| 2007-02-03 08:30:14 | BUILDING PLAN REVIEW |
| | PERMIT: |
| | ADD: |
| | CONT: |
| | TEL: (561)###-#### |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1)THE LETTER FROM THE ENGINEER IS NOT WHAT THE NOA |
| | REQUIRES. THE NOA STATE CLEARLY "CALCULATIONS PREPARED, |
| | SIGNED AND SEALED BYA FLORIDA REGISTERED PROFESSIONAL |
| | ENGENEER, ARCHITECT, OR ROOF CONSULTANT. PROVIDE THE |
| | CALCULATIONS FROM THE ENGINEER WHICH WILL MEET THE |
| | REQUIRED UPLIFT PRESSURES AS CALCULATED BY THE |
| | ENGINEER. THE CALCULATIONS SHALL THE PRESSURE |
| | CALCULATED FOR ZONES 1 / 2 AND 3. USING THE NOA |
| | SUBMITTED.SEE (RAS) NO. 117 FOR MORE INFORMATION. |
| | |
| | ROOFING PERMIT; ONLY CHECKED ITEMS APPLY |
| | |
| | _OK___1.)A NOTICE OF COMMENCEMENT MUST BE FILED |
| | WITH THE CLERK OF COURTS PRIOR TO PERMIT PICKUP, |
| | FS713.13. |
| | |
| | __OK__2.)CONTRACTOR IS TO PROVIDE THE FOLLOWING |
| | INFORMATION ON THE APPLICATION, SEE ATTACHED |
| | POLICY:MEAN ROOF HEIGHT/ ROOF PITCH / ROOF DECK TYPE / |
| | AREA OF EACH ROOF TYPE |
| | |
| | ____3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| | REQUIRED IN ADDITION TO THE EVALUATION REPORT |
| | SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG |
| | |
| | _OK__4.)FOR THE FLAT DECK, SELECT THE APPROVED |
| | ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER |
| | IF THE OPTIONS HAVE DIFFERENT PRESSURE LIMITATIONS. |
| | |
| | _XX___5.)FOR THE FLAT DECK, SPECIFY THE ENHANCED |
| | FASTENING FOR CORNER AND PERIMETER ZONES. |
| | |
| | _XX___ 6)SEE PRODUCT LIMITATION #7.CALCULATIONS |
| | PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF |
| | CONSULTANT REQUIRED FOR ENHANCED FASTENING. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |