Plan Review Details - Permit 07020042
Plan Review Stops For Permit 07020042
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-09-08 Cont ID  
Sent By jwitmer Date 2007-09-08 Time 11:29 Rev Time 0.77
Received By jwitmer Date 2007-09-08 Time 11:29 Sent To  
Notes
2007-09-08 11:30:08REVISION# 4- OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-08-16 Cont ID  
Sent By jwitmer Date 2007-08-16 Time 17:22 Rev Time 1.33
Received By jwitmer Date 2007-08-16 Time 17:22 Sent To  
Notes
2007-08-16 17:37:12BUILDING PLAN REVIEW
 PERMIT: 07020042
 ADD: 1400 NORTHPOINT PARKWAY
 CONT: BRICAR ENTERPRISES, INC
 TEL: (954)675-1976
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW REVISION # 4
 ACTION: DENIED
  
 1) SHEET A4 DETAIL P2 & P3 DOES NOT INDICATE HOW THE
 TOP OF THE WALL WILL BE ANCHORED. IT CURRENTLY IS
 FLOATING WITH NO LATERAL BRACING.
 WHAT TYPE OF MATERIALS WILL BE USED IN THIS LAB, IS IT
 TO BE CONSIDERED A CONTROLED AREA ?IF SO:414.2.3
 SEPARATION.
 THE REQUIRED FIRE-RESISTANCE RATING FOR FIRE BARRIER
 ASSEMBLIES SHALL BE IN ACCORDANCE WITH TABLE 414.2.2 .
 THE FLOOR CONSTRUCTION OF THE CONTROL AREA , AND THE
 CONSTRUCTION SUPPORTING THE FLOOR OF THE CONTROL AREA ,
 SHALL HAVE A MINIMUM 2-HOUR FIRE-RESISTANCE RATING.
  
 2) PLEASE PROVIDE THE CRITERIA TO DETERMINE THE 5 LBS.
 PER SQ FT FOR BOTH STRESS AND DEFLECTION REQUIREMENTS,
 WHAT ARE THE DEFLECTION LIMITS?
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-05-30 Cont ID  
Sent By lmartine Date 2007-05-30 Time 15:11 Rev Time 0.00
Received By lmartine Date 2007-05-30 Time 15:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-09 Cont ID  
Sent By jwitmer Date 2007-03-09 Time 16:38 Rev Time 2.22
Received By jwitmer Date 2007-03-09 Time 16:38 Sent To FIRE
Notes
2007-03-09 16:58:51BUILDING PLAN REVIEW
 PERMIT: 07020042
 ADD: 1400 NORTHPOINT PRKY# 10
 CONT: FISHER CONSTRUCTION
 TEL: (561758-6545
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS
 NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE
 OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 3) 106.1.2*ADDITIONAL INFORMATION REQUIRED, THE PLANS
 INDICATE ROOMS 106 & 110 TO BE ELECTRICAL ROOMS? IS
 THERE ANY GAS CYLINDERS IN EITHER OF TTHESE ROOMS? IF
 SO WHAT TYPE OF GASSES ARE THERE AND IN WHAT SIZE
 CYLINDERS, POUNDS OR GALLONS?
 THIS SITE WAS PERMITTED WITH THESE ROOMS BEING
 EXPLOSION PROOF ROOMS WITH BLOW OUT PANELS THROUGH THE
 ROOF AS WELL AS THE WALLS AND DOORS BECAUSE OF THE
 HYDROGEN
 CYLINDERS BEING HOUSED IN THESE ROOMS. THERE WAS ALSO A
 KNOX BOX INCORPORATED INTO THE SITE WITH MSDS SHEETS AS
 TO THE CHEMICALS BEING STORED AND THE QUANITIES. THIS
 SITE WAAS CONSIDERED A BUSINESS OCCUPANCY WITH CONTROL
 AREAS, ARE ANY OF THE LABS ADDING EQUIPMENT REQUIRING
 PIPING, AND OR VENTILATION?
  
 4)ROOMS 116, 117B & 119B PLEASE SEE ACCESSIBLE
 DOORS,
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE
 CLEAR & LEVEL.
  
 5) DISCREPANCY BETWEEN LS-1 AND A1 IN THE AREA OF
 COVERED PATIO VS BEING AN AREADESIGNATED AS A CHILLER
 COMPOUND? LS PLAN INDICATES 2 MEANS OF EGRESS TRAVELING
 THROUGH THE
 CHILLER COMPOUND, IF THIS IS SUCH AN AREA WOULDN'T THE
 GATES BE LOCKED , FOR AUTHORIZED PERSONEL ONLY?
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-09-07 Cont ID  
Sent By dpalmer Date 2007-09-07 Time 20:08 Rev Time 0.00
Received By dpalmer Date 2007-09-07 Time 19:50 Sent To  
Notes
2007-09-07 20:09:132007-09-07 20:09:13
  
 REV OK,STAMPED ELEC SHEETS.
  
 PENDING FIRE REVIEW

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-07-04 Cont ID  
Sent By dpalmer Date 2007-07-04 Time 09:54 Rev Time 0.00
Received By dpalmer Date 2007-07-04 Time 08:59 Sent To I
Notes
2007-07-04 09:54:542007-07-04 09:54:54
  
 ** UNSAT **
  
  
 1) NOTE: PLEASE SUBMIT REVISED ENERGY CALCULATIONS.
 PLEASE SEE THE ENERGY CALCULATION AS SUBMITTED UNDER
 PERMIT APPLICATION WERE THE INCORRECT VERSION. PLEASE
 SEE THE VERSION SUBMITTED WAS 2.1 WHICH WAS IN EFFECT
 ON THE PREVIOUS REVISIONS TO THE FBC AND NOT IN EFFECT
 AFTER DECEMBER 8TH, 2006. PLEASE SEE THE REVISED ENERGY
 CALCULATIONS ARE NEEDED AS LIGHTING HAS BEEN REVISED.
 13-415.1.C, 13-415.2
  
 2) NOTE: PLEASE CLARIFY THE FOLLOWING ROOMS AS THESE
 ARE NOTED ON PLANS AS EXISTING HOWEVER THE LIGHTING
 APPEARS TO BE SHOWN BEING REPLACED? PLEASE SEE OTHER
 ROOMS WHICH ARE EXISTING INDICATE LIGHTING AS *LT GRAY*
 AND DASHED LINES. PLEASE KNOW ANY OF THESE FOLLOWING
 ROOMS WHICH LIGHTING FIXTURES ARE BEING REPLACED OR
 CONTROL DEVICES ARE BEING CHANGED/REPLACE OR RELOCATED
 WILL BE REQUIRED TO MEET THE FBC CHAPTER 13 AS OTHER
 ROOMS ARE DONE.
 PLEASE SEE THE ROOMS ARE AS NOTED:
 LAB E, GUEST LOUNGE, OFFICES 131-137. 13-415.1.1,.1.2,
 13-101
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-07-04 09:01:072007-07-04 09:01:07
 PLANS REMOVED FROM INCOMING, WILL RETURN TO INCOMING
 ONCE ELECTRICAL REVIEW IS DONE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-04-18 Cont ID  
Sent By dpalmer Date 2007-04-18 Time 15:03 Rev Time 0.00
Received By dpalmer Date 2007-04-18 Time 15:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-02-13 Cont ID  
Sent By dpalmer Date 2007-02-13 Time 12:15 Rev Time 0.00
Received By dpalmer Date 2007-02-13 Time 09:53 Sent To  
Notes
2007-02-13 12:19:11*** UNSAT ***
  
  
 1) NOTE: PLEASE SEE THE CODE WHICH SHOULD BE STATED ON
 PLANS ARE THE 2005 NFPA-70 AND THE 2004 FBC 2006
 REVISIONS.
 PLEASE SEE THE OTHER CODES REFLECTED ON ELECTRICAL
 PLANS ARE OK AND CURRENT.
  
 ** ALL PERMIT APPLICATIONS WHICH ARE APPLIED FOR AFTER
 DECEMBER 8TH, 2006 FALL UNDER THE NEW CODES.
  
 2) NOTE: PLEASE SEE THE EGRESS PATH ON THE LIFE SAFETY
 PLAN DOES NOT CORRELATE WITH THE ELECTRICAL PLANS AND
 ARCHITECTURAL SHEETS FOR THE LAYOUT OF FURNITURE ETC.
 PLEASE SEE BUILDING AND FIRE REVIEW COMMENTS AS THIS
 MAY DIRECTLY AFFECT THE EGRESS PATHS AND ELECTRICAL
 LAYOUTS FOR EQUIPMENT/CUBICLES ETC
 LS 101
  
 3) NOTE: PLEASE CLARIFY USE AND OCCUPANCY AS THE PLANS
 MENTIONS "LAB", HOWEVER WHAT TYPE OF LAB WORK IS BEING
 DONE, WHAT TYPE PF MATERIALS ETC.
 PLEASE SEE NEC 500.
 REVIEW FOR USE AND ELECTRICAL CAN NOT BE VERIFIED AT
 THIS TIME.
  
 4) NOTE: PLEASE CLARIFY NOTE WHICH MENTIONS THE ENTIRE
 SPACE IS GOING TO HAVE CONTROLS IN FOR CHAPTER 13
 REQUIREMENTS HOWEVER THE PLANS DO NOT CORRELATE WITH
 THE ENTIRE SPACE?
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE THERE ARE SOME AREAS WHICH WALL SWITCH TYPE
 OCCUPANCY DEVICES ARE BEING INDICATED FOR HALL AND
 LARGER OPEN AREAS, HOWEVER THE WALL DEVICE DOES NOT
 SEEM IT WILL PROVIDE THE COVERAGE AS NEEDED FOR
 LIGHTING CONTROL FOR THE OCCUPANTS. PLEASE SEE THE
 POSSIBILITY OF CEILING MOUNTED DEVICES IN HALLS AND
 LARGER AREAS. (WALLS AND OTHER OBSTRUCTIONS WILL
 INTERFERE WITH WALL DEVICES).
 PLEASE SEE HALLS ALSO.
  
 *PLEASE PROVIDE LIGHTING PERFORMANCE CALCULATIONS FOR
 NEW FIXTURES AND LPD AS STATED IN 13-415.2.
  
 5) NOTE: PLEASE SEE RISER SHOWS PANEL TSC AND EPA,
 HOWEVER THESE WERE NOT SUBMITTED. PLEASE CLARIFY.
 408.4, 310.16, 240.4.
 FBC 106.1.2 ADMIN SECTION.
  
  
 6) NOTE: PLEASE PROVIDE CALCULATIONS ON NEUTRAL
 CONDUCTORS FOR ALL NON-LINEAR CIRCUITS. PLEASE SEE ALL
 CIRCUITS WHICH CONTAIN THESE LOADS SHALL MEET THE
 SIZING REQUIREMENTS TO HANDLE AND ALLEVIATE THE OVER
 LOADING OF THE NEUTRAL ON A 3-PHASE 4-WIRE SYSTEM WITH
 PREDOMINATELY OR ACTUALLY IN MANY CASES ALL NON-LINEAR
 LOADS. PLEASE SEE THIS CAN BE DONE BY USING MANY
 METHODS, K-RATED TRANSFORMERS, FULL NEUTRAL LOAD
 CALCULATION ON EACH CIRCUIT AND FEEDERS BASED ON ALL
 NON-LINEAR LOADS OR THE SIZING OF THE NEUTRAL(S) AT
 200%.
 PLEASE SEE THE RISK OF FIRE, LIFE SAFETY AND CAUSE TO
 PROPERTY DAMAGE CAN BE SUBSTANTIAL AND IT IS THE
 CONCERN OF THE OFFICE BASED ON OUR INFORMATION KNOWN
 AND PLEASE SEE STUDIES IN WHITE PAPERS FROM NUMEROUS
 MANUFACTURES OF ELECTRONIC/COMPUTER EQUIPMENT WHICH
 INDICATE AS MUCH AS 1.7 TIMES THE RATED LOAD OF THE
 CONDUCTOR OR CIRCUIT AND FEEDERS.
 PLEASE SEE THE FOLLOWING CODES: THIS OFFICE IS AWARE OF
 WHAT A FPN MEANS, HOWEVER SEE SOME SECTIONS GIVEN WHICH
 DO NOT CONTAIN FPN.PLEASE SEE 210.4A (FPN),310.10,
 310.15B4(C), 400.5, 520.44, 408.16.
 PLEASE SEE NFPA-70B, ANSI/IEEE 519 AND FBC 104.6
 ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY OF WEST
 PALM BEACH.
 PLEASE PROVIDE MORE INFORMATION ON WHAT STEPS WILL BE
 TAKEN TO ALLEVIATE THESE RISKS.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-09-10 Cont ID  
Sent By mawillia Date 2007-09-10 Time 14:16 Rev Time 0.00
Received By mawillia Date 2007-09-10 Time 14:00 Sent To P
Notes
2007-09-10 14:10:08*****APPROVED*****
  
 THE COMMENTS OF 07/26/2007 HAVE BEEN ADDRESSED; REVISED
 PLAN SHEETS LS1 AND E2 WERE STAMPED, INITIALED, AND
 DATED
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-07-26 Cont ID  
Sent By mawillia Date 2007-07-26 Time 19:11 Rev Time 0.00
Received By mawillia Date 2007-07-26 Time 18:43 Sent To  
Notes
2007-07-26 19:06:55*****UNSAT*****
  
  
 1.PLEASE EXPLAIN THE LACK OF EMERGENCY LIGHTING IN
 THE FOLLOWING LAB ROOMS 116, 117, 119 ON SHEET LS1.
  
 2.ON SHEET LS1, THE EMERGENCY LIGHTING IN LAB A (ROOM
 103 AND LAB B (ROOM 104)APPEARS TO BE DIVIDED BY BY A
 WALL.PLEASE EXPLAIN.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-05-08 Cont ID  
Sent By mawillia Date 2007-05-08 Time 11:02 Rev Time 0.00
Received By mawillia Date 2007-05-08 Time 10:34 Sent To  
Notes
2007-05-08 11:02:22*****APPROVED*****
  
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;PLAN SHEETS LS1 AND E2 WERE STAMPED,
 INITIALED, AND DATED.
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-03-20 Cont ID  
Sent By mawillia Date 2007-03-20 Time 11:37 Rev Time 0.00
Received By mawillia Date 2007-03-20 Time 10:26 Sent To  
Notes
2007-03-20 11:37:40*****DENIED*****
  
  
 1.PLEASE EXPLAIN THE DISCREPANCY ON SHEET LS 1
 (EXISTING CHILLER COMPOUND) COMPARED TO SHEET A 1
 (EXISTING COVERED PATIO) AREA.IF THIS AREA IS INDEED
 REFERENCED AS AN EXISTING CHILLER COMPOUND AREA,
 EXPLAIN WHAT THIS AREA IS AND ENTAILS.PLEASE BE
 ADVISED THAT IF THIS AREA IS IDENTIFIED AS MORE
 HAZARDOUS, EXITING OR EXIT ACCESS SHALL NOT BE THROUGH
 SUCH ROOMS OR SPACES.
  
 2.THE INTERIOR WALL AND CEILING FINISH MATERIALS
 SHALL BE CLASS A OR CLASS B IN EXITS AND EXIT ACCESS
 CORRIDORS, AND SHALL BE CLASS A, CLASS B, OR CLASS C IN
 ALL OTHER SPACES.PLEASE SPECIFY.
  
 3.IT IS STATED THAT THIS SPACE IS FULLY SPRINKLERED,
 WILL THE LOCATION OF FIRE SPRINKLER HEADS/DEVICES BE
 MODIFIED DUE TO THE SCOPE OF WORK?IF SO,SEPARATE
 PERMIT AND PLANS WILL BE REQUIRED FOR THE FIRE
 SPRINKLER REMODEL.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-09-07 Cont ID  
Sent By dpalmer Date 2007-09-07 Time 19:50 Rev Time 0.00
Received By dpalmer Date 2007-09-07 Time 19:50 Sent To  
Notes
2007-09-07 19:50:59TO COMM BOARD SPACE #61

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-08-30 Cont ID  
Sent By adarroug Date 2007-08-30 Time 11:58 Rev Time 0.00
Received By adarroug Date 2007-08-30 Time 11:58 Sent To  
Notes
2007-08-30 11:58:33WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-06-24 Cont ID  
Sent By adarroug Date 2007-06-24 Time 15:31 Rev Time 0.00
Received By adarroug Date 2007-06-24 Time 15:31 Sent To  
Notes
2007-07-09 15:32:01TO "COMM" BD#61
2007-06-24 15:31:31WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-16 Cont ID  
Sent By adarroug Date 2007-04-16 Time 10:11 Rev Time 0.00
Received By adarroug Date 2007-04-16 Time 10:11 Sent To  
Notes
2007-04-16 10:11:23TO "COMM" BD#15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-20 Cont ID  
Sent By mawillia Date 2007-03-20 Time 10:27 Rev Time 0.00
Received By mawillia Date 2007-02-06 Time 11:02 Sent To  
Notes
2007-02-12 16:00:25TO "COMM" BD#11
2007-02-06 11:02:34WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-10-22 Cont ID  
Sent By hmoser Date 2007-10-22 Time 09:56 Rev Time 0.00
Received By hmoser Date 2007-10-22 Time 09:56 Sent To  
Notes
2007-10-22 10:01:1910/22/07
 TEST & BALANCE REPORT OK . DICGARD EXTRA REPORT
 CONTRACTOR DOES NOT WANT IT ,HE SAID HE HAS EXTRA
 COPIES.
 HAROLD MOSER

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-07-17 Cont ID  
Sent By tgordon Date 2007-07-17 Time 13:49 Rev Time 0.25
Received By tgordon Date 2007-07-17 Time 13:49 Sent To  
Notes
2007-07-17 13:50:42REVISION TO MECH. PLANS PAGE M1 AND M2.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-02-26 Cont ID  
Sent By tgordon Date 2007-02-26 Time 13:46 Rev Time 0.30
Received By tgordon Date 2007-02-26 Time 13:46 Sent To  
Notes
***NONE***