Plan Review Details - Permit 07020122
Plan Review Stops For Permit 07020122
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-07-18 Cont ID  
Sent By jgomez Date 2007-07-18 Time 14:55 Rev Time 0.00
Received By jgomez Date 2007-07-18 Time 14:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-06-11 Cont ID  
Sent By jgomez Date 2007-06-11 Time 15:07 Rev Time 0.00
Received By jgomez Date 2007-06-11 Time 15:05 Sent To M
Notes
2007-06-11 16:49:23BUILDING REVIEW SECOND CHECKLIST:
 1- BRING DRAWINGS TO PALM BEACH COUNTY (2300 N. JOG RD.
 (561)233-5115)TO VERIFY IF IMPACT FEES ARE DUE OR
 NOT.BRING BACKSTAMPED PLANS BY PALM BEACH COUNTY
 AND COPY OF PAID RECEIPT IF FEES ARE DUE.
  
 2- NEED RECORDED NOTICE OF COMMENCEMENT. SEE ATTACHED
 LEGAL FORM.
  
 3- SOIL TEST REPORT NEEDS TO HAVE ENGINEERING FIRM
 CERTIFICATE OF AUTHORIZATION NUMBER AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTE AND SEC. 61G15-23.002
 FLORIDA ADMINISTRATIVE CODE.
  
 4- SHEET 2:
 A) SPECIFY ALL LIVE AND DEAD LOADS, INCLUDING ATTIC
 LIVE LOADS,AS REQUIRED BY SEC. R301 AND TABLE R301.5
 OF 2004 FLORIDA RESIDENTIAL CODE (WITH 2006
 REVISIONS).
 ***CLARIFY WHY DEAD LOADS SPECIFIIED ON ROOF FRAMING
 PLAN ARE LARGER THAN THE LIVE LOADS. PROVIDE COMPLETE
 ENGINEERING ANALYSIS TO SHOW WHY THIS DESIGN CRITERIA
 WAS USED. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 B) TRUSS ANCHOR SCHEDULE IS CONFUSING.IS NOT CLEAR
 WHICH ARE CONNECTORS'A'AND WHICH ARE CONNECTORS
 'B'.THEY ARE SHOWN ON THE LEFT HAND SIDE, BUT
 CONNECTORS SPECIFIED ON THE PRODUCT CODE COLUMN DON'T
 SHOW ANY RELATION TO CONNECTOR 'A' OR 'B'.
 REVISE/CLARIFY AS REQUIRED. SEC. 106.1L.2 CITY
 AMENDMENTS TO FBC 2004.
  
 C)NUMBER OF FASTENERSAND LOADS SHOWN ON TRUSS
 ANCHOR SCHEDULE DON'T MATCH INFORMATION SHOWN ON
 PRODUCT APPROVAL SUBMITTED FOR THIS TYPE OF CONNECTORS.
 SEE PRODUCT APPROVAL AND REVISE AS REQUIRED. OTHERWISE,
 PROVIDE COMPLETE ENGINEERING ANALYSIS FOR NUMBER OF
 FASTENERS AND LOADS THAT DIFFER FROM THOSE TESTED AND
 PUBLISHED BY THE MANUFACTURER. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 D) HANDWRITTEN INFORMATION SHOWN ON VALLEY TRUSSES
 IS NOT CLEAR.SPECS : "TS12/W 7-8D TO THE THE TRUSS
 AND 7-8D TO EXISTINGEACH END END TYP" IS NOT CLEAR.
 REVISE AS REQUIRED OR PROVIDE CLEAR DETAIL. AND,
 HANDWRITTEN INFORMATION ON PLANS IS NOT ACCEPTABLE.
 REVISE INFORMATION ON ORIGINAL CAD DRAWING.
  
 E) REVISE PLYWOOD SHEATHING NAILING SCHEDULE. NEED
 MIN. 8D RING SHANK NAILS IN ALL ZONES. SEE SEC.
 R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE AND REVISE
 AS REQUIRED.
  
 F)INFORMATION ON ITEM 4(E)NEED TO MATCH
 INFORMATION ONTYPICAL WALL SEC.REVISE AS REQUIRED.
  
 G) INFORMATION FOR GABLE ENDS AND WOOD FRAME WALLS
 IS NOT CLEAR.CLARIFY ASREQUIRED OR OMIT TO AVOID
 CONFLICTS SINCE PROPOSED ROOF DOESN'T HAVE GABLE ENDS.
  
 H) SPECIFY CONNECTORSFOR WOOD TRUSSES RESTING ON
 EXISTING BEARING WALL.SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 5- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) ASPHALT SHINGLES. NOA 02-1209.10 SUBMITTED IS
 CLOSED BY DADE COUNTY. NEED TO PROVIDE CURRENT PRODUCT
 APPROVAL.
  
 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BYSEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 7- ENERGY CALCULATIONS:
 A) EXTERIORINSULATION VALUEDOESN'T MATCH
 INFORMATION ON PLANS. REVISE AS REQUIRED.
  
 B) SEE SURVEY FOR CORRECT HOUSE ORIENTATION AND
 REVISE AS REQUIRED.
  
 C) NUMBER OF AND SIZE OF WINDOWS DON'TMATCH PLANS.
 REVISE AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINE(561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-26 Cont ID  
Sent By jgomez Date 2007-03-26 Time 18:00 Rev Time 0.00
Received By jgomez Date 2007-03-26 Time 17:23 Sent To PC
Notes
2007-03-26 18:00:32BUILDING REVIEW CHECKLIST:
 1- BUILDING VALUATION DECLARED ON PERMIT APPLICATION IS
 TOO LOW.VALUE WAS UPDATED. OWES $630.39 FOR UPDATED
 VALUE AND RADON FEES.
  
 2- AFTER DRAWINGS ARE REVISED BRING THEM TO PALM BEACH
 COUNTY AT 2300 N. JOG RD TO PAY IMPACT FEES. BRING BACK
 STAMPED PLANS AND COPY OF PAID RECEIPT.
  
 3- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 4- PROVIDE SOIL TEST REPORT.
  
 5- SHEET 1:
 A) NORTH ARROW IN SITE PLAN IS POINTING TO THE WRONG
 DIRECTION. SEE SURVEY AND REVISE AS REQUIRED.
  
 B) FOUNDATION WALL DOESN'T SHOW VERTICAL
 REINFORCEMENT IN NORTH AND SOUTH WALL. PROVIDE
 ENGINEERING CALCULATIONS SHOWING WHY REINFORCEMENT IS
 NOT REQUIRED FOR LATERAL SUPPORT. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 C) FOUNDATION PLAN DOESN'T INDICATE WHICH COLUMN IS
 C-1 AND WHICH IS C-2.ALSO, CLARIFY IF COLUMN C-2 IS
 CONCRETE BLOCK WITH FILLED CELL OR TRUE CAST IN PLACE
 CONCRETE COLUMN.DRAWING SHOW CONCRETE BLOCK WITH
 FILLED CELL. WHILE SPECS CALL FOR CAST IN PLACE
 CONCRETE COLUMN. REVISE AS REQUIRED. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 D) CLARIFY SPECS FOR COLUMN C-1: IT'S NOT CLEAR WHY
 CALLING FOR DOWELS AT 4'-8" O.C. INTO EXISTING SLAB IF
 ALL THIS IS NEW CONSTRUCTION?
  
 E) NOTE #4 SAYS "NO A/C WITHIN THE SCOPE OF THIS
 PROJECT" BUT FLOOR PLAN ON SHEET 2 SPECIFIES A/C WORK.
 CLARIFY/REVISE AS REQUIRED.
  
 6- SHEET 2:
 A) SPECIFY ATTIC ACCESS AS REQUIRED BY SEC. R807 OF
 2004 FLORIDA RESIDENTIAL CODE.
  
 B) SPECIFY SAFETY GLASS FOR WINDOW IN SHOWER AREA.
 SEC. R308.4 OF 2004 FLORIDA RESIDENTIAL CODE.
 ***NOTE: SAFETY GLASS IS REQUIRED NEXT TO THE EXTERIOR
 DOOR IF WINDOW IS WITHIN 24" OF THE DOOR. SEE SEC.
 R308.4 ABOVE.
  
 C) SPECIFY ALL LIVE AND DEAD LOADS AS REQUIRED BY
 SEC. R301 OF 2004 FLORIDA RESIDENTIAL CODE AND TABLE
 R301.5.
  
 D) SECOND STRUCTURAL NOTE CALLS FOR 40' (FEET?) MIN.
 LENGTH FOR SPLICING. REVISE AS REQUIRED.
  
 E) SIMPSON CONNECTORS A AND B. SEE CURRENT CATALOG
 FOR SPECIFIC NUMBER OF FASTENERS TO BE USED. OTHERWISE,
 PROVIDE COMPLETE ENGINEERING ANALYSIS FOR FASTENERS
 THAT DIFFER FROM THOSE TESTED AND PUBLISHED BY THE
 MANUFACTURER. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 F) REVISE PLYWOOD SHEATHING NAILING SCHEDULE AND
 ASTERISK NOTE. SEE SEC. R803.2.3.1OF 2004 FLORIDA
 RESIDENTIAL CODE AND REVISE AS REQUIRED.
  
 G) REVISE ROOF SKETCH SHOWING ROOF ZONES. SEE FIGURE
 R301.2(8) OF 2004 FLORIDA RESIDENTIAL CODE FOR CORRECT
 ZONES ON HIP ROOF.
 ***NOTE: SPECIFY DIMENSION A FOR WITH OF ZONES THAT
 APPLY TO THIS PROJECT.SEC. R301 2004 FLORIDA
 RESIDENTIAL CODE.
  
 H) ANCHOR VALLEY TRUSSES.THESE TRUSSES ARE
 DESIGNED WITH CONTINUOUS UPLIFT LOADS AT BOTTOM CHORD,
 NOT AT THE ENDS OF TRUSS. SEE TRUSS DRAWINGS AND REVISE
 CONNECTORS AS REQUIRED. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 7- SHEET 3:
 A) PROVIDE ACTUAL CALCULATIONS FOR DESIGN PRESSURES
 AT DOORS AND WINDOWS. SOME OF THESE OPENINGS ARE
 LOCATED ON END ZONES, THEREFORE DESIGN PRESSURES ARE
 HIGHER. SEE TABLER301.2(2) OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 B) DESIGN CERTIFICATION FOR BUILDING CODE COMPLIANCE
 INFORMATION NEEDS TO BE UPDATED:
 * CODE EDITION 2004 FLORIDA RESIDENTIAL CODE AND
 2004 FBC.
 ** ASCE 7-02, NOT ASCE 7-98.
 *** SPECIFY BUILDING EXPOSURE. SEE SEC. R301 OF 2004
 FLORIDA RESIDENTIAL CODE.
 **** SOIL BEARING CAPACITY: EXISTING?
 ***** IMPACT PROTECTION. THERE IS NOT IMPACT GLASS
 SPECIFIED ON PLANS.
  
 8- SHEET 4:
 A) ALL DRAWINGS AND SPECIFICATIONS FOR STRUCTURAL
 BUCK DETAILS AT DOORS AND WINDOWS TO MATCH. SEE ANCHOR
 TYPE AND SPACING.
  
 B) SEE SEC. R613.6.2 OF 2004 FLORIDA RESIDENTIAL
 CODE FOR PROPER WAY OF INSTALLING STRUCTURAL BUCKS.
 BUCKS NEED TO PROVIDE COMPLETE SUPPORT OF WINDOW/DOOR
 FRAME.
  
 C) TYPICAL WALL SECTION:
 * REVISE ROOF SHEATHING SPECS.
 ** THERE IS NO SUPPORT SHOWN TO RECEIVE THE PLYWOOD
 SOFFIT.
 *** CLARIFY SPECS FOR 2X4 SUB FASCIA. FASTEN
 W/12-16D NAILS?
 **** SPECIFY FIREBLOCKING AS REQUIRED BY SEC.
 R602.1.2 OF 2004 FLORIDA RESIDENTIAL CODE.
 ***** REVISE NOTE REGARDING #5 EMBEDEMNT ON EXISTING
 SLAB. THIS IS ALL NEW CONSTRUCTION.
  
 9- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) EXTERIOR DOOR THAT MEETS THE DESIGN PRESSURES
 CALCULATED ON PLANS. . CHECK DESIGN PRESSURES AFTER
 DESIGN PRESSURES ARE REVISED ON PLANS.
  
 B) ASPHALT SHINGLES. NOA #02-1209.10 SUBMITTED FILE
 IS CLOSED. SEE ATTACHED COPY OF DADE COUNTY WEBSITE.
  
 C) SINGLE HUNG WINDOW NOA #02-0604.03 SUBMITTED FILE
 IS CLOSED ALSO.
  
 D) WINDOW MULLIONS.
  
 E) TRUSS STRUCTURAL CONNECTORS SPECIFIED ON PLANS.
  
 10- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 11- STORM SHUTTERS. PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE OF INSTALLATION SCHEDULE.
 ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 PRODUCT APPROVAL.
  
 12- ENERGY CALCULATIONS:
 A) NEED TO USE 2004 FORM.
  
 B) SLAB ON GRADE INSULATION AND TOTAL PERIMETER
 DIMENSION AREWRONG. REVISE AS REQUIRED. SEE PLANS.
  
 C) MINIMUM SEER REQUIRED IS 13. REVISE AS REQUIRED.
  
 D) SEE SURVEY FOR CORRECT HOUSE CARDINAL ORIENTATION
 AND REVISE AS REQUIRED.
  
 E) OVERHANG HEIGHT AND LENGTH IS INCORRECT. REVISE
 AS REQUIRED.
  
 F) WALL EXTERIOR INSULATION IS WRONG. SEE PLANS AND
 REVISE AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-07-17 Cont ID  
Sent By btrobaug Date 2007-07-17 Time 10:21 Rev Time 0.00
Received By btrobaug Date 2007-07-17 Time 07:55 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-06-01 Cont ID  
Sent By btrobaug Date 2007-06-01 Time 16:12 Rev Time 0.50
Received By btrobaug Date 2007-06-01 Time 15:47 Sent To P
Notes
2007-06-01 16:12:29 
 DENIED/INCOMPLETE INFORMATION
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE FEEDER TO PANEL 'B' IS LISTED AS #4 IN PANEL
 "A", AND SHOWN AS #1 ON THE RISER. CORRELATE SAME.
  
 2} INDICATE WHAT "WT" MEANS LISTED AFTER THE LOADS.
  
 3} THE AIR HANDLER LOCATED IN THE CLOSET, HAVING
 OVERCURRENT PROTECTION BUILT IN, IS IN VIOLATION OF
 240.24(B), 2005NEC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-06 Cont ID  
Sent By btrobaug Date 2007-03-06 Time 15:02 Rev Time 1.00
Received By btrobaug Date 2007-03-06 Time 14:01 Sent To M
Notes
2007-03-06 15:02:37 
  
 DENIED/INCOMPLETE INFORMATION
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PROVIDE A LOAD CALCULATION FOR THE ELECTRICAL
 SERVICE, INDICATING ALL EXISTING LOADS AND ALL LOADS TO
 BE IMPOSED BY THE ADDITION OF THE NEW EQUIPMENT. 215.5
 NEC 2005.
  
 2} SUBMIT A PANEL SCHEDULE PER 408.4 NEC AND
 106.3.5.4(8) FBC.
  
 3} THE AIR HANDLER LOCATED IN THE CLOSET, HAVING
 OVERCURRENT PROTECTION BUILT IN, IS IN VIOLATION OF
 240.24(B), 2005NEC.
  
 4} SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14,RECEPTACLE PER 210.63, FOR THE CONDENSING
 UNIT.
  
 5} A SMOKE ALARM MUST BE LOCATED OUTSIDE THE "NEW
 FLORIDA ROOM" , A SLEEPING AREA BY DEFINITION.THE ONE
 SHOWN IN THE HALL IS NOT "OUTSIDE, AS IT IS IN THE SAME
 AREA WITH THE DOOR SHUT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-07-12 Cont ID  
Sent By adarroug Date 2007-07-12 Time 10:25 Rev Time 0.00
Received By adarroug Date 2007-07-12 Time 10:25 Sent To Z
Notes
2007-07-12 10:26:12TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-06-01 Cont ID  
Sent By adarroug Date 2007-06-01 Time 08:33 Rev Time 0.00
Received By adarroug Date 2007-06-01 Time 08:33 Sent To E
Notes
2007-06-01 08:34:07TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-05-22 Cont ID  
Sent By adarroug Date 2007-05-22 Time 11:40 Rev Time 0.00
Received By adarroug Date 2007-05-22 Time 11:40 Sent To Z
Notes
2007-05-22 11:40:55TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-02-22 Cont ID  
Sent By adarroug Date 2007-02-22 Time 14:03 Rev Time 0.00
Received By adarroug Date 2007-02-22 Time 14:03 Sent To E
Notes
2007-02-22 14:03:38TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-15 Cont ID  
Sent By adarroug Date 2007-02-15 Time 11:10 Rev Time 0.00
Received By adarroug Date 2007-02-15 Time 11:10 Sent To Z
Notes
2007-02-15 11:11:03TO "Z" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-26 Cont ID  
Sent By jgomez Date 2007-03-26 Time 18:00 Rev Time 0.00
Received By jgomez Date 2007-02-06 Time 14:38 Sent To  
Notes
2007-02-06 14:38:40TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-07-18 Cont ID  
Sent By tgordon Date 2007-07-18 Time 16:10 Rev Time 0.20
Received By tgordon Date 2007-07-18 Time 16:10 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-06-13 Cont ID  
Sent By tgordon Date 2007-06-13 Time 08:13 Rev Time 0.25
Received By tgordon Date 2007-06-13 Time 08:13 Sent To P
Notes
2007-06-13 08:15:10*** DENIED ***
 1) SEE BUILDING REVIEW NOTE #7 A), PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-03-07 Cont ID  
Sent By tgordon Date 2007-03-07 Time 13:48 Rev Time 0.25
Received By tgordon Date 2007-03-07 Time 13:48 Sent To P
Notes
2007-03-07 14:10:33*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON FORM 600A-04R
 (2004) PER FBC 13-600.3.A .
  
 2) SEE A/CPLAN PAGE 2 OF 4 EQUIPMENT SCHEDULE, "SEE"
 DO YOU MEAN SEER IF SO THE MINIMUM SEER THAT MAY BE
 INSTALLED IS 13 SEER, SEE 2004 FBC 13-607.1.ABC.3.2.1.
 PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-07-26 Cont ID  
Sent By mperson Date 2007-07-26 Time 13:19 Rev Time 0.10
Received By mperson Date 2007-07-26 Time 13:19 Sent To  
Notes
2007-07-26 13:20:47NOTE: RESTAMP NEW SHEET, NO PLUMBING CHANGES.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-07-18 Cont ID  
Sent By mperson Date 2007-07-18 Time 15:41 Rev Time 0.00
Received By mperson Date 2007-07-18 Time 15:41 Sent To M
Notes
2007-07-18 15:43:12NOTE: PLUMBING PERMIT REQUIRED FOR SCOPE OF WORK.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-06-15 Cont ID  
Sent By mperson Date 2007-06-15 Time 13:37 Rev Time 0.33
Received By mperson Date 2007-06-15 Time 13:37 Sent To PC
Notes
2007-06-15 13:38:49NOTE: PLUMBING PERMIT REQUIRED FOR SCOPE OF WORK.

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-03-08 Cont ID  
Sent By mperson Date 2007-03-08 Time 10:31 Rev Time 0.33
Received By mperson Date 2007-03-08 Time 10:31 Sent To B
Notes
2007-03-08 10:42:16DENIED
 REFERENCE: FBC-2004 PLUMBING
  
 THE FOLLOWING CORRECTION IS REQUIRED FOR PLUMBING PLAN
 REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET 4 OF 4 ISOMETRIC SANITARY RISER DIAGRAM: PER
 FBC-2004 PLUMBING, SECTION 1002.1 A FIXTURE SHALL NOT
 BE DOUBLE TRAPPED. THE WATER CLOSET HAS AN INTEGRAL
 TRAP AND DOES NOT REQUIRE A TRAP. PLEASE DELETE THE
 TRAP FOR THE WATER CLOSET ON THE RESUBMITTAL.
  
 IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 4 Status P Date 2007-07-26 Cont ID  
Sent By adavila Date 2007-07-26 Time 14:03 Rev Time 0.00
Received By adavila Date 2007-07-26 Time 14:03 Sent To  
Notes
2007-07-26 14:03:44PER ERIC SCHNEIDER, PRINCIPAL PLANNER

Review Stop Z ZONING
Rev No 3 Status F Date 2007-07-12 Cont ID  
Sent By adavila Date 2007-07-12 Time 16:29 Rev Time 0.00
Received By adavila Date 2007-07-12 Time 15:25 Sent To  
Notes
2007-07-19 14:11:40NEW COMMENT
  
 1.PLEASE NOTE THAT THE SURVEY AND THE SITE PLAN SHALL
 SHOW SAME CONDITIONS.WIDTH AND DEPTH DIMENSIONS OF
 THE PROPOSED ADDITION ON THE FLOOR PLAN AND SITE PLAN,
 SHALL MATCH THE DIMENSIONS SHOWN ON THE SURVEY.
2007-07-12 16:29:48PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. PROVIDE RESPONSE TO COMMENTS IN WRITING.
  
 2. SETBACK DIMENSIONS OF THE EXISTING SHED ON THE
 SURVEY AND SITE PLAN DO NOT MATCH.SURVEY AND SITE
 PLAN SHALL REFLECT ACTUAL CONDITIONS (REPEAT COMMENT).
 A. ACCORDING TO THE SURVEY, THE EXISTING SHED IS 9 FEET
 FROM THE METAL FENCE, AND NOT FROM THE PROPERTY LINE.
 SIDE SETBACK DIMENSION SHALL BE REVISED ON THE SITE
 PLAN.
 B. ACCORDING TO THE SURVEY, THE EXISTING SHED IS 13.9
 FEET FROM THE CONCRETE WALL AND NOT FROM THE PROPERTY
 LINE.REAR SETBACK DIMENSION SHALL BE REVISED ON THE
 SITE PLAN.
  
 3. PROVIDE REAR SETBACK DIMENSION FROM THE PROPERTY
 LINE TO THE EXISTING SHED ON THE SITE PLAN (REPEAT
 COMMENT).
 A. PLEASE NOTE THAT THE SURVEY SHOWS REAR SETBACK
 DIMENSION FROM THE SHED TO THE CONCRETE WALL AND NOT
 THE PROPERTY LINE (REPEAT COMMENT).
  
 4. ACCORDING TO THE SURVEY, THE PROPOSED ADDITION HAS A
 REAR SETBACK OF 29.4 FEET; HOWEVER, ACCORDING TO THE
 SITE PLAN THE PROPOSED ADDITION HAS A REAR SETBACK OF
 34.6 FEET (29.4 + 5.2).REAR SETBACK DIMENSION OF THE
 PROPOSED ADDITION SHALL BE REVISED ON THE SITE PLAN.
  
 5. PROVIDE BUILDING HEIGHT DIMENSIONS ON SHEET 3 FROM
 GRADE TO THE MID POINT BETWEEN THE RIDGE AND THE EVE OF
 THE PROPOSED ROOF (REPEAT COMMENT).
  
 6. PROVIDE BUILDING HEIGHT DIMENSIONS ON SHEET 3 FROM
 GRADE TO THE TOP OF THE ROOF RIDGE.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-05-25 Cont ID  
Sent By adavila Date 2007-05-25 Time 12:07 Rev Time 0.00
Received By adavila Date 2007-05-23 Time 15:40 Sent To I
Notes
2007-05-25 12:12:47PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1.SETBACK DIMENSIONS OF THE EXISTING SHED ON THE
 SURVEY AND SITE PLAN DO NOT MATCH.SURVEY AND SITE
 PLAN SHALL REFLECT ACTUAL DIMENSIONS.
  
 2.PROVIDE REAR SETBACK DIMENSION FROM THE PROPERTY
 LINE TO THE EXISTING SHED ON THE SITE PLAN.
 A.PLEASE NOTE THAT THE SURVEY SHOWS REAR SETBACK
 DIMENSION FROM THE SHED TO THE CONCRETE WALL AND NOT
 THE PROPERTY LINE.
  
 3.PROVIDE BUILDING HEIGHT DIMENSIONS ON SHEET 3 OF 4
 FROM GRADE TO THE MID POINT BETWEEN THE RIDGE AND THE
 EVE OF THE PROPOSED ROOF.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-02-14 Cont ID  
Sent By adavila Date 2007-02-14 Time 11:58 Rev Time 0.00
Received By adavila Date 2007-02-13 Time 17:56 Sent To I
Notes
2007-02-14 11:58:29PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. PLEASE PROVIDE RESPONSE TO COMMENTS IN WRITING.
  
 2. PROVIDE TWO (2) SIGNED AND SEALED SURVEYS.THE
 SURVEY SHALL BE LESS THAN A YEAR OLD.
  
 3. PROVIDE DIMENSION BETWEEN PROPOSED ADDITION AND
 EXISTING STORAGE BUILDING.
  
 4. PROVIDE ALL SETBACK DIMENSIONS ON THE SITE PLAN.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.