SCOPE OF WORK FOR BOTH
 FLOORS INCLUDING ELECTRICAL, MECHANICAL AS SHOWN ON
 PLANS SEEMS LOW. PLEASE ADJUST.
 ONCE THIS IS DONE PLANS WILL BE PLACED INTO A PAST
 STATUS WITH CONDITIONS THAT AN ELECTRICAL PERMIT FOR
 ELECTRICAL DEMO AND TO SAFE OFF ALL ELECTRICAL WILL BE
 REQUIRED BEFORE THE DEMO WORK COMMENCES.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-04-18 Cont ID  
Sent By mwennerg Date 2007-04-18 Time 11:06 Rev Time 0.00
Received By mwennerg Date 2007-04-18 Time 11:06 Sent To  
Notes
2007-04-18 11:09:11***DENIED***
  
 1) PLEASE NOTE VALUE AND MAKE CORRECTION WHERE
 APPLICABLE AS IT APPLIES TO THIS SCOPE OF WORK. SEE
 OTHER REVIEW COMMENTS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-04-13 Cont ID  
Sent By mwennerg Date 2007-04-13 Time 10:21 Rev Time 0.00
Received By mwennerg Date 2007-04-13 Time 10:21 Sent To  
Notes
2007-04-13 10:22:48***DENIED***
  
 THESE COMMENTS ARE TAKEN DIRECTLY FROM THE FIRST FIRE
 REVIEW.
  
 1) PLEASE SEE OTHER REVIEW COMMENTS REGARDING SCOPE OF
 WORK AND WHAT IS SHOWN ON PLANS. WILL THIS WORK INCLUDE
 MORE THAN WHAT IS INDICATED ON THE APPLICATION?
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW(561) 805-6722
 FIRE PREVENTION(561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-02-23 Cont ID  
Sent By mwennerg Date 2007-02-23 Time 13:50 Rev Time 0.00
Received By mwennerg Date 2007-02-23 Time 13:50 Sent To  
Notes
2007-02-23 13:53:44***DENIED***
  
 1) PLEASE SEE OTHER REVIEW COMMENTS REGARDING SCOPE OF
 WORK AND WHAT IS SHOWN ON PLANS. WILL THIS WORK INCLUDE
 MORE THAN WHAT IS INDICATED ON THE APPLICATION?
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW(561) 805-6722
 FIRE PREVENTION(561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-04-17 Cont ID  
Sent By adarroug Date 2007-04-17 Time 10:01 Rev Time 0.00
Received By adarroug Date 2007-04-17 Time 10:01 Sent To  
Notes
2007-04-17 10:01:49TO "BOB"#4

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-03 Cont ID  
Sent By spalmer Date 2007-04-03 Time 18:27 Rev Time 0.00
Received By spalmer Date 2007-04-03 Time 18:27 Sent To  
Notes
2007-04-03 18:27:19TO BOB # 7

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-03 Cont ID  
Sent By jleech Date 2007-03-03 Time 06:47 Rev Time 0.00
Received By jleech Date 2007-02-14 Time 16:19 Sent To  
Notes
2007-02-14 16:22:20TO "BOB"#13

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-02-15 Cont ID  
Sent By tgordon Date 2007-02-15 Time 10:00 Rev Time 0.15
Received By tgordon Date 2007-02-15 Time 10:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2007-03-03 Cont ID  
Sent By jleech Date 2007-03-03 Time 06:47 Rev Time 0.00
Received By jleech Date 2007-03-03 Time 06:47 Sent To  
Notes
2007-03-03 06:49:14NO PLUMBING WORK SHOWN ON DEMO PLANS.