| Plan Review Stops For Permit 07020247 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2007-03-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-03-29 |
Time |
19:30 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-03-29 |
Time |
19:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-02-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-02-27 |
Time |
13:49 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-02-27 |
Time |
13:48 |
Sent To |
|
|
| Notes |
| 2007-02-27 13:49:39 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC RFLORIDA BUILDING CODE 2004 | | | RESIDENTIAL | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | | | | 1.)ENGINEERING TO BE SIGNED, SEALED, DATED ORIGINALS | | | AND TO HAVE ALL INFORMATION REQUIRED BY | | | FAC61G15-23.002. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2007-03-22 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-03-22 |
Time |
17:09 |
Rev Time |
0.33 |
| Received By |
btrobaug |
Date |
2007-03-22 |
Time |
16:48 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-02-23 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-02-22 |
Time |
09:38 |
Rev Time |
0.33 |
| Received By |
btrobaug |
Date |
2007-02-22 |
Time |
09:25 |
Sent To |
B |
|
| Notes |
| 2007-02-23 13:42:00 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | THE ENGINEER OF RECORD SHALL INDICATE THE CERTIFICATE | | | OF AUTHORIZATIONNUMBER ALONG WITH OTHER INFORMATION | | | REQUIRED BY 61G15-23.002FLORIDA ADMINISTRATIVE CODE. | | | ALSO THE ENGINEER MUST SEAL THE PLANS PER 471.025. | | | | | | WILLIAM R. TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-03-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-03-19 |
Time |
08:37 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-03-19 |
Time |
08:37 |
Sent To |
E |
|
| Notes |
| 2007-03-19 08:37:45 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-03-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-03-14 |
Time |
10:29 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-03-14 |
Time |
10:29 |
Sent To |
Z |
|
| Notes |
| 2007-03-14 10:29:25 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-02-20 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-02-20 |
Time |
17:21 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-02-20 |
Time |
17:21 |
Sent To |
E |
|
| Notes |
| 2007-02-20 17:22:23 | TO "E" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-02-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-02-27 |
Time |
13:49 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-02-09 |
Time |
16:51 |
Sent To |
|
|
| Notes |
| 2007-02-09 16:51:19 | TO "Z" BOX |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2007-03-27 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-03-27 |
Time |
08:49 |
Rev Time |
0.33 |
| Received By |
mperson |
Date |
2007-03-27 |
Time |
08:49 |
Sent To |
B |
|
| Notes |
| 2007-03-27 08:50:53 | NOTE- POOL HEATER IS AN ELECTRIC HEAT PUMP |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-02-23 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-02-23 |
Time |
13:37 |
Rev Time |
0.45 |
| Received By |
mperson |
Date |
2007-02-23 |
Time |
13:13 |
Sent To |
E |
|
| Notes |
| 2007-02-23 13:21:53 | DENIED | | | REFERENCE: FLORIDA ADMINISTRATIVE CODE | | | | | | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING | | | PLAN REVIEW TO MEET CODE COMPLIANCE: | | | | | | 1. FAC-61G1-16.004 TITLE BLOCK: | | | A TITLE BLOCK MUST APPEAR ON ALL | | | ARCHITECTURAL OR INTERIOR DESIGN | | | DRAWINGS AND SPECIFICATION | | | IDENTIFICATION SHEETS. THE TITLE BLOCK | | | MUST, AT A MINIMUM, CONTAIN THE | | | FOLLOWING INFORMATION: | | | (1) FIRM NAME, ADDRESS, AND TELEPHONE | | | NUMBER. | | | (A) FIRM LICENSE NUMBER. | | | (B) NAME OR IDENTIFICATION OF PROJECT. | | | (C) DATE PREPARED. | | | (D) A SPACE FOR THE SIGNATURE AND DATED | | | SEAL. | | | (E) A SPACE FOR THE PRINTED NAME OF THE | | | PERSON SEALING THE DOCUMENT. | | | NOTE: (A) IS MISSING FROM THE TITLE BLOCK. PLEASE ADD | | | FIRM LICENSE NUMBER TO TITLE BLOCK AND RESUBMIT. | | | | | | 2. FAC-61G15-23.002 SEAL SIGNATURE AND DATE | | | SHALL BE AFFIXED: | | | EACH SHEET OF PLANS AND PRINTS WHICH | | | MUST BE SEALED UNDER PROVISIONS OF | | | CHAPTER 471 SHALL BE SEALED, SIGNED AND | | | DATED BY THE PROFESSIONAL ENGINEER IN | | | RESPONSIBLE CHARGE. ENGINEERS SHALL | | | LEGIBLY INDICATE THEIR NAME, ADDRESS, | | | AND LICENSE NUMBER ON EACH SHEET. IF | | | PRACTICING THROUGH A DULY AUTHORIZED | | | ENGINEERING BUSINESS, ENGINEERS SHALL | | | LEGIBLY INDICATE THEIR NAME LICENSE NUM- | | | BER, AS WELL AS, THE NAME, ADDRESS, AND CERTIFICATE OF | | | AUTHORIZATION NUMBER OF | | | THE ENGNEERING BUSINESS ON EACH SHEET. | | | NOTE: PLEASE SEAL PAGES AND RESUBMIT. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2007-03-16 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2007-03-16 |
Time |
13:46 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2007-03-16 |
Time |
13:46 |
Sent To |
I |
|
| Notes |
| 2007-03-16 13:46:41 | ***PROVISO*** | | | | | | EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE OR | | | SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT ACCESS | | | BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF THE | | | RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED. | | | BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN | | | HEIGHT ABOVE GRADE. | | | | | | ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE THROUGH A | | | BUILDING OR THROUGH A SELF-CLOSING AND SELF-LATCHING | | | GATE OR THROUGH A SCREEN ENCLOSURE DOOR WITH LATCHES | | | PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF GATE.(CHILD | | | SAFETY BARRIERS DO NOT SATISFY THIS REQUIREMENT).AT | | | LEAST 90 PERCENT OF THE SURFACE AREA OF ALL SCREEN | | | ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH WHICH | | | AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT SHALL | | | BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A | | | 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE, | | | AT THE PROPERTY LINE, TO ENSURE PRIVACY. | | | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER, | | | AT (561) 822-1435. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-02-15 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2007-02-15 |
Time |
11:57 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2007-02-15 |
Time |
11:57 |
Sent To |
I |
|
| Notes |
| 2007-02-15 13:31:06 | ***FAILED*** | | | | | | 1) SWIMMING POOLS, SPAS, ETC. WITH THE COPING SHALL NOT | | | EXTEND MORE THAN ONE (1) FOOT ABOVE THE ESTABLISHED | | | GRADE. | | | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER, | | | AT (561) 822-1435. |
|
|