| 2007-03-28 15:18:43 | BUILDING REVIEW CHECKLIST: |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| | SEC. 713.13 FLORIDA STATUTES. |
| | |
| | 2- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH |
| | COUNTY(2300 N. JOG RD - (561)233-5115)TO VERIFY IF |
| | IMPACT FEES ARE DUE.BRING BACK STAMPED PLANS AND COPY |
| | OF PAID RECEIPT IF FEES ARE DUE. |
| | |
| | 3- NEED CLEAR AND COMPLETE SET OF DRAWINGS TO BE |
| | DESIGNED BY PROFESSIONAL ENGINEER OR ARCHITECT TO MEET |
| | THE STRUCTURAL REQUIREMENTS OF SECTIONS R301 OF 2004 |
| | FLORIDA RESIDENTIAL CODE AND SEC. 2002 OF 2004 FLORIDA |
| | BUILDING CODE.PROPOSED CONSTRUCTION IS NOT CLEAR AND |
| | IS MIXING STRUCTURAL ALUMINUM WITH WOOD FRAMING. |
| | THEREFORE, SPECIAL CONSIDERATION IS REQUIRED FOR THE |
| | DESIGN OF THE STRUCTURE. |
| | *** NOTE: SCREEN ENCLOSURES DESIGN LOADS ARE DIFFERENT |
| | THAN THOSE FOR ENCLOSED STRUCTURES. IN ADDITION |
| | PRESSURE TREATED WOOD AND ALUMINUM ARE DISSIMILAR |
| | MATERIALS. THEY CAN'T BE USED TOGETHER. |
| | *** NOTE: PROFESSINAL OF RECORD TO TAKE INTO |
| | CONSIDERATION FOOTING SIZE AND FINISH FLOOR ELEVATION |
| | WHEN DESIGNING THE ADDITION. (THIS INFORMATION WAS NOT |
| | CONSIDERED ON SUBMITTED DRAWINGS). |
| | |
| | 4- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | 13-600 FBC 2004. |
| | |
| | 5- PROVIDE FLORIDA PRODUCT APPROVAL AS REQUIRED BY RULE |
| | 9B-72 FOR: |
| | A) SINGLE HUNG WINDOWS. |
| | |
| | B) EXTERIOR DOORS. |
| | |
| | C) STRUCTURAL CONNECTORS SPECIFIED ON PLANS AND |
| | DETAILS. |
| | |
| | D) ROOF COVERING. |
| | |
| | 6- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 7- BRING DRAWINGSFOR HISTORIC APPROVAL AFTER PLANS |
| | ARE REVISED, THEN BRING THEM BACK TO THIS OFFICE. |
| | |
| | 8- VALUATION DECLARED ON THE PERMIT APPLICATION IS TOO |
| | LOW.PERMIT VALUATION WILL BE UPDATED AND ADDITIONAL |
| | FEES WILL BE DUE.SEC. 108.3 CITY AMENDMENTS TO FBC |
| | 2004. |
| | |
| | 9-SPECIFY SAFETY GLASS FORWINDOWS THAT ARE WITHING |
| | 24" OF DOORS.SEC. R308.4 OF 2004 FLORIDA RESIDENTIAL |
| | CODE. |
| | |
| | 10- STORM SHUTTERS: |
| | A) PROVIDE PRODUCT APPROVAL REVIEWED AND APPROVED IN |
| | WRITING BY DESIGNER OF RECORD. |
| | |
| | B) PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE |
| | ATTACHED SAMPLE OF INSTALLATION SCHEDULE. COMPLETE ALL |
| | THE INFORMATION. |
| | |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561) 805-6712 |