Plan Review Details - Permit 07011380
Plan Review Stops For Permit 07011380
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-04-09 Cont ID  
Sent By mjacobs Date 2007-04-09 Time 07:15 Rev Time 0.00
Received By mjacobs Date 2007-04-09 Time 06:01 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-03-16 Cont ID  
Sent By mjacobs Date 2007-03-16 Time 09:41 Rev Time 0.00
Received By mjacobs Date 2007-03-16 Time 07:40 Sent To  
Notes
2007-03-16 09:41:30BUILDING PLAN REVIEW
 PERMIT: 07011380
 ADD: 224 ALPINE RD
 CONT: 3 - HOMES INC.
 TEL: (561)433-3440
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)THE VALUE IS TO LOW, WPB.AMENDMENTS 108.3IF IN
 THE OPINION OF THE BUILDING OFFICIAL, THE CLAIMED
 VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION, THEPERMIT
 SHALL BE DENIED, OUR VALUATION REFERENCE IS ICC (BVD),
 MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES. THE
 VALUE NEEDS ADJUSTING TO A FAIR MARKET VALUE, IF THE
 VALUE IS NOT ADJUSTED, WE WILL ADJUST THE VALUE TO A
 FAIR MARKET VALUE.
  
 3)SEE 2004 FLORIDA RESIDENTIAL BUILDING CODE CH.41
 FOR MORE INFORMATION. ALSO SEPERATE PERMIT IS REQUIRED
 FOR THE FENCE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-02-27 Cont ID  
Sent By mjacobs Date 2007-02-27 Time 16:36 Rev Time 0.00
Received By mjacobs Date 2007-02-27 Time 12:06 Sent To PC
Notes
2007-02-27 14:05:55BUILDING PLAN REVIEW
 PERMIT: 07011380
 ADD: 224 ALPINE RD
 CONT: 3-D HOMES INC.
 TEL: (561)433-3440
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)THE VALUE IS TO LOW.WPB AMENDMENTS 108.3IF IN
 THE OPINION OF THE BUILDING OFFICIAL, THE CLAIMED
 VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION, THE PERMIT
 SHALL BE DENIED. OUR VALUATION REFERENCE IS ICC (BVD),
 MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES.
  
 4)INDICATE ON THE DRAWINGS THE LOCATION OF THE 4 POOL
 LIGHTS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-02-21 Cont ID  
Sent By btrobaug Date 2007-02-21 Time 06:52 Rev Time 0.33
Received By btrobaug Date 2007-02-21 Time 06:40 Sent To P
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2007-02-21 Cont ID  
Sent By mperson Date 2007-02-21 Time 08:52 Rev Time 0.00
Received By mperson Date 2007-02-21 Time 08:52 Sent To B
Notes
2007-02-21 08:54:37NOTE: REFERENCE PLUMBING COMMENTS.
  
 CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL POOL INSPECTION.
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-03-27 Cont ID  
Sent By spalmer Date 2007-03-27 Time 17:34 Rev Time 0.00
Received By spalmer Date 2007-03-27 Time 17:34 Sent To P
Notes
2007-03-27 17:34:56TO MIKE PERSON

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-03-22 Cont ID  
Sent By adarroug Date 2007-03-22 Time 16:09 Rev Time 0.00
Received By adarroug Date 2007-03-22 Time 16:09 Sent To Z
Notes
2007-03-22 16:10:14TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-03-06 Cont ID  
Sent By adarroug Date 2007-03-06 Time 10:26 Rev Time 0.00
Received By adarroug Date 2007-03-06 Time 10:26 Sent To P
Notes
2007-03-06 10:26:32TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-05 Cont ID  
Sent By adarroug Date 2007-03-05 Time 15:29 Rev Time 0.00
Received By adarroug Date 2007-03-05 Time 15:29 Sent To Z
Notes
2007-03-05 15:30:09TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-20 Cont ID  
Sent By adarroug Date 2007-02-20 Time 17:36 Rev Time 0.00
Received By adarroug Date 2007-02-20 Time 17:36 Sent To E
Notes
2007-02-20 17:36:25TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-02-27 Time   Rev Time 0.00
Received By adarroug Date 2007-02-02 Time 09:17 Sent To  
Notes
2007-02-02 09:17:43TO "Z" BOX

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-04-05 Cont ID  
Sent By mperson Date 2007-04-05 Time 09:28 Rev Time 0.33
Received By mperson Date 2007-04-05 Time 09:28 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-03-14 Cont ID  
Sent By mperson Date 2007-03-14 Time 15:02 Rev Time 0.33
Received By mperson Date 2007-03-14 Time 15:02 Sent To B
Notes
2007-03-14 15:21:52DENIED 2ND TIME
 REFERENCE: FBC-2004 SECTIONS 424.2 OR R4101 SWIMMING
 POOLS.
  
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1. **OK**
  
 2. **OK**
  
 3. **OK**
  
 4. **OK**
  
 5. **OK**
  
 **THE FOLLOWING ARE NEW COMMENTS**
  
 6. SHEET 2/4 VENT PIPE MAXIMUM LENGTH TABLE INDICATES
 THE VENT SIZE AT ONE INCH (1") BUT ALL OF THE
 RESUBMITTED CORRECTION ARE INDICATING 1-1/2" PLEASE
 CORRECT AND RESUBMIT THE VENT PIPE MAXIMUM LENGTH TABLE
 CORRELATED WITH THE RESUBMITTED CORRECTIONS.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-02-21 Cont ID  
Sent By mperson Date 2007-02-21 Time 08:33 Rev Time 0.33
Received By mperson Date 2007-02-21 Time 08:33 Sent To G
Notes
2007-02-21 08:51:49DENIED
 REFERENCE: FBC-2004 SECTION 424.2 OR R4101 SWIMMING
 POOLS.
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1) COMPLY WITH FBC-2004 SEC 424.2, OR
 FBCR-2004 SEC R4101 PRIVATE SWIMMING
 POOLS. (PLEASE ADD TO NOTES ON THE RESUBMITTAL)
  
 2) SHEETS 1/4 AND 2/4 INDICATE AN 1" VENT LINE BUT
 SHEET 3/4 INDICATES AN 1-1/2" VENT LINE ON THE MAIN
 DRAIN AND VENT LINE DETAIL. PLEASE CORRELATE THE VENT
 SIZE PIPING ON THE RESUBMITTAL.
  
 3) FBC-2004 SEC. 424.2.14.1, OR
 FBCR-2004 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (MANUFACTURE
 SHEETS REQUIRED, PLEASE SUBMIT)
  
 4) FBC-2004 SEC. 424.2.14.2, OR
 FBCR-2004 SEC. R4101.14.2 WATER
 RETENTION, PROVIDE A POSITIVE MEANS OF
 RETAINING WATER IN THE HEATER WHEN PUMP
 IS SHUT OFF.(MANUFACTURE SHEETS
 REQUIRED, PLEASE SUBMIT)
  
 5) FBC-2004 SEC. 424.2.14, OR FBCR-2004
 SEC. R4101.15 GAS PIPING SHALL COMPLY
 WITH FBC FUEL GAS.SEPARATE PLANS AND
 PERMIT REQUIRED. (PLEASE ADD TO NOTES ON THE
 RESUBMITTAL)
  
 ******IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2007-03-26 Cont ID  
Sent By adavila Date 2007-03-26 Time 17:48 Rev Time 0.00
Received By adavila Date 2007-03-26 Time 17:48 Sent To I
Notes
2007-03-26 17:49:01PER ERIC SCHNEIDER, PRINCIPAL PLANNER.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-03-05 Cont ID  
Sent By adavila Date 2007-03-05 Time 17:18 Rev Time 0.00
Received By adavila Date 2007-03-05 Time 17:12 Sent To I
Notes
2007-03-05 17:22:50PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1.PLEASE PROVIDE THE LOCATION OF THE POOL EQUIPMENT
 ON THE SURVEY WITH SETBACK DIMENSIONS (REPEAT
 COMMENT).
  
 2.PER SECTION 94-304(D)(2)(B) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS, EVERY SWIMMING POOL SHALL BE
 ENCLOSED BY A FENCE OR SIMILAR STRUCTURE WHICH IS
 INSTALLED TO OBSTRUCT ACCESS BY OTHER THAN THE OWNERS
 OR OCCUPANTS OF THE RESIDENCE WITHIN WHICH A SWIMMING
 POOL IS LOCATED.PLEASE SHOW THE LOCATION OF FENCE ON
 SURVEY.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-02-14 Cont ID  
Sent By adavila Date 2007-02-14 Time 16:54 Rev Time 0.00
Received By adavila Date 2007-02-12 Time 14:26 Sent To I
Notes
2007-02-14 16:56:11PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.
2007-02-12 14:28:00DENIED,
 1. PLEASE PROVIDE TWO COPIES OF SURVEYS SHOWING THE
 PROPOSED POOL WITH DISTANCE FROM PROPERTY LINE (SIDE &
 REAR).
 2. PLEASE SHOW THE LOCATION OF THE PROPOSED POOL
 EQUIPMENT WITH SETBACKS ON THE TWO COPIES OF SURVEYS.
 3. NO SURVEYS WERE SUBMITTED IN PACKAGE.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720