Plan Review Details - Permit 07011240
Plan Review Stops For Permit 07011240
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-04-04 Cont ID  
Sent By mjacobs Date 2007-04-04 Time 07:55 Rev Time 0.00
Received By mjacobs Date 2007-04-04 Time 06:50 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-03-30 Cont ID  
Sent By mjacobs Date 2007-03-30 Time 14:49 Rev Time 0.00
Received By mjacobs Date 2007-03-30 Time 13:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-02-06 Cont ID  
Sent By mjacobs Date 2007-02-06 Time 10:05 Rev Time 0.00
Received By mjacobs Date 2007-02-05 Time 18:12 Sent To  
Notes
2007-02-05 18:56:11BUILDING PLAN REVIEW
 PERMIT:07011240
 ADD: 90145THSTREET.
 CONT: PHOENIX MEDICAL CONSTRUCTION
 TEL: (914)927-8955
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)THE FLORIDA CODE EDITION INDICATED ON THE DRAWINGS
 ARE INCORRECT. THE CODE EDITION AT THIS TIME IS THE
 2004 FBC NOT THE 2006.ALL PLANS SUBMITTED AFTER
 OCTOBER, 1, 2004 SHALL BE DESIGNED TO THE 2004 FLORIDA
 BUILDING CODE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-02-05 Cont ID  
Sent By btrobaug Date 2007-02-05 Time 14:35 Rev Time 1.00
Received By btrobaug Date 2007-02-05 Time 12:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-04-13 Cont ID  
Sent By mwennerg Date 2007-04-13 Time 14:17 Rev Time 0.00
Received By mwennerg Date 2007-04-13 Time 14:17 Sent To  
Notes
2007-04-13 14:21:29***DENIED***
  
 1) PLANS SHOW (9) NEW SPRINKLER HEADS BEING INSTALLED
 TO EXISTING SYSTEM. SEPARATE SHOP DRAWINGS AND PERMIT
 REQUIRED.
  
 2) PLEASE PROVIDE MANUFACTURER CUT SHEETS WITH
 SUBMITTAL FOR REVIEW.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-04-03 Cont ID  
Sent By mwennerg Date 2007-04-03 Time 14:32 Rev Time 0.00
Received By mwennerg Date 2007-04-03 Time 14:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-02-21 Cont ID  
Sent By mawillia Date 2007-02-21 Time 17:35 Rev Time 0.00
Received By mawillia Date 2007-02-21 Time 17:35 Sent To  
Notes
2007-02-21 18:19:54*****DENIED*****
  
  
 1.THE COMPLETE ADDRESS OF THE JOB SITE SHALL BE IN
 THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.SEE
 ID1.1, LS1.1, IC1.1, ASP1.1, A1.1, A1.2, A2.1, A2.2,
 A2.3;E-1, E-2, E-3, E-4, M-1, M-2, M-3, M-4, M-5, AND
 M-6.
  
 2.ON SHEET ID1.1, THE TYPE OF OCCUPANCY IS LISTED AS
 INSTITUTIONAL.CHAPTER 19 OF NFPA 101 2003 EDITION
 REFERENCES THIS TYPE OF OCCUPANCY AS EXISTING HEALTH
 CARE.
  
 3.ON SHEET ID1.1, UNDER APPLICABLE CODES, FLORIDA
 FIRE PREVENTION CODE 2004 SHALL BE REFERENCED.
  
 4.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 5.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 6.THE BUILDING OR PORTIONS OF THE BUILDING MAYBE
 OCCUPIED DURING CONSTRUCTION, ALTERATIONS, OR
 DEMOLITION ONLY WHERE REQUIRED MEANS OF EGRESS AND
 REQUIRED FIRE PROTECTION FEATURES ARE IN PLACE AND
 MAINTAINED FOR THE PORTION OCCUPIED.
  
 7.THE INTERIOR FINISH MATERIAL FOR WALLS AND CEILINGS
 SHALL BE CLASS A OR CLASS B.
  
 8.ON SHEET E-2, IT IS NOTED THAT THE SMOKE DETECTORS
 (SD'S) ARE TO BE REMOVED TO ALLOW THE REMOVAL OF THE
 CEILING AND THAT THEY ARE TO BE RE-INSTALLED AT THE
 SAME LOCATION ONCE THE NEW CEILING IS PLACE.WHAT IS
 THE ANTICIPATED TIME FRAME FOR THIS ASPECT OF THE JOB
 TO BE COMPLETED AS TO MINIMIZE DOWNTIME FOR THE FIRE
 ALARM SYSTEM?
  
 09.UPON COMPLETION OF THE RE-INSTALLING OF THE SMOKE
 DETECTORS, VERIFY THEIR OPERABILITY AS PER NFPA 72.
  
 10.AS PER WEST PALM BEACH FIRE PREVENTION,THE NEWLY
 INSTALLED DUCT SMOKE DETECTOR SHALL INITIATE A GENERAL
 FIRE ALARM.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE ON THE PLANS EACH OF THE
 ABOVE COMMENTS WERE ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-07-06 Cont ID  
Sent By adarroug Date 2007-07-06 Time 13:45 Rev Time 0.00
Received By adarroug Date 2007-07-06 Time 13:45 Sent To M
Notes
2007-07-06 13:45:51TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-06-26 Cont ID  
Sent By adarroug Date 2007-06-26 Time 11:46 Rev Time 0.00
Received By adarroug Date 2007-06-26 Time 11:46 Sent To M
Notes
2007-06-26 11:46:33TO "M"BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-05-17 Cont ID  
Sent By adarroug Date 2007-05-17 Time 13:31 Rev Time 0.00
Received By adarroug Date 2007-05-17 Time 13:31 Sent To M
Notes
2007-05-17 13:31:25TO"M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-04-12 Cont ID  
Sent By adarroug Date 2007-04-12 Time 13:28 Rev Time 0.00
Received By adarroug Date 2007-04-12 Time 13:28 Sent To FIRE
Notes
2007-04-12 13:29:10TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-22 Cont ID  
Sent By adarroug Date 2007-03-22 Time 11:41 Rev Time 0.00
Received By adarroug Date 2007-03-22 Time 11:41 Sent To  
Notes
2007-03-22 11:41:24TO "BOB"#1

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-21 Cont ID  
Sent By mawillia Date 2007-02-21 Time 17:35 Rev Time 0.00
Received By mawillia Date 2007-02-01 Time 09:03 Sent To  
Notes
2007-02-01 09:06:11TO "BOB"#16

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-07-09 Cont ID  
Sent By tgordon Date 2007-07-09 Time 08:18 Rev Time 0.30
Received By tgordon Date 2007-07-09 Time 08:18 Sent To  
Notes
2007-07-09 08:19:16REVISION TO MECH. PLANS PAGE M-3.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-06-27 Cont ID  
Sent By tgordon Date 2007-06-27 Time 14:12 Rev Time 0.25
Received By tgordon Date 2007-06-27 Time 14:12 Sent To  
Notes
2007-06-27 14:14:03SMD-1 SUPPLEMENTAL DRAWING SHOWING AHU HANGING DETAIL.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-05-18 Cont ID  
Sent By tgordon Date 2007-05-18 Time 09:22 Rev Time 0.30
Received By tgordon Date 2007-05-18 Time 09:22 Sent To  
Notes
2007-05-18 09:23:28MECH. REVISION TO PLANS PAGE M-3.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-02-09 Cont ID  
Sent By tgordon Date 2007-02-09 Time 11:21 Rev Time 0.45
Received By tgordon Date 2007-02-09 Time 11:21 Sent To  
Notes
***NONE***