Plan Review Details - Permit 07011206
Plan Review Stops For Permit 07011206
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-01-02 Cont ID  
Sent By jgomez Date 2008-01-02 Time 14:28 Rev Time 0.00
Received By jgomez Date 2008-01-02 Time 14:28 Sent To PC
Notes
2008-01-02 14:28:47BAR AREA REVISION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-11-30 Cont ID  
Sent By jgomez Date 2007-11-30 Time 08:00 Rev Time 0.00
Received By jgomez Date 2007-11-30 Time 07:43 Sent To PC
Notes
2007-11-30 08:01:13WET BAR AREA REVISION.CABINETS FOR FUTURE
 INSTALLATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-05-30 Cont ID  
Sent By jgomez Date 2007-05-30 Time 12:18 Rev Time 0.00
Received By jgomez Date 2007-05-30 Time 07:38 Sent To PC
Notes
2007-05-30 12:24:44BUILDING REVIEW APPROVED WITH PROVISO:
 1- NEED TO PROVIDE ELEVATION CERTIFICATE FOR NEW
 ADDITION AND OUTSIDE EQUIPMENT.
  
 2- SEE GENERATOR SPECS FOR REQUIRED CONCRETE SLAB SIZE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-04-19 Cont ID  
Sent By jgomez Date 2007-04-19 Time 15:59 Rev Time 0.00
Received By jgomez Date 2007-04-19 Time 09:33 Sent To PC
Notes
2007-04-19 16:31:43BUILDING REVIEW SECOND CHECKLIST:
 1- NEW GENERATOR: ADDRESS COMMENTS BY ELECTRICAL AND
 MECHANICAL PLAN REVIEWERS REGARDING LOCATION NEAR
 OPENINGS AND EQUIPMENT CLEARANCES.
  
 2- PROVIDE COMPLETE SPECS FROM BBQ AND HOOD
 MANUFACTURER STATING THAT LOCATION OF THIS EQUIPMENT
 NEXT TO A WINDOW IS OK. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 3- BRING DRAWINGS TO PALM BEACH COUNTY TO SEE IF IMPACT
 FEES ARE DUE OR NOT. THEY ARE THE ONES WHO DETERMINE IF
 IMPACT FEES ARE DUE OR NOT.LETTER SUBMITTED IS ONLY
 TO STATE THAT THERE WAS A BUILDING IN THIS LOCATION.
 SHOWLETTER TO PALM BEACH COUNTY TO SEE WHAT CREDIT IS
 GRANTED. BRING BACK STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE.
  
 4- NOTICE OF COMMENCEMENT IS EXPIRED AFTER 90 DAYS OF
 BEING RECORDED IF WORK IS NOT STARTED.SEC. 713.13
 FLORIDA STATUTE. NEED RE-RECORDED NOTICE OF
 COMMENCEMENT.
  
 5- SHEET A-2:MISSING THE COVERED PORCH AREA IN THE
 TOTAL AREA CALCULATIONS.PROVIDE INFORMATION AS
 REQUIRED.
  
 6- SHEET A-6: NEED TO REVISE THE DESIGN PRESSURES. NEED
 TO USE REVISED TABLE 1609.6.2.1(2) OF FBC 2004, NOT
 TABLE 1609.6B.
  
 7- SUBMITTED DRAWINGS ARE TOO DARK AND THEY WON'T BE
 ABLE TO BE COPIED FOR CITY RETENTION FILES. PROVIDE
 CLEAR AND LEGIBLE DRAWINGS AS REQUIRED BY SEC. 106.1.3
 CITY AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-14 Cont ID  
Sent By jgomez Date 2007-03-14 Time 18:56 Rev Time 3.00
Received By jgomez Date 2007-03-14 Time 17:33 Sent To  
Notes
2007-03-14 19:00:05BUILDING REVIEW CHECKLIST:
 1- PROVIDE COMPLETE INFORMATION FOR GENERATOR.
 INCLUDING SPECS, CLEARANCES, ETC. . SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 2- PROVIDE COMPLETE SPECS FOR BBQ HOOD APPROVED FOR
 EXTERIOR LOCATION.SEC. G2447 AND SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
 ***NOTE: VERIFY WITH MANUFACTURER SPECS IF LOCATION
 NEXT TO WINDOW IS ACCEPTABLE.PROVIDE SPECS.
  
 3-BRING DRAWINGS TO PALM BEACH COUNTY. BRING BACK
 STAMPED PLANS AND COPY OF THE PAID RECEIPT.
  
 4- SHEET A-2:REVISE A/C AREA AND PORCH AREA
 CALCULATIONS.BRING PLANS TO PALM BEACH COUNTY FOR
 IMPACT FEES ASSESMENT AFTER AREAS ARE REVISED.
  
 5- SHEET A-5:REVISE DESIGN PRESSURES FOR WIND LOADS
 AT CORNER AREAS. SEE TABLE 1609.6.2.1(2).
  
 6- SOIL TEST REPORT NEEDS THE ENGINEERING FIRM
 CERTIFICATE OF AUTHORIZATION NUMBER ON EACH SHEET AS
 REQUIRED BY SEC. 61G15-23.002 FLORIDA ADMINISTRATIVE
 CODE.
  
 7- SPECIFY SIZE OF CONTINUOUS ATTIC VENTILATION AS
 REQUIRED BY SEC. R806 2004 FLORIDA RESIDENTIAL CODE.
  
 8- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) HARDI SIDING AND HARDI SOFFIT.
  
 B) SLIDING GLASS DOORS.
  
 C) PRECAST LINTELS.
  
 D) TRUSS CONNECTORS SPECIFIED ON PLANS.
  
 E) METAL ROOFING.NOA 04-0503.03 SUBMITTED WAS
 SUPERSED. SEE COPY OF DADE COUNTY NOA WEBSITE. PROVIDE
 CURRENT PRODUCT APPROVAL.
  
 9- DESIGNER OF RECORD TO REVIEW AND APPROVE (NOT SIGN
 AND SEAL) IN WRITING ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 10- DESIGNER OF RECORD TO SEE PRODUCT APPROVAL FOR
 HARDISOFFIT AND SPECIFYHOW THE STRUCTURE WILL BE
 REINFORCED TO RECEIVED THIS TYPE OF SOFFIT. SEE TRUSS
 SPACING. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 11- SPECIFY SIZE, LOCATION,DESIGN PRESSURESAND
 NUMBER OFEXISTING SLIDING GLASS DOORS TO BE REPLACED
 AS DESCRIBEDON PERMIT APPLICATION. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 12- SPECIFY ATTIC ACCESS SIZE. SEC. R807 2004 FLORIDA
 RESIDENTIAL CODE.
  
 13- SHEET A-3:
 A) MISSING SHEET A-6 SHOWING DETAILS A/A-6, B/A-6.
  
 B) ROOFING FRAMING PLAN:SPECIFY CALCULATED UPLIFT
 LOADS AT THE ENDS OF PORCH MICROLLAM WHERE SIMPSON
 HU410 CONNECTORS WHERE SPECIFIED. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 C) ROOF TRUSS DESIGN LOADS CHART IS MISSING THE
 ATTIC LIVE LOAD AS REQUIRED BY TABLER301.5 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 D) SIMPSON HGA 10 CONNECTOR SPECIFIED ON SECTION
 4/A-3IS A WOOD TO WOOD CONNECTOR. NEED TO SPECIFY
 MASONRY CONENCTOR. REVISE AS REQUIRED.
  
 14- PROVIDE DRAINAGE PLANS TO SHOW COMPLIANCE WITH SEC.
 R401.3 2004 FLORIDA RESIDENTIAL CODE.
  
 15- BUILDING IS LOCATED ON FLOOD ZONE A5.NEED TO
 SPECIFYFINISH FLOOR ELEVATION AND WILL NEED THE FLOOR
 ELEVATION CERTIFICATETO GET FINAL C.O.
  
 16- ENERGY CALCULATIONS:
 A) MAKE SURE A/C AREA MATCHES REVISED A/C AREA ON
 ARCHITECTURAL PLANS.
  
 B) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.
  
 17- PROVIDE DETAIL/SECTION FOR 2X STRUCTURAL BUCK
 DETAIL AS REQUIRED BY SWING DOOR PRODUCT APPROVAL
 SUBMITTED.SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2008-01-02 Cont ID  
Sent By dpalmer Date 2008-01-02 Time 09:45 Rev Time 0.00
Received By dpalmer Date 2008-01-02 Time 09:42 Sent To PC
Notes
2008-01-02 09:45:25REVISED PANEL SCHEDULE.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-12-13 Cont ID  
Sent By dpalmer Date 2007-12-13 Time 11:13 Rev Time 0.00
Received By dpalmer Date 2007-12-13 Time 11:13 Sent To Z
Notes
2007-12-13 11:14:05** PROVISO **
  
 1) NOTE: PLEASE SEE THE PANEL SCHEDULE WHICH STILL
 INDICATES CIRCUITS FOR KITCHEN AND OTHER AREAS WHICH
 ARE NOW SHOWN AS J-BOX ON PLANS.
 PLEASE REVISE BEFORE INSPECTIONS.
 408.4, 310.16
 FBC 106.3.5.1.2, 106.1.2
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-11-09 Cont ID  
Sent By dpalmer Date 2007-11-09 Time 12:02 Rev Time 0.00
Received By dpalmer Date 2007-11-09 Time 11:54 Sent To P
Notes
2007-11-09 12:02:15** DENIEDREVISION/ NOT APPLICABLE **
  
  
 1) NOTE:PLANS SUBMITTED ARE LABELED FOR REVISION #4
 BASED ON TITLE BLOCK AND PLANS.
 NO CLEAR CHANGE IN ELECTRICAL.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTIONS SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-06-11 Cont ID  
Sent By dpalmer Date 2007-06-11 Time 17:03 Rev Time 0.00
Received By dpalmer Date 2007-06-11 Time 15:17 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-05-09 Cont ID  
Sent By dpalmer Date 2007-05-09 Time 12:56 Rev Time 0.00
Received By dpalmer Date 2007-05-09 Time 09:08 Sent To Z
Notes
2007-05-09 12:58:41** UNSAT 3RD REVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW, ALONG
 WITH NEW COMMENTS NEED TO BE ADDRESSED. SOME NEW
 COMMENTS ARE BASED ON REVISED ITEMS ON RISER WHICH WERE
 NOT PART OF PREVIOUS PLANS.
 PLEASE SEE NEW COMMENTS ALSO.
  
 1) NOTE: PLEASE COORDINATE THE RISER WITH THAT OF THE
 GENERATOR EQUIPMENT, SPECS/CUT SHEETS SUBMITTED.
 PLEASE SEE THE SPECS INDICATE AN ATS AND PANEL
 COMBINATION WHICH WAS SUBMITTED ALONG WITH SPECS FOR A
 STRAIGHT ATS ONLY. PLEASE CORRELATE WHICH ONE WILL BE
 USED, HIGH-LIGHT AND ADJUST PLANS AS NEEDED.
 PLEASE SEE MISSING DISCONNECTING MEANS AS THE SPECS ARE
 UNCLEAR WHICH IS BEING USED.
 PLEASE SEE THE LOAD ON THE GENERATOR EXCEEDS THAT OF
 THE SIZE OF THE GENERATOR UNDER NATURAL AND PROPANE
 GAS.
 PLEASE SEE THE RISER HAS NOW BEEN REVISED TO SHOW 3/0
 CONDUCTOR SIZES FOR FEEDERS FROM 100AMP DISCONNECT TO
 THE ATS, ATS TO SUB PANEL AND THE FROM THE GENERATOR TO
 THE ATS. PLEASE KNOW THAT BASED ON THE BREAKER ON THE
 GENERATOR BEING AT 65AMPS, AND THE REST OF THE
 EQUIPMENT BEING SIZED AT 100AMPS, THE 3/0 CONDUCTORS
 WILL NOT FIT UNDER LUGS ETC.
 PLEASE SEE PIPE FILL OF 3/0'S IF INSTALLED AND ALSO
 TYPE OF ADAPTERS FROM 3/0'S DOWN TO LUGS UNDER THE
 BREAKERS FOR SMALLER EQUIPMENT.
 PLEASE SEE THE SPECS UNDER ONE OF THE ATS PANELS AS
 STATED WHICH REQUIRES BREAKERS FOR BEDROOM BRANCH
 CIRCUITS TO BE CHANGED OUT. (210.12)(DEPENDS ON
 EQUIPMENT USED.)
 PLEASE SEE PLUMBING REVIEW NOTES AS NO GAS RISERWAS
 SHOWN. (NOT AN ELECTRICAL COMMENT)
 PLEASE SEE SPEC SHEETS FOR GENERATOR REQUIRES SLAB TO
 BE 6 INCHES LARGER THAN THE GENERATOR IN EACH
 DIRECTION, THIS WILL AFFECT THE 24X48 SLAB AS SHOWN.
 ** PLEASE COORDINATE ALL OF THE ABOVE.
 90.7, 110.3, 310.16, 240.4, TABLES CHAPTER 9, 702.5,
 225.31-225.39. ETC
  
 2) NOTE: PLEASE INDICATE THE AIC RATINGS FOR THE NEW
 MAINS AT THE NEW SERVICE.
 110.9
 FBC 106.1.2
  
 3) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTOR FROM THE MAIN DISCONNECT AT MAIN HOUSE TO THE
 CABANA DISCONNECT. 250.32, 250.110, 250.122
  
 4) NOTE: PLEASE SEE THE NEW GROUNDING ELECTRODE AT THE
 DETACHED BUILDING NOW STATES THE SLAB STEEL, PLEASE
 INDICATE THE *FOOTER* STEEL AS THE CONNECTION IS
 REQUIRED FOR THE STEEL WHICH WOULD LOCATED WITHIN THE
 2INCHES OF THE BOTTOM OF THE FOOTER. 250.50, 250.32.
 (ONLY NEED TO CHANGE THE WORDING OF SLAB TO FOOTER.)
  
 5) NOTE: PLEASE SEE THE FIRST REVIEW WHICH SPOKE OF THE
 REQUIREMENT TO SHOW THE SMOKE DEVICE AS SMOKE ALARM IF
 120V WHICH DETECTS AND SOUNDS AN ALARM. THIS WAS
 REDLINED ON THE SECOND REVIEW AND NOTED ON REVIEW ABOUT
 THE AFCI REQUIREMENT BUT NO CHANGES WERE MADE TO THE
 SYMBOL FOR THE SMOKE DEVICE. THIS COULD BE REDLINED,
 HOWEVER AS PLANS ARE COMING BACK FOR OTHER COMMENTS,
 PLEASE MAKE THE ADJUSTMENT AT THIS TIME. PLEASE SEE
 SYMBOL LEGEND, PLANS, AND PANEL SCHEDULE WHICH ALL CALL
 FOR *SMOKE DETECTOR*.
 PLEASE SEE NFPA-72 DEFINITIONS, THE FBC.
  
 6) NOTE: PLEASE SEE PREVIOUS NOTES WHICH REQUESTED THE
 CODES TO BE ADDED TO THE ELECTRICAL SHEETS FOR 2005
 NFPA-70 (NEC) AND 2002 NFPA-72. ONLY THE 2002 NFPA-72
 WAS ADDED TO PLANS.
 PLEASE SEE OTHER SECTIONS OF CODES BEING QUOTED ON
 PLANS ON LIEU OF SHOWING CODE COMPLIANT DETAIL MAY NOT
 BE USED.
  
 7) NOTE: PLEASE SEE THE PANEL ON RISER MENTIONS
 32CIRCUIT PANEL, PANEL SCHEDULE SHOWS 30 CIRUCITS?
 408.4,
 FBC 106.1.2
  
 8) NOTE: PLEASE CLARIFY THE STACK WASHER AND DRYER. THE
 PLANS SHOW ONE RECEPTACLE OUTLET, YET THE PANEL
 SCHEDULE SHOWS WHAT APPEARS AS TWO SEPARATE SINGLE POLE
 CIRCUITS?
 IF THIS IS INDEED A SINGLE RECEPTACLE, WOULD THIS NOT
 BE A 2-POLE BREAKER?
 PLEASE SEE 210.4 AND THE NEXT COMMENT FOR SINGLE YOKES
 BEING FED FROM MORE THAN ONE CIRCUIT.
  
 9) NOTE: PLEASE SEE 210.4 AS THE DISHWASHER AND
 DISPOSAL IF BEING FED FROM THE SAME RECEPTACLE/YOKE
 MUST BE ON A 2-POL BREAKER. PLEASE REVISE PLANS TO SHOW
 TWO DEDICATE RECEPTACLES OR SHOW A 2-POLE BREAKER WHICH
 FEEDS THIS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-04-13 Cont ID  
Sent By dpalmer Date 2007-04-13 Time 14:43 Rev Time 0.00
Received By dpalmer Date 2007-04-13 Time 10:16 Sent To M
Notes
2007-04-13 14:43:42** UNSAT 2ND REVIEW **
  
 ** PLEASE SEE THAT AS THE PLANS HAVE SUBSTANTIALLY
 CHANGED FROM PREVIOUSLY SUBMITTED PLANS, THERE ARE NEW
 COMMENTS.
 NOTES ON PREVIOUS REVIEW MENTION AS THERE WERE SEVERAL
 ITEMS NOT SUBMITTED FOR REVIEW THERE MAY BE NEW
 COMMENTS ON THIS REVIEW.
  
 1) NOTE:PLEASE SUBMIT ONLY THE MANUFACTURES SPECS/CUT
 SHEETS WHICH INDICATE THE MAIN EQUIPMENT FOR THE
 GENERATOR AND ATS. PLEASE SEE THE DOCUMENTS WHICH ARE
 THE MAINTENANCE AND PARTS LIST SHEETS ARE NOT NEEDED.
 PLEASE BE SURE THE SPECS INDICATE THE MINIMUM
 CLEARANCES FOR THE EQUIPMENT AND SURROUNDING
 CLEARANCE.
 PLEASE KNOW THAT THE LATEST INFORMATION FROM GENERAC IS
 THAT THIS PARTICULAR EQUIPMENT REQUIRES A MINIMUM OF
 3FT AROUND EQUIPMENT FOR PROPER VENTILATION. PLEASE SEE
 THE GENERATOR AT THIS TIME IS SHOWN TOO CLOSE TO
 DWELLING. PLEASE ALSO SEE MECHANICAL COMMENTS FOR
 MINIMUM CLEARANCES FOR EXHAUST WHICH MAY BE REQUIRED TO
 BE 5FT FROM OPENING INTO BUILDING.
 ** PLEASE BE SURE TO REVISE ALL SHEETS WHICH INDICATE
 THIS LOCATION OF THE GENERATOR ETC.
 110.3, 90.7.
 FBC 106.1.2
  
 2) NOTE: PLEASE INDICATE THE MINIMUM LEVEL FOR THE
 GENERATOR WHICH IS REQUIRED TO BE A MINIMUM OF 6INCHES
 ABOVE THE BFE.
 PLEASE SEE THE PLANS INDICATE THIS IN A FLOOD ZONE A5,
 AND BEFORE FINAL AN ELEVATION CERTIFICATE WILL BE
 REQUIRED FOR EQUIPMENT AND GENERATOR.
  
 3) NOTE: PLEASE SEE NEW RISER DIAGRAM WHICH IS NOW
 SUBMITTED FOR REVIEW FOR THE FIRST TIME.
 PLEASE SEE 250.6 AND 250.24B AS *EQUIPMENT GROUNDING
 CONDUCTORS* ARE NOT TO BE INSTALLED BEFORE THE FIRST
 MEANS OF DISCONNECT. THIS CREATES OBJECTIONABLE
 CURRENT.
 PLEASE SEE RISER AND ADJUST.
  
 4) NOTE: PLEASE SEE THE RISER DOES NOT INCLUDE THE
 GROUNDING ELECTRODE SYSTEM AT THE DETACHED BUILDING AS
 REQUIRED PER 250.32.
 PLEASE SEE 250.50 AND 250.66. *QUOTING THE CODE IN LIEU
 OF SHOWING SPECIFIC DETAIL IS NOT PERMITTED. PLEASE
 SHOW DETAIL OF THIS.
  
 5) NOTE: PLEASE SEE RISER AND NEW PANEL. PLEASE
 INDICATE HOW THE NEW ATS IS BEING FED. PLEASE SEE THE
 PANEL SCHEDULE FOR THE CABANA SHOWS ALL OF THE CIRCUITS
 BEING FED FROM THIS PANEL AND NOT CIRCUITS FROM THE NEW
 ATS PANEL????
 PLEASE INDICATE THE OCP TO NEW ATS PANEL. PLEASE
 INDICATE THE CIRCUITS AND LOADS WHICH ARE BEING
 PROPOSED ON THIS NEW ATS PANEL.
 PLEASE SEE NO CONDUCTORS, OCP ETC ARE BEING SHOWN ON
 PANEL?
 PLEASE COMPLETE.
 408.4, 240.4, 310.16 ETC.
 FBC 106.3.5.4
  
 6) NOTE: PLEASE CORRELATE PLANS FOR NEW ATS PANEL
 LOCATION. PLEASE SEE SHEET A-2 WHICH INDICATES THE
 ATS/PANEL OUTSIDE, YET THIS PANEL IS AN INDOOR PANEL
 WHICH IS LISTED AND RATED AS A NEMA 1 PANEL. PLEASE
 KNOW, IF LOCATING THE ATS PANEL OUTSIDE, PLEASE INCLUDE
 SPECS FOR THE ATS WHICH IS RATED FOR NEMA 3 LOCATIONS.
 PLEASE SEE ELECTRICAL PLANS INDICATE THIS SAME
 EQUIPMENT INSIDE??
 PLEASE CORRELATE.
 110.3, 90.7
 FBC 106.1.2
  
 7) NOTE: PLEASE SEE 422.13 WHICH REQUIRES ALL ELECTRIC
 TYPE WATER HEATERS LOADS TO BE SHOWN AT 125%. PLEASE
 SEE THE 2005 NEC.
  
 8) NOTE: PLEASE INDICATE THE FOLLOWING APPROPRIATE
 CODES ON THE ELECTRICAL SHEETS.
 2005 NFPA-70 (NEC) AND 2002 NFPA-72.
  
 9) NOTE: PLEASE SEE MISSING REQUIRED DEDICATED BATH
 CIRCUITS PER 210.52D, 210.11C3.
 PLEASE SEE THAT THE SIZE OF THE BRANCH CIRCUIT AS SHOWN
 ON PLANS IS NOT CORRECT.
  
 10) NOTE: PLEASE CLARIFY THE STACK WASHER DRYER ON LOAD
 CALCULATIONS, AS THIS IS SHOWN AS 2-POLE 30AMP ON PANEL
 SCHEDULE? PLEASE CLARIFY.
 FBC 106.1.2
  
 11) NOTE: PLEASE SEE 210.12 AS AFCI PROTECTION IS
 REQUIRED ON THE SMOKE ALARM DEVICE(S). THIS SHOULD BE
 ON ONE OF THE OTHER CIRCUITS AS SHOWN ON PLANS. PLEASE
 ALSO SEE THAT THE PLANS INDICATE THE DEVICE AS A SMOKE
 DETECTOR AND THE PANEL SCHEDULE INDICATES SMOKE ALARMS.
 PLEASE COORDINATE.
  
 12) NOTE: PLEASE BE SURE THE SEAL FROM DESIGNER OF
 RECORD IS CLEAR AND VISIBLE WITH ALL INFORMATION ON
 SAID SEAL.
 FS481.221
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-02-08 Cont ID  
Sent By dpalmer Date 2007-02-08 Time 09:30 Rev Time 0.00
Received By dpalmer Date 2007-02-07 Time 16:54 Sent To M
Notes
2007-02-08 09:31:03***** UNSAT *****
  
  
 1) NOTE: PLEASE SEE THE PLANS SHALL STATE THE FOLLOWING
 MINIMUM CODES FOR DESIGN.
 2005 NFPA-70 AND THE 2002 NFPA-72
  
 2) NOTE: PLEASE SEE ZONING COMMENTS FOR THE SIZE OF THE
 STRUCTURE ALONG WITH THE SEPARATE METERED SERVICE WHICH
 IS NOT PERMITTED AS THIS IS ZONED SF-7.
 PLEASE SEE COMMENTS ALSO WITH RESPECT TO THE LOCATION
 OF THE GENERATOR.
 PLEASE KNOW AT THIS TIME THE RISER WILL NEED TO BE
 COMPLETELY REVISED TO FEED THE NEW CABANA FROM THE
 EXISTING HOUSE.
  
 3) NOTE: PLEASE SEE THAT LOCATION OF THE GENERATOR IS
 NOT PERMITTED PER ZONING, PLEASE ALSO SHOW AND INDICATE
 ALL DISTANCES FROM ALL SURROUNDING WALLS, WINDOWS,
 SOFFIT OPENINGS ETC.
 PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT SHEETS FOR THE
 PROPOSED GENERATOR, ATS ETC. WHAT IS THE PRIME-MOVER?
 PLEASE BE SURE THE MANUFACTURES CUT SHEETS INDICATE THE
 MINIMUM CLEARANCES REQUIRED.
 PLEASE SEE THAT THE ATS SHALL BE SERVICE ENTRANCE
 RATED, MEANS OF DISCONNECT FOR THE GENERATOR SHALL MEET
 702.6, 702.11
 90.7, 110.3, 230.70, 230.76, 230.79 ETC
 FBC 106.1.2
  
 4) NOTE: PLEASE SEE RISER WHICH SHOWS AND EQUIPMENT
 GROUNDING CONDUCTOR FROM THE METER TO THE FIRST MEANS
 OF DISCONNECT. PLEASE KNOW THAT EVEN THOUGH THE METER
 IS COMING OUT, PLEASE KNOW THAT IN ANY CASE AN *
 EQUIPMENT GROUNDING CONDUCTOR* IS NOT INSTALLED UNTIL
 AFTER THE FIRST MEANS OF DISCONNECT.
 250.6, 250.24
  
 5) NOTE: PLEASE SEE MISSING COUNTER SPACE GFI
 RECEPTACLES AS THIS IS BEING NOTED AS A KITCHEN WITH
 SMALL APPLIANCE CIRCUITS ETC.
 PLEASE SEE 210.52C1-5. MISSING COUNTER AND PENINSULAR.
  
 6) NOTE: PLEASE SEE NFPA-72 11.8.3 AS A SMOKE DETECTOR
 OR SMOKE ALARM IS NOT PERMITTED WITHIN 20FT OF ANY
 COOKING APPLIANCES UNLESS MEETING THE EXCEPTIONS OF
 THIS SECTION FOR THE TYPE OF DEVICE BEING INSTALLED.
 PLEASE KNOW THAT A MEETING WAS HELD AT THE SOUTHERN
 SECTION MEETING IN OCT 06 WHERE WE WERE DIRECTLY
 INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE DETECTORS
 ON PLANS FOR RESIDENTIAL HOMES IS NOT ACCEPTABLE WHEN
 THESE DEVICES ANY ACTUALLY FALL UNDER THE DEFINITIONS
 OF SMOKE ALARMS WHICH WOULD BE SHOWN AS SA/SMOKE
 ALARMS.
 THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE
 OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED.
 BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE
 DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL
 NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY
 HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF
 SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS
 SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS
 SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS
 FOR OTHER NEW HOMES.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72.
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 7) NOTE: PLEASE CLARIFY THE PLANS WHICH INDICATE A
 STACK WASHER /DRYER. PLEASE SEE COMMENT WITH RESPECT TO
 MISSING PANEL SCHEDULE BELOW.
 106.1.2
  
 8) NOTE: PLEASE SUBMIT A COMPLETE PANEL SCHEDULE FOR
 ALL CIRCUITS, OVER CURRENT PROTECTION DEVICES AND
 CONDUCTOR SIZES SHOWING ALL OF THE MINIMUM REQUIRED
 CIRCUITS.
 210.52, 210.11, 220, 408.4. PLEASE SEE THE FOLLOWING
 TEXT FROM THE CODE COMMENTARY WHICH STATES * THE CODE
 TO REQUIRE THAT THE IDENTIFICATION FOR EVERY CIRCUIT
 SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND
 CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE
 CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE
 MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE,
 SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN
 THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS.
 IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH
 CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE
 IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING
 ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP
 RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES
 CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR
 ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL
 REQUIRED BY THIS SECTION.
  
 9) NOTE: PLEASE SUBMIT THE FOLLOWING INFORMATION WHEN
 RISER IS REVISED WHICH WILL BE FED FROM THE MAIN HOUSE
 SERVICE. PLEASE INDICATE THE OVER CURRENT PROTECTION
 FOR NEW FEEDERS FROM THE EXISTING SERVICE. PLEASE
 SUBMIT COMPLETE LOAD CALCULATIONS ON THE EXISTING
 SERVICE WHICH WILL INCLUDE THE LOADS FOR THE NEW.
 SHOW ALL FEEDERS AND GROUNDING ELECTRODE SYSTEM. ETC
 DISCONNECTING MEANS AT THE DETACHED BUILDING ETC.
 215.5, 220, 240.4, 408.4, 310.16, 250.32, 225.31 ETC
 106.1.2, 106.3.5.4
  
 10) NOTE: PLEASE BE SURE TO INCLUDE THE REQUIRED
 DEDICATED BATH(S) CIRCUIT(S) PER 210.52D, 210.11C3.
 MUST BE 20AMP AND #12.
  
 11) NOTE: PLEASE SEE MISSING ARC FAULT PROTECTION PER
 210.12B. (THE AREA OUTSIDE KITCHEN IS BEING CONSIDERED
 ADAPTABLE SLEEPING ROOM WHICH WILL REQUIRE THIS
 PROTECTION FOR ALL OUTLETS).
  
 12) NOTE: PLEASE SEE THE MISSING PRINTED LICENSE NUMBER
 ON THE TITLE BLOCKS FOR THE DESIGNER OF RECORD ON
 SHEETS.
 FAC 61G1-16.004
  
 13) NOTE: PLEASE SEE THE ADDRESS AS ASSIGNED IS 122 AS
 THE PREVIOUS HOUSE AT 126 IS NO LONGER PRESENT AND THIS
 IS NOW PART OF THE 122 LEGAL ADDRESSED PROPERTIES.
 PLEASE ADJUST TITLE BLOCKS.
  
 14) NOTE: PLEASE KNOW THAT AT THIS TIME AS THERE ARE
 MANY ITEMS WHICH WERE NOT SUBMITTED AND THERE ARE ITEMS
 WHICH CAN NOT BE REVIEWED FOR CODE COMPLIANCE THERE MAY
 BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH ARE NOT
 PRESENT ON THIS REVIEW.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-02-07 16:55:02IN ELEC FOR REVIEW.

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2007-06-18 Cont ID  
Sent By mperson Date 2007-06-18 Time 13:48 Rev Time 0.00
Received By mperson Date 2007-06-18 Time 13:48 Sent To PC
Notes
2007-06-18 13:50:15NOTE: GAS PERMIT APPROVED ON PERMIT #07050861

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2007-05-16 Cont ID  
Sent By jleech Date 2007-05-16 Time 14:53 Rev Time 0.00
Received By jleech Date 2007-05-16 Time 14:53 Sent To M
Notes
2007-05-16 14:57:35 
 GAS PERMIT REQUIRED. A LICENSED PLUMBING OR GAS
 CONTRACTOR SHALL MAKE APPLICATION AND SUBMIT PLANS FOR
 APPROVAL. NO GAS PIPING SHALL BE INSTALLED BEFORE
 PERMIT IS ISSUED.

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2007-12-10 Cont ID  
Sent By adarroug Date 2007-12-10 Time 14:12 Rev Time 0.00
Received By adarroug Date 2007-12-10 Time 14:12 Sent To E
Notes
2007-12-10 14:13:21TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-11-14 Cont ID  
Sent By adarroug Date 2007-11-14 Time 16:47 Rev Time 0.00
Received By adarroug Date 2007-11-14 Time 16:47 Sent To P
Notes
2007-11-14 16:47:40TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-11-06 Cont ID  
Sent By jroach Date 2007-11-08 Time 11:29 Rev Time 0.00
Received By adarroug Date 2007-11-06 Time 11:04 Sent To Z
Notes
2007-11-06 11:04:25TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-11-02 Cont ID  
Sent By adarroug Date 2007-11-02 Time 11:18 Rev Time 0.00
Received By adarroug Date 2007-11-02 Time 11:18 Sent To P
Notes
2007-11-02 11:18:50TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-06-11 Cont ID  
Sent By adarroug Date 2007-06-11 Time 09:28 Rev Time 0.00
Received By adarroug Date 2007-06-11 Time 09:28 Sent To E
Notes
2007-06-11 09:28:37TO "DPALMER" DESK/RESUB--NEW SHEETS FOR "P"

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-05-15 Cont ID  
Sent By adarroug Date 2007-05-15 Time 14:54 Rev Time 0.00
Received By adarroug Date 2007-05-15 Time 14:54 Sent To  
Notes
2007-05-15 14:54:30TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-05-03 Cont ID  
Sent By adarroug Date 2007-05-03 Time 15:13 Rev Time 0.00
Received By adarroug Date 2007-05-03 Time 15:13 Sent To E
Notes
2007-05-03 15:13:54TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-05-03 Cont ID  
Sent By adarroug Date 2007-05-03 Time 15:11 Rev Time 0.00
Received By adarroug Date 2007-05-03 Time 15:11 Sent To E
Notes
2007-05-03 15:11:47TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-04-12 Cont ID  
Sent By adarroug Date 2007-04-12 Time 09:46 Rev Time 0.00
Received By adarroug Date 2007-04-12 Time 09:46 Sent To E
Notes
2007-04-12 09:46:30TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-04-04 Cont ID  
Sent By spalmer Date 2007-04-04 Time 17:18 Rev Time 0.00
Received By spalmer Date 2007-04-04 Time 17:18 Sent To Z
Notes
2007-04-04 17:18:38TO ZONING

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-05 Cont ID  
Sent By adarroug Date 2007-02-05 Time 13:56 Rev Time 0.00
Received By adarroug Date 2007-02-05 Time 13:56 Sent To E
Notes
2007-02-05 13:57:03TO "DPALMER" DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-14 Cont ID  
Sent By jgomez Date 2007-03-14 Time 19:00 Rev Time 0.00
Received By jgomez Date 2007-01-31 Time 10:12 Sent To  
Notes
2007-01-31 10:12:49TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2007-11-29 Cont ID  
Sent By tgordon Date 2007-11-29 Time 14:25 Rev Time 0.20
Received By tgordon Date 2007-11-29 Time 14:25 Sent To B
Notes
2007-11-29 14:27:13BUILDING PLAN REVISION, NO REVISIONS TO MECHANICAL
 PLAN.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-05-17 Cont ID  
Sent By tgordon Date 2007-05-17 Time 08:20 Rev Time 0.30
Received By tgordon Date 2007-05-17 Time 08:20 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-04-16 Cont ID  
Sent By tgordon Date 2007-04-16 Time 09:09 Rev Time 0.45
Received By tgordon Date 2007-04-16 Time 09:09 Sent To P
Notes
2007-04-16 09:43:49*** DENIED ***
 1) AS REQUESTED IN LAST REVIEW 2-12-07 NOTE #3,PLEASE
 SUBMIT COMBUSTION AIR CALCULATIONS OR PROVIDE
 COMBUSTION AIR FOR ALL NEW GAS APPLIANCES (GAS CLOTHES
 DRYER AND GAS WATER HEATER), PER 2004 FBC/R M1701.1.
  
 2) SEE GAS CLOTHES DRYER LOCATION ON PLANS, REFER TO
 2004 FBC/R M1701.4 PROHIBITED SOURCES.
 COMBUSTION AIR DUCTS AND OPENINGS SHALL NOT CONNECT
 APPLIANCE ENCLOSURES WITH SPACE IN WHICH THE OPERATION
 OF A FAN MAY ADVERSELY AFFECT THE FLOW OF COMBUSTION
 AIR. COMBUSTION AIR SHALL NOT BE OBTAINED FROM AN AREA
 IN WHICH FLAMMABLE VAPORS PRESENT A HAZARD. FUEL-FIRED
 APPLIANCES SHALL NOT OBTAIN COMBUSTION AIR FROM ANY OF
 THE FOLLOWING ROOMS OR SPACES:
 1.SLEEPING ROOMS.
 2.BATHROOMS.
 3.TOILET ROOMS.
  
 3) PLEASE SHOW THE LOCATION OF THE CLOTHES DRYER VENT
 ON MECHANICAL PLANS. CLOTHES DRYER VENT TERMINATION MAY
 NOT DISCHARGE NEAR THE A/C CONDENSER UNIT OR POOL
 HEATER, PER 2004 FBC/M 501.2 .
  
 4) PLEASE SHOW LOCATION OF A/C CONDENSER UNIT ON
 MECHANICAL PLANS.
  
 5) PLEASE BE AWARE THE GENERATOR MAY NOT BE WITHIN 5
 FEET OF THE DOOR TO THE STORAGE ROOM, SEE NFPA 37.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-02-12 Cont ID  
Sent By tgordon Date 2007-02-12 Time 14:30 Rev Time 0.40
Received By tgordon Date 2007-02-12 Time 14:29 Sent To P
Notes
2007-02-12 14:36:25*** DENIED ***
 1) NO MECHANICAL PLANS WERE SUBMITTED FOR
 REVIEW. PLEASE SUBMIT MECHANICAL PLANS
 FOR REVIEW, PER 2004 FBC WPB AMEND. 106.3.5.4.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 3) PLEASE SUBMIT COMBUSTION AIR CALCULATIONS OR
 COMBUSTION AIR FOR ALL NEW GAS APPLIANCES, PER 2004
 FBC/R M1701.1.
  
 4) PLEASE SUBMIT MANUFACTURER'S SPECIFICATION'S AND
 INSTALLATION INSTRUCTIONS FOR GAS BBQ GRILL AND HOOD.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 6 Status P Date 2007-12-28 Cont ID  
Sent By jleech Date 2007-12-28 Time 08:30 Rev Time 0.00
Received By jleech Date 2007-12-28 Time 08:30 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status N Date 2007-11-29 Cont ID  
Sent By jleech Date 2007-11-29 Time 13:21 Rev Time 0.00
Received By jleech Date 2007-11-29 Time 13:11 Sent To M
Notes
2007-11-29 13:33:08REVISION 4 IS FOR GAS. GAS PERMIT # 07050861 REVISION
 WAS SUBMITTED AND APPROVED ON 11/27/07.
 IF THERE IS OTHER PLUMBING CHANGES, REMOVE ALL CLOUDS
 FROM PREVIOUS CHANGES AND CLEARLY SHOW NEWCHANGES.
 PLUMBING PLAN REVIEW BY
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-06-18 Cont ID  
Sent By mperson Date 2007-06-18 Time 13:44 Rev Time 0.33
Received By mperson Date 2007-06-18 Time 13:44 Sent To G
Notes
2007-06-18 13:46:31****************PROVISO****************
 NOTE: PER FBC-2004, PLUMBING, SECTION 909.1 WET VENT
 PERMITTED: ONLY THE FIXTURES WITHIN THE BATHROOM GROUPS
 SHALL CONNECT TO THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-05-16 Cont ID  
Sent By jleech Date 2007-05-16 Time 14:50 Rev Time 0.00
Received By jleech Date 2007-05-16 Time 14:50 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-04-16 Cont ID  
Sent By jleech Date 2007-04-16 Time 14:28 Rev Time 0.00
Received By jleech Date 2007-04-16 Time 14:28 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-02-13 Cont ID  
Sent By jleech Date 2007-02-13 Time 08:06 Rev Time 0.00
Received By jleech Date 2007-02-13 Time 08:06 Sent To B
Notes
2007-02-13 08:32:20DENIED;
 1. SANITARY RISER DIAGRAM;
 A) SINKS AND W/M TO DISCHARGE DOWN STREAM OF THE
 BATHROOM SINK. SECTION 909.1 WET VENTS.
 B) AUTOMATIC CLOTHES WASHER BRANCH DRAIN TO BE
 3" WITH A C.O. AT 48" AFF. VENT REQUIRED.
 2. SHOW ON PLANS THE TYPE OF THERMAL EXPANSION CONTROL
 TO BE USED . SECTION 607.3.
 3.ADD NOTE TO PLAN, HOT WATER PIPES TO BE INSULATED,
 PER ENERGY CODE SECTION 13-612.1.
 4. PLANS MUST BE APPROVED BY ZONING BEFORE PLUMBING
 PLAN REVIEW CAN BE COMPLETE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 6 Status P Date 2007-12-18 Cont ID  
Sent By jroach Date 2007-12-18 Time 14:19 Rev Time 0.00
Received By jroach Date 2007-12-18 Time 14:19 Sent To P
Notes
2007-12-18 14:19:36***PROVISO***
  
 1) ALL MECHANICAL EQUIPMENT (I.E. POOL EQUIP.,
 CONDENSING UNIT, AND GENERATOR) SHALL BE A MINIMUM OF
 ONE (1) FOOT FROM THE WEST PROPERTY LINE AND AT LEAST
 11 FEET FROM THE SOUTH PROPERTY LINE.
  
 2) THERE SHALL TO NO COOKING FACILITIES AND THIS CANNOT
 BE A SEPARATE DWELLING UNIT.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 5 Status P Date 2007-11-08 Cont ID  
Sent By jroach Date 2007-11-08 Time 11:30 Rev Time 0.00
Received By jroach Date 2007-11-08 Time 11:29 Sent To E
Notes
2007-11-08 11:29:41***PROVISO***
  
 1) ALL MECHANICAL EQUIPMENT (I.E. POOL EQUIP.,
 CONDENSING UNIT, AND GENERATOR) SHALL BE A MINIMUM OF
 ONE (1) FOOT FROM THE WEST PROPERTY LINE AND AT LEAST
 11 FEET FROM THE SOUTH PROPERTY LINE.
  
 2) THERE SHALL TO NO COOKING FACILITIES AND THIS CANNOT
 BE A SEPARATE DWELLING UNIT.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 4 Status P Date 2007-05-14 Cont ID  
Sent By jroach Date 2007-05-14 Time 16:54 Rev Time 0.00
Received By jroach Date 2007-05-14 Time 16:54 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2007-04-11 Cont ID  
Sent By jroach Date 2007-04-11 Time 19:44 Rev Time 0.00
Received By jroach Date 2007-04-11 Time 19:44 Sent To I
Notes
2007-04-11 19:48:13***PROVISO***
  
 1) ALL MECHANICAL EQUIPMENT (I.E. POOL EQUIP.,
 CONDENSING UNIT, AND GENERATOR) SHALL BE A MINIMUM OF
 ONE (1) FOOT FROM THE WEST PROPERTY LINE AND AT LEAST
 11 FEET FROM THE SOUTH PROPERTY LINE.
  
 2) REF/FREEZER IN THE CABANA SHALL ONLY BE
 UNDER-THE-COUNTER.THERE SHALL TO NO COOKING
 FACILITIES AND THIS CANNOT BE A SEPARATE DWELLING
 UNIT.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status P Date 2007-11-08 Cont ID  
Sent By mmclean Date 2007-02-03 Time 11:49 Rev Time 0.00
Received By mmclean Date 2007-02-03 Time 11:49 Sent To I
Notes
2007-02-03 13:29:15DENIED,
 1. SHALL APPLY FOR A SEPARATE PERMIT FOR THE PROPOSED
 FENCE WITH EASEMENT APPROVAL FROM THE CITY OF WEST PALM
 BEACH UTILITY DEPT.
 2. SHALL PROVIDE THE DISTANCE OF THE PROPOSED LANI AND
 CANBANA COVERED PORCH ON TWO COPIES OF
 SITEPLANS/SURVEYS.
 3. THE REF. IN THE POOL CABANA SHALL BE AN U/C REF. NO
 COOKING FACILITY SHALL BE ALLOWED AND CABANA SHALL NOT
 BE USED AS A SEPARATE LIVING SPACE.
 4. CANNOT HAVE A SEPARATE ELECTRICAL SERVICE AT
 LOCATION, SHALL BE FED FROM THE MAIN STRUCTURE, ZONED
 SF7.
 5. PLEASE PROVIDE A COPY OF THE UNITY OF TITLE FOR THE
 PROPERTY (UNIFYING THE PROPERTY AS ONE) AND REFERECE
 THE DEMO PERMIT FOR THE STRUCTURE ON THE PROPERTY.
 6. THE PROPOSED POOL EQUIPMENT AND GENERATOR SHALL
 SHOWN ON THE TWO COPIES OF SITEPLANS.
 7. THE PROPOSED POOL QUIPMENT. A/C UNIT AND GENERATOR
 SHALL BE NO CLSOER THAN 11.7FT FROM THE REAR PROPERTY
 LINE.
 8. THE SUBMITTED SITEPLANS DOES NOT SHOW THE POOL
 EQUIPMENT AND GENERATOR.
 9. THE PROPOSED CABANA INCLUDING ROOF COVERED PORCH
 CANNOT EXCEED THE 1000SQ FT TOTAL. SEC 94-304(B)(1)
 MAXIMUM SQUARE FOOTAGE. THE TOTAL FLOOR AREA OF ALL
 ROOFED ACCESSORY BUILDINGS ON A PROPERTY SHALL NOT
 EXCEED 75% OF THE GROSS FLOOR AREA OF THE PRIMARY
 STRUCTURE WITH A MAXIMUM FLOOR OF 1,000 SQ FEET. THE
 PROPOSED CABANA WILL EXCEED THE SQUARE FOOTAGE OF TOTAL
 ROOF.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720
  