Plan Review Details - Permit 07020305
Plan Review Stops For Permit 07020305
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-06-05 Cont ID  
Sent By mjacobs Date 2007-06-05 Time 10:49 Rev Time 0.00
Received By mjacobs Date 2007-06-05 Time 06:02 Sent To PC
Notes
2007-06-05 10:49:17 
 BUILDING PLAN REVIEW
 PERMIT: 07020305
 ADD: 319 BELVEDERE RD
 CONT: ROBERT G FRANKLYN INC.
 TEL: (561)748-0043
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FBC. 106.1SUBMIT TWO COMPLETE SETS OF PLANS FOR
 REVIEW NOT LOOSE PAGES.
  
 3)THE VALUE IS TO LOW.IF IN THE OPINION OF THE
 BUILDING OFFICIAL, THE CLAIMED VALUATION OF THE
 BUILDING ALTERATION, APPEARS TO BE UNDERESTIMATED ON
 THE APPLICATION, THE PERMIT SHALL BE DENIED. OUR
 VALUATION REFERENCES IS ICC (BVD), MARSHALL-SWIFT AND
 MEANS COST ANALYSIS SERVICES. FBC 108.3*
  
 4)FBC 1210.2 WALLS WITHIN 2 FEET OF URINALS AND WATER
 CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE, TO A HEIGHT OF 4 FEET ABOVE THE FLOOR, AND
 EXCEPT FOR STRUCTURAL ELEMENTS, THE MATERIALS USED IN
 SUCH WALLS SHALL BE OF A TYPE THAT IS NOT ADVERSELY
 AFFECTED BY MOISTURE.
  
 5)FBCTOILET AND BATHING ROOM FLOORS SHALL HAVE
 SMOOTH, HARD, NONABSORBENT SURFACE THAT EXTENDS UPWARD
 ONTO THE WALLS AT LEAST 6 INCHES.
  
 6)IF STORETECH IS A REGISTERED INTERIOR DESIGN AND
 CONSTRUCTION COMPANY THE CERTIFICATE OF AUTHORIZATION
 NUMBER SHALL BE INDICATED ON THE TITLE BLOCK OF THE
 PLANS PER F.S. 481.221 (3)
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-02-15 Cont ID  
Sent By mjacobs Date 2007-02-15 Time 06:40 Rev Time 0.00
Received By mjacobs Date 2007-02-14 Time 17:27 Sent To  
Notes
2007-02-14 18:59:39BUILDING PLAN REVIEW
 PERMIT:
 ADD:
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)FBC 11-5.2 COUNTERS AND BARS (WINE TASTING AREA)
 WHERE FOOD OR DRINK IS SERVED @ COUNTERS
 EXCEEDING 34" IN HEIGHT FOR CONSUMPTION
 BY CUSTOMERS SEATED ON STOOLS OR STAND-
 ING AT THE COUNTER, A PORTION OF THE
 MAIN COUNTER WHICH IS 60" IN LENGTH MIN-
 IMUM SHALL BE PROVIDED IN COMPLIANCE
 WITH 11-4.32 OR SERVICE SHALL BE AVAIL-
 ABLE AT ACCESSIBLE TABLES WITHIN THE
 SAME AREA. PROVIDE AN ELEVATION DRAWINGS OF THIS AREA
 WITH THE DIMENTIONS WHICH SHALL MEET THE REQUIREMENTS
 OF THIS SECTION.
  
 4)FBC 11-4.3ALL WALKS, HALLS, CORRIDORS, ASILES,
 SKYWALKS, TUNNELS, AND OTHER SPACES THAT ARE PART OF AN
 ACCESSIBLE ROUTE SHALL COMPLY WITH SECTION 11-4.3 SHOW
 COMPLIANCE.
  
 5)FBC 11-7.2SALES AND SERVICE COUNTERS, TELLER
 WINDOWS, INFORMATION COUNTERS SHALL HAVE A SECTION OF
 THE COUNTER AT LEAST 36 INCHES IN LENGTH WITH A MAXIMUM
 HEIGHT OF 36 INCHES ABOVE THE FINISH FLOOR. SEE SECTION
 11-7 FOR MORE INFORMATION AND SHOW THE ELEVATION
 DETAILS OF THE COUNTERS AT THE COUNTERS.11-7.3 AT LEAST
 ONE CHECK-OUT AISLE SHALL BE ACCESSIBLE.
  
 5)THE VALUE IS TO LOW. WPB AMENDMENTS 108.3.IF, IN
 THE OPINION OF THE BUILDING OFFICIAL. THE CLAIMED
 VALUATION OF THE BUILDING ALTERATION, APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION. THE PERMIT SHALL BE
 DENIED. OUR VALUATION REFERENCES IS ICC (BVD),
 MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES.
  
 6)WHAT IS THE PURPPOSE OF THE KIDS ROOM?
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-06-03 Cont ID  
Sent By dpalmer Date 2007-06-03 Time 14:02 Rev Time 0.00
Received By dpalmer Date 2007-06-03 Time 12:48 Sent To  
Notes
2007-06-03 14:04:19** UNSAT 2RDREVIEW **
  
  
 ** PLEASE SEE THERE ARE MANY COMMENTS FROM THE PREVIOUS
 REVIEWWHICH ARE STILL IN NEED OF ADDRESSING.
 **PLEASE ALSO SEE SEVERAL NEW COMMENTS BASED ON NEW
 PLANS WHICH ARE FROM CHANGES AND INFORMATION WHICH IS
 NOW BEING SUBMITTED FOR THE FIRST TIME FOR REVIEW.
  
 ***IMPORANT***
 PLEASE ALSO KNOW DUE TO THE PLANS NOT BEING COMPLETE AT
 THIS TIME AND THE FOLLOWING COMMENTS FOR PLANS
 SUBMITTED, THERE MAY BE COMMENTS ON NEXT REVIEW WHICH
 ARE NOT ON THIS REVIEW.
 **** DUE TO THE EXTENT OF THE ELECTRICAL COMMENTS, ONE
 SET OF THE ELECTRICAL PLANS ARE BEING RETAINED. PLEASE
 SEE COMMENTS WITH RESPECT TO FLORIDA STATUTES FOR
 REPEAT COMMENTS.
  
  
  
 1) NOTE: PLEASE SEE THE ARCHITECTURAL SHEETS WHICH DO
 NOT CONTAIN THE CORRECT CODES. PLEASE SEETHE CODES
 LISTED BELOW WHICH WERE PREVIOUSLY NOTED.
 PLEASE BE SURE THE PLANS STATE ALL OF THE CURRENT
 ADOPTED CODES ON PLANS.
 PLEASE SEE THE FOLLOWING ARE REQUIRED FOR ELECTRICAL
 AND OTHERS WILL BE REQUIRED FOR OTHER TRADES. PLEASE
 KNOW AS OF DECEMBER 8TH, 2006 THE STATE ADOPTED THE
 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70.
 PLEASE LIST THE FOLLOWING
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
  
  
  
 2) NOTE:PLEASE SEE THAT COMPLIANCE WITH CHAPTER 13
 HAS NOT BEEN INDICATED. PLEASE SEE THE LIGHTING
 CONTROLS NEED TO BE SHOWN IN DETAIL FOR TYPES, TIMES ON
 OVER RIDES ETC. IF A LC SYSTEM IS TO BE INSTALLED,
 PLEASE INDICATE SCHEDULING AND OVER RIDES.
 PLEASE SEE THAT EACH DEVICE NEEDS TO BE SHOWN. RESPONSE
 WAS THAT *DUAL SWITCHING HAD BEEN ADDED*IT IS UNCLEAR
 WHERE THIS IS FROM? IS THIS MEANT TO RESPOND TO *TANDEM
 WIRING* AS STATED IN 13-415.1.ABC.3?
 PLEASE COMPLETE FIXTURE LEGEND. PLEASE SEE LEGEND
 MENTIONS A *STANDARD FLUORESCENT FIXTURE* HOWEVER DUE
 TO THE FACT THERE IS NO STANDARD FIXTURE ON THE MARKET,
 ONE IS TO BE SPECIFIED.
 PLEASE SEE ENERGY CALCULATIONS ARE TO BE UNDER THE 2006
 REVISIONS TO THE 2004 FBC. PLEASE VERIFY VERSION,
 PLEASE ALSO VERIFY METHOD FOR WHOLE BUILDING WHEN THIS
 IS A TENANT SPACE WHICH IS PART OF A LARGER *BUILDING*
 BY DEFINITION.
 PLEASE SEE THE ENERGY CALCULATIONS FOR SOME KW RATINGS
 DO NOT MATCH WITH ELECTRICAL PLANS FOR THE SAME LOADS
 ON APPLIANCES. PLEASE SEE THE CALCULATIONS DO NOT
 CORRELATE AS SOME SHEETS INDICATE ONE LOAD FOR WATER
 HEATER AND ANOTHER SHEET INDICATES A LARGER LOAD?
 PLEASE ADJUST AND CORRELATE ALL.
 PLEASE SEE THE 2004 FBC CHAPTER 13 FOR LIGHTING
 CONTROLS PER 13-415.1.ABC.1.1, .1.2 AND .1.3. PLEASE
 ALSO SUBMIT ENERGY CALCULATIONS AND PERFORMANCE
 CALCULATIONS PER 13-415.1AB.1.1, 13415.2.
  
 3) NOTE:PLEASE COMPLETE ALL CIRCUITING ON PLANS AND
 CORRELATE WITH PANEL(S).
 PLEASE SEE THIS IS THE FIRST REVIEW WHERE PANELS ARE
 BEING SUBMITTED FOR REVIEW.
 A) PLEASE SEE THE RISER IS NOT COMPLETE AS IS DOES NOT
 SHOW HOW PANEL *B* IS BEING FED.
 B) PLEASE SEE RISER NOW SHOWS NEW PANELS, DISCONNECTS
 AND METERS, YET THE RISER SHOWS THE CONDUCTORS AS
 EXISTING?
 C) PLEASE SEE THE LOAD AND THE SIZE OF THE PANEL *A*
 EXCEEDS THE RATING OF THE PROPOSED 100AMP DISCONNECT AS
 SHOWN ALONG WITH CONDUCTORS ETC.
 PLEASE SEE THE LOAD IS SHOWN AT 134+ AMPS, ON A 150A
 MCB PANEL. (FED FROM100AMP DISCONNECT?)
 D) PLEASE SEE PANEL *B* DOES NOT SHOW WHERE IT IS BEING
 FED FROM? NO OCP, CONDUCTORS ETC.?
 PLEASE KNOW, AT THIS TIME RISER IS NOT COMPLETE FOR
 REVIEW.
 PLEASE SUBMIT A PANEL SCHEDULE WHICH WILL CORRELATE
 WITH ALL OF THE CIRCUITING AS SHOWN ON PLANS. PLEASE BE
 SURE ALL OF THE CIRCUITS NEW AND EXISTING ARE SHOWN,
 THE SIZE OF THE PANEL, THE OVER CURRENT PROTECTION
 DEVICES AND THE CONDUCTORS SIZES. 215.5, 408.4, 310.16,
 240.4 ETC
 FBC ADMIN SECTION 106.1.2, 106.3.5.1.2
  
 4) NOTE: PLEASE BE SURE BOTH SETS OF PLANS ARE COMPLETE
 WITH ALL SHEETS INSERTED AND MADE INTO SETS. MANY OF
 THE SHEETS SUBMITTED ARE LOOSE AND NOT IN SETS OR
 ATTACHED IN ANY FASHION.
  
 5) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR
 ALL EXISTING LOADS AND NEW LOADS BEING ADDED TO THE
 PANEL.
 AS PREVIOUSLY STATED, INCLUDE ALL NEW LOADS ON THE
 EXISTING SERVICE, INCLUDE LOAD OF THE EXISTING SERVICE
 WHERE THE PROPOSED NEW TENANT SERVICE IS BEING SHOWN.
 PLEASE SEE THE LOAD CALCULATIONS ARE NOT COMPLETE
 AND/OR DO NOT SHOW HOW THE FINAL LOADS FOR TRACK
 LIGHTING DERIVED.
 SHOWS THE 150VA PER 2FT, HOWEVER THE TOTAL FT AND LOAD
 FOR THIS COULD NOT BE LOCATED IN ANY BREAKDOWN.
 PLEASE SEE AS PANEL *B* DOES NOT INDICATE HOW THIS IS
 BEING FED, IT IS UNCLEAR WHERETHE LOADS ARE BEING
 ADDED. ARE THESE LOADS ON PANEL *A*?
 AS THERE ARE SEVERAL ITEMS WHICH ARE NOT COMPLETE ARE
 STATED IN NOTE #3 ABOVE, SOME COMMENTS CAN NOT BE MADE
 OR ITEMS REVIEWED.
 PLEASE BE SURE TO SHOW THE SIZE OF THE MAIN/OVER
 CURRENT PROTECTION, SIZE OF SERVICE PROVIDED. PLEASE
 SEE 220.12,220.14, 220.42, 220.44, ETC. PLEASE SEE
 215.3, 230.42 AND SHOW ALL CONTINUOUS LOADS AT 125%.
  
 6) NOTE:THIS NOT WILL REMAIN AS NOTED ABOVE. PLEASE
 SEE 220.43B FOR MINIMUM CALCULATIONS TO BE SHOWN FOR
 TRACK LIGHTING.
  
 7) NOTE:THIS NOT REMAINS AS THE CORRECT LOADS FOR
 SERVICE ARE NOT COMPLETE FOR CODE COMPLIANCE. WHERE ARE
 LOADS IN LOAD CALCULATIONS AS REQUIRED PER SECTIONS
 BELOW?
 PLEASE SEE MISSING SHOW WINDOW RECEPTACLES WHICH WILL
 BE REQUIRED PER 210.62 AND LOADS TO BE SHOWN PER
 210.43A.
  
 8) NOTE:PLEASE SEE MISSING LICENSE INFORMATION FOR
 *STORETECH* WHICH IS BEING LISTED ON TITLE BLOCKS AS
 DESIGNERS?
 PLEASE SEE FS 471.023, 481.219.
 FAC 61G1-16.004, 61G15-23.002
 THIS IS A NEW COMMENT HOWEVER MUST BE ADDRESSED.
  
 9) NOTE:THIS COMMENT IS TO REMAIN. PLEASE SEE THAT NO
 RESPONSE WAS MADE IN THE RESPONSE LETTER FOR THIS?
 PLEASE SEE THAT THE SIGNATURE ON THE RESPONSE LETTER IS
 DIFFERENT THAN THAT OF THE SIGNATURE ON PLANS.
 PLEASE ALSO SEE THIS LETTER DOES *NOT* CONTAIN AN
 ORIGINAL SIGNATURE. THE LETTER IN FACT CONTAINS A
 RAISED SEAL OVER A *PHOTO-COPIED* SIGNATURE.
 NOW THAT TWO SIGNATURES HAVE BEEN PRESENTED, THIS
 OFFICE HAS NO WAY TO VERIFY WHICH THE LEGAL SIGNATURE
 OF THE DESIGNER OR RECORD IS. PLEASE SEND A COPY OF THE
 DRIVER'S LICENSE ALONG WITH THE REQUESTED NOTARIZED
 LETTER. THIS DL # AND PERSONNEL ADDRESS INFORMATION MAY
 BE CROSSED OUT. PLEASE BE SURE ALL RAISED SEALS ARE
 CLEAR AND VISIBLE WITH ALL INFORMATION ON SAID SEAL.
 PLEASE SEE MANY OF THEM ARE VERY FAINT AND NOT EASILY
 READ. PLEASE SEE FS 481.221,471.025
 PLEASE ALSO SEE PLANS APPEAR TO BE SIGNED WITH
 INITIALS, IF THIS IS INDEED THE LEGAL SIGNATURE OF THE
 DESIGNER OF RECORD, PLEASE PROVIDE A SIGNED, DATED,
 SEALED AND NOTARIZED LETTER FOR SIGNATURE VERIFICATION.
 THIS WILL BE PLACED IN SIGNATURE FILE FOR FUTURE
 REFERENCES.
 ANY LETTERS WHICH ARE NOTARIZED MUST CONTAIN THE
 STATEMENTS AS REQUIRED UNDER FS 117.05 FOR NOTARIES.
 * ONE SET OF PLANS AND LETTERS ARE BEING RETAINED BY
 THIS OFFICE.
  
 10) NOTE: PLEASE SEE VALUE SHALL BE ADJUSTED AS STATED
 FOR SCOPE PER FBC 108.3. NO RESPONSE WAS MADE TO THIS
 AND THE APPLIED VALUE REMAINS THE SAME. THE VALUE SHALL
 INCLUDE ALL LABOR AND MATERIALS AND EQUIPMENT, EVEN IF
 ANY OF THIS IS OWNER SUPPLIED.
  
 11) NOTE: PLEASE SEE COPY OF FS 553.80(2)(B) ATTACHED
 WITH RESPECT TO DESIGN PROFESSIONALS AND REPEAT
 COMMENTS.
 THIS IS ONLY A NOTICE GIVEN AT THIS TIME.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-02-15 Cont ID  
Sent By dpalmer Date 2007-02-15 Time 08:31 Rev Time 0.00
Received By dpalmer Date 2007-02-15 Time 08:06 Sent To  
Notes
2007-02-15 08:32:03**** UNSAT ****
  
 1) NOTE: PLEASE BE SURE THE PLANS STATE ALL OF THE
 CURRENT ADOPTED CODES ON PLANS.
 PLEASE SEE THE FOLLOWING ARE REQUIRED FOR ELECTRICAL
 AND OTHERS WILL BE REQUIRED FOR OTHER TRADES. PLEASE
 KNOW AS OF DECEMBER 8TH, 2006 THE STATE ADOPTED THE
 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70.
 PLEASE LIST THE FOLLOWING
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72 (IF APPLICABLE FOR ANY FIRE ALARM SYSTEM
 OR DEVICES PRESENT).
  
 ** PLEASE SEE CODES ON PLANS WHICH REFERENCE BACK TO
 THE 1996 NFPA-70.
  
 2) NOTE: PLEASE SEE THE 2004 FBC CHAPTER 13 FOR
 LIGHTING CONTROLS PER 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE ALSO SUBMIT ENERGY CALCULATIONS AND PERFORMANCE
 CALCULATIONS PER 13-415.1AB.1.1, 13415.2.
  
 3) NOTE: PLEASE SUBMIT A PANEL SCHEDULE WHICH WILL
 CORRELATE WITH ALL OF THE CIRCUITING AS SHOWN ON PLANS.
 PLEASE BE SURE ALL OF THE CIRCUITS NEW AND EXISTING ARE
 SHOWN, THE SIZE OF THE PANEL, THE OVER CURRENT
 PROTECTION DEVICES AND THE CONDUCTORS SIZES. 215.5,
 408.4, 310.16, 240.4 ETC
 FBC ADMIN SECTION 106.1.2, 106.3.5.1.2
  
 4) NOTE: PLEASE VERIFY NEW OR EXISTING SIGN CIRCUIT PER
 600.5.
 (LOAD MIN 1200VA )
  
 5) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR
 ALL EXISTING LOADS AND NEW LOADS BEING ADDED TO THE
 PANEL. PLEASE BE SURE TO SHOW THE SIZE OF THE MAIN/OVER
 CURRENT PROTECTION, SIZE OF SERVICE PROVIDED. PLEASE
 SEE 220.12,220.14, 220.42, 220.44, ETC. PLEASE SEE
 215.3, 230.42 AND SHOW ALL CONTINUOUS LOADS AT 125%.
  
 6) NOTE: PLEASE SEE 220.43B FOR MINIMUM CALCULATIONS TO
 BE SHOWN FOR TRACK LIGHTING.
  
 7) NOTE: PLEASE SEE MISSING SHOW WINDOW RECEPTACLES
 WHICH WILL BE REQUIRED PER 210.62 AND LOADS TO BE SHOWN
 PER 210.43A.
  
 8) NOTE: PLEASE SEE MISSING DISCONNECT FOR AHU, PER
 440.11, 110.26.
  
 9) NOTE: PLEASE BE SURE ALL RAISED SEALS ARE CLEAR AND
 VISIBLE WITH ALL INFORMATION ON SAID SEAL. PLEASE SEE
 MANY OF THEM ARE VERY FAINT AND NOT EASILY READ. PLEASE
 SEE FS 481.221.
 PLEASE ALSO SEE PLANS APPEAR TO BE SIGNED WITH
 INITIALS, IF THIS IS INDEED THE LEGAL SIGNATURE OF THE
 DESIGNER OF RECORD, PLEASE PROVIDE A SIGNED, DATED,
 SEALED AND NOTARIZED LETTER FOR SIGNATURE VERIFICATION.
 THIS WILL BE PLACED IN SIGNATURE FILE FOR FUTURE
 REFERENCES.
  
 10) NOTE: PLEASE SEE VALUE SHALL BE ADJUSTED AS STATED
 FOR SCOPE PER FBC 108.3.
  
 11) NOTE: PLEASE KNOW IF THE BUILDING CONTAINS ANY FIRE
 ALARM SYSTEM OR DEVICES, PLEASE INDICATE THE DEVICES ON
 THE BASE PLANS.
 PLEASE SEE FBC 11-4.28.1, .2 AND .3(4).
 FBC ADMIN SECTION 106.3
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-05-30 Cont ID  
Sent By mawillia Date 2007-05-30 Time 14:48 Rev Time 0.00
Received By mawillia Date 2007-05-30 Time 14:32 Sent To  
Notes
2007-05-30 14:43:17*****UNSAT*****
  
 THE FOLLOWING COMMENT FROM THE PREVIOUS FIRE PLAN
 REVIEW STILL NEEDES TO BE REVIEWED:
  
 1.THE SUITE NUMBER SHALL BE INCLUDED WITH THE ADDRESS
 IN THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
 PLEASE BE ADVISED THAT 319 IS THE NUMERICAL ADDRESS FOR
 THE BUILDING, THE SUITE/UNIT NUMBER IS 7
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-02-26 Cont ID  
Sent By mawillia Date 2007-02-26 Time 11:57 Rev Time 0.00
Received By mawillia Date 2007-02-26 Time 11:57 Sent To  
Notes
2007-02-26 12:43:11*****DENIED*****
  
  
 1.THE SUITE NUMBER SHALL BE INCLUDED WITH THE ADDRESS
 IN THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 2.THE 2003 EDITION OF NFPA 101 SHALL BE REFERENCED.
  
 3.INDICATE WHETHER THE BUILDING IS SPRINKLERED AND/OR
 HAS A FIRE ALARM SYSTEM.
  
 4.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 5.SPECIFY INTERIOR FINISH MATERIAL CLASSIFICATION FOR
 WALLS AND CEILINGS.
  
 6.PROVIDE A LIFE SAFETY PLAN SHEET WHICH INDICATES
 THE TRAVEL DISTANCE TO THE EXIT(S).THE LOCATION OF
 THE 2A-10BC RATED FIRE EXTINGUISHERS MAY BE NOTED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-17 Cont ID  
Sent By adarroug Date 2007-05-17 Time 13:54 Rev Time 0.00
Received By adarroug Date 2007-05-17 Time 13:54 Sent To  
Notes
2007-05-29 14:10:21TO "BOB"#5
2007-05-17 13:54:36WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-26 Cont ID  
Sent By mawillia Date 2007-02-26 Time 14:41 Rev Time 0.00
Received By mawillia Date 2007-02-14 Time 14:05 Sent To  
Notes
2007-02-14 14:06:19TO "BOB"#11

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-06-06 Cont ID  
Sent By rregueir Date 2007-06-06 Time 15:32 Rev Time 0.00
Received By rregueir Date 2007-06-06 Time 14:36 Sent To PC
Notes
2007-06-06 15:32:50----------------DENIED------------------
  
 2004 FBC CODE FAMILY W/ 2006 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. ENERGY CALCULATIONS SHOW ONE RTU SYSTEM, BUT PLANS
 INDICATE TWO SPLIT SYSTEMS. PLEASE CORRECT
 CALCULATIONS.
  
 2. M-1 IS SHOWN AS A "DUCT PLAN" BUT THERE IS NO DUCT
 ON PLAN. PLEASE SHOW COMPLETE SCOPE OF WORK, SHOWING
 LOCATIONS AND SIZES OF EXISTING DUCTS TO REMAIN AS WELL
 AS NEW DUCTS. SHOW WHICH GRILLS ARE TO BE NEW AND WHICH
 ARE TO REMAIN. SHOW LOCATION OF EXISTING A/C EQUIPMENT.
 FBC 106.1.1
  
 3. PG T-1 STATES THAT THERE IS NO MECHANICAL OR
 PLUMBING WORK TO BE DONE, BUT THERE IS A MECHANICAL
 SCOPE OF WORKK AS INDICATED ON M-1. PLEASE CORRECT.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-06-06 Cont ID  
Sent By jleech Date 2007-06-06 Time 08:50 Rev Time 0.00
Received By jleech Date 2007-06-06 Time 07:42 Sent To  
Notes
2007-06-06 09:01:41DENIED;
 1. PAGE P-1 DRINKING FOUNTAIN NOT SHOW ON EQUIPMENT
 SCHEDULE, FLOOR PLAN OR RISER DIAGRAMS ( WATER OR
 SANITARY).
 2.FLOOR SINK NOT VENTED.
 3.SHUTOFF VALVE REQUIRED FOR TENANT WATER SERVICE. (
 SHOW ON WATER RISER DIAGRAM)
 4. WATER HEATER, FLOOR SINK, AND GLASS WASHER ARE NOT
 SHOWN ON FLOOR PLAN, PAGE A-3.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-02-26 Cont ID  
Sent By jleech Date 2007-02-26 Time 07:08 Rev Time 0.00
Received By jleech Date 2007-02-26 Time 07:08 Sent To  
Notes
2007-02-26 07:28:03DENIED;
 1. FBC-2004 EXISTING BUILDING CODE CHAPTER 8;
 A) SECTION 806 REFURES TO CHAPTER 11 OF THE
 BUILDING CODE. SEE SECTION 11-45.22.2(1) DOORS CAN NOT
 SWING INTO THE CLEAR FLOOR SPACE OF THE BATHROOM
 FIXTURES. BATHROOM DOORS SHOULD SWING OUT.
 B) EX-B CODE SECTION 810 REFURES TO FBC-2004
 PLUMBING. SEE TABLE 403.1 (6M) A DRINKING FOUNTAIN IS
 REQUIRED. DRINKING FOUNTAIN MUST MEET THE REQUIREMENTS
 OF CHAPTER 11 SECTIONS 11-4.1.3(10),11-4.15.2,3,4,
 AND 5. PLEASE SHOW DETAIL WITH ALL REQUIRED
 MEASUREMENTS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695