| 2007-02-07 16:59:17 | BUILDING REVIEW CHECKLIST: |
| | |
| | ***NOTE:PROVIDE ALL THE INFORMATION REQUIRED BY CITY |
| | POLICY FOR ROOFING PERMITS. SEE ATTACHED COPY. |
| | |
| | 1-WOOD DECK: |
| | A) FROM NOA SUBMITTED,CLEARLY IDENTIFY WHICH |
| | APPROVED ASSEMBLY IS GOING TO BE INSTALLED. |
| | |
| | B) FROM NOA SUBMITTED, CLEARLY IDENTIFYSPECIFIC |
| | BASE SHEET FASTENING OPTION. |
| | |
| | B) FROM NOA SUBMITTED. PROVIDERAS 117 CALCULATIONS |
| | FOR NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS |
| | REQUIRED BY GENERAL LIMITATION #7. SEE LAST PAGE OF |
| | NOA. |
| | |
| | 2- CONCRETE DECK: |
| | A) FROM NOA SUBMITTED, CLEARLY IDENTIFY WHICH |
| | APPROVED ASSEMBLY IS GOING TO BE INSTALLED. |
| | |
| | B) IF SELECTED ASSEMBLY IS LIMITED BY GENERAL |
| | LIMITATION #7, THEN PROVIDE RAS 117 CALCULATIONS FOR |
| | NAIL ENHANCING AT PERIMETER AND CORNER AREAS IF |
| | ASSEMBLY IS DESIGNED FOR DESIGN PRESSURES LESS THAN |
| | THOSE SPECIFIED ON TABLE 1609.6.2.1(2) 2004 FBC. SEE |
| | LAST PAGE OF NOA. |
| | |
| | C) IF SELECTED ASSEMBLY IS LIMITED BY GENERAL |
| | LIMITATION #9, THEN IT MAY NOT BE USED IN THIS AREA IF |
| | ASSEMBLY IS DESIGNED FOR DESIGN PRESSURES LESS THAN |
| | THOSE SPECIFIED ON TABLE 1609.6.2.1(2) 2004 FBC 2004. |
| | NAIL ENHANCING IS NOT ALLOWED IN GENERAL LIMITATION #9. |
| | SEE LAST PAGE OF NOA. |
| | |
| | 3- SEPARATE PERMITS REQUIRED TO REMOVE AND RE-INSTALL |
| | ALL ROOF EQUIPMENT. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |
| | |