| 2007-06-03 14:04:19 | ** UNSAT 2RDREVIEW ** |
| | |
| | |
| | ** PLEASE SEE THERE ARE MANY COMMENTS FROM THE PREVIOUS |
| | REVIEWWHICH ARE STILL IN NEED OF ADDRESSING. |
| | **PLEASE ALSO SEE SEVERAL NEW COMMENTS BASED ON NEW |
| | PLANS WHICH ARE FROM CHANGES AND INFORMATION WHICH IS |
| | NOW BEING SUBMITTED FOR THE FIRST TIME FOR REVIEW. |
| | |
| | ***IMPORANT*** |
| | PLEASE ALSO KNOW DUE TO THE PLANS NOT BEING COMPLETE AT |
| | THIS TIME AND THE FOLLOWING COMMENTS FOR PLANS |
| | SUBMITTED, THERE MAY BE COMMENTS ON NEXT REVIEW WHICH |
| | ARE NOT ON THIS REVIEW. |
| | **** DUE TO THE EXTENT OF THE ELECTRICAL COMMENTS, ONE |
| | SET OF THE ELECTRICAL PLANS ARE BEING RETAINED. PLEASE |
| | SEE COMMENTS WITH RESPECT TO FLORIDA STATUTES FOR |
| | REPEAT COMMENTS. |
| | |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE ARCHITECTURAL SHEETS WHICH DO |
| | NOT CONTAIN THE CORRECT CODES. PLEASE SEETHE CODES |
| | LISTED BELOW WHICH WERE PREVIOUSLY NOTED. |
| | PLEASE BE SURE THE PLANS STATE ALL OF THE CURRENT |
| | ADOPTED CODES ON PLANS. |
| | PLEASE SEE THE FOLLOWING ARE REQUIRED FOR ELECTRICAL |
| | AND OTHERS WILL BE REQUIRED FOR OTHER TRADES. PLEASE |
| | KNOW AS OF DECEMBER 8TH, 2006 THE STATE ADOPTED THE |
| | 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70. |
| | PLEASE LIST THE FOLLOWING |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | |
| | |
| | |
| | 2) NOTE:PLEASE SEE THAT COMPLIANCE WITH CHAPTER 13 |
| | HAS NOT BEEN INDICATED. PLEASE SEE THE LIGHTING |
| | CONTROLS NEED TO BE SHOWN IN DETAIL FOR TYPES, TIMES ON |
| | OVER RIDES ETC. IF A LC SYSTEM IS TO BE INSTALLED, |
| | PLEASE INDICATE SCHEDULING AND OVER RIDES. |
| | PLEASE SEE THAT EACH DEVICE NEEDS TO BE SHOWN. RESPONSE |
| | WAS THAT *DUAL SWITCHING HAD BEEN ADDED*IT IS UNCLEAR |
| | WHERE THIS IS FROM? IS THIS MEANT TO RESPOND TO *TANDEM |
| | WIRING* AS STATED IN 13-415.1.ABC.3? |
| | PLEASE COMPLETE FIXTURE LEGEND. PLEASE SEE LEGEND |
| | MENTIONS A *STANDARD FLUORESCENT FIXTURE* HOWEVER DUE |
| | TO THE FACT THERE IS NO STANDARD FIXTURE ON THE MARKET, |
| | ONE IS TO BE SPECIFIED. |
| | PLEASE SEE ENERGY CALCULATIONS ARE TO BE UNDER THE 2006 |
| | REVISIONS TO THE 2004 FBC. PLEASE VERIFY VERSION, |
| | PLEASE ALSO VERIFY METHOD FOR WHOLE BUILDING WHEN THIS |
| | IS A TENANT SPACE WHICH IS PART OF A LARGER *BUILDING* |
| | BY DEFINITION. |
| | PLEASE SEE THE ENERGY CALCULATIONS FOR SOME KW RATINGS |
| | DO NOT MATCH WITH ELECTRICAL PLANS FOR THE SAME LOADS |
| | ON APPLIANCES. PLEASE SEE THE CALCULATIONS DO NOT |
| | CORRELATE AS SOME SHEETS INDICATE ONE LOAD FOR WATER |
| | HEATER AND ANOTHER SHEET INDICATES A LARGER LOAD? |
| | PLEASE ADJUST AND CORRELATE ALL. |
| | PLEASE SEE THE 2004 FBC CHAPTER 13 FOR LIGHTING |
| | CONTROLS PER 13-415.1.ABC.1.1, .1.2 AND .1.3. PLEASE |
| | ALSO SUBMIT ENERGY CALCULATIONS AND PERFORMANCE |
| | CALCULATIONS PER 13-415.1AB.1.1, 13415.2. |
| | |
| | 3) NOTE:PLEASE COMPLETE ALL CIRCUITING ON PLANS AND |
| | CORRELATE WITH PANEL(S). |
| | PLEASE SEE THIS IS THE FIRST REVIEW WHERE PANELS ARE |
| | BEING SUBMITTED FOR REVIEW. |
| | A) PLEASE SEE THE RISER IS NOT COMPLETE AS IS DOES NOT |
| | SHOW HOW PANEL *B* IS BEING FED. |
| | B) PLEASE SEE RISER NOW SHOWS NEW PANELS, DISCONNECTS |
| | AND METERS, YET THE RISER SHOWS THE CONDUCTORS AS |
| | EXISTING? |
| | C) PLEASE SEE THE LOAD AND THE SIZE OF THE PANEL *A* |
| | EXCEEDS THE RATING OF THE PROPOSED 100AMP DISCONNECT AS |
| | SHOWN ALONG WITH CONDUCTORS ETC. |
| | PLEASE SEE THE LOAD IS SHOWN AT 134+ AMPS, ON A 150A |
| | MCB PANEL. (FED FROM100AMP DISCONNECT?) |
| | D) PLEASE SEE PANEL *B* DOES NOT SHOW WHERE IT IS BEING |
| | FED FROM? NO OCP, CONDUCTORS ETC.? |
| | PLEASE KNOW, AT THIS TIME RISER IS NOT COMPLETE FOR |
| | REVIEW. |
| | PLEASE SUBMIT A PANEL SCHEDULE WHICH WILL CORRELATE |
| | WITH ALL OF THE CIRCUITING AS SHOWN ON PLANS. PLEASE BE |
| | SURE ALL OF THE CIRCUITS NEW AND EXISTING ARE SHOWN, |
| | THE SIZE OF THE PANEL, THE OVER CURRENT PROTECTION |
| | DEVICES AND THE CONDUCTORS SIZES. 215.5, 408.4, 310.16, |
| | 240.4 ETC |
| | FBC ADMIN SECTION 106.1.2, 106.3.5.1.2 |
| | |
| | 4) NOTE: PLEASE BE SURE BOTH SETS OF PLANS ARE COMPLETE |
| | WITH ALL SHEETS INSERTED AND MADE INTO SETS. MANY OF |
| | THE SHEETS SUBMITTED ARE LOOSE AND NOT IN SETS OR |
| | ATTACHED IN ANY FASHION. |
| | |
| | 5) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR |
| | ALL EXISTING LOADS AND NEW LOADS BEING ADDED TO THE |
| | PANEL. |
| | AS PREVIOUSLY STATED, INCLUDE ALL NEW LOADS ON THE |
| | EXISTING SERVICE, INCLUDE LOAD OF THE EXISTING SERVICE |
| | WHERE THE PROPOSED NEW TENANT SERVICE IS BEING SHOWN. |
| | PLEASE SEE THE LOAD CALCULATIONS ARE NOT COMPLETE |
| | AND/OR DO NOT SHOW HOW THE FINAL LOADS FOR TRACK |
| | LIGHTING DERIVED. |
| | SHOWS THE 150VA PER 2FT, HOWEVER THE TOTAL FT AND LOAD |
| | FOR THIS COULD NOT BE LOCATED IN ANY BREAKDOWN. |
| | PLEASE SEE AS PANEL *B* DOES NOT INDICATE HOW THIS IS |
| | BEING FED, IT IS UNCLEAR WHERETHE LOADS ARE BEING |
| | ADDED. ARE THESE LOADS ON PANEL *A*? |
| | AS THERE ARE SEVERAL ITEMS WHICH ARE NOT COMPLETE ARE |
| | STATED IN NOTE #3 ABOVE, SOME COMMENTS CAN NOT BE MADE |
| | OR ITEMS REVIEWED. |
| | PLEASE BE SURE TO SHOW THE SIZE OF THE MAIN/OVER |
| | CURRENT PROTECTION, SIZE OF SERVICE PROVIDED. PLEASE |
| | SEE 220.12,220.14, 220.42, 220.44, ETC. PLEASE SEE |
| | 215.3, 230.42 AND SHOW ALL CONTINUOUS LOADS AT 125%. |
| | |
| | 6) NOTE:THIS NOT WILL REMAIN AS NOTED ABOVE. PLEASE |
| | SEE 220.43B FOR MINIMUM CALCULATIONS TO BE SHOWN FOR |
| | TRACK LIGHTING. |
| | |
| | 7) NOTE:THIS NOT REMAINS AS THE CORRECT LOADS FOR |
| | SERVICE ARE NOT COMPLETE FOR CODE COMPLIANCE. WHERE ARE |
| | LOADS IN LOAD CALCULATIONS AS REQUIRED PER SECTIONS |
| | BELOW? |
| | PLEASE SEE MISSING SHOW WINDOW RECEPTACLES WHICH WILL |
| | BE REQUIRED PER 210.62 AND LOADS TO BE SHOWN PER |
| | 210.43A. |
| | |
| | 8) NOTE:PLEASE SEE MISSING LICENSE INFORMATION FOR |
| | *STORETECH* WHICH IS BEING LISTED ON TITLE BLOCKS AS |
| | DESIGNERS? |
| | PLEASE SEE FS 471.023, 481.219. |
| | FAC 61G1-16.004, 61G15-23.002 |
| | THIS IS A NEW COMMENT HOWEVER MUST BE ADDRESSED. |
| | |
| | 9) NOTE:THIS COMMENT IS TO REMAIN. PLEASE SEE THAT NO |
| | RESPONSE WAS MADE IN THE RESPONSE LETTER FOR THIS? |
| | PLEASE SEE THAT THE SIGNATURE ON THE RESPONSE LETTER IS |
| | DIFFERENT THAN THAT OF THE SIGNATURE ON PLANS. |
| | PLEASE ALSO SEE THIS LETTER DOES *NOT* CONTAIN AN |
| | ORIGINAL SIGNATURE. THE LETTER IN FACT CONTAINS A |
| | RAISED SEAL OVER A *PHOTO-COPIED* SIGNATURE. |
| | NOW THAT TWO SIGNATURES HAVE BEEN PRESENTED, THIS |
| | OFFICE HAS NO WAY TO VERIFY WHICH THE LEGAL SIGNATURE |
| | OF THE DESIGNER OR RECORD IS. PLEASE SEND A COPY OF THE |
| | DRIVER'S LICENSE ALONG WITH THE REQUESTED NOTARIZED |
| | LETTER. THIS DL # AND PERSONNEL ADDRESS INFORMATION MAY |
| | BE CROSSED OUT. PLEASE BE SURE ALL RAISED SEALS ARE |
| | CLEAR AND VISIBLE WITH ALL INFORMATION ON SAID SEAL. |
| | PLEASE SEE MANY OF THEM ARE VERY FAINT AND NOT EASILY |
| | READ. PLEASE SEE FS 481.221,471.025 |
| | PLEASE ALSO SEE PLANS APPEAR TO BE SIGNED WITH |
| | INITIALS, IF THIS IS INDEED THE LEGAL SIGNATURE OF THE |
| | DESIGNER OF RECORD, PLEASE PROVIDE A SIGNED, DATED, |
| | SEALED AND NOTARIZED LETTER FOR SIGNATURE VERIFICATION. |
| | THIS WILL BE PLACED IN SIGNATURE FILE FOR FUTURE |
| | REFERENCES. |
| | ANY LETTERS WHICH ARE NOTARIZED MUST CONTAIN THE |
| | STATEMENTS AS REQUIRED UNDER FS 117.05 FOR NOTARIES. |
| | * ONE SET OF PLANS AND LETTERS ARE BEING RETAINED BY |
| | THIS OFFICE. |
| | |
| | 10) NOTE: PLEASE SEE VALUE SHALL BE ADJUSTED AS STATED |
| | FOR SCOPE PER FBC 108.3. NO RESPONSE WAS MADE TO THIS |
| | AND THE APPLIED VALUE REMAINS THE SAME. THE VALUE SHALL |
| | INCLUDE ALL LABOR AND MATERIALS AND EQUIPMENT, EVEN IF |
| | ANY OF THIS IS OWNER SUPPLIED. |
| | |
| | 11) NOTE: PLEASE SEE COPY OF FS 553.80(2)(B) ATTACHED |
| | WITH RESPECT TO DESIGN PROFESSIONALS AND REPEAT |
| | COMMENTS. |
| | THIS IS ONLY A NOTICE GIVEN AT THIS TIME. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |