| 2007-03-13 14:44:00 | BUILDING PLAN REVIEW |
| | PERMIT: 07020189 |
| | ADD: 2300 PRESIDENTIAL WAY |
| | CONT: ALTEK STEEL INDUSTRIES |
| | TEL: (561)662-8352 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2)FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF |
| | THE COURT. |
| | NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS |
| | NOT ACTUALLY |
| | COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF, |
| | SUCH NOTICE IS |
| | NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE |
| | OF COMMENCEMENT |
| | AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3)110.2* W. P. B. ADMINISTRATIVE |
| | CODE, INFORMATION THAT IS REQUIRED FOR |
| | RECORD KEEPING & FOR CERTIFICATE OF |
| | OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH |
| | THE PERMIT WAS ISSUED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. |
| | D) THE OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| | IS REQUIRED. |
| | F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| | OF THE BUILDING PERMIT. |
| | G) SQ. FT. FOOTPRINT |
| | H) SQ. FT. UNDER ROOF (TOTAL) |
| | I ) FLOOD ZONE |
| | J ) FLOOD ELEVATION |
| | |
| | 4) NOTE THE LOCATION OF THIS NEW BUILDING APPEARS TO BE |
| | APPROX. 5'-0" AWAY FROM ANOTHER BUILDING, PLEASE SEE |
| | 503.1.3 2 BUILDINGS ON THE SAME LOT, THIS MAY EFFECT |
| | THE ANSWER TO QUESTION |
| | 3-C. |
| | |
| | 5) SHEET # 1 FROM B+C APPEARS TO HAVE A TYPOONE SIDE |
| | INDICAATES 40'-" VS. 60'-0" ON THE OTHER SIDE. |
| | |
| | 6)NOTE AS OF THIS DATE B+ C ARCHITECTURE, INC'S |
| | CERTIFICATE OF AUTHORIZATION IS DELINGUENT 2/28/07. |
| | |
| | 7) BUILDING CODE ANYLISIS THERE IS A DISCREPANCY, |
| | BUILDING CODE CATEGORY "M",TABLE 1604.5 THERE'S NO |
| | DESIGNATION AS SUCH. DEPENDING ON THE RESPONCE TO |
| | QUESTION 3B, THIS BUILDING COULD POSSIBLY |
| | BE LISTED AS A CATEGORY III OR IV WITH AN IMPORTANCE |
| | FACTOR OF 1.15 FOR FERTILIZERS AND QUANITITIES STORED. |
| | |
| | 8)IT APPEARS THE EXISTING CONCRETE SLAB IS TO BE |
| | REUSED. PLEASE PROVIDE COMPLIANCE WITH 1816.1 TERMITE |
| | PROTECTION. |
| | |
| | 9) SHEET E-1 ENGINEERING NOTE "SPECIFICATION FOR |
| | STRUCTURAL JOINTS USING ASTM A 325 OR ASTM A490 BOLTS |
| | PLEASE REFER TO FBC 2006 CHAPTER 35 RCSC-88. |
| | |
| | 10)THERE IS ALSO A NOTE ON E-1 INDICATING THE |
| | POSSIBLE USE OF (LTP) LIGHT TRANSFERING PANELS AND THE |
| | REQUIREMENT FOR HURRICANE PROTECTION, PLANS DO INDICATE |
| | AS SUCH, CONFIRMING THERE |
| | WILL BE NO SUCH PANELS? 106.1.2* ADDITIONAL INFORMATION |
| | REQUIRED. |
| | |
| | 11)FL BLD CODE 1609.1.4: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) WALL PANELS- NO REPORT SUBMITTED |
| | B) ROOF ASSEMBLIES- NO REPORT SUBMITTED NOTE SLOPE ON |
| | ROOF 1:12,HIGHLIGHT SYSTEM USED. |
| | C) ROLL UP DOOR- REQUIRES FLORIDA COVER SHEET, |
| | TECHNICAL SHEETS ARE NOT LEGIBLE |
| | D) DOMINION EXTERIOR DOOR- OK |
| | E) STRUCTURAL ZEE SECTION- NO REPORT SUBMITTED |
| | |
| | 12) WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 13)BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |