| Plan Review Stops For Permit 07020042 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2007-09-08 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-09-08 |
Time |
11:29 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2007-09-08 |
Time |
11:29 |
Sent To |
|
|
| Notes |
| 2007-09-08 11:30:08 | REVISION# 4- OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2007-08-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-08-16 |
Time |
17:22 |
Rev Time |
1.33 |
| Received By |
jwitmer |
Date |
2007-08-16 |
Time |
17:22 |
Sent To |
|
|
| Notes |
| 2007-08-16 17:37:12 | BUILDING PLAN REVIEW | | | PERMIT: 07020042 | | | ADD: 1400 NORTHPOINT PARKWAY | | | CONT: BRICAR ENTERPRISES, INC | | | TEL: (954)675-1976 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1STREVIEW REVISION # 4 | | | ACTION: DENIED | | | | | | 1) SHEET A4 DETAIL P2 & P3 DOES NOT INDICATE HOW THE | | | TOP OF THE WALL WILL BE ANCHORED. IT CURRENTLY IS | | | FLOATING WITH NO LATERAL BRACING. | | | WHAT TYPE OF MATERIALS WILL BE USED IN THIS LAB, IS IT | | | TO BE CONSIDERED A CONTROLED AREA ?IF SO:414.2.3 | | | SEPARATION. | | | THE REQUIRED FIRE-RESISTANCE RATING FOR FIRE BARRIER | | | ASSEMBLIES SHALL BE IN ACCORDANCE WITH TABLE 414.2.2 . | | | THE FLOOR CONSTRUCTION OF THE CONTROL AREA , AND THE | | | CONSTRUCTION SUPPORTING THE FLOOR OF THE CONTROL AREA , | | | SHALL HAVE A MINIMUM 2-HOUR FIRE-RESISTANCE RATING. | | | | | | 2) PLEASE PROVIDE THE CRITERIA TO DETERMINE THE 5 LBS. | | | PER SQ FT FOR BOTH STRESS AND DEFLECTION REQUIREMENTS, | | | WHAT ARE THE DEFLECTION LIMITS? | | | | | | BUILDING PLAN REVIEW II | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2007-05-30 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2007-05-30 |
Time |
15:11 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2007-05-30 |
Time |
15:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-03-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-03-09 |
Time |
16:38 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2007-03-09 |
Time |
16:38 |
Sent To |
FIRE |
|
| Notes |
| 2007-03-09 16:58:51 | BUILDING PLAN REVIEW | | | PERMIT: 07020042 | | | ADD: 1400 NORTHPOINT PRKY# 10 | | | CONT: FISHER CONSTRUCTION | | | TEL: (561758-6545 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1STREVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2 ) FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF | | | THE COURT. | | | NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS | | | NOT ACTUALLY | | | COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF, | | | SUCH NOTICE IS | | | NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE | | | OF | | | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST | | | INSPECTION. | | | | | | 3) 106.1.2*ADDITIONAL INFORMATION REQUIRED, THE PLANS | | | INDICATE ROOMS 106 & 110 TO BE ELECTRICAL ROOMS? IS | | | THERE ANY GAS CYLINDERS IN EITHER OF TTHESE ROOMS? IF | | | SO WHAT TYPE OF GASSES ARE THERE AND IN WHAT SIZE | | | CYLINDERS, POUNDS OR GALLONS? | | | THIS SITE WAS PERMITTED WITH THESE ROOMS BEING | | | EXPLOSION PROOF ROOMS WITH BLOW OUT PANELS THROUGH THE | | | ROOF AS WELL AS THE WALLS AND DOORS BECAUSE OF THE | | | HYDROGEN | | | CYLINDERS BEING HOUSED IN THESE ROOMS. THERE WAS ALSO A | | | KNOX BOX INCORPORATED INTO THE SITE WITH MSDS SHEETS AS | | | TO THE CHEMICALS BEING STORED AND THE QUANITIES. THIS | | | SITE WAAS CONSIDERED A BUSINESS OCCUPANCY WITH CONTROL | | | AREAS, ARE ANY OF THE LABS ADDING EQUIPMENT REQUIRING | | | PIPING, AND OR VENTILATION? | | | | | | 4)ROOMS 116, 117B & 119B PLEASE SEE ACCESSIBLE | | | DOORS, | | | 11-4.13.6 MANEUVERING CLEARENCES | | | AT DOORS. MINIMUM MANEUVERING CLEARANCES | | | AT DOORS THAT ARE NOT AUTOMATIC OR | | | POWER-ASSISTED SHALL BE AS SHOWN IN | | | FIG. 25. THE FLOOR OR GROUND AREA WITH | | | IN THE REQUIRED CLEARANCES SHALL BE | | | CLEAR & LEVEL. | | | | | | 5) DISCREPANCY BETWEEN LS-1 AND A1 IN THE AREA OF | | | COVERED PATIO VS BEING AN AREADESIGNATED AS A CHILLER | | | COMPOUND? LS PLAN INDICATES 2 MEANS OF EGRESS TRAVELING | | | THROUGH THE | | | CHILLER COMPOUND, IF THIS IS SUCH AN AREA WOULDN'T THE | | | GATES BE LOCKED , FOR AUTHORIZED PERSONEL ONLY? | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2007-09-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-09-07 |
Time |
20:08 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-09-07 |
Time |
19:50 |
Sent To |
|
|
| Notes |
| 2007-09-07 20:09:13 | 2007-09-07 20:09:13 | | | | | | REV OK,STAMPED ELEC SHEETS. | | | | | | PENDING FIRE REVIEW |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2007-07-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-07-04 |
Time |
09:54 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-07-04 |
Time |
08:59 |
Sent To |
I |
|
| Notes |
| 2007-07-04 09:54:54 | 2007-07-04 09:54:54 | | | | | | ** UNSAT ** | | | | | | | | | 1) NOTE: PLEASE SUBMIT REVISED ENERGY CALCULATIONS. | | | PLEASE SEE THE ENERGY CALCULATION AS SUBMITTED UNDER | | | PERMIT APPLICATION WERE THE INCORRECT VERSION. PLEASE | | | SEE THE VERSION SUBMITTED WAS 2.1 WHICH WAS IN EFFECT | | | ON THE PREVIOUS REVISIONS TO THE FBC AND NOT IN EFFECT | | | AFTER DECEMBER 8TH, 2006. PLEASE SEE THE REVISED ENERGY | | | CALCULATIONS ARE NEEDED AS LIGHTING HAS BEEN REVISED. | | | 13-415.1.C, 13-415.2 | | | | | | 2) NOTE: PLEASE CLARIFY THE FOLLOWING ROOMS AS THESE | | | ARE NOTED ON PLANS AS EXISTING HOWEVER THE LIGHTING | | | APPEARS TO BE SHOWN BEING REPLACED? PLEASE SEE OTHER | | | ROOMS WHICH ARE EXISTING INDICATE LIGHTING AS *LT GRAY* | | | AND DASHED LINES. PLEASE KNOW ANY OF THESE FOLLOWING | | | ROOMS WHICH LIGHTING FIXTURES ARE BEING REPLACED OR | | | CONTROL DEVICES ARE BEING CHANGED/REPLACE OR RELOCATED | | | WILL BE REQUIRED TO MEET THE FBC CHAPTER 13 AS OTHER | | | ROOMS ARE DONE. | | | PLEASE SEE THE ROOMS ARE AS NOTED: | | | LAB E, GUEST LOUNGE, OFFICES 131-137. 13-415.1.1,.1.2, | | | 13-101 | | | | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES | | | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | 2007-07-04 09:01:07 | 2007-07-04 09:01:07 | | | PLANS REMOVED FROM INCOMING, WILL RETURN TO INCOMING | | | ONCE ELECTRICAL REVIEW IS DONE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2007-04-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-04-18 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-04-18 |
Time |
15:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-02-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-02-13 |
Time |
12:15 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-02-13 |
Time |
09:53 |
Sent To |
|
|
| Notes |
| 2007-02-13 12:19:11 | *** UNSAT *** | | | | | | | | | 1) NOTE: PLEASE SEE THE CODE WHICH SHOULD BE STATED ON | | | PLANS ARE THE 2005 NFPA-70 AND THE 2004 FBC 2006 | | | REVISIONS. | | | PLEASE SEE THE OTHER CODES REFLECTED ON ELECTRICAL | | | PLANS ARE OK AND CURRENT. | | | | | | ** ALL PERMIT APPLICATIONS WHICH ARE APPLIED FOR AFTER | | | DECEMBER 8TH, 2006 FALL UNDER THE NEW CODES. | | | | | | 2) NOTE: PLEASE SEE THE EGRESS PATH ON THE LIFE SAFETY | | | PLAN DOES NOT CORRELATE WITH THE ELECTRICAL PLANS AND | | | ARCHITECTURAL SHEETS FOR THE LAYOUT OF FURNITURE ETC. | | | PLEASE SEE BUILDING AND FIRE REVIEW COMMENTS AS THIS | | | MAY DIRECTLY AFFECT THE EGRESS PATHS AND ELECTRICAL | | | LAYOUTS FOR EQUIPMENT/CUBICLES ETC | | | LS 101 | | | | | | 3) NOTE: PLEASE CLARIFY USE AND OCCUPANCY AS THE PLANS | | | MENTIONS "LAB", HOWEVER WHAT TYPE OF LAB WORK IS BEING | | | DONE, WHAT TYPE PF MATERIALS ETC. | | | PLEASE SEE NEC 500. | | | REVIEW FOR USE AND ELECTRICAL CAN NOT BE VERIFIED AT | | | THIS TIME. | | | | | | 4) NOTE: PLEASE CLARIFY NOTE WHICH MENTIONS THE ENTIRE | | | SPACE IS GOING TO HAVE CONTROLS IN FOR CHAPTER 13 | | | REQUIREMENTS HOWEVER THE PLANS DO NOT CORRELATE WITH | | | THE ENTIRE SPACE? | | | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. | | | PLEASE SEE THERE ARE SOME AREAS WHICH WALL SWITCH TYPE | | | OCCUPANCY DEVICES ARE BEING INDICATED FOR HALL AND | | | LARGER OPEN AREAS, HOWEVER THE WALL DEVICE DOES NOT | | | SEEM IT WILL PROVIDE THE COVERAGE AS NEEDED FOR | | | LIGHTING CONTROL FOR THE OCCUPANTS. PLEASE SEE THE | | | POSSIBILITY OF CEILING MOUNTED DEVICES IN HALLS AND | | | LARGER AREAS. (WALLS AND OTHER OBSTRUCTIONS WILL | | | INTERFERE WITH WALL DEVICES). | | | PLEASE SEE HALLS ALSO. | | | | | | *PLEASE PROVIDE LIGHTING PERFORMANCE CALCULATIONS FOR | | | NEW FIXTURES AND LPD AS STATED IN 13-415.2. | | | | | | 5) NOTE: PLEASE SEE RISER SHOWS PANEL TSC AND EPA, | | | HOWEVER THESE WERE NOT SUBMITTED. PLEASE CLARIFY. | | | 408.4, 310.16, 240.4. | | | FBC 106.1.2 ADMIN SECTION. | | | | | | | | | 6) NOTE: PLEASE PROVIDE CALCULATIONS ON NEUTRAL | | | CONDUCTORS FOR ALL NON-LINEAR CIRCUITS. PLEASE SEE ALL | | | CIRCUITS WHICH CONTAIN THESE LOADS SHALL MEET THE | | | SIZING REQUIREMENTS TO HANDLE AND ALLEVIATE THE OVER | | | LOADING OF THE NEUTRAL ON A 3-PHASE 4-WIRE SYSTEM WITH | | | PREDOMINATELY OR ACTUALLY IN MANY CASES ALL NON-LINEAR | | | LOADS. PLEASE SEE THIS CAN BE DONE BY USING MANY | | | METHODS, K-RATED TRANSFORMERS, FULL NEUTRAL LOAD | | | CALCULATION ON EACH CIRCUIT AND FEEDERS BASED ON ALL | | | NON-LINEAR LOADS OR THE SIZING OF THE NEUTRAL(S) AT | | | 200%. | | | PLEASE SEE THE RISK OF FIRE, LIFE SAFETY AND CAUSE TO | | | PROPERTY DAMAGE CAN BE SUBSTANTIAL AND IT IS THE | | | CONCERN OF THE OFFICE BASED ON OUR INFORMATION KNOWN | | | AND PLEASE SEE STUDIES IN WHITE PAPERS FROM NUMEROUS | | | MANUFACTURES OF ELECTRONIC/COMPUTER EQUIPMENT WHICH | | | INDICATE AS MUCH AS 1.7 TIMES THE RATED LOAD OF THE | | | CONDUCTOR OR CIRCUIT AND FEEDERS. | | | PLEASE SEE THE FOLLOWING CODES: THIS OFFICE IS AWARE OF | | | WHAT A FPN MEANS, HOWEVER SEE SOME SECTIONS GIVEN WHICH | | | DO NOT CONTAIN FPN.PLEASE SEE 210.4A (FPN),310.10, | | | 310.15B4(C), 400.5, 520.44, 408.16. | | | PLEASE SEE NFPA-70B, ANSI/IEEE 519 AND FBC 104.6 | | | ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY OF WEST | | | PALM BEACH. | | | PLEASE PROVIDE MORE INFORMATION ON WHAT STEPS WILL BE | | | TAKEN TO ALLEVIATE THESE RISKS. | | | | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2007-09-10 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-09-10 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-09-10 |
Time |
14:00 |
Sent To |
P |
|
| Notes |
| 2007-09-10 14:10:08 | *****APPROVED***** | | | | | | THE COMMENTS OF 07/26/2007 HAVE BEEN ADDRESSED; REVISED | | | PLAN SHEETS LS1 AND E2 WERE STAMPED, INITIALED, AND | | | DATED | | | | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2007-07-26 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-07-26 |
Time |
19:11 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-07-26 |
Time |
18:43 |
Sent To |
|
|
| Notes |
| 2007-07-26 19:06:55 | *****UNSAT***** | | | | | | | | | 1.PLEASE EXPLAIN THE LACK OF EMERGENCY LIGHTING IN | | | THE FOLLOWING LAB ROOMS 116, 117, 119 ON SHEET LS1. | | | | | | 2.ON SHEET LS1, THE EMERGENCY LIGHTING IN LAB A (ROOM | | | 103 AND LAB B (ROOM 104)APPEARS TO BE DIVIDED BY BY A | | | WALL.PLEASE EXPLAIN. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2007-05-08 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-05-08 |
Time |
11:02 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-05-08 |
Time |
10:34 |
Sent To |
|
|
| Notes |
| 2007-05-08 11:02:22 | *****APPROVED***** | | | | | | | | | ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE | | | BEEN ADDRESSED;PLAN SHEETS LS1 AND E2 WERE STAMPED, | | | INITIALED, AND DATED. | | | | | | | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-03-20 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-03-20 |
Time |
11:37 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-03-20 |
Time |
10:26 |
Sent To |
|
|
| Notes |
| 2007-03-20 11:37:40 | *****DENIED***** | | | | | | | | | 1.PLEASE EXPLAIN THE DISCREPANCY ON SHEET LS 1 | | | (EXISTING CHILLER COMPOUND) COMPARED TO SHEET A 1 | | | (EXISTING COVERED PATIO) AREA.IF THIS AREA IS INDEED | | | REFERENCED AS AN EXISTING CHILLER COMPOUND AREA, | | | EXPLAIN WHAT THIS AREA IS AND ENTAILS.PLEASE BE | | | ADVISED THAT IF THIS AREA IS IDENTIFIED AS MORE | | | HAZARDOUS, EXITING OR EXIT ACCESS SHALL NOT BE THROUGH | | | SUCH ROOMS OR SPACES. | | | | | | 2.THE INTERIOR WALL AND CEILING FINISH MATERIALS | | | SHALL BE CLASS A OR CLASS B IN EXITS AND EXIT ACCESS | | | CORRIDORS, AND SHALL BE CLASS A, CLASS B, OR CLASS C IN | | | ALL OTHER SPACES.PLEASE SPECIFY. | | | | | | 3.IT IS STATED THAT THIS SPACE IS FULLY SPRINKLERED, | | | WILL THE LOCATION OF FIRE SPRINKLER HEADS/DEVICES BE | | | MODIFIED DUE TO THE SCOPE OF WORK?IF SO,SEPARATE | | | PERMIT AND PLANS WILL BE REQUIRED FOR THE FIRE | | | SPRINKLER REMODEL. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2007-09-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-09-07 |
Time |
19:50 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-09-07 |
Time |
19:50 |
Sent To |
|
|
| Notes |
| 2007-09-07 19:50:59 | TO COMM BOARD SPACE #61 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-08-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-08-30 |
Time |
11:58 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-08-30 |
Time |
11:58 |
Sent To |
|
|
| Notes |
| 2007-08-30 11:58:33 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-06-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-24 |
Time |
15:31 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-24 |
Time |
15:31 |
Sent To |
|
|
| Notes |
| 2007-07-09 15:32:01 | TO "COMM" BD#61 | | 2007-06-24 15:31:31 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-04-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-04-16 |
Time |
10:11 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-04-16 |
Time |
10:11 |
Sent To |
|
|
| Notes |
| 2007-04-16 10:11:23 | TO "COMM" BD#15 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-03-20 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-03-20 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-02-06 |
Time |
11:02 |
Sent To |
|
|
| Notes |
| 2007-02-12 16:00:25 | TO "COMM" BD#11 | | 2007-02-06 11:02:34 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2007-10-22 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2007-10-22 |
Time |
09:56 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2007-10-22 |
Time |
09:56 |
Sent To |
|
|
| Notes |
| 2007-10-22 10:01:19 | 10/22/07 | | | TEST & BALANCE REPORT OK . DICGARD EXTRA REPORT | | | CONTRACTOR DOES NOT WANT IT ,HE SAID HE HAS EXTRA | | | COPIES. | | | HAROLD MOSER |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2007-07-17 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-07-17 |
Time |
13:49 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2007-07-17 |
Time |
13:49 |
Sent To |
|
|
| Notes |
| 2007-07-17 13:50:42 | REVISION TO MECH. PLANS PAGE M1 AND M2. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2007-02-26 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-02-26 |
Time |
13:46 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2007-02-26 |
Time |
13:46 |
Sent To |
|
|
| Notes |
|
|