| 2007-01-31 07:39:54 | ** UNSAT ** |
| | |
| | |
| | 1) NOTE: PLEASE SEE MISSING ADDRESS INFORMATION FROM |
| | TITLE BLOCKS. PLEASE SEE THE SUITE/UNIT NUMBER IS BEING |
| | SHOWN, HOWEVER NOT THE ADDRESS/ LOCATION. THIS IS 444 |
| | RAILROAD AVE IN OUR SYSTEM AND THAT WHICH IS BEING |
| | APPLIED FOR. |
| | FAC 61G1-16.004, FAC61G15-23.002 |
| | |
| | 2) NOTE: PLEASE SEE MISSING COMPLETE INFORMATION FOR A |
| | TITLE BLOCK FOR THE ARCHITECT OF RECORD. PLEASE SEE |
| | ATTACHED SHEET FROM DEPARTMENT OF BUSINESS AND |
| | PROFESSIONAL REGULATION. PLEASE SEE NO ADDRESS |
| | INFORMATION ETC. |
| | PLEASE KNOW IF WORKING THROUGH PBM DEVELOPMENT, AND PBM |
| | IS OFFERING ARCHITECTURAL SERVICES, THEN PBM WOULD BE |
| | REQUIRED TO LIST THEIR CERTIFICATE OF AUTHORIZATION |
| | NUMBER. (THIS HAS ALREADY BEEN GONE OVER WITH STAFF |
| | FROM PBM AND IT IS OUR UNDERSTANDING THAT APPLICATION |
| | TO THE DEPARTMENT OF BUSINESS AND PROFESSIONAL |
| | REGULATIONS HAS/IS TAKING OR TAKEN PLACE. |
| | PLEASE KNOW IF PERMIT ISSUANCE IS DOWN TO ONLY THIS |
| | COMMENT AND THE CERTIFICATE OF AUTHORIZATION NUMBER HAS |
| | NOT YET BEEN ISSUED FROM THE STATE, THE TITLE BLOCKS |
| | WOULD BE REQUIRED TO BE REVISED TO BE LISTED WITH THE |
| | ARCHITECT ONLY. APPLICATION MADE TO THE STATE DOES NOT |
| | CONSTITUTE THE LICENSE BEING ISSUED AND THE COMPANY |
| | OFFERING ARCHITECTURAL SERVICES IS NOT PERMITTED. AS |
| | THIS COMMENT HAS BEEN MADE ON SEVERAL OCCASIONS, |
| | CONTACT WITH THE STATE BOARD OF ARCHITECT'S LEGAL |
| | COUNSEL MAY BE REQUIRED. |
| | FLORIDA ADMINISTRATIVE CODE 61G1-16.004, FLORIDA |
| | STATUTES 481.219 |
| | **THIS IS NOT A COMMENT RELATED TO KAMM CONSULTING, |
| | HOWEVER TITLE BLOCKS ARE REQUIRED FOR ALL SHEETS PER |
| | ABOVE AND WHETHER OR NOT COMMENT IS MADE BY ANY OTHER |
| | TRADE. |
| | |
| | 3) NOTE: PLEASE LIST THE FOLLOWING MINIMUM CODES |
| | RELEVANT TO THIS PROJECT AND DESIGN. |
| | 2002 NFPA-72, 2005 NFPA-70, 2003 NFPA-101 |
| | PLEASE SEE AS THE PERMIT WAS APPLIED FOR ON OR AFTER |
| | DECEMBER 8TH, 2006 THE 2006 REVISIONS TO THE 2004 FBC |
| | AND THE 2005 NATIONAL ELECTRICAL CODE WAS ADOPTED BY |
| | THE STATE OF FLORIDA. |
| | PLEASE ADJUST CODES ON PLANS. |
| | |
| | 4) NOTE: PLEASE SEE MISSING LIGHTING CONTROL FOR ALL |
| | PER 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE |
| | MISSING CONTROLS FOR COMMON AREAS AND STORAGE AREAS. |
| | PLEASE SEE THE COMMON AREA HALLWAY MUST CONTAIN A |
| | DEVICE(S) WHICH PROVIDE SUFFICIENT COVERAGE. PLEASE SEE |
| | OVER RIDES DEVICES FOR THESE AREAS ALSO DEPENDING ON |
| | "SYSTEM" OR DEVICES CHOSEN. PLEASE SEE THE SYMBOL |
| | LEGEND FOR ALL DEVICES SHALL INDICATE ALL MAXIMUM TIMES |
| | FOR DEVICES. (30MINS FOR OCCUPANCY SENSOR TYPE AND 4HRS |
| | MAX FOR TIMER TYPE) |
| | PLEASE PROVIDE SCHEDULING FOR ANY PROPOSED SYSTEM. |
| | PLEASE SEE ALL AREAS CONTAIN FLOOR TO CEILING HEIGHT |
| | PARTITIONS SHALL CONTAIN DEVICE(S) FOR CONTROL. (PLEASE |
| | SEE STORAGE) |
| | PLEASE SEE 13-415.2, 13-415.2.ABC.1 FOR MISSING MAXIMUM |
| | PERMITTED LIGHTING POWER DENSITIES. |
| | PLEASE ALSO SEE 13-415.AB.1 FOR MISSING ENERGY |
| | CALCULATIONS REQUIRED FOR NEW TENANT BUILD-OUT. |
| | ** PLEASE SUBMIT THE ABOVE. AS THERE ARE ITEMS NOT YET |
| | SUBMITTED, A REVIEW OF SAID SYSTEM/DEVICES ETC CAN NOT |
| | BE FULLY ACCOMPLISHED AT THIS TIME. |
| | |
| | 5) NOTE: PLEASE PROVIDE A DETAIL ON ALL EMERGENCY |
| | AND/OR EXIT LIGHTING WIRED AHEAD OF ANY OVER RIDE |
| | CONTROL DEVICES PER 700.12E. PLEASE SEE A |
| | CLOUDED/HIGHLIGHTED NOTE MAY ALSO BE DONE. THIS AHJ HAS |
| | BEEN HAVING MANY INSTANCES WHERE EMERGENCY AND EXIT |
| | LIGHTS ARE BEING WIRED ON THE LOAD SIDE OF OC/ TIMER |
| | DEVICES. |
| | |
| | 6) NOTE: PLEASE INDICATE ALL CONTINUOUS LOADS AT 125%. |
| | 215.3, 230.42 ETC. |
| | FBC 106.1.2 ADMIN SECTION. |
| | |
| | 7) NOTE: PLEASE KNOW EITHER AT THIS POINT OR BEFORE |
| | FINAL, A REVISION FOR ALL CIRCUITS TO SPECIFIC ROOMS |
| | AND AREAS WILL BE REQUIRED. (LIGHTING CIRCUITS ETC.) |
| | 408.4. |
| | ALL RECEPTACLE CIRCUITS ARE OK AS SHOWN. SEE EXCERPT |
| | FROM NEC HANDBOOK. |
| | *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| | SECTION.* |
| | |
| | 8) NOTE: PLEASE CLARIFY HOW THE PANEL SCHEDULE(S) |
| | INDICATE ALL THE CIRCUITS AS EXISTING FOR ALL THESE |
| | SPACES WHICH HAVE YET TO BE PERMITTED. PLEASE INDICATE |
| | NEW CIRCUITING AND WHAT?S EXISTING. PLEASE SEE THAT NO |
| | OTHER TENANT BUILD OUTS HAVE BEEN PERMITTED AT THIS |
| | TIME. |
| | |
| | 9) NOTE:** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDEDSHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS.PLEASE KNOW ONLY |
| | ONE SET OF THE OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |