Plan Review Details - Permit 07020194
Plan Review Stops For Permit 07020194
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-09-10 Cont ID UTICA
Sent By jjohnsto Date 2007-09-10 Time 09:55 Rev Time 2.00
Received By jjohnsto Date 2007-09-10 Time 09:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-07-31 Cont ID  
Sent By jwitmer Date 2007-07-31 Time 07:22 Rev Time 1.11
Received By jwitmer Date 2007-07-31 Time 07:17 Sent To PC
Notes
2007-07-31 07:29:26BUILDING PLAN REVIEW
 PERMIT: 07020194
 ADD: 2410 METROCENTRE BLVD.LASZLO HARANGOZO
 CONT:
 TEL: (703)843-1614
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) COVERSHEET A0.1 PLEASE SEE LISTED UNDER PROJECT TEAM
 ERIC HAFER PE STILL HAS THE COMPANY NAME LISTEDNATIONAL
 DESIGN CONSULTANT: ERIC HAFER & ASSOCIATES P A)
 471.023 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ENGINEERING
 SERVICES, SHALL INCLUDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER.
 ADD THE NUMBER TO EACH SHEET.THIS MAY
 BE ADDED BY HAND.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-06-13 Cont ID  
Sent By jwitmer Date 2007-06-13 Time 16:00 Rev Time 0.55
Received By jwitmer Date 2007-06-13 Time 15:38 Sent To PC
Notes
2007-06-13 16:07:35BUILDING PLAN REVIEW
 PERMIT: 07020194
 ADD: 2410 METROCENTRE BLVD.LASZLO HARANGOZO
 CONT:
 TEL: (703)843-1614
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) SHEET A0.1 NEW COMMENT TYYPE OF CONSTRUCTION, THE
 TABLE 601 WOULD READ THE CURRENT
 2004 BUILDING TYPES BUT LISTED IS" TYPE V- UNPROTECTED
 FULLY SPRINKLED, (PER ORIGINAL BUILDING SHELL
 DRAWINGS)
 THE CONVERSION FROM THE 2001 TYPE V-UNPROTECTED FULLY
 SPRINKLED TO THE 2004/2006 FBC EQUALLS TO A
 TYPE III-B SPRINKLED BUILDING. PLEASE CORRECT.
  
 3) SEE ELECTRICAL COMMENT# 3 ABOUT ERIC HAFER IS
 MISSING:471.023 F.S.CERTIFICATE OF AUTHORIZATION.
 THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ENGINEER PRACTICING UNDER
 A FICTITIOUS NAME, A CORPORATION, OR A PARTNERSHIP,
 OFFERING ENGINEERING SERVICES, SHALL INCLUDE THE
 CERTIFICATE OF AUTHORIZATION NUMBER. ADD THE NUMBER TO
 EACH SHEET.THIS MAY BE ADDED BY HAND.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-12 Cont ID  
Sent By jwitmer Date 2007-03-12 Time 14:27 Rev Time 3.55
Received By jwitmer Date 2007-03-12 Time 14:27 Sent To  
Notes
2007-03-12 15:28:20BUILDING PLAN REVIEW
 PERMIT: 07020194
 ADD: 2410 METROCENTRE BLVD.LASZLO HARANGOZO
 CONT:
 TEL: (703)843-1614
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS
 NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE
 OF COMMENCEMENT
 AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) SHEET A0.1 PLANS INDICATE THEY WERE DESIGNED TO THE
 FLORIDA BUILDING CODE, WHICH EDITION?
  
 4) SHEET A0.1 PLANS INDICATE THIS IS A BUSINESS
 OCCUPANCY, CONFIRMING THE STUDENTS THAT WILL ENROLL IN
 THIS PROGRAM WILL BE CONSIDERD
 ADULTS AND YOUTH IN THE 12TH GRADE OR LOWER?
  
 5) CURRENTLY THE PLANS ARE IN FOR A PLAN REVIEW ONLY,
 BUT ONCE THEY ARE IN FOR
 PERMIT THEY WILL NEEED TO BE SIGNED AND SEALED THE
 DESIGNER OF RECCORD,
 ORIGINAL SIGNATURES WILL BE REQUIRED, WITH RAISED
 SEAL.
  
 PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 6) SHEET A2.1 DOOR # 12 APPEARS TO BE AN EXISTING DOOR
 AND FRAME, INSPECTOR TO VERIFY THIS IS A 45 MIN (3/4
 HR) RATED DOOR ASSEMBLY.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-11-19 Cont ID  
Sent By dpalmer Date 2007-11-19 Time 12:14 Rev Time 0.00
Received By dpalmer Date 2007-11-19 Time 11:54 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-09-04 Cont ID  
Sent By dpalmer Date 2007-09-04 Time 17:25 Rev Time 0.00
Received By dpalmer Date 2007-09-04 Time 17:25 Sent To  
Notes
2007-09-04 17:25:28NEW ENERGY CALCS BROUGHT IN BY THE ARCHITECT.
 OK>.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-08-28 Cont ID  
Sent By dpalmer Date 2007-08-28 Time 17:32 Rev Time 0.00
Received By dpalmer Date 2007-08-28 Time 15:44 Sent To  
Notes
2007-08-28 17:33:072007-08-28 17:33:07
  
 ** DENIED 4TH REVIEW**
  
 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED
 STATES THE METHOD OF CONTROLS AS *MANUAL ON/OFF* WHICH
 IS NOT POSSIBLE WHEN LIGHTING ON PLANS ARE AUTOMATED.
 PLEASE OBTAIN NEW ENERGY CALCULATIONS WITH THE CORRECT
 METHODS CHOSEN TO COORDINATE WITH THE PLANS AND
 CONTROLS SHOWN.
 PLEASE KNOW THE OPTIONS ARE ON THE FORMS WHEN DATA IS
 BEING CHOSEN.
 PLEASE ALSO SEE THE CERTIFICATION SHEETS ALSO NEED THE
 OWNER AGENT TO SIGN SHEETS.
 13-103.1.1.1, 13-415.C.1 (AS SUBMITTED)
  
 ** IF NEW ENERGY CALCULATIONS CAN BE BROUGHT IN AS SOON
 AS POSSIBLE, THIS WOULD HELP ALLEVIATE ANY RESUBMISSION
 OF PLANS AND DELAYING POSSIBLE ISSUANCE OF PERMIT IF
 ALL OTHER TRADES ARE OK.
 PLEASE KNOW AS NEW ENERGY CALCULATIONS WERE SUBMITTED,
 THE MECHANICAL REVIEWER WILL STILL REVIEW FOR CODE
 COMPLIANCE. IF NO CHANGES ARE NEEDED FOR MECH REVIEW,
 THEN ONLY ADDRESS THIS ABOVE COMMENT AT THIS TIME.
  
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-07-02 Cont ID  
Sent By dpalmer Date 2007-07-02 Time 18:26 Rev Time 0.00
Received By dpalmer Date 2007-07-02 Time 17:05 Sent To I
Notes
2007-07-02 18:27:082007-07-02 18:27:08
 ** UNSAT3RD REVIEW**
 ** 1ST REVIEW UNDER PERMIT APPLICATION**
  
 ** PLEASE SEE THERE ARE NOTES FROM THE PREVIOUS REVIEW
 WHICH STILL NEED TO BE ADDRESSED ALONG WITH NEW NOTES.
  
  
 1) NOTE: *** IMPORTANT***
 PLEASE DO NOT ATTACHED SUPPORTING DOCUMENTS DOWN THE
 LEFT SIDE OF PLANS. THESE SHOULD BE PLACED INTO TWO
 SETS, FOLDER(S), SPIRAL NOTEBOOK, OR SOME OTHER FASHION
 TO KEEP TOGETHER. THESE WERE REMOVED FROM PLANS.
  
 2) NOTE PLEASE SEE MISSING INFORMATION REQUIRED ON
 TITLE BLOCKS FOR THE ARCHITECT AND THE ARCHITECTURAL
 FIRM.PLEASE SEE THE TITLE COVER SHEETS WHICH STILL
 INDICATE ERIC HAFER AND ASSOCIATES PA.
 RESPONSES MENTIONS THAT THIS WAS BEING REMOVED ON ALL
 SHEETS, HOWEVER THIS STILL SHOWN.
 PLEASE SEE THE FLORIDA ADMINISTRATIVE CODE 61G1-16.004
 AND FLORIDA STATUES 481.219
 * THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 ANY OTHER TRADE REVIEWER.
  
 3) NOTE: PLEASE SEE NEW SIGNED, DATED AND SEALED SHEETS
 BY THE ENGINEER FOR ELECTRICAL WHICH THE RAISED SEALS
 ARE NOT CLEAR AND VISIBLE. PLEASE SEE THE PREVIOUS
 SHEETS DATED APRIL 07 WERE OK, HOWEVER EVEN USING A
 LEAD DUST RUB ON SEALS, THE INFORMATION WHICH IS
 REQUIRED TO BE CLEAR AND VISIBLE IS NOT.
 PLEASE SEE FS 471.025, FAC 61G15-23.001.
  
 4) NOTE: PLEASE SEE COMPLIANCE WITH FBC CHAPTER 13 IS
 STILL IN QUESTION:
 PLEASE SEE SEVERAL CIRCUITS AS NOTED ON PLANS FOR LE,
 26, 28 AND 30 WHICH DO NOT SEEM TO SHOW ANY LIGHTING
 CONTROLS, OVER RIDES OR PART OF THE LCP.?
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 OF THE FBC
 CHAPTER 13.
 ** PLEASE SEE NOTES ON PLANS MENTIONS SOME ITEMS AND
 SOME CONTROLS HOWEVER NOT ALL INFORMATION FOR MINIMUM
 DESIGN FOR CODE IS PRESENT.
 PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED ARE IN
 FACT THE SAME AS PREVIOUSLY SUBMITTED. PLEASE SEE THE
 DESIGN WATTAGE IS STILL HIGHER THAN THE ALLOWANCE.
 PLEASE SEE THE VERSION IS STILL NOT CORRECT. PLEASE SEE
 ALL VERSIONS WITH AN EFFECTIVE DATE AS OF DECEMBER 8TH,
 2006. PLEASE SEE THE 2.1 IS NO LONGER IN EFFECT. PLEASE
 SEE THE INPUT DATA REPORTS ARE NOW NO LONGER ATTACHED.
 **AS PREVIOUSLY NOTED**
 PLEASE SUBMIT ENERGY CALCULATIONS/PERFORMANCE
 CALCULATIONS PER 13-415.AB.1.1, 13-415.1.A, 13-415.1.B,
 13-415.1.C, 13-415.2
 PLEASE SEE 13-103.1.1.1 FOR DESIGNER OF RECORD TO SIGN,
 DATE AND SEAL SAID DOCUMENTS.
  
 5) NOTE:PLEASE SEE DETAIL/RISER NOTE ON TRANSFORMER
 STILL STATES TO SEE THE SHEET E1.1 AND DETAIL 05 FOR
 GROUNDING OF TRANSFORMER WHICH IS BLANK. THE RESPONSE
 MENTIONS THIS IS TO BE CORRECTED AND SEE OTHER SHEET
 HOWEVER RISER WAS NOT ADJUSTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE THE ATTACHMENT LOCATION FOR THE NEW
 TRANSFORMER.
 PLEASE SEE THE RESPONSE LETTER MENTIONS TO SEE REVISED
 SINGLE LINE DIAGRAM WHICH SAYS TO SEE DETAIL #5 ON
 SHEET 1.1, HOWEVER THIS DETAIL #5 IS ACTUALLY BLANK ON
 SHEET 1.1.
 PLEASE COORDINATE PLANS AND POSSIBLE DETAIL ON SHEET
 1.5.
 PLEASE SEE 250.50, 250.30, 250.20.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-07-02 17:06:272007-07-02 17:06:27
 PLANS REMOVED FROM INCOMING, PLANS WILL BE SENT BACK TO
 INCOMING WAITING FOR COMM BOARD ONCE ELECTRICAL REVIEW
 IS DONE.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-04-24 Cont ID  
Sent By dpalmer Date 2007-04-24 Time 19:05 Rev Time 0.00
Received By dpalmer Date 2007-04-24 Time 17:41 Sent To  
Notes
2007-04-24 19:05:23 
  
 ** UNSAT2ND REVIEW**
  
 ** PLEASE SEE THERE ARE NOTES FROM THE PREVIOUS REVIEW
 WHICH STILL NEED TO BE ADDRESSED ALONG WITH NEW NOTES.
  
  
  
 1) NOTE:SAME NOTE.
 PLEASE SEE THAT PLANS HAVE ONLY BEEN SUBMITTED FOR *
 PLAN REVIEW* AND NOT SUBMITTED FOR PERMIT APPLICATION.
 PLEASE KNOW PLANS WILL REMAIN IN *F* STATUS FOR ALL
 TRADES EVEN IF PLANS ARE OK. PERMIT APPLICATION FOR
 SCOPE OF WORK, VALUE, RELEVANT CODES ETC WILL NEED TO
 BE VERIFIED ONCE APPLICATION IS MADE.
  
 2) NOTE:SAME NOTE. PLEASE SEE THERE ARE SEVERAL AREAS
 WHERE THE INCORRECT CODES ARE REFERENCED. PLEASE SEE
 THE STATE OF FLORIDA IS NOT UNDER THE IEC OR THE 1997
 SOUTH FLORIDA ENERGY CODE.
 PLEASE SEE PLANS WHICH ARE REDLINED AT MANY OF THE
 LOCATIONS WHICH STILL INDICATE THESE.
 PLEASE BE SURE ALL PLANS REFLECT THE LATEST ADOPTED
 CODES PER THE STATE OF FLORIDA. PLEASE SEE THE
 FOLLOWING WHICH ARE CURRENTLY ADOPTED AS OF DECEMBER
 8TH, 2006.
 2004 FBC W/ 2006 REVISION. (THIS WILL AFFECT PLANS
 SUBMITTED).
 2005 NFPA-70 (NEC). (THIS WILL AFFECT PLANS AS NUMEROUS
 LOCATIONS REFLECT CODES FROM THE 1999 NFPA-70.) 2002
 NFPA-72
 2003 NFPA-101
 ** THESE CODES ARE REQUIRED AT A MINIMUM FOR THIS TRADE
 REVIEWER; OTHERS MAY BE REQUIRED PER OTHER TRADES OR
 REVIEWER(S).
 PLEASE SEE THERE ARE MANY AREAS ON THE PLANS WHICH
 REFERENCE OLDER CODES FROM PREVIOUS CODES, THESE SHOULD
 BE REVISED ACCORDINGLY.
  
 3) NOTE: PLEASE SEE MISSING INFORMATION REQUIRED ON
 TITLE BLOCKS FOR THE ARCHITECT AND THE ARCHITECTURAL
 FIRM.THIS IS THE SAME COMMENT AS PREVIOUS REVIEW AS
 NO LICENSE INFORMATION FOR ERIC HAFER AND ASSOCIATES PA
 HAS BEEN SHOWN.
 PLEASE SEE THE MISSING FIRM LICENSE NUMBER WHICH IS
 ALSO KNOWN AS THE CERTIFICATE OF AUTHORIZATION NUMBER
 AND ALSO THE MISSING PRINTED NAME AND PRINTED LICENSE
 NUMBER OF THE ARCHITECT.
 PLEASE SEE THE FLORIDA ADMINISTRATIVE CODE 61G1-16.004
 AND FLORIDA STATUES 481.219
 * THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 ANY OTHER TRADE REVIEWER.
  
 4) NOTE: PLEASE SEE THE PREVIOUS NOTES WITH RESPECT TO
 CHAPTER 13. PLEASE SE THE LIGHTING ZONES AS SUBMITTED
 ALONG WITH THE SCHEDULE TABLES DOES NOT SEEM TO BE
 COMPLETE. MOST IS BLANK? PLEASE CLARIFY.
 PLEASE SEE SOME OF THE AREAS AND ROOMS DO NOT INDICATE
 ANY CONTROL DEVICES FOR AUTOMATED CONTROL OF LIGHTING
 AND THE PROPOSED ZONED LIGHTING SYSTEM DOES NOT PROVIDE
 ENOUGH INFORMATION.
 PLEASE SEE THE SYMBOL LEGEND SHOULD COORDINATE WITH THE
 SYMBOLS TO BE SHOWN ON PLANS.
 PLEASE SHOW ALL DEVICES/OCCUPANCY SENSORS ON PLANS.
 (COVERAGE NEEDS TO BE REVIEWED FOR LOCATIONS ETC)
 PLEASE BE SURE TO COORDINATE THE DEVICES AS SHOWN AND
 TO BE SHOWN ON THE LIGHTING CONTROL SHEETS WITH THAT OF
 THE LIGHTING PLANS. PLEASE UPDATE AND REVISE ALL
 DEVICES AND LOCATIONS.
 PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED UNDER
 METHOD *C* IS NOT CLEAR HOW THE DESIGN WATTAGE AS SHOWN
 IS SO MUCH HIGHER THAN THE EFFECTIVE AND THE
 ALLOWANCE.
 PLANS STILL INDICATES THE INCORRECT CODES AS REQUIRED
 AND NOTED IN NOTE #1 AND THIS NOTE FROM PREVIOUS
 REVIEW.
 PLEASE ADJUST AND PLEASE PROVIDE MORE SPECIFICATIONS ON
 PLEASE SEE THE ENERGY CODE AS STATED ON PLANS IS NOT
 THE 2004 FBC W/ 2006 REVISIONS TO CHAPTER 13. THE STATE
 OF FLORIDA CONTAINS ITS OWN ENERGY CODE. PLEASE SEE THE
 PLANS STATE THE 1997 ENERGY CODE ALONG WITH THE 2004
 IEC.
 PLEASE SUBMIT THE INFORMATION RELEVANT TO THE 2004 FBC
 AND 2006 REVISIONS FOR LIGHTING CONTROLS AND LOCATIONS
 PER 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE THAT SOME DEVICES ON PLANS APPEAR TO CONTROL
 LIGHTING, HOWEVER DOES NOT PROVIDE INFORMATION ON TYPE
 AND OVER RIDE TIMES. SOME DEVICES ARE NOTED ON PLANS
 AND TIMES ARE SHOWN, HOWEVER COVERAGE DOES NOT SEEM TO
 BE PROVIDED FOR SOME OTHER AREAS.
 PLEASE SEE NOTE ON PLANS WHICH MENTIONS HALLWAY
 LIGHTING AND CONTROLS ARE NOTED AS EXISTING TO REMAIN,
 HOWEVER THIS DOES NOT SEEM TO CORRELATE WITH THE OTHER
 WORK AS SHOWN ON PLANS.
 PLEASE CLARIFY HOW THE FIGURES AS SHOWN ON PLANS
 INDICATE A SWITCH ON THE LOAD SIDE OF THE POWER PACK.
 HOW WILL THESE DEVICES REACT ON AN AUTOMATIC BASIS WHEN
 AN OCCUPANT ENTERS AN AREA IF A SWITCH IS IN THE OFF
 POSITION? PLEASE ALSO SEE ANOTHER SCENARIO, WHERE A
 ROOM OR AREA IS OCCUPIED, SOMEONE LEAVES AND TURNS THE
 SWITCH OFF, THEN THIS WOULD LEAVE ANY OF THE OTHER
 OCCUPANTS IN DARKNESS ??
 PLEASE SUBMIT ENERGY CALCULATIONS/PERFORMANCE
 CALCULATIONS PER 13-415.AB.1.1, 13-415.1.A, 13-415.1.B,
 13-415.1.C, 13-415.2
 PLEASE SEE 13-103.1.1.1 FOR DESIGNER OF RECORD TO SIGN,
 DATE AND SEAL SAID DOCUMENTS.
  
 5) NOTE: NOTES WERE ADDED TO PLANS FOR VERIFICATION,
 HOWEVER THIS INFORMATION SHOULD BE OBTAINED FROM THE
 SITE AND PLACED ON PLANS ACCORDINGLY.
 ** PREVIOUS NOTE ** PLEASE VERIFY NEW OR EXISTING
 EMERGENCY LIGHTING OUTSIDE EXIT DOOR TO STAIR AREA AND
 DOOR LOCATED TO THE PUBLIC RIGHT OF WAY. IF EXISTING,
 PLEASE SHOW, IF NOT EXISTING, NEW WILL BE REQUIRED.
 PLEASE SEE 2003 NFPA-101 7.8, 7.9
  
 6) NOTE:PLEASE INDICATE THE ATTACHMENT LOCATION FOR
 THE NEW TRANSFORMER.
 PLEASE SEE THE RESPONSE LETTER MENTIONS TO SEE REVISED
 SINGLE LINE DIAGRAM WHICH SAYS TO SEE DETAIL #5 ON
 SHEET 1.1, HOWEVER THIS DETAIL #5 IS ACTUALLY BLANK ON
 SHEET 1.1.
 PLEASE COORDINATE PLANS AND POSSIBLE DETAIL ON SHEET
 1.5.
 PLEASE SEE 250.50, 250.30, 250.20.
  
 7) NOTE: PLEASE CLARIFY TAPPED CONDUCTORS FROM GUTTER
 TO EACH OF THE 150A MCB DISCONNECTS AS SHOWN ON RISER
 ON THE SECONDARY SIDE OF THE TRANSFORMER.
 240.21, 310.16, 240.4
  
 8) NOTE: PLEASE KNOW THAT THE LOW VOLTAGE AS SHOWN ON
 PLANS WILL BE REQUIRED TO BE UNDER SEPARATE PERMITS. LV
 SECURITY IS UNDER A SEPARATE PERMIT FROM OTHER LV
 WORK.
 PLANS PERMIT APPLICATIONS AND FEES WILL BE DUE FOR
 THESE SYSTEMS AS NOTED. IF THERE ARE ANY QUESTIONS ON
 THIS, PLEASE CALL TO GO OVER.
  
 ** PLEASE KNOW THAT DUE TO SOME INFORMATION NOT
 SUBMITTED AT THIS TIME, REVIEW OF SOME ITEMS FOR CODE
 COMPLIANCE CAN NOT BE DONE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-02-21 Cont ID  
Sent By dpalmer Date 2007-02-21 Time 18:00 Rev Time 0.00
Received By dpalmer Date 2007-02-20 Time 15:38 Sent To  
Notes
2007-02-21 18:01:52*** UNSAT ***
  
  
 1) NOTE:PLEASE SEE THAT PLANS HAVE ONLY BEEN
 SUBMITTED FOR * PLAN REVIEW* AND NOT SUBMITTED FOR
 PERMIT APPLICATION. PLEASE KNOW PLANS WILL REMAIN IN
 *F* STATUS FOR ALL TRADES EVEN IF PLANS ARE OK. PERMIT
 APPLICATION FOR SCOPE OF WORK, VALUE, RELEVANT CODES
 ETC WILL NEED TO BE VERIFIED ONCE APPLICATION IS MADE.
  
 2) NOTE: PLEASE BE SURE ALL PLANS REFLECT THE LATEST
 ADOPTED CODES PER THE STATE OF FLORIDA. PLEASE SEE THE
 FOLLOWING WHICH ARE CURRENTLY ADOPTED AS OF DECEMBER
 8TH, 2006.
 2004 FBC W/ 2006 REVISION. (THIS WILL AFFECT PLANS
 SUBMITTED).
 2005 NFPA-70 (NEC). (THIS WILL AFFECT PLANS AS NUMEROUS
 LOCATIONS REFLECT CODES FROM THE 1999 NFPA-70.) 2002
 NFPA-72
 2003 NFPA-101
 ** THESE CODES ARE REQUIRED AT A MINIMUM FOR THIS TRADE
 REVIEWER; OTHERS MAY BE REQUIRED PER OTHER TRADES OR
 REVIEWER(S).
 PLEASE SEE THERE ARE MANY AREAS ON THE PLANS WHICH
 REFERENCE OLDER CODES FROM PREVIOUS CODES, THESE SHOULD
 BE REVISED ACCORDINGLY.
  
 3) NOTE: PLEASE SEE MISSING THE REQUIRED RAISED SEALED
 FROM THE ARCHITECT OF RECORD PER FLORIDA ADMINISTRATIVE
 CODE 61G1-16.003, FLORIDA STATUES 481.221. THE USE OF A
 *RUBBER STAMP* IS NOT PERMITTED IN THE STATE OF
 FLORIDA.
 * THIS IS REQUIRED FOR ALL SHEETS AND WHETHER OR NOT
 COMMENT IS MADE BY ANY OTHER REVIEWER.
  
 4) NOTE: PLEASE SEE MISSING INFORMATION REQUIRED ON
 TITLE BLOCKS FOR THE ARCHITECT AND THE ARCHITECTURAL
 FIRM. PLEASE SEE THE MISSING FIRM LICENSE NUMBER WHICH
 IS ALSO KNOWN AS THE CERTIFICATE OF AUTHORIZATION
 NUMBER AND ALSO THE MISSING PRINTED NAME AND PRINTED
 LICENSE NUMBER OF THE ARCHITECT.
 PLEASE SEE THE FLORIDA ADMINISTRATIVE CODE 61G1-16.004
 AND FLORIDA STATUES 481.219
 * THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 ANY OTHER TRADE REVIEWER.
  
 5) NOTE: PLEASE SEE THE MISSING LICENSE INFORMATION FOR
 THE ENGINEERING FIRM. PLEASE SEE THE MISSING
 CERTIFICATE OF AUTHORIZATION NUMBER PER FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002 AND FLORIDA STATUES
 471.023.
 * THIS IS REQUIRED FOR ALL SHEETS WHETHER OR NOT
 COMMENT IS MADE BY OTHER TRADES.
  
 6) NOTE: PLEASE SEE THE SEAL USED ON SOME SHEETS FOR
 THE ENGINEER OF RECORD IS LONGER VALID FOR USE IN THE
 STATE OF FLORIDA. PLEASE SEE THAT THE WORDING OF
 *CERTIFICATE* IN SEAL WAS REQUIRED TO BE CHANGED TO THE
 WORDING OF *LICENSE* IN FEB 04. THE RULE 61G15-23.001
 WAS EXTENDED TO DECEMBER 31ST, 2005 HOWEVER ALL PLANS
 AFTER THAT DATE MAY NOT USE THE OLD SEAL. THIS IS ONLY
 THE CASE ON SOME OF THE SHEETS IN ONE OF THE SETS
 SUBMITTED. PLEASE CORRECT.
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES.
  
 7) NOTE: PLEASE SEE THE ENERGY CODE AS STATED ON PLANS
 IS NOT THE 2004 FBC W/ 2006 REVISIONS TO CHAPTER 13.
 THE STATE OF FLORIDA CONTAINS ITS OWN ENERGY CODE.
 PLEASE SEE THE PLANS STATE THE 1997 ENERGY CODE ALONG
 WITH THE 2004 IEC.
 PLEASE SUBMIT THE INFORMATION RELEVANT TO THE 2004 FBC
 AND 2006 REVISIONS FOR LIGHTING CONTROLS AND LOCATIONS
 PER 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE THAT SOME DEVICES ON PLANS APPEAR TO CONTROL
 LIGHTING, HOWEVER DOES NOT PROVIDE INFORMATION ON TYPE
 AND OVER RIDE TIMES. SOME DEVICES ARE NOTED ON PLANS
 AND TIMES ARE SHOWN, HOWEVER COVERAGE DOES NOT SEEM TO
 BE PROVIDED FOR SOME OTHER AREAS.
 PLEASE SEE NOTE ON PLANS WHICH MENTIONS HALLWAY
 LIGHTING AND CONTROLS ARE NOTED AS EXISTING TO REMAIN,
 HOWEVER THIS DOES NOT SEEM TO CORRELATE WITH THE OTHER
 WORK AS SHOWN ON PLANS.
 PLEASE CLARIFY HOW THE FIGURES AS SHOWN ON PLANS
 INDICATE A SWITCH ON THE LOAD SIDE OF THE POWER PACK.
 HOW WILL THESE DEVICES REACT ON AN AUTOMATIC BASIS WHEN
 AN OCCUPANT ENTERS AN AREA IF A SWITCH IS IN THE OFF
 POSITION? PLEASE ALSO SEE ANOTHER SCENARIO, WHERE A
 ROOM OR AREA IS OCCUPIED, SOMEONE LEAVES AND TURNS THE
 SWITCH OFF, THEN THIS WOULD LEAVE ANY OF THE OTHER
 OCCUPANTS IN DARKNESS ??
 PLEASE SUBMIT ENERGY CALCULATIONS/PERFORMANCE
 CALCULATIONS PER 13-415.AB.1.1, 13-415.2
 PLEASE SEE 13-103.1.1.1 FOR DESIGNER OF RECORD TO SIGN,
 DATE AND SEAL SAID DOCUMENTS.
  
 8) NOTE: PLEASE SEE THAT THE COLOR CODING FOR 277/480V
 SYSTEMS SHALL BE BROWN, PURPLE, YELLOW. PLEASE KNOW
 SYSTEMS LOCATED IN THE CITY OF WEST PALM BEACH ARE
 CURRENTLY UNDER THIS COLOR CODING FOR FEEDERS DUE TO
 PREVIOUS LOCAL AMENDMENTS.
 * PER NEC, *ORANGE* COLOR IS FOR A HIGH-LEG OF DELTA
 SYSTEM.
 FBC ADMIN SECTION 104.6
  
 9) NOTE: PLEASE SPECIFY THE MINIMUM LEVELS FOR HORN AND
 STROBE DEVICES ON PLANS. IT IS KNOW THAT THERE WILL BE
 SEPARATE PERMIT FOR ANY FIRE ALARM SYSTEM OR DEVICE
 WORK; HOWEVER THE BASE PLANS ARE REQUIRED TO SHOW THIS
 INFORMATION AT THIS TIME. PLEASE SEE FBC 11-4.28.1, .2,
 AND .3(4) FOR MINIMUM LEVELS TO BE ON PLANS.
  
 10) NOTE: PLEASE SEE THE MAIN ELECTRICAL ROOM EVEN AS
 EXISTING IS INDICATING THE DOOR SWING INWARDS. PLEASE
 VERIFY THIS. PLEASE SEE 110.26 OF THE NEC.
 PLEASE SEE THAT THE DOOR SWING IS REQUIRED TO SWING
 OUT. PLEASE ADJUST. DUE TO THE LEVEL OF WORK AND
 ALTERATION, DOOR SWING WILL BE REQUIRED TO BE CHANGED
 IF NOT ALREADY IN THE SWING OUT POSITION. PLEASE BE
 SURE TO SEE POSSIBLE SWING AND TRAVEL OF DOOR SWING IN
 EXIT CORRIDOR. PLEASE SEE THAT THE DOOR SWING MAY BE
 REQUIRED TO OPEN IN THE PATH OF EGRESS AND ON 180
 DEGREE HINGES? PLEASE ALSO SEE OTHER MAXIMUM DOOR WIDTH
 IN HALL WHEN IN OPEN POSITION. THIS MAY NOT BE A
 BUILDING REVIEW COMMENT AT THIS TIME, HOWEVER AS THE
 DOOR SWING WILL BE REQUIRED TO BE CHANGED, AND THEN
 PLEASE BE SURE TO CHECK WITH BUILDING CODE FOR
 ALLOWANCES.
 ** THIS IS A LIFE SAFETY ISSUE FOR EXITING FROM THE
 ELECTRICAL ROOM DURING AN EMERGENCY.
  
 11) NOTE: PLEASE VERIFY NEW OR EXISTING EMERGENCY
 LIGHTING OUTSIDE EXIT DOOR TO STAIR AREA AND DOOR
 LOCATED TO THE PUBLIC RIGHT OF WAY. IF EXISTING, PLEASE
 SHOW, IF NOT EXISTING, NEW WILL BE REQUIRED. PLEASE SEE
 2003 NFPA-101 7.8, 7.9
  
 12) NOTE: PLEASE INDICATE THE ATTACHMENT LOCATION FOR
 THE NEW TRANSFORMER.
 PLEASE SEE 250.50, 250.30, 250.20.
  
 13) NOTE: PLEASE SEE 250.66 FOR THE CORRECT SIZING OF
 THE GROUNDING ELECTRODE CONDUCTOR FOR THE TRANSFORMER.
  
 14) NOTE: PLEASE SEE THE FEEDERS ON THE RISER SHOW A
 NEUTRAL CONDUCTOR FROM THE MDP TO THE NEW TRANSFORMER.
 HOW IS THIS POSSIBLE WHEN THIS IS A SEPARATELY DERIVED
 SYSTEM AND THE TRANSFORMER CREATES ITS OWN NEW NEUTRAL
 POINT?
 PLEASE CLARIFY.
 250.20, 250.30 ETC
  
 15) NOTE: PLEASE PROVIDE A MORE DETAILED LOAD SUMMARY.
 : LOADS ARE CURRENTLY SHOWN AT CONNECTED LOADS FOR
 ALL.
 PLEASE SEE 220.12, 220.14, 220.42, 220.44 ETC. PLEASE
 INDICATE ALL CONTINUOUS LOADS AT 125%. 215.3, 230.42.
  
 16) NOTE: PLEASE NOTE OR PROVIDE INFORMATION IF THE
 EXISTING MAIN AT 277/480 AND OVER 1000AMPS CONTAINS GF
 PROTECTION.
 240.13, 230.95 ONLY NEEDS TO NOTE IF EXISTING.
  
 ** PLEASE KNOW THAT DUE TO SOME INFORMATION NOT
 SUBMITTED AT THIS TIME, REVIEW OF SOME ITEMS FOR CODE
 COMPLIANCE CAN NOT BE DONE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-02-19 10:10:00IN ELEC FOR REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-09-10 Cont ID  
Sent By mawillia Date 2007-09-10 Time 17:17 Rev Time 0.00
Received By mawillia Date 2007-09-10 Time 16:53 Sent To B
Notes
2007-09-10 17:17:23*****APPROVED*****
  
  
 PLAN SHEETSA2.5, F1.1, F2.1, E2.3 AND E2.6 WERE
 STAMPED, INTIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-07-26 Cont ID  
Sent By mawillia Date 2007-07-26 Time 16:13 Rev Time 0.00
Received By mawillia Date 2007-07-26 Time 16:00 Sent To  
Notes
2007-07-26 16:11:05*****PROVISO*****
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;HOWEVER THE APPROPIATE PLAN SHEET(S)
 WILL BE STAMPED WHEN ALL OTHER PLAN REVIEWS HAVE BEEN
 SATISFIED
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-05-07 Cont ID  
Sent By mawillia Date 2007-05-07 Time 14:24 Rev Time 0.00
Received By mawillia Date 2007-05-07 Time 14:04 Sent To  
Notes
2007-05-07 14:06:04*****PROVISO*****
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;HOWEVER THE APPROPIATE PLAN SHEET(S)
 WILL BE STAMPED WHEN ALL OTHER PLAN REVIEWS HAVE BEEN
 SATISFIED
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-03-19 Cont ID  
Sent By mawillia Date 2007-03-19 Time 16:24 Rev Time 0.00
Received By mawillia Date 2007-03-19 Time 13:57 Sent To  
Notes
2007-03-19 16:24:13*****DENIED*****
  
  
  
 1. NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE
 PREVENTION CODE (2004) EDITION) SHALL BE REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL
 NOT INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS TO
 THE SAID PROPERTY OR VICINITY THEREOF (INCLUDING FIRE
 LANES).
  
 4.PLEASE INDICATE IF THE BUILDING OR PORTIONS OF THE
 BUILDING WILL BE OCCUPIED DURING THE PROPOSED SCOPE OF
 WORK.IF SO,THIS WILL BE PERMITTED ONLY WHERE
 REQUIRED MEANS OF EGRESS AND REQUIRED FIRE PROTECTION
 FEATURES ARE IN PLACE AND MAINTAINED, OR WHERE
 ALTERNATIVE LIFE SAFETY MEASURES ACCEPTABLE TO THE AHJ
 ARE IN PLACE.
  
 5.INTERIOR WALL AND CEILING FINISH MATERIALS SHALL
 BE CLASS A OR CLASS B IN EXITS AND EXIT ACCESS
 CORRIDORS,CLASS A, CLASS B, OR CLASS C IN ALL OTHER
 AREAS.PLEASE SPECIFY.
  
 6.PROVIDE A LIFE SAFETY PLAN SHEET WHICH INDICATES
 THE TRAVEL DISTANCE TO THE EXIT(S).ALSO INDICATE THE
 LOCATION OF THE 2A:10BC FIRE EXTINGUISHERS WHICH
 SATISFY THE 75 ' TRAVEL DISTANCE REQUIREMENT.
  
 7.IF THE EXISTING FIRE ALARM AND/OR FIRE SPRINKLER
 SYSTEM IS/ARE MODIFIED DUE TO THE SCOPE OF WORK,
 SEPARATE PLANS AND PERMIT WILL BE REQUIRED.
  
 8.PLEASE NOTE THE DIFFERENCE IN THE LAYOUT OF THE
 FACIAL ROOM [116] ON SHEET E-2.2 AND E-2.6 COMPARED TO
 E-2.1 ANDE-2.3.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RE-SUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-12-12 Cont ID  
Sent By adarroug Date 2007-12-12 Time 16:28 Rev Time 0.00
Received By adarroug Date 2007-12-12 Time 16:28 Sent To M
Notes
2007-12-12 16:28:46TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-11-27 Cont ID  
Sent By adarroug Date 2007-11-27 Time 09:54 Rev Time 0.00
Received By adarroug Date 2007-11-27 Time 09:53 Sent To M
Notes
2007-11-27 09:54:17TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-11-07 Cont ID  
Sent By adarroug Date 2007-11-07 Time 08:57 Rev Time 0.00
Received By adarroug Date 2007-11-07 Time 08:57 Sent To  
Notes
2007-11-07 08:58:10WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-08-03 Cont ID  
Sent By adarroug Date 2007-08-03 Time 14:55 Rev Time 0.00
Received By adarroug Date 2007-08-03 Time 14:55 Sent To  
Notes
2007-08-28 15:13:08TO "COMM" BD#40
2007-08-03 14:55:38WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-06-21 Cont ID  
Sent By adarroug Date 2007-06-21 Time 15:57 Rev Time 0.00
Received By adarroug Date 2007-06-21 Time 15:57 Sent To  
Notes
2007-07-09 14:14:52TO "COMM" BD#18
2007-06-21 15:59:53WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-23 Cont ID  
Sent By adarroug Date 2007-04-23 Time 09:09 Rev Time 0.00
Received By adarroug Date 2007-04-23 Time 09:09 Sent To  
Notes
2007-04-23 09:17:16TO "COMM" BD#58

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-19 Cont ID  
Sent By mawillia Date 2007-03-19 Time 13:57 Rev Time 0.00
Received By mawillia Date 2007-02-12 Time 08:44 Sent To  
Notes
2007-02-19 07:52:22TO COMM BOARD SPACE #54
2007-02-12 08:45:01WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2007-12-13 Cont ID  
Sent By tgordon Date 2007-12-13 Time 08:15 Rev Time 0.25
Received By tgordon Date 2007-12-13 Time 08:15 Sent To  
Notes
2007-12-13 08:16:29REVISION TO MECH. PLAN PAGE M2.1 AND SUBMITTEL LETTER
 FOR DUCT SIZE CHANGE FROM 26"X24" TO 24"X24".

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2007-11-30 Cont ID  
Sent By tgordon Date 2007-11-30 Time 10:45 Rev Time 0.25
Received By tgordon Date 2007-11-30 Time 10:45 Sent To  
Notes
2007-11-30 10:46:46MECHANICAL REVISION TO PAGE M2.1.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2007-11-14 Cont ID  
Sent By tgordon Date 2007-11-14 Time 15:19 Rev Time 0.30
Received By tgordon Date 2007-11-14 Time 15:19 Sent To E
Notes
2007-11-14 15:34:52PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 MECHANICAL REVISION TO PAGE M2.1.
 *** DENIED ***
 1) THE EXHAUST MAY NOT TERMINATE WITHIN 10 FT. OF AN
 INTAKE OPENING, SEE 2004 FBC/M 401.5.1. PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-09-04 Cont ID  
Sent By tgordon Date 2007-09-04 Time 13:41 Rev Time 0.20
Received By tgordon Date 2007-09-04 Time 13:41 Sent To  
Notes
2007-09-04 13:42:16APPROVED MECH. PLANS PASSED REVIEW ON 7-10-07.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-07-10 Cont ID  
Sent By tgordon Date 2007-07-10 Time 12:22 Rev Time 0.45
Received By tgordon Date 2007-07-10 Time 12:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-04-30 Cont ID  
Sent By tgordon Date 2007-04-30 Time 14:42 Rev Time 0.30
Received By tgordon Date 2007-04-30 Time 14:42 Sent To  
Notes
2007-04-30 14:46:23** FOR PLAN REVIEW ONLYNOT FOR PERMIT **
 *** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTE #2, PLEASE CORRECT PLANS
 PAGE PME1.1.
  
 2) MECHANICAL PLANS ARE OK AT THIS TIME.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-02-27 Cont ID  
Sent By tgordon Date 2007-02-27 Time 11:57 Rev Time 1.30
Received By tgordon Date 2007-02-27 Time 11:57 Sent To  
Notes
2007-02-27 12:30:21** FOR PLAN REVIEW, NOT FOR PERMIT **
 *** DENIED ***
 1) CERTIFICATE OF AUTHORIZATION NUMBER FOR THE
 ENGINEERING BUSINESS (POLARIS) MUST APPEAR IN THE TITLE
 BLOCK, SEE FAC 61G15-23.002.
  
 2) THE 34X16 RETURN AIR TRANSFER DUCT FROM CLASSROOM
 107 TO SHAMPOO 103 IS PENETRATING FIRE RATED WALLS AND
 WILL NEED FIRE DAMPERS, SEE 2004 FBC/M 607.5.2. ALSO
 PLEASE EXPLAIN WHAT ( --- CBBC ) IS, I COULD NOT FIND
 IN THE ABBREVIATIONS.
  
 3) THE 9" SUPPLY AIR DUCT FROM THE CORRIDOR TO THE
 BOOKSTORE 116 WILL NEED A FIRE DAMPER ALSO, SEE 2004
 FBC/M 607.5.3, 2, 2.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-09-10 Cont ID  
Sent By mperson Date 2007-09-10 Time 14:15 Rev Time 0.00
Received By mperson Date 2007-09-10 Time 14:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-07-17 Cont ID  
Sent By kstevens Date 2007-07-17 Time 07:31 Rev Time 0.00
Received By kstevens Date 2007-07-17 Time 07:31 Sent To  
Notes
2007-07-17 07:35:27DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 MUNICIPAL CODE
  
 ********FROM PREVIOUS REVIEWS********
  
 1. SHTS A0.1 THRU A5.3 PLANS SHALL BE SEALED BY AN
 IMPRESSION TYPE SEAL. ALL INFORMATION REQUIRED FOR SEAL
 TO BE IMPRESSED ON TO EACH SHEET. THE BUSINESS LICENSE
 OF THE ARCHITECTURAL FIRM SHALL INDICATE THEIR
 CERTIFICATE OF AUTHORIZATION, (BUSINESS LICENSE
 NUMBER), IN THE TITLE BLOCK OF EACH SHEET. FAC
 61G1-16.001, 61G1-16.002, 61G1-16.004(2) AND FS
 481.219, 481.2055.
 ****RESPONSE NOTED, BUT THE ARCHITECTURAL FIRM LICENSE
 NUMBER, (CERTIFICATE OF AUTHORIZATION), IS NOT SHOWN IN
 THE TITLE BLOCK.
 ********RESPONSE NOTED, BUT NATIONAL DESIGN CONSULTANT:
 ERIC HAFNER & ASSOCIATES P. A. IS STILL REFERENCED ON
 SHT A0.1. DELETE ALL REFERENCES OF THE ARCHITECTURAL
 FIRM FROM PLANS OR SUBMIT FIRM LICENCE NUMBER.
  
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
 7. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-06-06 Cont ID  
Sent By kstevens Date 2007-06-06 Time 07:38 Rev Time 0.00
Received By kstevens Date 2007-06-05 Time 12:54 Sent To  
Notes
2007-06-06 08:44:14DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 MUNICIPAL CODE
  
 1. SHTS A0.1 THRU A5.3 PLANS SHALL BE SEALED BY AN
 IMPRESSION TYPE SEAL. ALL INFORMATION REQUIRED FOR SEAL
 TO BE IMPRESSED ON TO EACH SHEET. THE BUSINESS LICENSE
 OF THE ARCHITECTURAL FIRM SHALL INDICATE THEIR
 CERTIFICATE OF AUTHORIZATION, (BUSINESS LICENSE
 NUMBER), IN THE TITLE BLOCK OF EACH SHEET. FAC
 61G1-16.001, 61G1-16.002, 61G1-16.004(2) AND FS
 481.219, 481.2055.
 ****RESPONSE NOTED, BUT THE ARCHITECTURAL FIRM LICENSE
 NUMBER, (CERTIFICATE OF AUTHORIZATION), IS NOT SHOWN IN
 THE TITLE BLOCK.
  
 2. OK
  
 3. OK
 4. OK
 5. OK
 6. OK
 7. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-03-10 Cont ID  
Sent By kstevens Date 2007-03-10 Time 10:27 Rev Time 0.00
Received By kstevens Date 2007-03-10 Time 10:27 Sent To  
Notes
2007-03-10 10:57:59DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 MUNICIPAL CODE
  
 1. SHTS A0.1 THRU A5.3 PLANS SHALL BE SEALED BY AN
 IMPRESSION TYPE SEAL. ALL INFORMATION REQUIRED FOR SEAL
 TO BE IMPRESSED ON TO EACH SHEET. THE BUSINESS LICENSE
 OF THE ARCHITECTURAL FIRM SHALL INDICATE THEIR
 CERTIFICATE OF AUTHORIZATION, (BUSINESS LICENSE
 NUMBER), IN THE TITLE BLOCK OF EACH SHEET. FAC
 61G1-16.001, 61G1-16.002, 61G1-16.004(2) AND FS
 481.219, 481.2055.
  
 2. ALL P,M,E SHEETS. THE CERTIFICATE OF AUTHORIZATION
 FOR THE ENGINEERING COMPANY SHALL BE INDICATED IN THE
 TITLE BLOCK ON EACH SHEET. FAC 61G15-23.002(2) & FS
 471.025.
  
 3. SUBMIT A FLOOR PLAN PLAN VIEW FOR THE PLUMBING
 PIPING. SHOW THE CONNECTION POINT FOR THE WATER AND FOR
 THE SANITARY PLUMBING LINES, SECTIONS 106.1.2 AND
 106.3.5.1.3(3)(4)(10).
  
 4. SUBMIT THE SANITARY RISER DIAGRAM IN AN ISOMETRIC
 FORM THAT REFLECTS THE LAYOUT OF THE FIXTURES AND THE
 RELATED PIPING AS IT WILL BE INSTALLED, (FLOOR PLAN).
 INDICATE THE HAIR INTERCEPTOR LOCATIONS. SECTION
 106.1.1.
  
 5. SUBMIT THE WATER RISER ISOMETRIC IN AN ISTOMETRIC
 FORM THAT REFLECTS THE LAYOUT OF THE FIXTURES AND FLOOR
 PLAN. SHOW THE SHUT OFF VALVES FOR THE HOSE BIBBS ON
 THE SUPPLY PIPES REQUIRED IN SECTION 606.2(2) & SECTION
 106.3.5.1.3(3)(10)(13).
  
 6. SHT P1.2 GREASE WASTE RISER. IN THE REMOVAL OF ANY
 PART OF A DRAINAGE SYSTEM, DEAD ENDS SHALL BE
 PROHIBITED. SECTION 704.5. (SEE DEFINITION).
  
 7. SHT P1.2 IF THE GREASE INTERCEPTOR WILL BE
 ABANDONED, IT SHALL BE EMPTIED, CLEANED OUT AND
 REMOVED, OR EMPTIED, CLEANED OUT AND THE TOP REMOVED,
 BOTTOM BROKEN TO ALLOW DRAINAGE AND FILLED WITH CLEAN
 SAND OR OTHER SUITABLE MATERIAL. PLEASE INDICATE
 METHOD. MUMICIPAL CODE SECTION 90-123(E)(1)(2)(3).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS