| Plan Review Stops For Permit 07011231 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2007-02-05 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-02-05 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-02-05 |
Time |
09:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2007-03-01 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-03-01 |
Time |
08:11 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2007-03-01 |
Time |
08:11 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-02-26 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-02-26 |
Time |
16:17 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2007-02-26 |
Time |
15:26 |
Sent To |
|
|
| Notes |
| 2007-02-26 16:17:09 | | | | | | | DENIED/INCOMPLETE | | | | | | THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK MUST | | | SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002 FAC. | | | ONLY ONE SET IS SEALED | | | | | | WILLIAM R. TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-02-05 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-02-05 |
Time |
09:16 |
Rev Time |
0.75 |
| Received By |
btrobaug |
Date |
2007-02-05 |
Time |
07:50 |
Sent To |
|
|
| Notes |
| 2007-02-05 09:16:54 | | | | | | | DENIED/INCOMPLETE INFORMATION. | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE INDICATE THE AMPERAGE RATING OF THE MAIN | | | BREAKER FOR PANEL "1LA". | | | | | | 2} CIRCUIT 1LA-7 IS A DESIGNATED FOR LIGHTING ON SHEET | | | E-1.01, BUT LISTED AS PART OF A WATER HEATER CIRCUIT ON | | | THE PANEL SCHEDULE, SHEET E-2.02, PLEASE CORRELATE. | | | | | | 3} SUBMIT PANEL SCHEDULES FOR "1LB", "2LA" AND "2LB". | | | INCLUDE THE RATINGS OF SAME. | | | | | | 4} LIGHTING CIRCUIT "1LA-5" SHEET E-1.01, IS LISTED AS | | | A AHU CIRCUIT ON THE SCHEDULE, SHEET E2.01. PLEASE | | | CORRECT CIRCUIT NUMBER. | | | | | | 5} PER NOTE #1 SHEET E-1.02, LOCATE THE FIRE ALARM | | | ANNUNCIATOR ON THE PLAN. | | | | | | AN ELECTRICAL PERMIT IS REQUIRED PER 105.1 FBC AS | | | AMMENDED. | | | PLEASE REMOVE OLD SHEETS, INSERT NEW | | | ONES, SUBMIT OLD SHEETS TO EXPEDITE | | | REVIEW AND SUBMIT WRITTEN RESPONSE TO | | | THE COMMENTS MADE IN THIS REVIEW. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2007-02-27 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-02-27 |
Time |
09:42 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-02-27 |
Time |
09:41 |
Sent To |
|
|
| Notes |
| 2007-02-27 10:03:48 | *****APPROVED*****W/REMINDERS | | | | | | | | | ALL COMMENTS FROM PREVIOUS FIRE PLAN REVIEW HAVE BEEN | | | ADDRESSED.SHEETS F-1.01 AND LS WERE STAMPED, | | | INITIALED, AND DATED. | | | | | | | | | REMINDERS | | | | | | 1.IN ADDITION TO THE ELECTRONIC SWITCHES, A CHAIN AND | | | LOCK IS REQUIRED FOR THE FIRE SPRINKLER SYSTEM'S DOUBLE | | | CHECK DETECTOR ASSEMBLY. | | | | | | 2.KNOX LOCKING CAPS WILL BE REQUIRED FOR THE FIRE | | | DEPARTMENT CONNECTION (FDC).FOR APPLICATIONS, CONTACT | | | WEST PALM BEACH FIRE PREVENTION AT (561)804-4724. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-02-13 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-02-13 |
Time |
16:28 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-02-13 |
Time |
16:06 |
Sent To |
|
|
| Notes |
| 2007-02-13 16:49:53 | *****DENIED***** | | | | | | | | | | | | 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | | BE REMOVED FORM THE SITE AT THE END OF EACH SHIFT OR | | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | | | 3.WHAT IS THE INTERIOR FINISH CLASSIFICATION FOR THE | | | WALLS AND CEILINGS IN THE EXITS, EXIT ACCESS CORRIDORS, | | | AND IN ALL OTHER SPACES? | | | | | | 4.PROVIDE A LIFE SAFETY PLAN SHEET WHICH INDICATES | | | THE TRAVEL DISTANCE TO THE EXIT(S).ALSO ON THIS | | | SHEET, INDICATE EXIT LIGHTS, EMERGENCY LIGHTS, AND FIRE | | | EXTINGUISHER(S).FIRE EXTINGUSHERS SHALL SATISFY THE | | | 75' TRAVEL DISTANCE REQUIREMENT. | | | | | | 5.PROVIDE A LAYOUT OF THE FIRE ALARM SYSTEM FOR THIS | | | STRUCTURE.IF THE FIRE ALARM SYSTEM IS MODIFIED DUE TO | | | THE SCOPE OF WORK, SEPARATE PLANS AND PERMIT WILL BE | | | REQUIRED. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-02-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-02-21 |
Time |
10:12 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-02-21 |
Time |
10:12 |
Sent To |
|
|
| Notes |
| 2007-02-21 10:13:59 | TO "BOB"#8 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-02-13 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-02-13 |
Time |
16:06 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-01-31 |
Time |
09:08 |
Sent To |
|
|
| Notes |
| 2007-01-31 09:15:53 | TO "BOB"#11 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2007-02-08 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-02-08 |
Time |
14:06 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2007-02-08 |
Time |
14:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2007-02-03 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-02-03 |
Time |
13:19 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-02-03 |
Time |
13:19 |
Sent To |
|
|
| Notes |
|
|