Plan Review Details - Permit 07011226
Plan Review Stops For Permit 07011226
Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-06-08 Cont ID  
Sent By mawillia Date 2007-06-08 Time 11:21 Rev Time 0.00
Received By mawillia Date 2007-06-08 Time 11:17 Sent To  
Notes
2007-06-08 11:20:05*****APPROVED*****
  
  
 REVISED PLAN SHEET THREE (OF 5) WAS STAMPED, INITIALED
 AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-05-07 Cont ID  
Sent By mawillia Date 2007-05-07 Time 12:17 Rev Time 0.00
Received By mawillia Date 2007-05-07 Time 11:56 Sent To  
Notes
2007-05-07 12:02:08*****APPROVED*****
  
  
 ALL PLAN REVIEW COMMENTS HAVE BEEN ADDRESSED;PLAN
 SHEET 3 OF 5 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-04-19 Cont ID  
Sent By mawillia Date 2007-04-19 Time 16:41 Rev Time 0.00
Received By mawillia Date 2007-04-19 Time 16:32 Sent To  
Notes
2007-04-19 16:35:09*****DENIED*****
  
  
 PLEASE SEE MECHANICAL PLAN REVIEW
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-02-06 Cont ID  
Sent By mawillia Date 2007-02-06 Time 09:46 Rev Time 0.00
Received By mawillia Date 2007-02-06 Time 09:46 Sent To  
Notes
2007-02-06 10:05:56*****DENIED*****
  
  
 1.A SUB PERMIT CAN NOT BE ISSUED UNTIL THE MASTER
 PERMIT HAS BEEN ISSUED.
  
 2.A SEPARATE PERMIT AND PLAN WILL BE REQUIRED FOR THE
 HOOD SUPPRESSION SYSTEM.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-06-01 Cont ID  
Sent By adarroug Date 2007-06-01 Time 16:03 Rev Time 0.00
Received By adarroug Date 2007-06-01 Time 16:03 Sent To FIRE
Notes
2007-06-01 16:03:35TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-05-03 Cont ID  
Sent By adarroug Date 2007-05-03 Time 15:23 Rev Time 0.00
Received By adarroug Date 2007-05-03 Time 15:23 Sent To FIRE
Notes
2007-05-03 15:23:39TO "TGORDON" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-16 Cont ID  
Sent By adarroug Date 2007-04-16 Time 13:19 Rev Time 0.00
Received By adarroug Date 2007-04-16 Time 13:19 Sent To FIRE
Notes
2007-04-16 13:19:29TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-19 Cont ID  
Sent By mawillia Date 2007-02-06 Time 10:06 Rev Time 0.00
Received By tgordon Date 2007-01-30 Time 17:28 Sent To  
Notes
2007-01-30 17:30:11TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-06-08 Cont ID  
Sent By tgordon Date 2007-06-08 Time 11:06 Rev Time 0.30
Received By tgordon Date 2007-06-08 Time 11:06 Sent To FIRE
Notes
2007-06-08 11:09:08REVISION TO KITCHEN HOOD PLANS.( NOTE: MUST COMPLY WITH
 2004 FBC/M 506.3.6 OR TABLE 308.6.)

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-05-04 Cont ID  
Sent By tgordon Date 2007-05-04 Time 13:49 Rev Time 0.25
Received By tgordon Date 2007-05-04 Time 13:49 Sent To FIRE
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-04-19 Cont ID  
Sent By tgordon Date 2007-04-19 Time 14:48 Rev Time 0.45
Received By tgordon Date 2007-04-19 Time 14:48 Sent To FIRE
Notes
2007-04-19 14:59:40*** DENIED ***
 1) AS NOTED IN LAST REVIEW 2-2-07 #3, SHOW DETAIL HOW
 3/8" ROD IS TO BE SECURED TO "HOOD", SEE YELLOW HIGH
 LIGHTS ON PLANS PAGE 2 OF 5.
  
 2) WILL PERPENDICULAR BLOCKING NEED TO BE INSTALLED
 BETWEEN THE TRUSSES AT ROOF PENETRATIONS? SEE YELLOW
 HIGH LIGHTS ON PLANS PAGE 2 OF 5, IF SO PLEASE
 CORRECT.
  
 3) SEE PLANS PAGE 4 OF 5 DETAIL D-7 STATES WIND LOADS
 OF 120 MPH, WIND LOADS FOR THIS AREA ARE 140, SEE 2004
 FBC 1609, PLEASE CORRECT.
  
 4) SEE YELLOW HIGH LIGHTS ON PLANS PAGE 3 OF 5, PLEASE
 SHOW MINIMUM DISTANCE FROM EF-2 TO THE ROOF PEAK AND
 THE WALL TO COMPLY WITH 2004 FBC/M 506.3.12.3, OR IF
 FAN IS HIGHER PLEASE STATE SO ON PLANS.
  
 5) SEE YELLOW HIGH LIGHTS ON PLANS PAGE 3 OF 5, PLEASE
 SHOW THE MINIMUM HEIGHT FOR EF-2 TO THE GABLE ROOF TO
 COMPLY WITH 2004 FBC/M 506.3.12.1.
  
 6) THE PLANS SUBMITED ARE SEALED ENGINEERED PLANS AND
 CHANGES MAY NOT BE DONE BY HAND, PLEASE SUBMITT
 CORRECTED PLANS WITH NO HAND MADE CHANGES TO THEM.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-02-02 Cont ID  
Sent By tgordon Date 2007-02-02 Time 08:06 Rev Time 0.30
Received By tgordon Date 2007-02-02 Time 08:06 Sent To FIRE
Notes
2007-02-02 08:12:20*** DENIED ***
 1) PLEASE BE ADVISED THIS PERMIT CAN NOT BE ISSUED
 UNTIL THE MASTER PERMIT HAS BEEN.
  
 2) SHOW ON PLANS COMPLIANCE WITH 2004 FBC/M 506.3.12.1
 TERMINATION ABOVE THE ROOF.
  
 3) SHOW DETAIL HOW 3/8" ROD IS TO BE SECURED TO HOOD.
  
 4) SEE PAGE #3 OF 5 NOTES BUILDING CODES THAT ARE NO
 LONGER BEING USED, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.