| 2007-02-25 11:35:36 | *** UNSAT *** |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE PERMIT APPLICATION SUBMITTED |
| | DOES NOT CONTAIN ORIGINAL SIGNATURES FROM THE |
| | QUALIFIER, THIS IS IN FACT APPEARS TO BE A COLOR |
| | PHOTO-COPY AND APPLICATION WILL BE RETAINED. PLEASE SEE |
| | FS 117.5 FOR NOTARIES WHICH PROHIBIT A NOTARY TO |
| | NOTARIZE A SIGNATURE OR LEGAL DOCUMENT WHICH IS NOT |
| | ORIGINAL. |
| | PLEASE KNOW THAT THE PLANS AND PERMIT APPLICATION WILL |
| | NOT BE RELEASED BY THIS OFFICE. |
| | THIS MAY BE TURNED OVER TO THE GOVERNOR'S BOARD AND |
| | ECLB. |
| | THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| | OTHER TRADES. DOCUMENTATION SUCH AS SIGNED AND SEALED |
| | PLANS, PERMIT APPLICATION IS REQUIRED TO CONTAIN |
| | ORIGINAL SIGNATURES. THESE LAWS WERE IMPLEMENTED TO |
| | PROTECT THE CONTRACTOR. |
| | |
| | ** THERE HAVE BEEN SEVERAL CASES OF PERMIT APPLCATIONS |
| | BEING SUBMITTED FOR WORK BY OTHER THAN THE CONTRACTOR |
| | FOR RECORD WITHOUT KNWOLEDGE OF CONTRACTOR. THIS AHJ |
| | CURRENTLY HAS NUMEROUS SUCH CASES WITH THE CLB, ECLB. |
| | |
| | 2) NOTE: PLEASE BE SURE ALL PLANS REFLECT THE LATEST |
| | ADOPTED CODES PER THE STATE OF FLORIDA. PLEASE SEE THE |
| | FOLLOWING WHICH ARE CURRENTLY ADOPTED AS OF DECEMBER |
| | 8TH, 2006. |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 (NEC). |
| | ** THESE CODES ARE REQUIRED AT A MINIMUM FOR THIS TRADE |
| | REVIEWER; OTHERS MAY BE REQUIRED PER OTHER TRADES OR |
| | REVIEWER(S). |
| | PLEASE SEE THERE ARE MANY AREAS ON THE PLANS WHICH |
| | REFERENCE OLDER CODES FROM PREVIOUS CODES, THESE SHOULD |
| | BE REVISED ACCORDINGLY. |
| | |
| | 3) NOTE: PLEASE SEE THE SITE PLANS WHICH MENTIONS THE |
| | GENERATOR IS LOCATED 5FT FROM PROPERTY LINE, HOWEVER |
| | BASED ON THE SITE PLAN PROVIDED, THIS IS NOT THE CASE. |
| | PLEASE SCALE AND SHOW ALL SET BACKS AND LOCATIONS OF |
| | ANY ADJACENT BUILDINGS LOCATED ON THE PROPERTY NEXT TO |
| | THIS PROPERTY. |
| | PLEASE SEE ZONING COMMENTS ALSO. |
| | |
| | 4) NOTE: PLEASE SEE MANUFACTURES SPECS/CUT SHEETS WHICH |
| | REFLECT A 300AMP BREAKER FEEDING UNITS, WHERE PLANS |
| | INDICATE A 350AMP BREAKER AT THIS SAME LOCATION FOR THE |
| | GENERATOR? PLEASE CORRELATE AND ADJUST AS NEEDED. FBC |
| | 106.1.2, 106.3.5.1.2 ADMIN SECTION FOR ADDITIONAL |
| | INFORMATION. |
| | |
| | 4) NOTE: PLEASE SEE RISER SHOWS TAPPED CONDUCTORS FROM |
| | A J-BOX TO EACH ATS DEVICE. PLEASE SEE 240.21 AS TAPS |
| | ARE REQUIRED TO TERMINATE IN OVER CURRENT PROTECTION. |
| | PLEASE ALSO SEE THE NEXT COMMENT. |
| | |
| | 5) NOTE: PLEASE SEE 702.11 AS A DISCONNECTING MEANS PER |
| | 225.31-225.39 WILL BE REQUIRED AS THE BREAKER ON THE |
| | GENERATOR MAY NOT BE USED AS PER ZONING COMMENTS THIS |
| | MAY REQUIRE A WALL/FENCING ETC WHICH WILL NOT ALLOW |
| | READY ACCESS AND IF THE BREAKER ON THE GENERATOR IS NOT |
| | WITHIN SIGHT (50FT) READILY ACCESSIBLE, (NOT LOCKED) |
| | ETC THEN DISCONNECTING MEANS IS REQUIRED. PLEASE SEE |
| | NOTE ABOVE AS THIS WILL AFFECT THE TAPS FROM THE |
| | GENERATOR J-BOX WHICH REQUIRES THE CONDUCTORS TO |
| | TERMINATE IN OCP. |
| | PLEASE SEE DISCONNECTS FROM THE GEN BEFORE ATS MAY BE |
| | ONE SOLUTION OR ATS FOR ENTIRE SERVICE WHICH WILL BE |
| | REQUIRED TO BE SE RATED AND DISCONNECTING MEANS FOR |
| | FEEDERS FROM GEN. |
| | THESE ARE IN NO WAY THE ONLY SCENARIO. |
| | |
| | 6) NOTE: PLEASE SEE THE SIGNATURE ON THE SLAB |
| | ENGINEERING PLANS IS ALSO NOT ORIGINAL AND IS A COLOR |
| | PHOTO-COPY FROM THE ENGINEER WITH A RAISED SEAL. PLEASE |
| | SEE THAT THIS SAME COMMENT HAS BEEN MADE BY THIS OFFICE |
| | ON SEVERAL OTHER SETS OF PLANS SUBMITTED WHICH IS |
| | PROHIBITED UNDER FAC 61G15-23.002 AND FS 471.025. |
| | PLEASE KNOW THAT THESE WILL BE RETAINED AND PLACED WITH |
| | PREVIOUS RETAINED PLANS AND FORWARDED TO THE FLORIDA |
| | BOARD OF PROFESSIONAL ENGINEERS IF COMPLIANCE IS NOT |
| | MADE AND THIS PRACTICED IS CONTINUED BY THIS ENGINEER. |
| | THESE ARE COLORED PHOTO-COPIES. |
| | THIS COMMENT IS MADE AND REQUIRED WHETHER OR NOT |
| | COMMENT IS MADE BY OTHER TRADES. |
| | THESE LAWS AND ADMINISTRATIVE CODES WERE PLACED INTO |
| | LAW TO PROTECT THE ENGINEER AND FIRM. |
| | |
| | 7) NOTE: PLEASE SEE THE VALUE SHALL INCLUDE ALL LABOR |
| | AND MATERIALS EVEN IF MATERIALS ARE OWNER SUPPLIED. |
| | PLEASE KNOW DEPENDING ON SCOPE OF WORK REQUIRED FOR |
| | SCREENING BY ZONING, THIS MAY REQUIRE A GC TO PULL |
| | PERMIT FOR ANY WALL/BUILDING CONSTRUCTION. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |