2007-03-12 12:10:22BUILDING PLAN REVIEW
 PERMIT: 07020088
 ADD: 1220 OKEECHOBEE RD
 CONT: DARRYL SCHMIDT ELECTRIC
 TEL: (954)366-8085
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS
 NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE
 OF COMMENCEMENT
 AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)HENRY HILLMAN P. E. IS REQUIRD TO SIGN PERSONALLY AND
 AFFIX
 HIS SEAL TO ALL PLANS PREPARED UNDER HIS AUTHORITY, NOT
 BLUE INK COPIES!!!!!
 PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-06-19 Cont ID  
Sent By dpalmer Date 2007-06-19 Time 16:38 Rev Time 0.00
Received By dpalmer Date 2007-06-19 Time 15:14 Sent To  
Notes
2007-06-19 16:38:48*** UNSAT 2ND REVIEW **
  
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW STILL
 NEED TO BE ADDRESSED.
  
 1) NOTE: PLEASE SUBMIT TWO SET OF PLANS AND SUPPORTING
 DOCUMENTS. PLEASE BE SURE EACH PACKAGE IN PLACED INTO
 BOUND SETS AND SHEETS ARE NOT SUBMITTED LOOSELY.
 FBC 106.1
  
 2) NOTE: PLEASE SEE THE SUBMITTED LETTERS FOR SIGNATURE
 VERIFICATIONS DO NOT CONTAIN THE COMPLETEDNOTARY
 INFORMATION AS REQUIRED UNDER FS 117.05.
  
 3) NOTE: PLEASE BE SURE ALL PLANS REFLECT THE LATEST
 ADOPTED CODES PER THE STATE OF FLORIDA. PLEASE SEE THE
 FOLLOWING WHICH ARE CURRENTLY ADOPTED AS OF DECEMBER
 8TH, 2006.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70 (NEC).
 ** THESE CODES ARE REQUIRED AT A MINIMUM FOR THIS TRADE
 REVIEWER; OTHERS MAY BE REQUIRED PER OTHER TRADES OR
 REVIEWER(S).
 PLEASE SEE THERE ARE MANY AREAS ON THE PLANS WHICH
 REFERENCE OLDER CODES FROM PREVIOUS CODES, THESE SHOULD
 BE REVISED ACCORDINGLY.
  
 4) NOTE: PLEASE SEE RISER SHOWS TAPPED CONDUCTORS FROM
 A J-BOX/GUTTER TO EACH ATS DEVICE. PLEASE SEE 240.21 AS
 TAPS ARE REQUIRED TO TERMINATE IN OVER CURRENT
 PROTECTION. PLEASE SEE THE SPECS SUBMITTED FOR THE ATS
 EQUIPMENT DOES NOT INDICATE ANY OCP/ MAIN BREAKERS FOR
 THE TAPPED FEEDERS FROM THE GUTTER. PLEASE SEE 408.36
 AND PLEASE ALSO SEE THE NEXT COMMENT.
  
 5) NOTE:THIS COMMENT IS THE SAME FROM PREVIOUS REVIEW
 AS INFORMATION ABOVE IS NOT CLEAR. PLEASE SEE 702.11 AS
 A DISCONNECTING MEANS PER 225.31-225.39 WILL BE
 REQUIRED AS THE BREAKER ON THE GENERATOR MAY NOT BE
 USED AS PER ZONING COMMENTS THIS MAY REQUIRE A
 WALL/FENCING ETC WHICH WILL NOT ALLOW READY ACCESS AND
 IF THE BREAKER ON THE GENERATOR IS NOT WITHIN SIGHT
 (50FT) READILY ACCESSIBLE, (NOT LOCKED) ETC THEN
 DISCONNECTING MEANS IS REQUIRED. PLEASE SEE NOTE ABOVE
 AS THIS WILL AFFECT THE TAPS FROM THE GENERATOR J-BOX
 WHICH REQUIRES THE CONDUCTORS TO TERMINATE IN OCP.
 PLEASE SEE DISCONNECTS FROM THE GEN BEFORE ATS MAY BE
 ONE SOLUTION OR ATS FOR ENTIRE SERVICE WHICH WILL BE
 REQUIRED TO BE SE RATED AND DISCONNECTING MEANS FOR
 FEEDERS FROM GEN.
 THESE ARE IN NO WAY THE ONLY SCENARIO.
  
 6) NOTE: PLEASE KNOW AS THE VALUE WAS INCREASED THERE
 ARE FEES OWED WHICH WILL BE REQUIRED TO BE PAID BEFORE
 PLANS CAN BE RE-SUBMITTED FOR REVIEW.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-02-25 Cont ID  
Sent By dpalmer Date 2007-02-25 Time 11:32 Rev Time 0.00
Received By dpalmer Date 2007-02-25 Time 10:48 Sent To  
Notes
2007-02-25 11:35:36*** UNSAT ***
  
  
 1) NOTE: PLEASE SEE THE PERMIT APPLICATION SUBMITTED
 DOES NOT CONTAIN ORIGINAL SIGNATURES FROM THE
 QUALIFIER, THIS IS IN FACT APPEARS TO BE A COLOR
 PHOTO-COPY AND APPLICATION WILL BE RETAINED. PLEASE SEE
 FS 117.5 FOR NOTARIES WHICH PROHIBIT A NOTARY TO
 NOTARIZE A SIGNATURE OR LEGAL DOCUMENT WHICH IS NOT
 ORIGINAL.
 PLEASE KNOW THAT THE PLANS AND PERMIT APPLICATION WILL
 NOT BE RELEASED BY THIS OFFICE.
 THIS MAY BE TURNED OVER TO THE GOVERNOR'S BOARD AND
 ECLB.
 THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES. DOCUMENTATION SUCH AS SIGNED AND SEALED
 PLANS, PERMIT APPLICATION IS REQUIRED TO CONTAIN
 ORIGINAL SIGNATURES. THESE LAWS WERE IMPLEMENTED TO
 PROTECT THE CONTRACTOR.
  
 ** THERE HAVE BEEN SEVERAL CASES OF PERMIT APPLCATIONS
 BEING SUBMITTED FOR WORK BY OTHER THAN THE CONTRACTOR
 FOR RECORD WITHOUT KNWOLEDGE OF CONTRACTOR. THIS AHJ
 CURRENTLY HAS NUMEROUS SUCH CASES WITH THE CLB, ECLB.
  
 2) NOTE: PLEASE BE SURE ALL PLANS REFLECT THE LATEST
 ADOPTED CODES PER THE STATE OF FLORIDA. PLEASE SEE THE
 FOLLOWING WHICH ARE CURRENTLY ADOPTED AS OF DECEMBER
 8TH, 2006.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70 (NEC).
 ** THESE CODES ARE REQUIRED AT A MINIMUM FOR THIS TRADE
 REVIEWER; OTHERS MAY BE REQUIRED PER OTHER TRADES OR
 REVIEWER(S).
 PLEASE SEE THERE ARE MANY AREAS ON THE PLANS WHICH
 REFERENCE OLDER CODES FROM PREVIOUS CODES, THESE SHOULD
 BE REVISED ACCORDINGLY.
  
 3) NOTE: PLEASE SEE THE SITE PLANS WHICH MENTIONS THE
 GENERATOR IS LOCATED 5FT FROM PROPERTY LINE, HOWEVER
 BASED ON THE SITE PLAN PROVIDED, THIS IS NOT THE CASE.
 PLEASE SCALE AND SHOW ALL SET BACKS AND LOCATIONS OF
 ANY ADJACENT BUILDINGS LOCATED ON THE PROPERTY NEXT TO
 THIS PROPERTY.
 PLEASE SEE ZONING COMMENTS ALSO.
  
 4) NOTE: PLEASE SEE MANUFACTURES SPECS/CUT SHEETS WHICH
 REFLECT A 300AMP BREAKER FEEDING UNITS, WHERE PLANS
 INDICATE A 350AMP BREAKER AT THIS SAME LOCATION FOR THE
 GENERATOR? PLEASE CORRELATE AND ADJUST AS NEEDED. FBC
 106.1.2, 106.3.5.1.2 ADMIN SECTION FOR ADDITIONAL
 INFORMATION.
  
 4) NOTE: PLEASE SEE RISER SHOWS TAPPED CONDUCTORS FROM
 A J-BOX TO EACH ATS DEVICE. PLEASE SEE 240.21 AS TAPS
 ARE REQUIRED TO TERMINATE IN OVER CURRENT PROTECTION.
 PLEASE ALSO SEE THE NEXT COMMENT.
  
 5) NOTE: PLEASE SEE 702.11 AS A DISCONNECTING MEANS PER
 225.31-225.39 WILL BE REQUIRED AS THE BREAKER ON THE
 GENERATOR MAY NOT BE USED AS PER ZONING COMMENTS THIS
 MAY REQUIRE A WALL/FENCING ETC WHICH WILL NOT ALLOW
 READY ACCESS AND IF THE BREAKER ON THE GENERATOR IS NOT
 WITHIN SIGHT (50FT) READILY ACCESSIBLE, (NOT LOCKED)
 ETC THEN DISCONNECTING MEANS IS REQUIRED. PLEASE SEE
 NOTE ABOVE AS THIS WILL AFFECT THE TAPS FROM THE
 GENERATOR J-BOX WHICH REQUIRES THE CONDUCTORS TO
 TERMINATE IN OCP.
 PLEASE SEE DISCONNECTS FROM THE GEN BEFORE ATS MAY BE
 ONE SOLUTION OR ATS FOR ENTIRE SERVICE WHICH WILL BE
 REQUIRED TO BE SE RATED AND DISCONNECTING MEANS FOR
 FEEDERS FROM GEN.
 THESE ARE IN NO WAY THE ONLY SCENARIO.
  
 6) NOTE: PLEASE SEE THE SIGNATURE ON THE SLAB
 ENGINEERING PLANS IS ALSO NOT ORIGINAL AND IS A COLOR
 PHOTO-COPY FROM THE ENGINEER WITH A RAISED SEAL. PLEASE
 SEE THAT THIS SAME COMMENT HAS BEEN MADE BY THIS OFFICE
 ON SEVERAL OTHER SETS OF PLANS SUBMITTED WHICH IS
 PROHIBITED UNDER FAC 61G15-23.002 AND FS 471.025.
 PLEASE KNOW THAT THESE WILL BE RETAINED AND PLACED WITH
 PREVIOUS RETAINED PLANS AND FORWARDED TO THE FLORIDA
 BOARD OF PROFESSIONAL ENGINEERS IF COMPLIANCE IS NOT
 MADE AND THIS PRACTICED IS CONTINUED BY THIS ENGINEER.
 THESE ARE COLORED PHOTO-COPIES.
 THIS COMMENT IS MADE AND REQUIRED WHETHER OR NOT
 COMMENT IS MADE BY OTHER TRADES.
 THESE LAWS AND ADMINISTRATIVE CODES WERE PLACED INTO
 LAW TO PROTECT THE ENGINEER AND FIRM.
  
 7) NOTE: PLEASE SEE THE VALUE SHALL INCLUDE ALL LABOR
 AND MATERIALS EVEN IF MATERIALS ARE OWNER SUPPLIED.
 PLEASE KNOW DEPENDING ON SCOPE OF WORK REQUIRED FOR
 SCREENING BY ZONING, THIS MAY REQUIRE A GC TO PULL
 PERMIT FOR ANY WALL/BUILDING CONSTRUCTION.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-06-21 Cont ID  
Sent By mawillia Date 2007-06-21 Time 10:36 Rev Time 0.00
Received By mawillia Date 2007-06-21 Time 10:04 Sent To  
Notes
2007-06-21 10:35:44*****PROVISO*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED, HOWEVER THE APPROPIATE PLAN SHEET(S)
 WILL BE FIRE-STAMPED WHEN ALL OTHER PLAN REVIEWS HAVE
 BEEN SATISFIED.
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-03-19 Cont ID  
Sent By mawillia Date 2007-03-19 Time 17:23 Rev Time 0.00
Received By mawillia Date 2007-03-19 Time 17:08 Sent To E
Notes
2007-03-19 17:23:32*****DENIED*****
  
  
 1. PLEASE INDICATE WHETHER THE NEWLY INSTALLED
 STATIONARY GENERATOR WILL BE USED FOR EMERGENCY USE OR
 FOR STANDBY POWER FOR FIRE PROTECTION SYSTEM OR BOTH.
  
 2.STATIONARY GENERATORS FOR EMERGENCY USE OR STANDBY
 POWER SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 110,
 STANDARD FOR EMERGENCY AND STANDBY POWER SYSTEMS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-06-28 Cont ID  
Sent By kstevens Date 2007-06-28 Time 17:35 Rev Time 0.00
Received By kstevens Date 2007-06-28 Time 17:35 Sent To  
Notes
2007-06-28 17:40:40DENIED
 REFERENCE: FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. A MINIMUM OF TWO COMPLETE SETS OF PLANS SHALL BE
 SUBMITTED FOR REVIEW. AS SUBMITTED THEY ARE LOOSE
 SHEETS. PLEASE REMOVE ALL REVISED/VOIDED SHEETS.
 SECTION 106.1.
  
 2. ONCE COMMENT 1 AND THE ELECTRICAL COMMENTS 2, 3 & 6
 HAVE BEEN ADDRESSED AND APPROVED THE GAS WILL BE
 APPROVED ALSO.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-02-28 Cont ID  
Sent By kstevens Date 2007-02-28 Time 17:37 Rev Time 0.00
Received By kstevens Date 2007-02-28 Time 17:37 Sent To  
Notes
2007-02-28 17:52:46DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. THE PRINTED NAME AND SIGNATURE OF THE PERSON
 DESIGNING THE GAS ISOMETRIC SHALL BE INDICATED ON THE
 PLANS.SECTION 106.1.3.
  
 2. PLEASE INDICATE THE FOLLOWING ON THE GAS ISOMETRIC:
 A. TYPE OF GAS, (LP OR NATURAL).
 B. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 3. PLEASE ADDRESS THE ELECTRIC PLAN REVIEW COMMENTS 1,
 2, 6 & 7.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-22 Cont ID  
Sent By adarroug Date 2007-05-22 Time 16:36 Rev Time 0.00
Received By adarroug Date 2007-05-22 Time 16:36 Sent To  
Notes
2007-06-14 13:26:56TO "COMM" BD#35
2007-05-22 16:36:22WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-19 Cont ID  
Sent By mawillia Date 2007-03-19 Time 17:08 Rev Time 0.00
Received By mawillia Date 2007-02-05 Time 11:55 Sent To  
Notes
2007-02-20 13:09:32TO "COMM" BD#22
2007-02-05 11:57:57WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-06-20 Cont ID  
Sent By tgordon Date 2007-06-20 Time 11:03 Rev Time 0.20
Received By tgordon Date 2007-06-20 Time 11:03 Sent To  
Notes
2007-06-20 11:04:53*** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTES, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-02-26 Cont ID  
Sent By tgordon Date 2007-02-26 Time 09:37 Rev Time 0.20
Received By tgordon Date 2007-02-26 Time 09:36 Sent To  
Notes
2007-02-26 09:38:26*** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTES, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-06-19 Cont ID  
Sent By kdfreema Date 2007-06-19 Time 08:38 Rev Time 0.00
Received By kdfreema Date 2007-06-19 Time 08:38 Sent To  
Notes
2007-06-19 09:12:221. THE PROPOSED FENCE TREATMENT DOES NOT COMPLETELY
 SATISFY THE REQUIREMENTS OF THE ZONING CODE.
 LANDSCAPING IS REQUIRED TO BE PROVIDED IN ADDITION TO
 THE FENCING.
  
 2. IT WOULD BE IN YOUR BEST INTEREST TO DESIGN A
 COMBINATION GENERATOR/DUMPSTER ENCLOSURE. PRESENTLY,
 CODE ENFORCEMENT IS ISSUING CITATIONS FOR UNSCREENED
 DUMPSTERS THROUGHT THE CITY. THIS REPRESENTS A GOOD
 OPPORTUNITY TO TAKE CARE OF THE PROBLEM BEFORE CODE
 ENFORCEMENT COMES THROUGH YOUR AREA.
  
 3. AFTER ADDITIONAL RESEARCH INTO THE HISTORY OF THE
 BUILDING, AND THE REQUIREMENTS AT THE TIME OF
 CONSTRUCTION IN THE LATE 1960S, THE PARKING REQUIREMENT
 IS NOW REDUCED TO 6 SPACES. THIS SHOULD ALLOW YOU SOME
 EXTRA ROOM TO ACCOMMODATE THE DUMPSTER AND GENERATOR
 ENCLOSURE AND LANDSCAPING.
  
 4. I HAVE ATTACHED COPIES OF THE CITY'S STANDARD
 STRIPING DETAIL AS WELL AS THE REQUIREMENT FOR DUMPSTER
 ENCLOSURES FOR YOUR INFORMATION.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, WITH ANY
 QUESTIONS YOU HAVE AT 561-822-1435. I WOULD BE MORE
 THAN WILLING TO MEET TO DISCUSS VARIOUS APPROACHES TO
 GETTING THE SITE ISSUES SORTED OUT. I CAN ALSO BE
 REACHED VIA E-MAIL AT [email protected].

Review Stop Z ZONING
Rev No 1 Status F Date 2007-02-16 Cont ID  
Sent By kdfreema Date 2007-02-16 Time 16:28 Rev Time 0.00
Received By kdfreema Date 2007-02-16 Time 16:28 Sent To I
Notes
2007-02-16 16:31:38**FAILED**
  
 1) AS THE GENERATOR IS PROPOSED TO BE PLACED IN THE
 PARKING AREA, PLEASE SHOW THE NUMBER OF PARKING SPACES
 PROVIDED BEFORE, AND AFTER THE INSTALLATION OF THE
 GENERATOR. NOTE THAT YOU ARE REQUIRED TO PROVIDE 11
 PARKING SPACES, INCLUDING ONE HANDICAP ACCESSIBLE
 PARKING SPACE.
  
 2) THE SURVEY MUST BE SIGNED AND SEALED, AND NOT BE
 OLDER THAN 1 YEAR.
  
 3) THE SURVEY MUST BE TO SCALE.
  
 4) THE GENERATOR MUST BE SCREENED AND LANDSCAPED PER
 THE REQUIREMENTS OF SECTION 94-444(B) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435
 WITH ANY QUESTIONS.