Plan Review Details - Permit 07020247
Plan Review Stops For Permit 07020247
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-03-29 Cont ID  
Sent By shill Date 2007-03-29 Time 19:30 Rev Time 0.00
Received By shill Date 2007-03-29 Time 19:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-02-27 Cont ID  
Sent By shill Date 2007-02-27 Time 13:49 Rev Time 0.00
Received By shill Date 2007-02-27 Time 13:48 Sent To  
Notes
2007-02-27 13:49:39****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
  
 1.)ENGINEERING TO BE SIGNED, SEALED, DATED ORIGINALS
 AND TO HAVE ALL INFORMATION REQUIRED BY
 FAC61G15-23.002.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-03-22 Cont ID  
Sent By btrobaug Date 2007-03-22 Time 17:09 Rev Time 0.33
Received By btrobaug Date 2007-03-22 Time 16:48 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-02-23 Cont ID  
Sent By btrobaug Date 2007-02-22 Time 09:38 Rev Time 0.33
Received By btrobaug Date 2007-02-22 Time 09:25 Sent To B
Notes
2007-02-23 13:42:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 THE ENGINEER OF RECORD SHALL INDICATE THE CERTIFICATE
 OF AUTHORIZATIONNUMBER ALONG WITH OTHER INFORMATION
 REQUIRED BY 61G15-23.002FLORIDA ADMINISTRATIVE CODE.
 ALSO THE ENGINEER MUST SEAL THE PLANS PER 471.025.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-03-19 Cont ID  
Sent By adarroug Date 2007-03-19 Time 08:37 Rev Time 0.00
Received By adarroug Date 2007-03-19 Time 08:37 Sent To E
Notes
2007-03-19 08:37:45TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-14 Cont ID  
Sent By adarroug Date 2007-03-14 Time 10:29 Rev Time 0.00
Received By adarroug Date 2007-03-14 Time 10:29 Sent To Z
Notes
2007-03-14 10:29:25TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-20 Cont ID  
Sent By adarroug Date 2007-02-20 Time 17:21 Rev Time 0.00
Received By adarroug Date 2007-02-20 Time 17:21 Sent To E
Notes
2007-02-20 17:22:23TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-27 Cont ID  
Sent By shill Date 2007-02-27 Time 13:49 Rev Time 0.00
Received By shill Date 2007-02-09 Time 16:51 Sent To  
Notes
2007-02-09 16:51:19TO "Z" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-03-27 Cont ID  
Sent By mperson Date 2007-03-27 Time 08:49 Rev Time 0.33
Received By mperson Date 2007-03-27 Time 08:49 Sent To B
Notes
2007-03-27 08:50:53NOTE- POOL HEATER IS AN ELECTRIC HEAT PUMP

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-02-23 Cont ID  
Sent By btrobaug Date 2007-02-23 Time 13:37 Rev Time 0.45
Received By mperson Date 2007-02-23 Time 13:13 Sent To E
Notes
2007-02-23 13:21:53DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. FAC-61G1-16.004 TITLE BLOCK:
 A TITLE BLOCK MUST APPEAR ON ALL
 ARCHITECTURAL OR INTERIOR DESIGN
 DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK
 MUST, AT A MINIMUM, CONTAIN THE
 FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE
 NUMBER.
 (A) FIRM LICENSE NUMBER.
 (B) NAME OR IDENTIFICATION OF PROJECT.
 (C) DATE PREPARED.
 (D) A SPACE FOR THE SIGNATURE AND DATED
 SEAL.
 (E) A SPACE FOR THE PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT.
 NOTE: (A) IS MISSING FROM THE TITLE BLOCK. PLEASE ADD
 FIRM LICENSE NUMBER TO TITLE BLOCK AND RESUBMIT.
  
 2. FAC-61G15-23.002 SEAL SIGNATURE AND DATE
 SHALL BE AFFIXED:
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME, ADDRESS,
 AND LICENSE NUMBER ON EACH SHEET. IF
 PRACTICING THROUGH A DULY AUTHORIZED
 ENGINEERING BUSINESS, ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME LICENSE NUM-
 BER, AS WELL AS, THE NAME, ADDRESS, AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF
 THE ENGNEERING BUSINESS ON EACH SHEET.
 NOTE: PLEASE SEAL PAGES AND RESUBMIT.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2007-03-16 Cont ID  
Sent By jroach Date 2007-03-16 Time 13:46 Rev Time 0.00
Received By jroach Date 2007-03-16 Time 13:46 Sent To I
Notes
2007-03-16 13:46:41***PROVISO***
  
 EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE OR
 SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT ACCESS
 BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF THE
 RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED.
 BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN
 HEIGHT ABOVE GRADE.
  
 ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE THROUGH A
 BUILDING OR THROUGH A SELF-CLOSING AND SELF-LATCHING
 GATE OR THROUGH A SCREEN ENCLOSURE DOOR WITH LATCHES
 PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF GATE.(CHILD
 SAFETY BARRIERS DO NOT SATISFY THIS REQUIREMENT).AT
 LEAST 90 PERCENT OF THE SURFACE AREA OF ALL SCREEN
 ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH WHICH
 AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT SHALL
 BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A
 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE,
 AT THE PROPERTY LINE, TO ENSURE PRIVACY.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-02-15 Cont ID  
Sent By jroach Date 2007-02-15 Time 11:57 Rev Time 0.00
Received By jroach Date 2007-02-15 Time 11:57 Sent To I
Notes
2007-02-15 13:31:06***FAILED***
  
 1) SWIMMING POOLS, SPAS, ETC. WITH THE COPING SHALL NOT
 EXTEND MORE THAN ONE (1) FOOT ABOVE THE ESTABLISHED
 GRADE.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.