| 2007-03-21 18:54:48 | BUILDING REVIEWCHECKLIST: |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC 713.13 |
| | FLORIDA STATUTE. |
| | |
| | 2- BRING PLANS TO PALM BEACH COUNTY FOR IMPACT FEES. |
| | BRING BACK STAMPED PLANS AND COPY OF PAID RECEIPT. |
| | ***NOTE: MAKE SURE CORRECT BUILDING AREA IS SHOWN ON |
| | PLANS. |
| | |
| | 3- SHEET A-1.0: DRIVEWAY APPROACH IS NOT SHOWN |
| | CORRECTLY. ALSO, CONTACT ENGINEERING DEPARTMENT AT |
| | (561) 494-1040 FOR DRIVEWAY AND APPROACH STANDARDS. |
| | |
| | 4- ENERGY CALCULATIONS: |
| | A) REVISE OVERHANG LENGTH AND HEIGHT. SEE PLANS. |
| | |
| | B) MAKE SURE A/C AREA MATCHES PLANS. |
| | |
| | C) COMPLETE ALL INFORMATION ON TOP OF FORM. |
| | |
| | D) REVISE RAISED WOOD, ADJACENT AREA. SEE PLANS FOR |
| | CORRECT INFORMATION. |
| | |
| | 5- PROVIDE COMPLETE INFORMATION FOR STORM SHUTTERS. |
| | PROVIDE PRODUCT APPROVAL AND COMPLETE INSTALLATION |
| | SCHEDULE. SEE ATTACHED SAMPLE OF INSTALLATION |
| | SCHEDULE. |
| | *** NOTE: DESIGNER OF RECORD TO REVIEW AND APPROVE IN |
| | WRITING PRODUCT APPROVAL AS REQUIRED BY SEC. 106.3.3 |
| | CITY AMENDMENTS TO FBC 2004. |
| | |
| | 6- BUILDING VALUATION AND RADON FEES WILL BE UPDATED |
| | WHEN CORRECT FLOOR AREAS ARE PROVIDED. |
| | |
| | 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72 |
| | FOR: |
| | A) ENTRY DOOR WITH IMPACT GLASS AS SPECIFIED ON |
| | PLANS. |
| | |
| | B) ASPHALT SHINGLES.NOA #04-0305.03 EXPIRED ON |
| | 02/21/07. |
| | |
| | C) SINGLE HUNG WINDOWS. NEED LEGIBLE DRAWINGS. |
| | |
| | D) COLONIAL SHUTTERS SHOWN ON EXTERIOR ELEVATIONS. |
| | |
| | E) WINDOW MULLIONS. NEED CLEAR AND LEGIBLE |
| | DRAWINGS. |
| | |
| | F) LOUVERS IN GABLE END WALLS. |
| | |
| | G) REAR AND 2ND FLOOR FRENCH DOORS. |
| | |
| | 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 9- ARCHITECT TO PROVIDE ALL HIS INFORMATION AND FIRM'S |
| | REGISTRATION NUMBERAS REQUIRED BY SEC. 61G1-16.004 OF |
| | FLORIDA ADMINISTRATIVE CODE. |
| | |
| | 10- A) PROVIDE SURVEY WITH PROPOSED BUILDING LAYOUT AND |
| | SETBACKS. |
| | |
| | B) SURVEY TO HAVE ORIGINAL SIGNATURE AS REQUIRED BY |
| | CHAPTER 472 FLORIDA STATUTE. |
| | |
| | 11- SHEET 2.1:SPECIFY TOP AND BOTTOM CONNECTORS FOR |
| | 4" WOOD COLUMNS. SEC. 106.1.2 CITY AMENDMENTS TO FBC |
| | 2004. |
| | |
| | 12- SHEET 3.1: |
| | A) REVISE PLYWOOD SHEATHING NAILING SCHEDULEAND |
| | NOTE REGARDING RING SHANK NAILS. SEE SEC. R803.2.3.1 OF |
| | 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | B) REVISE SKETCHSHOWING ROOF ZONES.SEE FIGURE |
| | R301.2(8) 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | C) PROVIDE DETAIL C/3.1 SHOWING CONNECTION OF GABLE |
| | END BEAM WITH STEEL CAP. SEC. 106.1.2 CITY AMENDMENT TO |
| | FBC 2004. |
| | |
| | D) CLARIFY WHY USING ONLY ONE LEDGER TO SUPPORT |
| | FLOOR TRUSSES. TAKE INTO CONSIDERATION HOW MUCH BEARING |
| | IS REQUIRED AT THE END OF TRUSSES AND AT THE END OF |
| | GIRDER TRUSSES. SEC. 106.1.2 CITY AMENDMENTS TO FBC |
| | 2004. |
| | |
| | E) PROVIDE DETAIL SHOWING CONNECTION OF FRONT PORCH |
| | WOOD BEAM TO CONTINUOUS STEEL COLUMN AT CORNER AREAS. |
| | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | F) SPECIFY HOW LONG ARE THE HILTI EXP.ANCHORS |
| | SPECIFIED TO SUPPORT 2X8 JOISTS AT FRONT PORCH. SEC. |
| | 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | G) SPECIFY CONNECTORS AT THE ENDS OF 2X8 JOISTS AT |
| | FRONT PORCH. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | H) WIND DESIGN INFORMATION ITEM #5: CLARIFY WHY THE |
| | INTERNAL PRESSURE COEFFICIENT IS NOT APPLICABLE IF THIS |
| | BUILDING IS DESIGNED ASCLOSED?. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | I) CLEARLY SPECIFY DESIGN PRESSURES FOR EACH OPENING |
| | IN THIS BUILDING. SEC. 106.1.2 CITY AMENDMENTS TO FBC |
| | 2004. |
| | |
| | 13- SHEET 4.1: |
| | A) SPECIFY SAFETY GLASS FOR WINDOW NEXT TO THE BATH |
| | TUB IN MASTER BATHROOM AS REQUIRED BY SEC. R308.4 OF |
| | 2004 FLORIDA RESIDENTIAL CODE |
| | |
| | B) REVISE ALL AREA CALCULATIONS. |
| | |
| | 14- SHEET 6.1: REVISE CARDINAL ORIENTATION OF EACH |
| | ELEVATION.SEE SURVEY FOR CORRECT BUILDING |
| | ORIENTATION. |
| | |
| | |
| | 15- SHEET 7.1 WALL SECTION 2/7.1: CLARIFY TYPE OF ROOF |
| | COVERING. SHINGLES OR TILE. REVISE AS REQUIRED. |
| | |
| | 16- SHEET 9.1: |
| | A) PROVIDE COMPLETE STRUCTURAL BUCK DETAIL FOR ALL |
| | DOORAND WINDOW TYPES.SEE SEC. R 613.6.2 OF 2004 |
| | FLORIDA RESDIENTIAL CODE FOR PROPERINSTALLATION. |
| | SPECIFY ALL FASTENERS. ALSO, SEE PRODUCT APPROVALS FOR |
| | REQUIRED BUCK SIZE. |
| | |
| | B) WINDOW F IS NOT AN EGRESS WINDOW. REVISE AS |
| | REQUIRED. |
| | |
| | 16- SOIL TEST REPORT TO HAVE ENGINEERING FIRM |
| | CERTIFICATE OF AUTHORIZATION NUMBER IN ALL SHEETS AS |
| | REQUIRED BY SEC. 61G15-23.002 FLORIDA ADMINISTRATIVE |
| | CODE |
| | |