| 2007-02-05 18:58:32 | BUILDING REVIEW CHECKLIST: |
| | 1- FLAT ROOF NOA 02-0212.07 SUBMITTEDIS MISSING THE |
| | SPECIFIC APPROVED ASSEMBLY TO BE INSTALLED AS REQUIRED |
| | BY CITY POLICY FOR ROOFING PERMITS. SEE ATTACHED COPY |
| | OF CITY POLICY. |
| | |
| | 2- IF SELECTED ASSEMBLY HAS MORE THAN ONE FASTENING |
| | OPTION FOR BASE SHEET, THEN CLEARLY IDENTIFYWHICH |
| | OPTION WILL BE USED.SEE ROOFING POLICY. |
| | |
| | 3- IF SELECTED ASSEMBLYIS LIMITED BY GENERAL |
| | LIMITATION #7, THEN NEED TO PROVIDERAS 117 |
| | CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND CORNER |
| | AREAS.NOA 02-0212.07 SUBMITTED REQUIRES CALCULATIONS |
| | TO BE DONE ONLY BY ARCHITECT, ENGINEER OR REGISTERED |
| | ROOFING CONSULTANT. SEE GENERAL LIMITATIONS ON LAST |
| | PAGE OF NOA. |
| | |
| | 4- IF SELECTED ASSEMBLY IS LIMITED BY GENERAL |
| | LIMITATION #9, THEN IT CAN'T BE INSTALLED IN THIS AREA |
| | BECAUSE NAIL ENHANCING IS NOT ALLOWED AND APPROVED |
| | ASSEMBLIES DON'T MEET THE DESIGN PRESSURES OF TABLE |
| | 1609.6.2.1(2). SEE GENERAL LIMITATIONS ON LAST PAGE OF |
| | THE NOA. |
| | |
| | 5- A) PERMIT APPLICATION SCOPE OF WORKDOESN'T INCLUDE |
| | THE SKYLIGHTS. INCLUDE THEM ONLY IF WORK IS TO REPLACE |
| | EXISTING SKYLIGHTS.NEW SKYLIGHTS ON NEW OPENINGS |
| | REQUIRE SEPARATE PERMIT BY PROPER CONTRACTOR. |
| | B) IF REPLACING SKYLIGHTS, THEN SPECIFY HOW MANY |
| | AND INCLUDE THEM IN TOTAL BUILDING VALUATION. IF |
| | DECLARE VALUATION IS TOO LOW, THEN IT WILL BE UPDATED |
| | AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC 2004. |
| | C) PROVIDE LEGIBLEDRAWINGS FOR THE SKYLIGHTS. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |