| 2007-03-14 11:31:21 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | 1.)THE PLAN STATES THAT THE DAMAGE IS 6' NORTH FROM |
| | COMMON LINE OF BUILDINGS, ENGINEER'S NOTES 2, SHEET 1. |
| | WERE FIRE RATED WALLS AFFECTED?FROM THE WRITTEN |
| | DESCRIPTION IT DOES NOT APPEAR TO BE AT THE WALL |
| | SEPARATING THE BUILDINGS, BUT THE ELEVATION ON SHEET 1 |
| | SHOWS THE DAMAGE AT A CORNER/WALL.THE EXISTING FLOOR |
| | PLAN SHOWS THIS CORNER AS A TENANT SEPARATION.IF A |
| | FIRE RATED WALL WAS AFFECTED, PROVIDE A DETAIL FOR |
| | REPAIR SHOWING FIRE RATING REQUIREMENT (TENANT OR |
| | OCCUPANCY SEPARATION OR OTHER FIRE RATING REQUIRED BY |
| | FBC CHAPTER 5 OR FBC CHAPTER 6) AND COMPLIANCE WITH |
| | EITHER A TESTED ASSEMBLY OR CALCULATED FIRE RESISTANCE, |
| | FBC CHAPTER 9. |
| | |
| | 2.)NEW SHEETS WERE SUBMITTED.IT IS NOT CLEAR WHY AN |
| | EXISTING BUILDING PLANS WERE SUBMITTED, ESPECIALLY AS |
| | ONE OF THE SHEETS IS ILLEGIBLE.PLEASE SHOW LOCATION |
| | OF THE REPAIR ON THESE SHEETS, ALTHOUGH IT IS NOT CLEAR |
| | WHY ELECTRIC SHEETS ARE SUBMITTED. |
| | |
| | 3.)THE PROJECT DESCRIPTON STATES THAT THE WINDOWS |
| | WILL BE REPLACED.NO PRODUCT APPROVALS SUBMITTED.ANY |
| | PRODUCT APPROVALS NOT REVIEWED PRIOR TO PERMIT ISSUANCE |
| | WILL REQUIRE SEPARATE PERMITS.PRODUCT APPROVALS ARE |
| | TO BE REVIEWED BY DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL,FBC*106.3.3. |