Plan Review Details - Permit 07011231
Plan Review Stops For Permit 07011231
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-02-05 Cont ID  
Sent By mjacobs Date 2007-02-05 Time 11:33 Rev Time 0.00
Received By mjacobs Date 2007-02-05 Time 09:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-03-01 Cont ID  
Sent By btrobaug Date 2007-03-01 Time 08:11 Rev Time 1.00
Received By btrobaug Date 2007-03-01 Time 08:11 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-02-26 Cont ID  
Sent By btrobaug Date 2007-02-26 Time 16:17 Rev Time 1.00
Received By btrobaug Date 2007-02-26 Time 15:26 Sent To  
Notes
2007-02-26 16:17:09 
  
 DENIED/INCOMPLETE
  
 THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK MUST
 SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002 FAC.
 ONLY ONE SET IS SEALED
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-02-05 Cont ID  
Sent By btrobaug Date 2007-02-05 Time 09:16 Rev Time 0.75
Received By btrobaug Date 2007-02-05 Time 07:50 Sent To  
Notes
2007-02-05 09:16:54 
  
 DENIED/INCOMPLETE INFORMATION.
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PLEASE INDICATE THE AMPERAGE RATING OF THE MAIN
 BREAKER FOR PANEL "1LA".
  
 2} CIRCUIT 1LA-7 IS A DESIGNATED FOR LIGHTING ON SHEET
 E-1.01, BUT LISTED AS PART OF A WATER HEATER CIRCUIT ON
 THE PANEL SCHEDULE, SHEET E-2.02, PLEASE CORRELATE.
  
 3} SUBMIT PANEL SCHEDULES FOR "1LB", "2LA" AND "2LB".
 INCLUDE THE RATINGS OF SAME.
  
 4} LIGHTING CIRCUIT "1LA-5" SHEET E-1.01, IS LISTED AS
 A AHU CIRCUIT ON THE SCHEDULE, SHEET E2.01. PLEASE
 CORRECT CIRCUIT NUMBER.
  
 5} PER NOTE #1 SHEET E-1.02, LOCATE THE FIRE ALARM
 ANNUNCIATOR ON THE PLAN.
  
 AN ELECTRICAL PERMIT IS REQUIRED PER 105.1 FBC AS
 AMMENDED.
 PLEASE REMOVE OLD SHEETS, INSERT NEW
 ONES, SUBMIT OLD SHEETS TO EXPEDITE
 REVIEW AND SUBMIT WRITTEN RESPONSE TO
 THE COMMENTS MADE IN THIS REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-02-27 Cont ID  
Sent By mawillia Date 2007-02-27 Time 09:42 Rev Time 0.00
Received By mawillia Date 2007-02-27 Time 09:41 Sent To  
Notes
2007-02-27 10:03:48*****APPROVED*****W/REMINDERS
  
  
 ALL COMMENTS FROM PREVIOUS FIRE PLAN REVIEW HAVE BEEN
 ADDRESSED.SHEETS F-1.01 AND LS WERE STAMPED,
 INITIALED, AND DATED.
  
  
 REMINDERS
  
 1.IN ADDITION TO THE ELECTRONIC SWITCHES, A CHAIN AND
 LOCK IS REQUIRED FOR THE FIRE SPRINKLER SYSTEM'S DOUBLE
 CHECK DETECTOR ASSEMBLY.
  
 2.KNOX LOCKING CAPS WILL BE REQUIRED FOR THE FIRE
 DEPARTMENT CONNECTION (FDC).FOR APPLICATIONS, CONTACT
 WEST PALM BEACH FIRE PREVENTION AT (561)804-4724.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-02-13 Cont ID  
Sent By mawillia Date 2007-02-13 Time 16:28 Rev Time 0.00
Received By mawillia Date 2007-02-13 Time 16:06 Sent To  
Notes
2007-02-13 16:49:53*****DENIED*****
  
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FORM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 3.WHAT IS THE INTERIOR FINISH CLASSIFICATION FOR THE
 WALLS AND CEILINGS IN THE EXITS, EXIT ACCESS CORRIDORS,
 AND IN ALL OTHER SPACES?
  
 4.PROVIDE A LIFE SAFETY PLAN SHEET WHICH INDICATES
 THE TRAVEL DISTANCE TO THE EXIT(S).ALSO ON THIS
 SHEET, INDICATE EXIT LIGHTS, EMERGENCY LIGHTS, AND FIRE
 EXTINGUISHER(S).FIRE EXTINGUSHERS SHALL SATISFY THE
 75' TRAVEL DISTANCE REQUIREMENT.
  
 5.PROVIDE A LAYOUT OF THE FIRE ALARM SYSTEM FOR THIS
 STRUCTURE.IF THE FIRE ALARM SYSTEM IS MODIFIED DUE TO
 THE SCOPE OF WORK, SEPARATE PLANS AND PERMIT WILL BE
 REQUIRED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-21 Cont ID  
Sent By adarroug Date 2007-02-21 Time 10:12 Rev Time 0.00
Received By adarroug Date 2007-02-21 Time 10:12 Sent To  
Notes
2007-02-21 10:13:59TO "BOB"#8

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-13 Cont ID  
Sent By mawillia Date 2007-02-13 Time 16:06 Rev Time 0.00
Received By mawillia Date 2007-01-31 Time 09:08 Sent To  
Notes
2007-01-31 09:15:53TO "BOB"#11

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-02-08 Cont ID  
Sent By tgordon Date 2007-02-08 Time 14:06 Rev Time 0.20
Received By tgordon Date 2007-02-08 Time 14:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-02-03 Cont ID  
Sent By jleech Date 2007-02-03 Time 13:19 Rev Time 0.00
Received By jleech Date 2007-02-03 Time 13:19 Sent To  
Notes
***NONE***