Plan Review Details - Permit 07011298
Plan Review Stops For Permit 07011298
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-15 Cont ID  
Sent By jgomez Date 2007-03-15 Time 18:52 Rev Time 3.00
Received By jgomez Date 2007-03-15 Time 18:51 Sent To  
Notes
2007-03-15 18:57:30BUILDING REVIEW CHECKLIST:
 1- AFTER PLANS ARE REVISED BY THE ENGINEER, BRING THEM
 TO PALM BEACH COUNTY(2300 N. JOG RD. (561)233-5115)
 TO PAY IMPACT FEES. BRING BACK STAMPED PLANS AND COPY
 OF PAID RECEIPT.
  
 2- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 3- PROVIDE TWO COPIES OF EVERYTHING: PLANS, ENERGY
 CALCULATIONS, PRODUCT APPROVALS, SURVEYS, ETC.
  
 4- ENERGY CALCULATIONS:
 A) NEED TO BE LEGIBLE.
  
 B) REVISESQUARE FOOTAGE OFEXTERIOR WALL AREA.
  
 C) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM
  
 5- PROVIDE DRAINAGE PLAN AS REQUIRED BY SEC. R401.3
 2004 FLORIDA RESIDENTIAL CODE. ALSO, RAIN WATER CAN'T
 BE DIRECTED TO NEIGHBOR'S PROPERTY.
  
 6- BUILDING VALUATION DECLARED ON THE PERMIT
 APPLICATION IS TOO LOW.VALUE UPDATED TO $125,620.
 OWES $1773.76 THIS IS THE TOTAL PERMIT FEE.
  
 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) ROOF SHINGLES.
 B) EXTERIOR DOORS.
 C) STORM SHUTTERS.
 D) SINGLE HUNG WINDOWS.
 E) ALL STRUCTURAL CONNECTORS SPECIFIED ON PLANS.
  
 8- SPECIFY ATTIC ACCESS AS REQUIRED BY SEC. R807 2004
 FLORIDA RESIDENTIAL CODE.
  
 9- WHERE IS THE EXISTING KITCHEN LOCATED AND HOW IS
 THAT ROOM GOING TO BE REMODELED. ZONING DOESN'T ALLOW 2
 KITCHENS IN THE SAME RESIDENCE.
  
 10- PROVIDE COMPLETE INFORMATION FOR STORM SHUTTERS,
 INCLUDING PRODUCT APPROVAL AND COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED COPY OF INSTALLATION SCHEDULE.
  
 11- ENGINEER TO PROVIDE THE FIRM' S CERTIFICATE OF
 AUTHORIZATIONNUMBER AS REQUIRED BY 61G15-23.002 OF
 FLORIDA ADMINISTRATIVE CODE.
  
 12- SHEET A1:
 A) SITE PLAN DOESN'T SHOW NEW LAUNDRY.
  
 B) INFORMATION ON STRUCTURAL NOTES AND DESIGN
 PARAMETERS AND ANALYSIS DON'T MATCH.REVISE LIVE AND
 DEAD LOADS AS REQUIRED.
  
 C) SPECIFYALLLIVE LOADS INCLUDING UNIFORMLY
 DISTRIBUTED LIVE LOADS AS REQUIRED BY TABLE R301.5 2004
 FLORIDA RESIDENTIAL CODE.
  
 D) DESIGN PARAMETERS AND ANALYSIS:
 * ROOF PITCH DOESN'T MATCH ELEVATIONS. REVISE AS
 REQUIRED.
 ** WHY FLOOR LOADS IS N/A?
 *** PROVIDE CALCULATIONS FOR DOOR AND WINDOW DESIGN
 PRESSURES AND CLEARLY IDENTIFYIF THEY ARE LOCATED IN
 THE END OR INTERIOR ZONE.DESIGN PRESSURES CAN'T BE
 THE SAME FOR INTERIOR AND END ZONES. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
 **** THERE IS NO MEAN BUILDING HEIGHT, BUT MEAN ROOF
 HEIGHT. AND, MEAN ROOF HEIGHT IS INCORRECT. WHERE IS IT
 TAKEN FROM?REVISE AS REQUIRED.
  
  
 13- SHEET A2:
 A) SPECIFY SAFETY GLASS FOR WINDOWS BY BATHROOM TUB
 AREA AS REQUIRED BY SEC. R308.4 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 B) SPECIFY SAFETY GLASS FOR WINDOW NEXT TO THE DOOR
 IN FAMILY ROOM AREA IN NORTH WALL. SEC. R308.4 2004
 FLORIDA RESIDENTIAL CODE.
  
 C) IDENTIFY ROOM THAT CONNECTS EXISTING HOUSE TO THE
 NEW ADDITION. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 D) PROVIDE COMPLETE SPECIFICATIONS FOR ATTACHMENT OF
 NEW FOOTING TO EXISTING FOOTING.RE-BARS SHOWN, BUT NO
 INFORMATION WAS GIVEN. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 E) SPECIFICATIONS FOR CONCRETE SLAB ARE NOT CLEAR.
 IS IT FIBER MESH OR WELDED WIRE MESH?. REVISE AS
 REQUIRED.
  
 F) SPECIFY DROP AT EXTERIOR DOORS. INCLUDING LAUNDRY
 ROOM.ONLY ONE DOOR PROVIDED THIS INFORMATION.
  
 G) SPECIFY WHAT FINISH MATERIAL IS GOING TO BE
 OUTSIDE SWING DOORS. CONCRETE, PAVERS?. SHOW ON PLANS.
 INCLUDING OUTSIDE OF LAUNDRY AREA.. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 14- SHEET A3:WEST ELEVATION SHOWS PITCHED ROOF AT
 LAUNDRY AREA. CURRENT CARPORT HAS A FLAT ROOF. REVISE
 AS REQUIRED.
  
 15- SHEET A4:
 A) THERE IS NOT ROOF FRAMING INFORMATION FOR NEW
 LAUNDRY AREA. PROVIDE COMPLETE INFORMATION.
  
 B) ROOF TRUSSES ABOVE EXISTING ROOF ARE DESIGNED
 WITH LINEAR UPLIFT LOADS, NO AT THE ENDS. SEE TRUSS
 PACKAGE. SPECIFY CONNECTORS AS REQUIRED.
  
 C) SPECIFIED CONNECTORS NEED TO RESIST CALCULATED
 ALL THE UPLIFT LOADS.CONNECTORS DON'T RESIST
 ENGINEERED TRUSSES CALCULATED UPLIFT LOADS ON SOME
 TRUSSES. REVIEW ENGINEERED TRUSSES AND REVISE AS
 REQUIRED.
  
 D) ENGINEEROF RECORD TOSPECIFY CALCULATED UPLIFT
 LOADS. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 E) ENGINEER OF RECORD TO SPECIFY SUPPORTS (COLUMNS)
 TO RECEIVE GIRDER TRUSSES. SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004.
  
 F) ENGINEER OF RECORD TO CLARIFY WHY SPECIFYING
 2-SIMPSON MTS 20CONNECTORSFOR ROOF TRUSSES ON WEST
 SIDE ROOF, WHILE SPECIFYING ONLY ONE ON EAST SIDE ROOF.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 16- SHEET A5:
 A) DOOR JAMB DETAIL: CLARIFY WHY USING TAPCONS
 INSTEAD OF WOOD SCREWS.PROVIDE MANUFACTURER SPECS
 FOR TAPCONS IN WOOD CONSTRUCTION. SPECIFY HOW LONG ARE
 THE TAPCONS. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 ***NOTE: SAME COMMENT APPLIES TO WINDOW JAMB DETAIL.
  
 B) FRAME WALL DETAIL DOESN'T MATCH WINDOW/DOOR JAMB
 DETAIL.. NUMBER OF STUDS TO MATCH. REVISE AS REQUIRED.
  
 C) FRAME WALL DETAIL:
 * USING 2X4 OR 2X6 STUDS. DETAIL CALLS FOR BOTH
 SIZES. REVISE AS REQUIRED.
 ** PROVIDE HEADER SPECIFICATIONS. THERE IS NOT
 INFORMATION ON PLAN. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 D) WALL SECTION:
 * THERE ARE NO SPECIFICATIONS FOR WALL SHEATHING.
 SPECIFY THICKNESS, AND NAIL SIZE AND SPACING. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
 ** THERE ARE NO SPECIFICATIONS FOR ATTACHMENT OF
 BOTTOM PLATE AND TYPE OF WOOD. SPECIFY TREATED WOOD AND
 ANCHOR SIZE AND SPACING. SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004.
 *** CONCRETE SLAB INFORMATION DOESN'T MATCH
 INFORMATION IN FOUNDATION PLAN.
 **** PROVIDE SPECIFICATIONS SHOWING COMPLIANCE WITH
 SEC. R319.1(5) OF 2004 FLORIDA RESIDENTIAL CODE.
  
 17- TRUSS PACKAGE:
 A) ENGINEER OF RECORD TO REVIEW AND APPROVE TRUSSES
 PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 B) ALL ENGINEER DRAWINGS TO HAVE ENGINEER'S ORIGINAL
 SEAL, SIGNATURE AND DATE AS REQUIRED BY SEC. 471
 FLORIDA STATUTE AND SEC. 61G15-23.002 FLORIDA
 ADMINISTRATIVE CODE.
  
 C) ENGINEER TO PROVIDE ALL HIS INFORMATION IN ALL
 DRAWINGS AS REQUIRED BY SEC. 61G15-23.002 FLORIDA
 ADMINISTRATIVE CODE.
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-02-20 Cont ID  
Sent By btrobaug Date 2007-02-14 Time 13:21 Rev Time 1.00
Received By btrobaug Date 2007-02-14 Time 07:45 Sent To M
Notes
2007-02-14 13:21:07 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE ENGINEER OF RECORD SHALL INDICATE THE
 CERTIFICATE OF AUTHORIZATIONNUMBER ALONG WITH OTHER
 INFORMATION REQUIRED BY 61G15-23.002FLORIDA
 ADMINISTRATIVE CODE.
  
 2} THE ENGINEER OF RECORD MUST SEAL THE DOCUMENTS WITH
 A SEALACCEPTABLETO THE BOARD PER 61G15-23.001, AND
 ILLUSTRATED IN SAME.
  
 3} IF THE SERVICE IS TO BE MOVED OR UPGRADED, TH
 FOLLOWING IS APPLICABLE.
 A) SHOW THE PHYSICAL LOCATION OF ALL SERVICE
 EQUIPMENT ON THE PLAN. 215.5.
 B) PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 4} ALL RECEPTS SERVING KITCHEN COUNTERSPACE MUST BE
 GFI/GFIPROTECTEDAS REQUIRED PER 210.8(A)(6). INDICATE
 SAME ON PLAN.
  
 5} LIST THE REQ'D ARCFAULT PROTECTED CURCUIT(S) ON
 PANELSCHEDULE. PLEASE SEE THAT ALL "OUTLETS"IN BEDROOMS
 ARE TO BE PROTECTED ,INCLUDING, LTS, RECEPTS, SD'S
 ETC.
  
 6} PROVIDE A LOAD CALCULATION PER 220.31, INCLUDE ADDED
 LOADS. THE ONE ON THE PLAN IS INCOMPLETE.
  
 7} BATH CIRCUITS ARE REQUIRED TO HAVE A 20 AMP
 RECEPTACLE PER 210.11(C) (3), THE SCHEDULE ALSO
 MENTIONS GENERAL LIGHTING ON THE CIRCUIT IN VIOLATION.
  
 NOTE: IT IS PROHIBITED TO HAVE TWO COOKING FACILITIES
 IN A SINGLE FAMILY RESIDENCE. IT THE KITCHEN ON THE
 PLANS IS THE SECOND ONE IT MUST BE REMOVED. CALL ZONING
 @ 805-6720.
  
 TWO SETS OF ALL CONSTRUCTION DOCUMENTS ARE REQUIRED FOR
 REVIEW PER 106.1 FBC AS AMENDED.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-12 Cont ID  
Sent By adarroug Date 2007-02-12 Time 11:19 Rev Time 0.00
Received By adarroug Date 2007-02-12 Time 11:19 Sent To E
Notes
2007-02-12 11:19:19TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-15 Cont ID  
Sent By jgomez Date 2007-03-15 Time 18:57 Rev Time 0.00
Received By jgomez Date 2007-02-01 Time 14:22 Sent To  
Notes
2007-02-01 14:22:19TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-02-15 Cont ID  
Sent By btrobaug Date 2007-02-20 Time 07:54 Rev Time 0.45
Received By tgordon Date 2007-02-15 Time 11:29 Sent To P
Notes
2007-02-15 11:58:23*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 2) NEED TO SUBMIT TWO (2) COPY'S OF THE ENERGY
 CALCULATIONS AND ALL PLANS.
  
 3) THE MECHANICAL PLANS NEED KEEP IT COOL INC. LICENSE
 NUMBER, PHONE NO., AND ADDRESS IN THE TITLE BLOCK.
  
 5) THE MECHANICAL PLANS NEED TO BE SIGNED. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER FBC 104.2.1 .
  
 6) PLEASE SHOW ON THE MECHANICAL PLANS ANY BATHROOM
 EXHAUST FANS BEING INSTALLED, THE WATER CLOSET IN THE
 MASTER BATH MUST HAVE AN EXHAUST FAN, PER 2004 FBC/R
 303.3.
  
 7) THE 9" RETURN AIR TRANSFER DUCT IN THE MASTER SUITE
 NEEDS TO BE 12", SEE 2004 FBC/R M1602.4 (A) AND (C)
 EXCEPT.
  
 8) THE 8" RETURN AIR TRANSFER DUCT IN BEDROOM #2 NEEDS
 TO BE 9", SEE 2004 FBC/R M1602.4 (A).
  
 9) THE 7" RETURN AIR TRANSFER DUCT IN BEDROOM #3 NEEDS
 TO BE 9", SEE 2004 FBC/R M1602.4 (A).
  
 *** 2004 FBC/R M1602.4. BALANCED RETURN AIR MAY BE
 ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS
 SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR
 HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO
 ACHIEVE PROPER RETURN AIR BALANCE.
 (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET
 THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR
 EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY
 ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-02-20 Cont ID  
Sent By jleech Date 2007-02-20 Time 07:34 Rev Time 0.00
Received By jleech Date 2007-02-20 Time 07:34 Sent To B
Notes
2007-02-20 07:50:30DENIED;
 1. PLUMBING NOTES; MINIMUN SLOPE FOR HORIZONTAL PIPE 2
 1/2" AND SMALLER IS 1/4" PER FOOT. FBC-2004 PLUMBING
 TABLE 704.1.
 2. A SANITARY RISER DIAGRAM IS REQUIRED. FBC-2004
 BUILDING CHAPTER 1 SECTION 106.3.5.4 (9). SIZE ALL
 DRAIN AND VENT PIPES. SHOW SEWER TIE-IN LOCATIONS. THE
 DRAIN PIPE FOR THE AUTOMATIC CLOTHES WASHER IS REQUIRED
 TO BE 3" WITH A CLEANOUT AT 48" OFF FINISH FLOOR.
 SECTION 406.3.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status F Date 2007-02-05 Cont ID  
Sent By mmclean Date 2007-02-05 Time 14:34 Rev Time 0.00
Received By mmclean Date 2007-02-05 Time 14:34 Sent To I
Notes
2007-02-05 15:01:20DENIED,
 1. PLEASE PROVIDE A COPY OF CURRENT SURVEY SHOWING THE
 EXISTING PROPERTY AND STRUCTURE WITH SETBACKS.
 2. PLEASE PROVIDE THE INTERIOR ACCESS OF THE PROPOSED
 TO THE EXISTING STRUCTURE AND IDENTIFY THE ROOM THAT
 WILL PROVIDE THE ACCESS (EXISTING).
 3. THE PROPOSED LAUNDRY ROOM IS NOT SHOWN ON THE
 SITEPLAN. PLEASE SHOW ON TWO COPIES WITH SETBACKS.
 4. SHEET A2 SHOWS A SOLID WALL AND NO INTERIOR ACCESS
 FROM THE PROPOSED TO THE EXISTING.
 5. PLEASE SHOW THE LOCATION OF THE A/C PAD ON THE TWO
 COPIES OF SITEPLANS.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720