Plan Review Details - Permit 07020094
Plan Review Stops For Permit 07020094
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-02-13 Cont ID  
Sent By mjacobs Date 2007-02-13 Time 06:59 Rev Time 0.00
Received By mjacobs Date 2007-02-13 Time 05:57 Sent To  
Notes
2007-02-13 06:25:48BUILDING PLAN REVIEW
 PERMIT:07020094
 ADD:1101 CHARLES STREET
 CONT: LANCE H. MOONEY
 TEL: (561)747-4643
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 2)) 106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE RGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. PROVIDE TWO COPIES OF THE
 PRODUCT APPROVALS FOR THE NEW DOOR.
  
 3)FBC. 1210.2WALLS WITHIN 2 FEET OF URINALS AND
 WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE, TO A HEIGHT OF 4 FEET ABOVE THE FLOOR, AND
 EXCEPT FOR STRUCTURAL ELEMENTS, THE MATERIALS USED IN
 SUCH WALLS SHALL BE OF A TYPE THAT IS NOT AVERSELY
 AFFECTED BY MOISTURE.
  
 4)THE H.C. GRAB BARS ON THE BACK WALL SHALL BE
 INSTALLED IN ACCORDANCE WITH FBC. CH. 11.FIG30E.THE
 GRAB BAR ON THE BACK WALL SHALL BE 6 INCHES MAX FROM
 THE SIDE WALL.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-02-21 Cont ID  
Sent By btrobaug Date 2007-02-21 Time 12:09 Rev Time 0.50
Received By btrobaug Date 2007-02-21 Time 10:48 Sent To P
Notes
2007-02-21 12:09:04 
  
 PROVISO
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW PRIOR TO ROUGH
 ELECTRICAL INSPECTION.
  
 1}INDICATE THE PANEL DESIGNATION AND BRANCH CIRCUIT
 NUMBER(S) USEDFOR NEW WORK. 106.3.5.1.2 FBC AS
 AMMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-02-13 Cont ID  
Sent By btrobaug Date 2007-02-13 Time 13:55 Rev Time 0.50
Received By btrobaug Date 2007-02-13 Time 13:35 Sent To  
Notes
2007-02-13 13:55:04 
  
 DENIED/INCOMPLETE INFORMATION
  
 PLEASE INDICATE THE PANEL DESIGNATION AND BRANCH
 CIRCUIT NUMBER(S) USEDFOR NEW WORK. 106.3.5.1.2 FBC
 AS AMMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2007-02-21 Cont ID  
Sent By mawillia Date 2007-02-21 Time 09:29 Rev Time 0.00
Received By mawillia Date 2007-02-21 Time 09:29 Sent To  
Notes
2007-02-21 09:35:36** NO FIRE REVIEW NEEDED**
  
  
 THE SCOPE OF WORK CONDUCTED DOES NOT AFFECT FIRE/LIFE
 SAFETY CONCERNS.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-21 Cont ID  
Sent By kstevens Date 2007-02-20 Time 10:32 Rev Time 0.00
Received By kstevens Date 2007-02-09 Time 09:30 Sent To  
Notes
2007-02-09 09:31:32TO "BOB"#8

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-02-13 Cont ID  
Sent By tgordon Date 2007-02-13 Time 14:24 Rev Time 0.20
Received By tgordon Date 2007-02-13 Time 14:24 Sent To  
Notes
2007-02-13 14:26:07BATHROOM EXHAUST FAN ONLY.

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-02-13 Cont ID  
Sent By jleech Date 2007-02-13 Time 10:00 Rev Time 0.00
Received By jleech Date 2007-02-13 Time 10:00 Sent To  
Notes
2007-02-13 10:15:26DENIED;
 1. SHOW CLEAR FLOOR SPACE FOR LAVATORY ON FLOOR PLAN.
 2. INTERIOR ELEV. "D", CENTER LINE OF TOILET SHALL BE
 18" OFF WALL NOT 24".
 3. INTERIOR ELEV. "B" HEIGHT OF LAVATORY TO THE RIM CAN
 BE 34". IF YOU MOUNT LAV AT 30" YOU MAY NOT HAVE THE
 27" REQUIRED FOR KNEE CLEARANCE .
 4. WALL FINISH WITHIN 2' OF THE WATER CLOSET SHALL HAVE
 A SMOOTH HARD NONABRORBENT SURFACE. FBC-2004 BUILDING
 SECTION 1210.2.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695