Plan Review Details - Permit 07020242
Plan Review Stops For Permit 07020242
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-03-16 Cont ID  
Sent By jgomez Date 2007-03-16 Time 16:23 Rev Time 0.50
Received By jgomez Date 2007-03-16 Time 12:37 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-03-05 Cont ID  
Sent By jgomez Date 2007-03-05 Time 14:37 Rev Time 0.50
Received By jgomez Date 2007-03-05 Time 14:22 Sent To  
Notes
2007-03-05 16:29:39BUILDING REVIEW THIRD CHECKLIST:
 1- CALCULATED WIND PRESSURES ARE TOO LOW. SEE FIGURE
 6-3 ASCE 7-02.WHAT'S THE EFFECTIVE WIND AREA USED FOR
 THE CALCULATIONS?.ENGINEER NEEDS TO USE AT LEAST 10SF
 OF EFFECTIVE WIND AREA.SEE EFFECTIVE WIND AREA
 DEFINITION ON SEC. 1609.2 FBC 2004.
  
 2- IF USING WIND PRESSURE OF -89PSF FOR ENTIRE ROOF,
 THEN PROVIDEDFASTENER SPACINGDOESN'T WORK.PROVIDE
 RAS 117 CALCULATIONS.SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004. CLARIFY WHERE WAS THE -89PSF WIND PRESSURE
 TAKEN FROM?.IT HAS NOTHING TO DO WITH CALCULATED
 WIND PRESSURES.SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 3- PROVIDE THE ENGINEERING FIRM CERTIFICATE OF
 AUTHORIZATION NUMBER IN ALL SHEETS AS REQUIRED BY SEC.
 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE.
  
 4- ENGINEER SEAL IS NOT LEGIBLE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-02-12 Cont ID  
Sent By jgomez Date 2007-02-12 Time 15:02 Rev Time 0.50
Received By jgomez Date 2007-02-12 Time 12:45 Sent To  
Notes
2007-02-12 13:09:50BUILDING REVIEW SECOND CHECKLIST:
 1-SELECTED ASSEMBLY ON PAGE 38 OF NOA 03-0827.02 HAS
 A MAXIMUM DESIGN PRESSURE OF -60PSF.UPLIFT PRESSURES
 AT CORNER AREAS ARE HIGHER. SEE TABLE 1609.6.2.1(2) FBC
 2004.THEREFORE, NEED TO PROVIDE RAS 117 CALCULATIONS
 FOR NAIL ENHANCING AT CORNER AREAS. ACCORDING TO
 GENERAL LIMITATION #7 OF NOA SUBMITTED THESE
 CALCULATIONS SHALL BE PREPARED, SINGED AND SEALED ONLY
 BYARCHITECT, ENGINEER OR REGISTERED ROOF CONSULTANT.
 SEE LAST PAGE OF NOA SUBMITTED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-02-09 Cont ID  
Sent By jgomez Date 2007-02-09 Time 12:47 Rev Time 0.50
Received By jgomez Date 2007-02-09 Time 12:35 Sent To  
Notes
2007-02-09 13:06:45BUILDING REVIEW CHECKLIST:
 1-CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING
 TO BE INSTALLED AS REQUIRED BY CITY POLICY FOR ROOFING
 PERMITS. SEE ATTACHED COPY OF CITY POLICY.
  
 2- IF SELECTED ASSEMBLY IS LIMITED BY GENERAL
 LIMITATION #7, THEN NEED TO PROVIDE THE RAS 117
 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND CORNER
 AREAS. CALCULATIONS NEED TO BE SIGNED AND SEALED BY
 ARCHITECT, ENGINEER OR REGISTERED ROOFING CONSULTANT.
 SEEGENERAL LIMITATION #7 ON PAGE 40 OF 40 OF NOA
 03-0827.02 SUBMITTED.
  
 3- IF SELECTED ASSEMBLY IS LIMITED BY GENERAL
 LIMITATION #9, THEN IT CAN'T BE INSTALLED IN THIS AREA
 BECAUSE NAIL ENHANCING IS NOT ALLOWED. SEE GENERAL
 LIMITATION #9 ON PAGE 40 OF 40OF NOA 03-0827.02
 SUBMITTED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712