Plan Review Details - Permit 07020102
Plan Review Stops For Permit 07020102
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-09-26 Cont ID  
Sent By jwitmer Date 2007-09-26 Time 16:43 Rev Time 0.55
Received By jwitmer Date 2007-09-26 Time 16:42 Sent To B
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-07-20 Cont ID  
Sent By jwitmer Date 2007-07-20 Time 11:53 Rev Time 0.77
Received By jwitmer Date 2007-07-20 Time 11:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-06-05 Cont ID  
Sent By jwitmer Date 2007-06-05 Time 15:22 Rev Time 2.22
Received By jwitmer Date 2007-06-05 Time 15:22 Sent To PC
Notes
2007-06-05 15:34:08BUILDING PLAN REVIEW
 PERMIT: 07020102
 ADD: 6810 GEORGIA AV
 CONT: GREAT AMERICAN REALITY
 TEL: (561)628-5465
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) COMPLIED.
  
 4)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WILL BEISSUED. PLEASE ADD THE FOLLOWING
 NOTE;
 NOTE 2004/2006 REVISIONS EXISTING BUILDING CODE.
 CHAPTER 9 ADDITIONS
 B) COMPLIED.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601. CODE IS A MINIMUM BUILD
 TYPE VB
 D) COMPLIED
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.NO
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.NO
  
 5) COMPLIED.
  
 6) SHEET# 4 IS INDICATING THE WRONG EDITION OF THE OF
 ASCE 7-02 IS WHAT IS REFRENENCED UNDER THE 2004/2006
 FBC.
  
 7) MULE HIDE ROOFING :) THIS ROOF IS MISSING OR NOT
 IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 _X__ THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE _3__ .ZONE 3 REQUIRES -89.0
  
 _X__ THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 8) SHEET # 2 INDICATES A FAN ON THE PROPERTY LINE .
 0-3'-0" NO OPENINGS ARE ALLOWED INTHE WALL TABLE 602.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-12 Cont ID  
Sent By jwitmer Date 2007-03-12 Time 12:29 Rev Time 1.22
Received By jwitmer Date 2007-03-12 Time 12:29 Sent To  
Notes
2007-03-12 12:45:42BUILDING PLAN REVIEW
 PERMIT: 07020102
 ADD: 6810 GEORGIA AV
 CONT: GREAT AMERICAN REALITY
 TEL: (561)628-5465
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)FBC 1802.2.1 QUESTIONABLE SOILS,
 1802.2.1 QUESTIONABLE SOIL.
 WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE A LOAD-BEARING
 VALUE SUPERIOR TO THAT SPECIFIED IN THIS CODE IS
 CLAIMED, THE BUILDING OFFICIAL SHALL
 REQUIRE THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY
 WITH THE PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6
 .
  
 4)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 NOTE 2004/2006 REVISIONS EXISTING BUILDING CODE.
 CHAPTER 9 ADDITIONS
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 5) SHEET# 4 IS MISSING SIGNATURE AND SEAL.
 PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 6) SHEET# 4 IS MISSING WHICH ADDITION OF ASCE 7-XX?
  
 7)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 8)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 9) FLEMING DOOR REPORT PROVIDE THE FLORIDA COVERSHEET,
 ALSO HIGHLIGHT WHICH DOOR APPLICATION WILL BE
 INSTALLED.
  
 10) BEST DOORS PROVIDE FLORIDA COVER SHEET.
  
 MULE-HIDE REQUIRES FL COVERSHEET HIGHLIGHT WHICH
 SUBSYSTEM SHALL BE INSTALLED ON THE STRUCTURE, NOTE
 THE
 PRESSURES, NOTE IF LIMITATION IS REFRENCED A LICENSED
 ARCHITECT OR ENGINEER SHALL PROVIDE THE SEALED
 CALCULATIONS FOR RAS 117, IF LIMITATION NOTE NUMBER
 NINE APPEARS THERE IS NO ENHANCED FASTENING ALLOWED.
  
 11) IT APPEARS THERE IS A LOVER ON THE BACK OF THE
 BUILDING, 0-3' NO OPENINGS ALLOWED.TABLE 704.8.
  
 12)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-06-23 Cont ID  
Sent By dpalmer Date 2007-06-23 Time 15:55 Rev Time 0.00
Received By dpalmer Date 2007-06-23 Time 15:51 Sent To  
Notes
2007-06-23 15:55:24ELEC OK, STAMPED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-04-08 Cont ID  
Sent By dpalmer Date 2007-04-08 Time 09:11 Rev Time 0.00
Received By dpalmer Date 2007-04-08 Time 08:23 Sent To  
Notes
2007-04-08 09:11:44** UNSAT **
  
 1) NOTE: PLEASE SEE THE PANEL SCHEDULE HAS NOW BEEN
 SUBMITTED THE NEW CIRCUITS AND OTHERS APPEAR TO BE
 EXISTING HOWEVER REVISED LOAD CALCULATIONS WAS NOT DONE
 FOR EXISTING LOADS AND NEW LOADS BEING ADDED. PLEASE
 SEE THE .25VA PER SQFT BEING SHOWN FOR COMPLETE NEW
 LOADS IS NOT CORRECT AT THIS TIME.
 PLEASE SEE 220.12 AS THIS LOAD IS ONLY FOR THE LIGHTING
 LOADS WHEN NO SPECIFIC LOADS ARE KNOWN.
 PLEASE SEE THE LOADS WHICH ARE TO BE FIGURED FOR ANY
 RECEPTACLES LOADS ARE TO BE BASED ON 220.14I. PLEASE
 SEE THIS IS A MINIMUM OF 180VA FOR EACH KNOWN
 DEVICE/YOKE.
 PLEASE SEE THE PLANS DO CONTAIN THE SPECIFIC NUMBER OF
 DEVICES. PLEASE ALSO SEE THE SPECIFIC LOADS SUCH AS THE
 GARAGE DOOR WHICH IS A MOTOR LOAD MAY NOT FIGURED INTO
 THE .25VA FOR LIGHTS.
 PLEASE SEE PLANS NOW ALSO CONTAIN A NEW EXHAUST FAN
 WHICH ALSO CAN NOT BE FIGURED INTO THE GENERAL LIGHT
 LOADS.
  
 PLEASE SEE 220, 430 OF THE NEC AND PLEASE ADJUST AND
 REVISE.
  
 2) NOTE: PLEASE SEE BOTH SETS OF THE ARCHITECTURAL
 SHEETS ARE SIGNED AND DATED, HOWEVER DO NOT CONTAIN A
 RAISED SEAL ON ANY SHEET IN EITHER SET.
 FS 481.221
  
 3) NOTE: PLEASE SEE THE LOCATION OF THE NEW EXHAUST FAN
 IS IN QUESTION AS IT SEEM TO BE ON THE WALL WHICH ABUTS
 UP TO THE SOUTH WALL WHICH IS ALSO ADJACENT TO THE
 OTHER WALL OF THE BUILDING WHICH IS ON ANOTHER
 PROPERTY?
 PLEASE SEE THIS ISSUE MAY COME UP AS EXHAUSTING OVER
 THE PROPERTY LINE AND AS SHOWN IS INTO THE BUILDING
 NEXT DOOR.
 ** PLEASE SEE NOTES FROM MECHANCIAL AND BUILDING
 REVIEWER.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-02-14 Cont ID  
Sent By dpalmer Date 2007-02-14 Time 15:16 Rev Time 0.00
Received By dpalmer Date 2007-02-14 Time 13:04 Sent To  
Notes
2007-02-14 15:18:20**** UNSAT ****
  
 1) NOTE: PLEASE SEE BUILDING REVIEW COMMENTS WITH
 RESPECT TO THE REAR OF BUILDING AND RELATIVE LOCATION
 OF THE PROPERTY LINE AND FEC.
  
 2) NOTE: PLEASE SEE BUILDING REVIEW COMMENTS WITH
 RESPECT TO PALM BEACH COUNTY IMPACT FEES REQUIRED FOR
 ADDITION.
  
 3) NOTE: PLEASE SEE LANDSCAPE PLANS WHICH IS MISSING
 REQUIRED INFORMATION IN TITLE BLOCK(S) PER FAC
 61G1-16.004 AND FLORIDA STATUTES 481.219. PLEASE SEE
 THE MISSING " CERTIFICATE OF AUTHORIZATION* NUMBER. IF
 THERE ARE ANY QUESTIONS ON THIS PLEASE DO NOT HESITATE
 IN CONTACTING THIS OFFICE.
  
 4) NOTE: PLEASE SEE NOTE ON PLANS MENTIONS THE EM/ EXT
 LTS ARE GOING TO BE WIRED AHEAD OF THE NORMAL LIGHTING
 BRANCH CIRCUIT; HOWEVER THE CIRCUITS AS SHOWN ON THE
 PLANS DO NOT CORRELATE WITH THIS. THEY ARE ACTUALLY
 SHOWING TWO SEPARATE CIRCUITS.
 PLEASE SEE 700.12E.
  
 5) NOTE: PLEASE PROVIDE THE UPDATE PANEL SCHEDULE AND
 LOADS BEING INCREASED ON THE EXISTING PANEL WITH THE
 EXISTING LOADS. PLEASE INDICATE THE CONDUCTOR SIZES
 WITH THE OVER CURRENT PROTECTION FOR BREAKERS. 215.5,
 220, 310.16, 240.4,ETC.
 106.3.5.1.2, 106.1.2 ADMIN SECTION OF THE FBC.
  
 6) NOTE: PLEASE KNOW THAT AS OF DECEMBER 8TH, 2006 THE
 STATE OF FLORIDA ADOPTED THE 2006 REVISIONS TO THE 2004
 FBC AND THE 2005 NFPA-70.
 PLEASE KNOW THAT THIS ADDITION AND PLANS ARE REQUIRED
 TO STATE THESE CODES AT A MINIMUM AND SHALL ALSO BE
 DESIGNED UNDER ANY NEW CODES.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-07-23 Cont ID  
Sent By mawillia Date 2007-07-23 Time 15:02 Rev Time 0.00
Received By mawillia Date 2007-07-23 Time 13:07 Sent To  
Notes
2007-07-23 14:43:02*****PROVISO*****
  
 **STRUCTURES UNDERGOING CONSTRUCTION. ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 **THE ERECTING AND (OR) INSTALLATION OF THE STORAGE
 ADDITION SHALL NOT INTERFERE OR HINDER EMERGENCY ACCESS
 TO THE PROPERTY OR VICINITY THEREOF (INCLUDING FIRE
 LANES).
  
 **COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE (ON THE PLANS) EACH COMMENT
 WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-05-08 Cont ID  
Sent By mawillia Date 2007-05-08 Time 12:33 Rev Time 0.00
Received By mawillia Date 2007-05-08 Time 12:06 Sent To  
Notes
2007-05-08 12:33:47*****DENIED*****
  
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEEDS TO BE ADDRESSED:
  
  
 2.STRUCTURES UNDERGOING CONSTRUCTION. ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.THE ERECTING AND (OR) INSTALLATION OF THE STORAGE
 ADDITION SHALL NOT INTERFERE OR HINDER EMERGENCY ACCESS
 TO THE PROPERTY OR VICINITY THEREOF (INCLUDING FIRE
 LANES).
  
 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE (ON THE PLANS) EACH COMMENT
 WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-03-20 Cont ID  
Sent By mawillia Date 2007-03-20 Time 12:45 Rev Time 0.00
Received By mawillia Date 2007-03-20 Time 12:02 Sent To  
Notes
2007-03-20 12:44:58*****DENIED*****
  
  
  
 1.NFPA 101- 2003 EDITION SHALL BE REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION. ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.THE ERECTING AND (OR) INSTALLATION OF THE STORAGE
 ADDITION SHALL NOT INTERFERE OR HINDER EMERGENCY ACCESS
 TO THE PROPERTY OR VICINITY THEREOF (INCLUDING FIRE
 LANES).
  
 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 5.INDICATE THE CLASSIFICATION OF CONTENT TO BE STORED
 AS LOW HAZARD, INTERMEDIATE HAZARD, OR HIGH HAZARD
 DEPENDING ON THE CHARACTER OF THE MATERIALS STORED,
 THEIR PACKAGING, AND OTHER FACTORS.
  
 6.PROVIDE THE OCCUPANT LOAD OR MAXIMUM PROBABLE
 POPULATION FOR THIS SPACE UNDER CONSIDERATION.
  
 7.PROVIDE THE INTERIOR WALL AND CEILING
 CLASSIFICATION.PLEASE BE ADVISED THAT CLASS A, CLASS
 B, OR CLASS C SHALL BE REQUIRED FOR STORAGE AREAS AND
 EXIT ENCLOSURES.PLEASE SPECIFY WHICH CLASSIFICATION.
  
 8.WILL THE STRUCTURE HAVE A FIRE SPRINKLER AND (OR)
 FIRE ALARM SYSTEM?
  
 9.ALTHOUGH NOT REQUIRED BY NFPA 101, IT IS
 RECOMMENDED BY WEST PALM BEACH FIRE PREVENTION THAT AT
 LEAST ONE 2A:10BC FIRE EXTINGUISHER BE INSTALLED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE (ON THE PLANS) EACH COMMENT
 WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-10-31 Cont ID  
Sent By adarroug Date 2007-10-31 Time 16:26 Rev Time 0.00
Received By adarroug Date 2007-10-31 Time 16:26 Sent To B
Notes
2007-10-31 16:26:46TO "JWITMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-09-18 Cont ID  
Sent By adarroug Date 2007-09-18 Time 15:44 Rev Time 0.00
Received By adarroug Date 2007-09-18 Time 15:44 Sent To B
Notes
2007-09-18 15:45:02TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-09-18 Cont ID  
Sent By adarroug Date 2007-09-18 Time 15:43 Rev Time 0.00
Received By adarroug Date 2007-09-18 Time 15:43 Sent To B
Notes
2007-09-18 15:43:23TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-06-12 Cont ID  
Sent By adarroug Date 2007-06-12 Time 08:37 Rev Time 0.00
Received By adarroug Date 2007-06-12 Time 08:37 Sent To  
Notes
2007-06-22 16:43:08TO "COMM" BD#48
2007-06-12 08:40:05WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-02 Cont ID  
Sent By lfranco Date 2007-04-19 Time 19:20 Rev Time 0.00
Received By spalmer Date 2007-04-02 Time 17:30 Sent To  
Notes
2007-04-02 18:13:32TO COMM BOARD # 25
2007-04-02 17:30:56WAITING FOR COMM BOARD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-20 Cont ID  
Sent By mawillia Date 2007-03-20 Time 12:07 Rev Time 0.00
Received By mawillia Date 2007-02-06 Time 08:33 Sent To  
Notes
2007-02-13 14:36:24TO "COMM" BD#28
2007-02-06 08:33:38WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2007-06-27 Cont ID  
Sent By tgordon Date 2007-06-27 Time 12:03 Rev Time 0.20
Received By tgordon Date 2007-06-27 Time 12:03 Sent To  
Notes
2007-06-27 12:04:10NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-06-27 Cont ID  
Sent By tgordon Date 2007-05-02 Time 14:20 Rev Time 0.25
Received By tgordon Date 2007-05-02 Time 14:20 Sent To  
Notes
2007-05-02 14:34:09*** DENIED ***
 1) THE ARCHITECT WHO'S INFORMATION IS IN THE TITLE
 BLOCK MUST SEAL THE PLANS. SEE FAC 61G1-16.003 SEAL,
 SIGNATURE AND DATE SHALL BE AFFIXED.
  
 2) PLANS PAGE 2 SHOW AN EXHAUST FAN ON THE SOUTH WALL
 NEXT TO ANOTHER BUILDING ON A ZERO LOT LINE, SEE 2004
 FBC/M 502.7.3.6. PLEASE CORRECT.
  
 ** 2004 FBC/M 502.7.3.6 TERMINATION POINT.
 THE TERMINATION POINT FOR EXHAUST DUCTS DISCHARGING TO
 THE ATMOSPHERE SHALL BE LOCATED WITH THE FOLLOWING
 MINIMUM DISTANCES.
 1.FOR DUCTS CONVEYING EXPLOSIVE OR FLAMMABLE
 VAPORS, FUMES OR DUSTS: 30 FEET (9144 MM) FROM THE
 PROPERTY LINE; 10 FEET (3048 MM) FROM OPENINGS INTO THE
 BUILDING; 6 FEET (1829 MM) FROM EXTERIOR WALLS AND
 ROOFS; 30 FEET (9144 MM) FROM COMBUSTIBLE WALLS AND
 OPENINGS INTO THE BUILDING WHICH ARE IN THE DIRECTION
 OF THE EXHAUST DISCHARGE; 10 FEET (3048 MM) ABOVE
 ADJOINING GRADE.
 2.FOR OTHER PRODUCT-CONVEYING OUTLETS: 10 FEET
 (3048 MM) FROM THE PROPERTY LINE; 3 FEET (914 MM) FROM
 EXTERIOR WALLS AND ROOFS; 10 FEET (3048 MM) FROM
 OPENINGS INTO THE BUILDING; 10 FEET (3048 MM) ABOVE
 ADJOINING GRADE.
 3.FOR ENVIRONMENTAL AIR DUCT EXHAUST: 3 FEET (914
 MM) FROM THE PROPERTY LINE; 3 FEET (914 MM) FROM
 OPENINGS INTO THE BUILDING.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2007-04-19 Cont ID  
Sent By lfranco Date 2007-04-19 Time 19:20 Rev Time 0.00
Received By lfranco Date 2007-04-19 Time 19:19 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2007-02-23 Cont ID  
Sent By lfranco Date 2007-02-23 Time 18:50 Rev Time 0.00
Received By lfranco Date 2007-02-23 Time 18:49 Sent To I
Notes
***NONE***