Plan Review Details - Permit 07011202
Plan Review Stops For Permit 07011202
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-03-28 Cont ID  
Sent By jwitmer Date 2007-03-28 Time 14:42 Rev Time 1.33
Received By jwitmer Date 2007-03-28 Time 14:41 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-07 Cont ID  
Sent By jwitmer Date 2007-03-07 Time 15:21 Rev Time 1.22
Received By jwitmer Date 2007-03-07 Time 15:21 Sent To FIRE
Notes
2007-03-07 15:55:44BUILDING PLAN REVIEW
 PERMIT: 07011202
 ADD: 2471 OKEECHOBEE BLVD.
 CONT: MILLER CONSTRUCTION
 TEL: (954)764-6550
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)COMPLIED. ARCHITECT JEFFERY L.PEAL
  
 3) S-1.1 DESIGN LOADS IN THE NOTE 2 & 3 BOTH INDICATE
 THE WRONG ASCE 7-98 PLEASE UPDATE.
  
 4) PLANS INDICATE THE USE OF EFIS WALL SYSTEMS, WILL
 REQUIRE:
 FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 EFIS WALL SYSTEMS
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5)) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-03-14 Cont ID  
Sent By dpalmer Date 2007-03-14 Time 11:49 Rev Time 0.00
Received By dpalmer Date 2007-03-14 Time 11:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-02-08 Cont ID  
Sent By dpalmer Date 2007-02-08 Time 13:51 Rev Time 0.00
Received By dpalmer Date 2007-02-08 Time 12:40 Sent To  
Notes
2007-02-08 13:51:15***** UNSAT *****
  
  
 1) NOTE: PLEASE SEE THE PLANS SHALL STATE THE FOLLOWING
 MINIMUM CODES FOR DESIGN.
 2005 NFPA-70, 2003 NFPA-101 AND THE 2002 NFPA-72
  
  
 ** PLANS WOULD HAVE PASSED AND WOULD HAVE HAD CODES
 REDLINED FOR NOTE #1 IF THIS IS THE ONLY COMMENT.
 THIS WILL BE PENDING COMMENTS FROM OTHER TRADES.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-03-27 Cont ID  
Sent By mawillia Date 2007-03-27 Time 11:17 Rev Time 0.00
Received By mawillia Date 2007-03-27 Time 10:59 Sent To  
Notes
2007-03-27 11:16:04*****APPROVED*****
  
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;PLAN SHEET A-6.1 STAMPED, INITIALED,
 AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-03-07 Cont ID  
Sent By mawillia Date 2007-03-07 Time 17:36 Rev Time 0.00
Received By mawillia Date 2007-03-07 Time 16:58 Sent To  
Notes
2007-03-07 17:35:38*****DENIED*****
  
  
 01.THE 2003 EDITION OF NFPA 101, LIFE SAFETY CODE,
 SHALL BE REFERENCED.
  
 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.MAY
 BE ADDED TO SHEET A-5.1
  
 03.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF
 NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE
 OR HINDER WITH ACCESS TO OR EXIT FROM THE STRUCTURE, OR
 THE VICINITY OF THE STRUCTURE (INCLUDING FIRE LANES).
 MAY BE ADDED TO SHEET A-5.1
  
 04.DISPLAY THE NUMERICAL ADDRESS ON THE APPROPIATE
 EXTERIOR ELEVATION FRONTING OKEECHOBEE BOULEVARD.AS
 PER WEST PALM BEACH CODE, NUMERALS SHALL BE NO LESS
 THAN 6" IN HEIGHT AND 1" IN WIDTH AND SHALL BE OF A
 COLOR IN DIRECT CONTRAST TO AND CLEARLY DISTINGUISHABLE
 FROM ITS BACKGROUND.ILLUSTRATE ON SHEET A-6.1,
 DIAGRAM # 03(DO NOT PLACE NUMBERS ON DOORS)
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-12 Cont ID  
Sent By adarroug Date 2007-03-12 Time 10:48 Rev Time 0.00
Received By adarroug Date 2007-03-12 Time 10:48 Sent To  
Notes
2007-03-12 10:48:48TO "COMM" BD#32

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-07 Cont ID  
Sent By jbabcock Date 2007-02-15 Time 13:11 Rev Time 0.00
Received By mawillia Date 2007-01-29 Time 19:20 Sent To  
Notes
2007-02-07 15:15:14TO "COMM" BD#50
2007-01-29 19:20:25WAITING FOR "COMM" BD

Review Stop Z ZONING
Rev No 1 Status P Date 2007-02-15 Cont ID  
Sent By jbabcock Date 2007-02-15 Time 13:10 Rev Time 0.00
Received By jbabcock Date 2007-02-15 Time 13:10 Sent To I
Notes
***NONE***