 |
Plan Review Details - Permit 07011175
| Plan Review Stops For Permit 07011175 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2008-07-21 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-07-21 |
Time |
15:53 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-07-21 |
Time |
13:52 |
Sent To |
PC |
|
| Notes |
| 2008-07-21 15:26:51 | PROVISOR: 11-4.6.2 ACCESSIBLE PARKING SPACES SERVING | | | THEBUILDING SHALL BE LOCATED ON THE SHORTEST SAFELY | | | ACCESSIBLE ROUTE OF TRAVEL FROM ADJACENT PARKING TO AN | | | ACCESSIBLE ENTRANCE. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2008-05-22 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-05-22 |
Time |
16:04 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-05-21 |
Time |
15:43 |
Sent To |
|
|
| Notes |
| 2008-05-22 16:03:44 | BUILDING PLAN REVIEW | | | PERMIT: 07011175 | | | ADD: 1115 ? 13TH STREET | | | CONT: ALL SITE CONST. | | | TEL: (561)848-1110 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 5TH | | | ACTION: DENIED | | | 5-21-08 | | | | | | 1A)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT | | | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 3)OK | | | | | | **NOTED; HOWEVER, THE VALUE INDICATED ON THE | | | APPLICATION IS FOR THE ADDITION, THE ADDITIONAL VALUE | | | FOR THE RENOVATION SHALL BE ADDED TO THE VALUE. | | | 4)5TH REQUEST. THE DECLARED VALUE OF THE PROJECT IS | | | LOW IN VALUE. IF THE VALUE OF THE PROJECT IS NOT | | | INCREASED, THE CITY WILL CALCULATE THE COST OF THE | | | PROJECT USING MARSHALL & SWIFT FOR CALCULATION PURPOSES | | | LATEST EDITION. 384 SQ FT X 105.10 (ADDITION ALONE) = | | | $40,359. THE COST FOR REMODELING THE EXISTING STRUCTURE | | | SHALL ALSO BE ADDED TO THE FIGURE MENTION ABOVE. THE | | | VALUE SHALL BE THE TOTAL REPLACEMENT COST INCLUDING | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISHES AND | | | ARCHITECTURAL DESIGN. WPB AMENDMENTS 108.3 | | | | | | 5)5TH REQUEST. A CHANGE IN OCCUPANCY PLUS AN ADDITION | | | IMPACT FEES ASSESSMENT: BEFORE A PERMIT TO CONSTRUCT, | | | MAY BE ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH | | | COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED | | | BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED | | | TO THE PERMIT APPLICATION. PLEASE CALL (561) 233-5025 | | | FOR MORE INFORMATION. | | | | | | 6)OK | | | | | | NOTE | | | 7)EXISTING BUILDING CODE, 812.5 ACCESSIBILITY. | | | EXISTING BUILDING OR PORTIONS THEREOF THAT UNDER GOES A | | | CHANGE IN OCCUPANCY CLASSIFICATION, SHALL COMPLY WITH | | | CHAPTER 11 OF THE FLORIDA BUILDING CODE. | | | | | | NOTE | | | 8)EXISTING BUILDING CODE 905.1 ACCESSIBILITY | | | PROVISIONS FOR NEW ADDITION THAT AFFECTS THE | | | ACCESSIBILITY TO OR CONTAIN AN AREA OF, PRIMARY | | | FUNCTION SHALL COMPLY WITH THE REQUIREMENTS IN CHAPTER | | | 11 OF THE FLORIDA BUILDING CODE. | | | | | | *NOTED: HOWEVER SUBMIT ELEVATION DRAWINGS SHOWING THE | | | SLOPE OF THE ACCESSIBLE ROUTE IN RELATION TO THE 5?X5? | | | LANDING AT EACH DOOR. 11-4.8.2 SLOPE & RISE. THE LEAST | | | POSSIBLE SLOPE SHALL BE USED FOR ANY RAMP. THE MAXIMUM | | | SLOPE FOR A RAMP IN NEW CONSTRUCTION SHALL BE 1 TO 12. | | | THE MAXIMUM RISE FOR RUN SHALL BE 30" (SEE FIGURE 16). | | | ADDITIONAL INFORMATION REQUIRED: WPB AMENDMENTS | | | 106.1.2 | | | 9)4TH REQUEST. PLEASE PROVIDE SITE PLAN INDICATING | | | THE HANDICAPPED PARKING AND ACCESSIBLE ROUTE TO THE | | | ENTRY 11-4.1.1 (A) (B) 11-4.1.2 (5) (A). | | | | | | *NOTED* | | | 10) 3RD REQUEST. FL BUILDING CODE 1609.1.4 COMPONENTS | | | AND CLADDING PROVIDE 2 COPIES OF UPDATED PRODUCT | | | APPROVALS FOR THE WINDOWS. THE ONES SUBMITTED WERE | | | UNDER THE 2001 CODE VERSION. THERE IS A NEW PRODUCT | | | APPROVAL FOR EXTERIOR DOORS IN THE PACKAGE WHICH WAS | | | NOT APPROVED BY THE DESIGNER OF RECORD. PLEASE CIRCLE | | | OR HI-LIGHT WHICH DOOR WILL BE USED FROM THE PACKAGE. | | | THE PRODUCT APPROVAL SHALL BE APPROVED BY THE DESIGNER | | | OF RECORD. | | | SHEET S-2 INDICATES FOAM INSTALLATION INJECTED INTO THE | | | NEW CMU WALLS (PROVIDE THE MANUFACTURE SPECS) AND FOAM | | | INSULATION SPRAYED BETWEEN THE UPPER PORTIONS OF THE | | | TRUSSES. THE INSULATION R-VALUE INDICATED IN THE ATTIC | | | AREA IS R-20. PROVIDE THE MANUFACTURE SPECS AND | | | INSTALLATION SPECIFICATIONS FOR THE SPRAYED INSULATION | | | WHICH WILL MEET THE R-20 VALUE WHEN SPRAYED ON 2?X4? | | | TRUSSES. SUBMIT THE PRODUCT APPROVAL FOR THE RIDGE VENT | | | SYSTEM WHICH IS SHOWN ON SHEET S-2. | | | | | | 11)OK | | | 12)OK | | | 13)OK | | | 14)OK | | | | | | **NEW: THE IMPUT DATA SHEETS DO NOT MATCH THE PLANS, | | | THERE ARE NO ALUMINIUM DOORS ON THE PROJECT AS STATED | | | ON SHEET #4. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | FAX (561) 805-6676 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2008-02-08 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-02-08 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-02-07 |
Time |
08:11 |
Sent To |
|
|
| Notes |
| 2008-02-08 09:27:56 | | | | | | | | | | | | | | | | | | | | | | BUILDING PLAN REVIEW | | | PERMIT: 07011175 | | | ADD: 1115 ? 13TH STREET | | | CONT: ALL SITE CONST. | | | TEL: (561)848-1110 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 4TH | | | ACTION: DENIED | | | 2-7-08 | | | | | | 1A)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT | | | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 3)OK | | | | | | 4)4TH REQUEST. THE DECLARED VALUE OF THE PROJECT IS | | | LOW IN VALUE. IF THE VALUE OF THE PROJECT IS NOT | | | INCREASED, THE CITY WILL CALCULATE THE COST OF THE | | | PROJECT USING MARSHALL & SWIFT FOR CALCULATION PURPOSES | | | LATEST EDITION. 384 SQ FT X 105.10 (ADDITION ALONE) = | | | $40,359. THE COST FOR REMODELING THE EXISTING STRUCTURE | | | SHALL ALSO BE ADDED TO THE FIGURE MENTION ABOVE. THE | | | VALUE SHALL BE THE TOTAL REPLACEMENT COST INCLUDING | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISHES AND | | | ARCHITECTURAL DESIGN. WPB AMENDMENTS 108.3 | | | | | | 5)4TH REQUEST. A CHANGE IN OCCUPANCY PLUS AN ADDITION | | | IMPACT FEES ASSESSMENT: BEFORE A PERMIT TO CONSTRUCT, | | | MAY BE ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH | | | COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED | | | BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED | | | TO THE PERMIT APPLICATION. PLEASE CALL (561) 233-5025 | | | FOR MORE INFORMATION. | | | | | | 6)4TH REQUEST. PLANS INDICATE THE USE OF 32? DOORS, | | | THE 32? POCKET DOORS ARE CODE COMPLIANT BUT THE OTHER | | | DOORS THAT ARE 32? WILL NOT PROVIDE A 32? OPENING. FBC | | | 11-4.13.5 DOORS SHALL HAVE A MINIMUM CLEAR OPENING OF | | | 32? WITH THE DOOR OPEN 90 DEGREES, MEASURED BETWEEN THE | | | FACE OF THE DOOR AND THE OPPOSITE STOP [SEE FIGURE | | | 24(A,B,C,D)]. PLEASE SEE INFORMATION IN PACKAGE SHOWING | | | THE EXAMPLES OF DIFFERENT DOOR TYPES. RESTROOM DOORS | | | ARE OK. | | | | | | NOTE | | | 7)EXISTING BUILDING CODE, 812.5 ACCESSIBILITY. | | | EXISTING BUILDING OR PORTIONS THEREOF THAT UNDER GOES A | | | CHANGE IN OCCUPANCY CLASSIFICATION, SHALL COMPLY WITH | | | CHAPTER 11 OF THE FLORIDA BUILDING CODE. | | | | | | NOTE | | | 8)EXISTING BUILDING CODE 905.1 ACCESSIBILITY | | | PROVISIONS FOR NEW ADDITION THAT AFFECTS THE | | | ACCESSIBILITY TO OR CONTAIN AN AREA OF, PRIMARY | | | FUNCTION SHALL COMPLY WITH THE REQUIREMENTS IN CHAPTER | | | 11 OF THE FLORIDA BUILDING CODE. | | | | | | 9)4TH REQUEST. PLEASE PROVIDE SITE PLAN INDICATING | | | THE HANDICAPPED PARKING AND ACCESSIBLE ROUTE TO THE | | | ENTRY 11-4.1.1 (A) (B) 11-4.1.2 (5) (A). | | | | | | 10) 3RD REQUEST. FL BUILDING CODE 1609.1.4 COMPONENTS | | | AND CLADDING PROVIDE 2 COPIES OF UPDATED PRODUCT | | | APPROVALS FOR THE WINDOWS. THE ONES SUBMITTED WERE | | | UNDER THE 2001 CODE VERSION. THERE IS A NEW PRODUCT | | | APPROVAL FOR EXTERIOR DOORS IN THE PACKAGE WHICH WAS | | | NOT APPROVED BY THE DESIGNER OF RECORD. PLEASE CIRCLE | | | OR HI-LIGHT WHICH DOOR WILL BE USED FROM THE PACKAGE. | | | THE PRODUCT APPROVAL SHALL BE APPROVED BY THE DESIGNER | | | OF RECORD. | | | | | | 11)OK | | | 12)OK | | | 13)OK | | | 14)OK | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | FAX (561) 805-6676 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2007-10-30 |
|
|
Cont ID |
|
| Sent By |
jjohnsto |
Date |
2007-10-30 |
Time |
10:28 |
Rev Time |
6.00 |
| Received By |
jjohnsto |
Date |
2007-10-30 |
Time |
10:26 |
Sent To |
|
|
| Notes |
| 2007-10-30 10:28:49 | CONSTRUCTION SERVICES DEPARTMENT | | | 200 SECOND STREET, 3RD FLOOR, | | | WEST PALM BEACH, FLORIDA33401 | | | TEL:561-805-6713 FAX:561-805-6731 | | | | | | JAMES JOHNSTON, | | | BUILDING PLAN EXAMINER II | | | E-MAIL:JJOHNSTON @WPB.ORG | | | | | | | | | PERMIT NO 07011175 | | | PROJECT LIL KING & QUEEN ACADEMY | | | ADDRESS 1115 13TH ST | | | DATE OCTOBER 29, 2007 | | | | | | | | | BUILDINGPLANREVIEW | | | | | | FLORIDA BUILDING CODES 2004 | | | | | | 1 | | | FLORIDA STATUE713.13NOTICE OF COMMENCEMENT FILE | | | NOTICE WITH THE CLERK OF COURT RECORDING DIVISION. IF | | | THE WORK | | | DESCRIBED IN THE NOTICE IS NOT COMMENCED WITHIN 90 DAYS | | | OF | | | FILING THE NOTICE WILL BECOME NULL AND VOID. SUBMIT THE | | | NOTICE | | | AT THE TIME OF PERMIT ISSUANCE AND POST A COPY AT THE | | | JOB SITE | | | BEFORE THE FIRST INSPECTION. | | | | | | COMMENT-FOR YOUR INFORMATION | | | | | | | | | 2(3) | | | PROJECT INFORMATION | | | FBC2004 BUILDING W/ 2005 AND 6 REVISIONS | | | FBC2004 ACCESSIBILITYCHAPTER 11 | | | FBC2004 EXISTING BUILDING | | | LEVEL OF ALTERATION,FBC EXISTING LEVEL III | | | TYPE OF CONSTRUCTION, FBC503 V - B | | | SPRINKLED / UN-SPRINKLED UN-SPRINKLED | | | BASIC WIND SPEEDMPHWPB AMEND 117.1140 | | | WIND EXPOSUREFBC1609.4B | | | WIND IMPORTANCE FACTOR,FBC 1604.5II-1 | | | TYPE OF OCCUPANCY, FBC CHAPTER 3D/E | | | OCCUPANT LOAD,FBC 100460 | | | | | | COMMENT-NOTE THE FOLLOWING INFORMATION ON THE COVER | | | SHEET | | | VERIFY THE INFORMATION PROVIDED WITH THE CODE SECTION | | | SUBMITTED | | | | | | | | | 3 | | | PERMIT FEES (3RD REQUEST) | | | (4)FEES ARE STILL OUTSTANDING. | | | | | | 4 | | | IMPACT FEES | | | BEFORE A PERMIT TO CONSTRUCT MAY BE ISSUED, IMPACT FEES | | | MUST | | | BE PAID TO PALM BEACH COUNTY. | | | THE PERMITTED SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE INFORMATION. PALM | | | BEACH COUNTY ASSESSMENT | | | PALM BEACH COUNTY IMPACT FEE ASSESSMENT HAS MOVED TO: | | | 2300 N JOG ROAD, SUITE 2 WPB 33411 | | | | | | COMMENT-FOR YOUR INFORMATION | | | | | | | | | 5 | | | FLORIDA STATUE481.2131INTERIOR DESIGN; PRACTICE | | | REQUIREMENTS; | | | DISCLOSURE OF COMPENSATION FOR PROFESSIONAL SERVICES.? | | | | | | COMMENT- THE CBD CHARLES FRANKLIN MUST BE LICENSED BY | | | THE | | | STATE OF FLORIDA TO HAVE THEIR NAME IN THE TITLE BLOCK. | | | PLEASE REMOVE. | | | | | | | | | 6 (3RD REQUEST) | | | FBC11-4HANDICAP PARKING | | | | | | COMMENT- PLEASE PROVIDE DETAILS FOR THE H.C. PARKING | | | SPACE TO INCLUDE | | | A-FREE STANDING SIGN, POLE HEIGHT FROM GRADE TO | | | BOTTOM OF SIGN. | | | B-SIGN WITH LETTERING AND FEE AMOUNT. | | | C-STRIPING PER WPBFLORIDA BUILDING CODE AMENDMENTS | | | DEFINING | | | DOUBLE LINES, COLOR OF STRIPING AND H.C. SYMBOL. D- | | | PROVIDE A SECTIONAL | | | VIEW OF THE ASPHALT ACCESS ISLE TO THE SIDEWALK | | | | | | | | | | | | 7 (3RD REQUEST) | | | A-PLEASE PROVIDE AN EXTERIOR DOOR SCHEDULE WITH WIND | | | DESIGN | | | PRESSURES, HARDWARE, SIZE, TYPE | | | | | | | | | 8 | | | FLORIDA ENERGY CODE | | | CEILING PLAN REFLECTSR-19 | | | ENERGY FORMR-30 | | | | | | WALL INSULATIONPLAN DETAILR 4.2, | | | ENERGY FORM R 5.0 | | | | | | COMMENT ? PLEASE CORRECT THIS FORM | | | SUBMIT TWO REPORTS COMPLETED IN INK , SIGNED SEALED | | | | | | | | | | | | | | | | | | STATUS OF COMMENTS FROM PREVIOUS | | | REVIEWER | | | | | | (1) COMPLIED | | | | | | (6) COMPLIED | | | | | | (7) COMPLIED | | | | | | (8) COMPLIED | | | | | | (10)COMPLIED | | | | | | (11)COMPLIED | | | | | | (12)COMPLIED | | | | | | (14)COMPLIED |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-06-04 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-06-04 |
Time |
15:28 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2007-06-04 |
Time |
15:28 |
Sent To |
PC |
|
| Notes |
| 2007-06-04 15:37:16 | BUILDING PLAN REVIEW | | | PERMIT: 07011175 | | | ADD: 1115 13TH ST | | | CONT: ALL-SITE CONSTRUCTION | | | TEL: (561)317-6959 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1STREVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2 ) FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF | | | THE COURT. | | | NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS | | | NOT ACTUALLY | | | COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF, | | | SUCH NOTICE IS NULL & VOID. | | | NOTE: 713.13(6)THE POSTING OF THE NOTICE OF | | | COMMENCEMENT AT THE CONSTRUCTION | | | SITE BEFORE THE FIRST INSPECTION. | | | | | | 3 ) 2ND REQUEST110.2* W. P. B. ADMINISTRATIVE CODE, | | | INFORMATION THAT IS REQUIRED FOR RECORD KEEPING & FOR | | | CERTIFICATE OF OCCUPANCY: | | | A) THE EDITION OFTHE CODE UNDER WHICH | | | THE PERMIT WILL BE ISSUED. PLAANS SUBMITTED AFTER | | | 12-08-06 ARE TO BE DESIGNED UNDER THE 2006 FBC NOTE | | | ALSO REFLECT EXISTING BUILDING CODE 2004/2006 | | | AMENDMENTS | | | NOTE CHAPTER 8 FOR CHANGE IN OCCUPANCY 2006 FBC | | | EXISTING BUILDING | | | NOTE CHAPTER 9 FOR ADDITIONS 2006 FBC EXISTING BUILDING | | | CODE | | | B) THE USE AND OCCUPANCY, IN ACCORDANCE | | | WITH THE PROVISIONS OF CHAPTER 3.NOTE CHANGE IN | | | OCCUPANCY. | | | C) THE TYPE OF CONSTRUCTION AS DEFINED | | | IN CHAPTER 6, TABLE 601. RESPONSE INDICATES THE | | | DESIGN AS TYPE III-B FOR A DAYCARE THE DAYCARE COULD | | | HAVE 14,500 SQ FT AND 2 STORY, THIS IS A MINIMUM CODE | | | PLEASE PROVIDE THE CORRECT INFORMATION. | | | D) THE OCCUPANTLOAD, SEE 1004. | | | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS | | | PROVIDED, WHETHER THE SPRINKLER SYSTEM | | | IS REQUIRED. | | | F) ANY SPECIAL STIPULATIONS & CONDITIONS | | | OF THE BUILDING PERMIT. | | | *** THIS INFORMATION IS TO APPEAR ON THE PLANS** | | | | | | 4) 2ND REQUEST,THE DECLARED VALUE OF THE PROJECT IS LOW | | | IN VALUE. IF THE VALUE OF THE PROJECT IS NOT | | | INCREASED, | | | THE CITY WILL CALCULATE THE COST OF THE PROJECT USING | | | MARSHALL & SWIFT FOR CALCULATING PURPOSES | | | LATEST EDITION. 384 SQ FT X $105.10(ADDITION ALONE)= | | | $40,359.00.I-4 OCCUPANCY / DAYCARE | | | SEE CALCULATED FEES + STATE RADON FEES= FEE BALANCE OF | | | $307.18.2ND REVIEW, M FEES ARE STILL OUTSTANDING. | | | | | | 5) 2ND REQUEST, A CHANGE IN OCCUPANCY PLUS ANADDITION | | | IMPACT FEES ASSESSMENT; | | | BEFORE A PERMIT TO CONSTRUCT, MAY | | | BE ISSUED, IMPACT FEES MUST BE PAID TO | | | PALM BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 6) 2ND REQUEST,PLANS INDICATE THE USE OF 32" DOORS, | | | THE 32" POCKET DOORS ARE | | | CODE COMPLIANTBUT THE OTHER DOORS THAT ARE A 32" DOOR | | | WILL NOT PROVIDE A 32" OPENING. | | | | | | RESTROOM DOORS:11-4.22.2 DOORS. | | | ALL DOORS TO ACCESSIBLE TOLIET ROOMS SHALL COMPLY WITH | | | 11-4.13. DOORS SHALL NOT SWING INTO | | | CLEAR FLOOR SPACE REQUIRED FOR ANY FIXTURE. | | | 11-4.13.6 MANEUVERING CLEARENCES | | | AT DOORS. MINIMUM MANEUVERING CLEARANCESAT DOORS THAT | | | ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL BE AS SHOWN | | | IN | | | FIG. 25. THE FLOOR OR GROUND AREA WITH IN THE REQUIRED | | | CLEARANCES SHALL BE CLEAR & LEVEL. | | | PROVIDE THE CLEAR FLOOR SPACE FOR THE PLUMBING | | | FIXTURES, HIGHLIGHT THIS AREA, YOU WILL SEE THE | | | RESTROOM DOORS SWING INTO THE CLEAR FLOOR SPACE | | | REQUIRED FOR THE FIXTURES!!!!! | | | | | | 7) EXISTING BUILDING CODE, 812.5 ACCESSIBILITY. | | | EXISTING BUILDINGS OR PORTIONS THERREOF THAT UNDERGO A | | | CHANGE IN OCCUPANCY CLASSIFICATION SHALL COMPLY WITH | | | CHAPTER 11 OF THE FLORIDA BUILDING CODE. | | | | | | 8) EXISTING BUILDING CODE 905.1 ACCESSIBILITY | | | PROVISIONS FOR NEW CONSTRUCTION SHALL APPLY TO | | | ADDITIONS. AN ADDITION THAT AFFECTS THE ACCESSIBILITY | | | TO OR CONTAIN AN AREA OF, PRIMARY FUNCTION SHALL COMPLY | | | WITH THE REQUIREMENTS IN CHAPTER 11 OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 9)2ND REQUEST,PLEASE PROVIDE SITE PLAN INDICATING THE | | | HANDICAPPED PARKING AND ACCESSIBLE ROUTE TO THE | | | ENTRY.11-4.1.1(A)(B) 11-4.1.2(5)(A). SHEET 2 INDICATES | | | A 44" ACCESS AISLE LEADING FROM THE DISABLED PARKING | | | SPACE BUT THE PLANS FAIL TO INDICATE A CURB CUT THROUGH | | | THE4" THICK SIDEWALK. PLANS ALSO FAIL TO INDICATE THE | | | TOP OF THE ACCESSIBLE SIDE WALK IN REGARDS TO THE | | | INTERIOR FINISH FLOOR. | | | | | | 10)2ND REQUEST,FL BLD CODE 1609.1.4: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A) WINDOWS SUBMITTED WERE 2001 | | | | | | 11 PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | | | | 12)WPB ADMIN CODE 106.3* PRODUCT | | | APPROVALS. THOSE PRODUCT WHICH ARE | | | REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL. | | | | | | 13) COMPLIED. | | | | | | 14)2ND REQUEST, 1203.2 ATTIC SPACES. | | | ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE | | | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF | | | FRAMING MEMBERS SHALL HAVE CROSS VENTILATION FOR EACH | | | SEPARATE SPACE BY VENTILATING OPENINGS PROTECTED | | | AGAINST THE ENTRANCE OF RAIN. BLOCKING AND BRIDGING | | | SHALL BE ARRANGED SO AS NOT TO INTERFERE WITH THE | | | MOVEMENT OF AIR. A MINIMUM OF 1 INCH (25 MM) OF | | | AIRSPACE SHALL BE PROVIDED BETWEEN THE INSULATION AND | | | THE ROOF SHEATHING. THE NET FREE VENTILATING AREA SHALL | | | NOT BE LESS THAN 1 / 150 OF THE AREA OF THE SPACE | | | VENTILATED, WITH 50 PERCENT OF THE REQUIRED VENTILATING | | | AREA PROVIDED BY VENTILATORS LOCATED IN THE UPPER | | | PORTION OF THE SPACE TO BE VENTILATED AT LEAST 3 FEET | | | (914 MM) ABOVE EAVE OR CORNICE VENTS WITH THE BALANCE | | | OF THE REQUIRED VENTILATION PROVIDED BY EAVE OR CORNICE | | | VENTS. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-03-12 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-03-12 |
Time |
09:06 |
Rev Time |
1.55 |
| Received By |
jwitmer |
Date |
2007-03-12 |
Time |
09:07 |
Sent To |
PC |
|
| Notes |
| 2007-03-12 09:25:21 | BUILDING PLAN REVIEW | | | PERMIT: 07011175 | | | ADD: 1115 13TH ST | | | CONT: ALL-SITE CONSTRUCTION | | | TEL: (561)317-6959 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1STREVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2 ) FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF | | | THE COURT. | | | NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS | | | NOT ACTUALLY | | | COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF, | | | SUCH NOTICE IS NULL & VOID. | | | NOTE: 713.13(6)THE POSTING OF THE NOTICE OF | | | COMMENCEMENT AT THE CONSTRUCTION | | | SITE BEFORE THE FIRST INSPECTION. | | | | | | 3 ) 110.2* W. P. B. ADMINISTRATIVE | | | CODE, INFORMATION THAT IS REQUIRED FOR | | | | | | RECORD KEEPING & FOR CERTIFICATE OF | | | OCCUPANCY: | | | A) THE EDITION OFTHE CODE UNDER WHICH | | | THE PERMIT WAS ISSUED. | | | NOTE ALSO REFLECT EXISTING BUILDING CODE 2004/2006 | | | AMENDMENTS | | | NOTE CHAPTER 8 FOR CHANGE IN OCCUPANCY | | | NOTE CHAPTER 9 FOR ADDITIONS | | | B) THE USE AND OCCUPANCY, IN ACCORDANCE | | | WITH THE PROVISIONS OF CHAPTER 3.NOTE CHANGE IN | | | OCCUPANCY. | | | C) THE TYPE OF CONSTRUCTION AS DEFINED | | | IN CHAPTER 6, TABLE 601. | | | | | | D) THE DESIGN OCCUPANT LOAD, SEE 1004. | | | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS | | | PROVIDED, WHETHER THE SPRINKLER SYSTEM | | | IS REQUIRED. | | | F) ANY SPECIAL STIPULATIONS & CONDITIONS | | | OF THE BUILDING PERMIT. | | | | | | 4) THE DECLARED VALUE OF THE PROJECT IS LOW IN VALUE. | | | IF THE VALUE OF THE PROJECT IS NOT INCREASED, | | | THE CITY WILL CALCULATE THE COST OF THE PROJECT USING | | | MARSHALL & SWIFT FOR CALCULATING PURPOSES | | | LATEST EDITION. 384 SQ FT X $105.10(ADDITION ALONE)= | | | $40,359.00.I-4 OCCUPANCY / DAYCARE | | | SEE CALCULATED FEES + STATE RADON FEES= FEE BALANCE OF | | | $307.18. | | | | | | 5) A CHANGE IN OCCUPANCY PLUS AN | | | ADDITION IMPACT FEES ASSESSMENT; | | | BEFORE A PERMIT TO CONSTRUCT, MAY | | | BE ISSUED, IMPACT FEES MUST BE PAID TO | | | PALM BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 6) PLANS INDICATE THE USE OF 32" DOORS, THE 32" POCKET | | | DOORS ARE | | | CODE COMPLIANTBUT THE OTHER DOORS THAT ARE A 32" DOOR | | | WILL NOT PROVIDE A 32" OPENING. | | | RESTROOM DOORS:11-4.22.2 DOORS. | | | ALL DOORS TO ACCESSIBLE TOLIET ROOMS SHALL COMPLY WITH | | | 11-4.13. DOORS SHALL NOT SWING INTO | | | CLEAR FLOOR SPACE REQUIRED FOR ANY | | | FIXTURE. | | | 11-4.13.6 MANEUVERING CLEARENCES | | | AT DOORS. MINIMUM MANEUVERING CLEARANCES | | | AT DOORS THAT ARE NOT AUTOMATIC OR | | | POWER-ASSISTED SHALL BE AS SHOWN IN | | | FIG. 25. THE FLOOR OR GROUND AREA WITH | | | IN THE REQUIRED CLEARANCES SHALL BE | | | CLEAR & LEVEL. | | | | | | 7) EXISTING BUILDING CODE, 812.5 ACCESSIBILITY. | | | EXISTING BUILDINGS OR PORTIONS THERREOF THAT UNDERGO A | | | CHANGE IN OCCUPANCY CLASSIFICATION SHALL COMPLY WITH | | | CHAPTER 11 OF THE FLORIDA BUILDING CODE. | | | | | | 8) EXISTING BUILDING CODE 905.1 ACCESSIBILITY | | | PROVISIONS FOR NEW CONSTRUCTION SHALL APPLY TO | | | ADDITIONS. AN ADDITION THAT AFFECTS THE ACCESSIBILITY | | | TO OR CONTAIN AN AREA OF, PRIMARY FUNCTION SHALL COMPLY | | | WITH THE REQUIREMENTS IN CHAPTER 11 OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 9) PLEASE PROVIDE SITE PLAN INDICATING THE HANDICAPPED | | | PARKING AND ACCESSIBLE ROUTE TO THE | | | ENTRY.11-4.1.1(A)(B)/ 11-4.1.2(5)(A). | | | | | | 10)FL BLD CODE 1609.1.4: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A) WINDOWS | | | B) EXTERIOR DOORS | | | C) TRUSS ANCHORS | | | D) LOUVERS | | | E) ROOF ASSEMBLIES | | | | | | 11 PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | | | | 12)WPB ADMIN CODE 106.3* PRODUCT | | | APPROVALS. THOSE PRODUCT WHICH ARE | | | REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL. | | | | | | 13) PLANS DO NOT PROVIDE SLOPE OF ROOF PLEASE COMPLY | | | WITH: | | | 1507.2.8 UNDERLAYMENT APPLICATION. | | | FOR ROOF SLOPES FROM TWO UNITS VERTICAL IN 12 UNITS | | | HORIZONTAL (17-PERCENT SLOPE), UP TO FOUR UNITS | | | VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT SLOPE), | | | UNDERLAYMENT SHALL BE TWO LAYERS APPLIED IN THE | | | FOLLOWING MANNER. APPLY A MINIMUM 19-INCH-WIDE (483 MM) | | | STRIP OF UNDERLAYMENT FELT PARALLEL WITH AND STARTING | | | AT THE EAVES, FASTENED SUFFICIENTLY TO HOLD IN PLACE. | | | STARTING AT THE EAVE, APPLY 36-INCH-WIDE (914 MM) | | | SHEETS OF UNDERLAYMENT OVERLAPPING SUCCESSIVE SHEETS 19 | | | INCHES (483 MM) AND FASTENED SUFFICIENTLY TO HOLD IN | | | PLACE. FOR ROOF SLOPES OF FOUR UNITS VERTICAL IN 12 | | | UNITS HORIZONTAL (33-PERCENT SLOPE) OR GREATER, | | | UNDERLAYMENT SHALL BE ONE LAYER APPLIED IN THE | | | FOLLOWING MANNER. UNDERLAYMENT SHALL BE APPLIED SHINGLE | | | FASHION, PARALLEL TO AND STARTING FROM THE EAVE AND | | | LAPPED 2 INCHES (51 MM), FASTENED ONLY AS NECESSARY TO | | | HOLD IN PLACE. | | | | | | 14) 1203.2 ATTIC SPACES. | | | ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE | | | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF | | | FRAMING MEMBERS SHALL HAVE CROSS VENTILATION FOR EACH | | | SEPARATE SPACE BY VENTILATING OPENINGS PROTECTED | | | AGAINST THE ENTRANCE OF RAIN. BLOCKING AND BRIDGING | | | SHALL BE ARRANGED SO AS NOT TO INTERFERE WITH THE | | | MOVEMENT OF AIR. A MINIMUM OF 1 INCH (25 MM) OF | | | AIRSPACE SHALL BE PROVIDED BETWEEN THE INSULATION AND | | | THE ROOF SHEATHING. THE NET FREE VENTILATING AREA SHALL | | | NOT BE LESS THAN 1 / 150 OF THE AREA OF THE SPACE | | | VENTILATED, WITH 50 PERCENT OF THE REQUIRED VENTILATING | | | AREA PROVIDED BY VENTILATORS LOCATED IN THE UPPER | | | PORTION OF THE SPACE TO BE VENTILATED AT LEAST 3 FEET | | | (914 MM) ABOVE EAVE OR CORNICE VENTS WITH THE BALANCE | | | OF THE REQUIRED VENTILATION PROVIDED BY EAVE OR CORNICE | | | VENTS. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2008-07-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-07-18 |
Time |
10:59 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-07-18 |
Time |
10:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2008-05-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-05-27 |
Time |
17:05 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-05-27 |
Time |
17:05 |
Sent To |
|
|
| Notes |
| 2008-05-27 17:05:57 | ** DENIED ** | | | | | | 1) NOTE: PLEASE KNOW AT THE REQUEST OF THE OWNER MR. | | | SLYDELL NO REVIEW IS TO BE PERFORMED ON ELECTRICAL | | | PLANS AS PLANS ARE KNOWN TO BE NON-CODE COMPLIANT. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF | | | THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT | | | HESITATE IN CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2008-01-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-01-31 |
Time |
19:40 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-01-31 |
Time |
19:40 |
Sent To |
|
|
| Notes |
| 2008-01-31 19:40:12 | ** DENIED 4TH REVIEW ** | | | | | | ** PLEASE SEE COMMENTS FROM PREVIOUS REVIEW ALONG WITH | | | NEW COMMENTS NOW BASED ON ENERGY CALCULATIONS NOW ONLY | | | BEING SUBMITTED FOR THE FIRST REVIEW. THESE WERE NOT | | | SUBMITTED ON PREVIOUS REVIEW AS PREVIOUS REVIEWS HAD | | | REQUESTED. | | | | | | *** IMPORTANT: PLEASE KNOW THIS IS THE 2ND REVIEW UNDER | | | NEW DESIGN PROFESSIONALS. PLEASE SEE THE LAST COMMENT | | | BELOW. | | | | | | 1) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.2, | | | 13-101.1.3, 13-101.1.1, 13-400.3A, 13-400.3B | | | PLEASE SEE NEW METHOD *A* IS NOW BEING SUBMITTED WHICH | | | REQUIRES COMPLIANCE WITH WHOLE BUILDING. | | | PLEASE SEE 13-103.1.1.1, FS 481.221, FAC 61G15-23.002, | | | FS 471.025 AS THE CERTIFICATION SHEET IS NOT FILLED OUT | | | WITH ALL INFORMATION AND CORRECT SIGNING, DATING AND | | | SEALING OF DOCUMENTS. | | | PLEASE SEE THIS IS BEING LEFT BLANK. THE ONLY SIGNATURE | | | DONE CORRECTLY WAS THAT OF THE OWNER. | | | PLEASE BE SURE THE DOCUMENTS ARE SIGNED, DATED AND | | | SEALED BY THE RESPONSIBLE DESIGNER BASED ON SCOPE OF | | | WORK. | | | PLEASE CORRELATE ALL INFORMATION ON PLANS WITH THAT OF | | | THE INFORMATION ON THE INPUT DATA REPORT WHICH IS PART | | | OF THE ENERGY CALCULATIONS. | | | FOR EXAMPLE: PLEASE SEE THE IDR DOES NOT SHOW ANY | | | EXTERIOR LIGHTING ENTERED. HOW IS THIS POSSIBLE WHEN | | | THE PLANS CLEARLY SHOW EXTERIOR LIGHTS? | | | | | | PLEASE SEE THE LIGHTING SHOWN ON PLANS ALONG WITH THE | | | FIXTURE LEGEND AS SUBMITTED DOES NOT CORRELATE WITH THE | | | INPUT DATA REPORT ON ENERGY CALCULATIONS. IN FACT THERE | | | ARE NUMEROUS INCONSISTENCIES. PLEASE SEE SOME EXAMPLES | | | GIVEN BELOW: | | | FOR EXAMPLE: PLEASE SEE THE FIXTURES SHOWN IN BATHROOMS | | | ARE NOTED WITH TWO-75WATT BULBSWHICH WOULD BE 150W | | | YET THE FIXTURES ON THE IDR INDICATE ONLY ONE SINGLE | | | 60W BULB. HOW IS THIS POSSIBLE? | | | FOR EXAMPLE: PLEASE SEE THE FLUORESCENT FIXTURES WHICH | | | ARE SHOWN ON THE FIXTURE LEGEND AS CONTAINING TWO 75W | | | BULBS WHICH WOULD BE 150W, YET THE IDR ONLY SHOWS 80W | | | FOR THE SAME FIXTURES. THE FIRST COMMENT FROM THIS | | | REVIEWER IS THAT A 75W FLUORESCENT BULB IS NOT PART OF | | | ANY KNOWN FIXTURE AS SHOWN. PLEASE CHECK THE BULB | | | WATTAGES ON THE PROPOSED FLUORESCENT FIXTURES. | | | PLEASE ALSO SEE THE AMOUNT OF FIXTURES ON PLANS AND | | | WATTAGES AS SHOWN WAY EXCEED THAT OF THE INFORMATION | | | AND FIXTURES ON PLANS. | | | | | | PLEASE SEE THE USE MAY NOT BE ENTERED AS | | | SCHOOL/UNIVERSITY. THIS OCCUPANCY IS NOT EITHER OF | | | THESE. | | | ** THESE ARE ONLY A FEW EXAMPLES ON HOW THE ENERGY | | | CALCULATIONS DO NOT MATCH OR CORRELATE WITH PLANS. | | | | | | 2) NOTE: PLEASE SEE PREVIOUS THREE REVIEWS WHICH | | | SPECIFICALLY STATED THAT THE LOAD CALCULATIONS BEING | | | SUBMITTED WERE FOR A *RESIDENTIAL HOUSE*. THIS IS NOT A | | | RESIDENTIAL HOUSE AND MAY NOT USE THE CALCULATIONS AS | | | SUBMITTED. PLEASE SEE ALL PREVIOUS REVIEW GAVE THE | | | SPECIFIC CODES ON COMMERCIAL USE/OCCUPANCY LOAD | | | CALCULATIONS YET THEY ARE STILL SHOWN FOR RESIDENTIAL | | | USE?????? | | | PLEASE SEE 220.3, 220.12, 220.14, 220.42, 220.44, ETC, | | | PLEASE SEE 215.3, 230.42 ETC FOR ALL CONTINUOUS LOADS | | | WHICH ARE REQUIRED TO BE SHOWN AT 125%. | | | | | | 3) NOTE: PLEASE SEE ONE OF THE NEW COMMENTS IS NOW THE | | | WATER HEATER WHICH HAS NOW CHANGED FROM THE PREVIOUS | | | REVIEWED PLANS. | | | PLEASE SEE THE PREVIOUS ELECTRICAL PLANS LISTED ON THE | | | PANEL SCHEDULE THE WH AT 4500VA AND YET NOW THE PANEL | | | SCHEDULE LIST THIS UNIT AS 3500VA AND 6000VA. HOW IS | | | THIS POSSIBLE? WHICH ONE IS IT? | | | PLEASE CORRELATE AND SEE NOTES ABOVE WITH RESPECT TO | | | LOAD CALCULATIONS. | | | | | | 4) NOTE: PLEASE SEE THE PREVIOUS REVIEW NOTED THAT AN | | | *EQUIPMENT GROUNDING CONDUCTOR* WAS MISSING AFTER THE | | | FIRST MEANS OF DISCONNECT AND NOW THE RISER SHOWS AN | | | EQUIPMENT GROUNDING CONDUCTOR WHICH IS OK EXCEPT IT IS | | | NOT IN THE CONDUIT ALONG WITH THE OTHER FEEDERS. PLEASE | | | PLACE THIS CONDUCTOR INSIDE THE NOTE FOR THE | | | CONDUCTORS. THIS CAN NOT BE RUN SEPARATELY BY ITSELF. | | | 250.110, 250.122, ETC | | | | | | 5) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO | | | REPEAT COMMENTS FOR CODE COMPLIANCE. | | | THIS IS ONLY A NOTICE GIVEN AT THIS TIME DUE TO THE | | | FACT THIS IS ONLY THE SECOND REVIEW UNDER NEW DESIGNER. | | | PLEASE KNOW IF ANY OF THE SAME CODE COMPLIANCE COMMENTS | | | ARE REPEATED ON THE NEXT REVIEW THIS OFFICE WILL AS | | | REQUIRED UNDER FLORIDA STATUTES HAVE NO CHOICE BUT TO | | | ASSESS A 4X PLAN REVIEW FEE TO THE DESIGNER OF RECORD. | | | ** AS STATED ON ALL PREVIOUS REVIEWS,,,,, IF THERE ARE | | | ANY QUESTIONS, PLEASE CALL THIS OFFICE OR REVIEWER TO | | | GO OVER THESE NOTES. | | | ONE COPY OF EACH ELECTRICAL SHEET ALONG WITH ENERGY | | | CALCULATIONS SUBMITTED ARE BEING RETAINED BY THIS | | | OFFICE. | | | | | | ** ONCE AGAIN IF COMMENTS ARE NOT UNDERSTOOD OR TYPED | | | IN ANY FASHION WHICH IS NOT CLEAR, PLEASE CONTACT THIS | | | REVIEWER AT THE CONTACT INFORMATION BELOW. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2007-10-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-10-22 |
Time |
18:33 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-10-22 |
Time |
17:35 |
Sent To |
|
|
| Notes |
| 2007-10-22 18:33:51 | 2007-10-22 18:33:51 | | | | | | *** DENIED 3RD REVIEW *** | | | | | | 1) NOTE: ** THIS IS THE FIRST REVIEW UNDER A NEW DESIGN | | | TEAM AND ALL NEW PLANS WERE SUBMITTED. | | | | | | ** PLEASE SEE HOWEVER THERE ARE SEVERAL COMMENTS FROM | | | THE TWO PREVIOUS REVIEWS WHICH ARE THE SAME AND STILL | | | APPLY. THERE ARE MANY OF THESE WHICH HAVE NOT BEEN | | | ADDRESSED AND THERE ARE SOME NEW COMMENTS ONCE AGAIN | | | DUE TO THE FACT THAT THERE ARE COMPLETELY NEW PLANS | | | SUBMITTED. | | | | | | ** PLEASE KNOW AS THERE IS STILL INFORMATION NOT | | | SUBMITTED OR DESIGNED INTO THE PLANS FOR *MINIMUM* CODE | | | COMPLIANCE, AND A FULL AND COMPLETE REVIEW CAN NOT BE | | | DONE. THE REVIEW COMMENTS CAN ONLY BE BASED ON PLANS | | | AND DOCUMENTS SUBMITTED. | | | | | | 2) NOTE: PLEASE LIST THE BELOW CODES ON ELECTRICAL | | | PLANS AS THEY ARE BEING PRINTED BELOW. THE PLANS APPEAR | | | TO TAKE PART OF MY PREVIOUS REVIEW COMMENTS AND PLACE | | | THIS ON THE SHEETS. PLEASE SEE CODE WHICH SEEMS TO BE | | | MISPRINT FOR NEPA. PLEASE ONLY INDICATE THE FOLLOWING. | | | 2004 FBC W/2006 REVISIONS. | | | 2005 NPPA-70 | | | 2002 NFPA-72 | | | 2003 NFPA-101 | | | | | | ** SOME ARE OK, HOWEVER NOT ALL AND ONLY MINOR | | | ADJUSTMENTS ARE NEEDED. PLANS ARE COMING BACK FOR | | | CORRECTIONS AT THIS TIME. | | | | | | 3) NOTE: PLEASE COMPLETE AND CORRELATE ALL CIRCUITING | | | ON PLANS. PLEASE SEE THAT THERE ARE CIRCUITS ON PLANS | | | FOR EXAMPLE FOR 120V GFI LOADS WHICH ARE SHOWN | | | CIRCUITED TO A/C SYSTEM WHICH IS NOT POSSIBLE. PLEASE | | | SEE FOR EXAMPLE: CIRCUITS 18 AND 19 ON PLANS. PLEASE | | | SEE 700.12F FOR CIRCUITING OF EMERGENCY AND EXIT | | | LIGHTS. THESE ARE REQUIRED TO BE CIRCUITED TO THE | | | NORMAL LIGHTING BRANCH CIRCUITS IN THE AREAS IN WHICH | | | THEY ARE LOCATED. | | | FBC 106.1.2, 106.3.5.1.2, 106.3.1. ETC | | | NEC 408.4, 310.16, 240.4. | | | PLEASE SEE THE FOLLOWING STATEMENT WHICH IS TAKEN | | | DIRECTLY FROM THE NEC. | | | *2005 CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY | | | CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE | | | LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR | | | WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME | | | PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR | | | EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY | | | OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN | | | COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL | | | APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD, | | | THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL | | | RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR | | | ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.'' | | | CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH | | | ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE | | | SUFFICIENT DETAIL REQUIRED BY THIS SECTION* | | | **SAME COMMENT ON TWO PREVIOUS REVIEWS. | | | | | | 4) NOTE: PLEASE LABEL ALL LIGHTING FIXTURES ON PLANS | | | AND CORRELATE WITH A COMPLETE FIXTURE LEGEND FOR | | | FIXTURES WHICH INDICATE TYPE AND ANY SAFETY ASPECTS FOR | | | FIXTURES (ENCLOSED LENSES ETC REQUIRED) PLEASE BE SURE | | | FIXTURES SPECIFIED MEET THE LIFE SAFETY CODE FOR DAY | | | CARE OCCUPANCIES. | | | A COMPLETED FIXTURE LEGEND OF FIXTURES IS REQUIRED. FBC | | | 106.1.2 LS 101 CHAPTER 16. | | | **SAME COMMENT ON PREVIOUS TWO REVIEWS. | | | | | | 5) NOTE:THIS WAS THE SAME COMMENT FROM TWO PREVIOUS | | | REVIEWS AND YET NO COMPLIANCE WITH FBC CHAPTER 13 OR | | | CALCULATIONS HAS BEEN SUBMITTED. | | | PLEASE SUBMIT COMPLETE ENERGY CALCULATIONS TO MEET THE | | | 2004 FBC 13-415.1.AB.1. | | | PLEASE ALSO PROVIDE INFORMATION ON LIGHTING POWER | | | DENSITIES PER 13-415.2 | | | PLEASE SEE THAT NONE WERE SUBMITTED. | | | PLEASE ALSO SEE 13-103.1.1.1 FOR REQUIRED | | | CERTIFICATIONS. | | | ** SAME AS TWO PREVIOUS REVIEWS. | | | | | | 6) NOTE: PLEASE SEE LS-101 16.5.1.2 | | | SPECIAL PROTECTIVE COVERS FOR ALL ELECTRICAL | | | RECEPTACLES SHALL BE INSTALLED IN ALL AREAS OCCUPIED BY | | | CLIENTS. | | | PLEASE KNOW THAT THIS DOES NOT MEAN THE PLASTIC PLUG-IN | | | TYPE DEVICES, THIS MEANS THE RECEPTACLE DEVICE SHALL BE | | | LISTED FOR USE (110.3) AND BE OF THE TYPE WHICH | | | PROVIDES AUTOMATIC PROTECTION IF AN APPLIANCE IS NOT | | | PLUGGED IN OR IN USE. | | | ** SAME AS TWO PREVIOUS REVIEWS. MAY NOT QUOTE THE CODE | | | OR REQUIREMENT IN LIEU OF ACTUAL DESIGN OR SPECIFIC | | | DETAILS NEEDED. 106.1.2 | | | | | | 7) NOTE: PLEASE SEE LS 101 2003, 6.1.4.1 FOR USE, | | | 9.6.4, 16.3.4.5. | | | PLEASE SEE ALL SMOKE DETECTION DEVICES AND SYSTEM SHALL | | | BE SHOWN. | | | THIS IS NOT A RESIDENCE OR SINGLE FAMILY DWELLING. | | | PLEASE SEE REVIEW COMMENTS FROM FIRE MARSHAL AS FIRE | | | ALARM SYSTEM IS REQUIRED. | | | PLEASE SEE FBC 11-4.28.1,.2 AND .3(4) FOR MINIMUM | | | LOCATIONS AND DEVICE LEVELS TO MEET ADA. | | | | | | | | | 8) NOTE: PLEASE INDICATE THE MINIMUM LEVELS FOR EGRESS | | | LIGHTING PER 7.8., 7.9. | | | PLEASE SEE 106.1.2 FBC FOR ADDITIONAL INFORMATION | | | NEEDED. | | | | | | 9) NOTE: THE LOAD CALCULATIONS SUBMITTED ONCE AGAIN ARE | | | FOR A RESIDENTIAL USE AND NOT FOR COMMERCIAL. PLEASE | | | REVISE AND CORRECT. | | | PLEASE SEE THE LOAD CALCULATIONS SHALL MEET 2005 NEC, | | | THESE ARE SUBMITTED AND SHOWN FOR DWELLING USE AND | | | OCCUPANCY. | | | PLEASE SEE 220.3, 220.12, 220.14, 220.42, 220.44, | | | PLEASE BE SURE ALL CONTINUOUS LOADS AT SHOWN AT 125%. | | | 215.3, 230.42 | | | ** SAME NOTE AS TWO PREVIOUS REVIEWS. | | | | | | 10) NOTE: PLEASE SEE THE NOTE #3 ON PANEL SCHEDULE | | | NOTES MENTIONS * AHU IS NOW- CONCURRENT WITH CONDENSING | | | UNIT*. | | | PLEASE VERIFY THIS AS THIS IS MOST LIKELY NOT WHAT IS | | | MEANT TO BE NOTED. PLEASE SEE 220.60 WHICH IS FOR A/C. | | | THIS IS EXTRACTED FROM THE NEC BELOW FOR CLARIFICATION | | | OF CODE. | | | *220.60 NONCOINCIDENT LOADS | | | WHERE IT IS UNLIKELY THAT TWO OR MORE NONCOINCIDENT | | | LOADS WILL BE IN USE SIMULTANEOUSLY, IT SHALL BE | | | PERMISSIBLE TO USE ONLY THE LARGEST LOAD(S) THAT WILL | | | BE USED AT ONE TIME FOR CALCULATING THE TOTAL LOAD OF A | | | FEEDER OR SERVICE.* | | | | | | 11) NOTE: PLEASE SEE MISSING DISCONNECT FOR WATER | | | HEATER. PLANS SHOW A RECEPTACLE WHICH CAN NOT BE USED | | | FOR CONNECTION OF WATER HEATERS. 422.30, 422.31. | | | | | | 12) NOTE: PLEASE SEE 422.13 AS STORAGE TYPE WATER | | | HEATERS ARE NOW CONSIDERED UNDER THE 2005 NEC AS A | | | CONTINUOUS LOADS WHICH REQUIRES LOAD TO BE FIGURED AT | | | 125% IN CALCULATIONS. | | | PLEASE SEE NOTE # 9 ABOVE AS ALL CALCULATIONS WILL BE | | | ADJUSTED. | | | | | | 13) NOTE: PLEASE PROVIDE ALL LICENSE INFORMATION AS | | | REQUIRED FOR ALL DESIGNERS ON PLANS AS LICENSED UNDER | | | FS 481. | | | PLEASE SEE 481.229 AS *DESIGNERS/DRAFTSPERSONS* NOT | | | LICENSED UNDER FS 481 MAY NOT DESIGN OR DO COMMERCIAL | | | WORK AS IN THE SCOPE AS LISTED ON PLANS. | | | PLEASE ADJUST TITLE BLOCKS WHICH REMOVES THE DESIGNER | | | AS SHOWN ON INCLUDE THE LICENSE INFORMATION AS REQUIRED | | | PER FAC61G1-16.004, FS 481. | | | ** THE COMMENT IS NOT FOR MR. WRONKSKY. | | | ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES | | | WHETHER OR NOT COMMENT IS MADE BY ANY OF THE OTHER | | | TRADE REVIEWS. | | | | | | 14) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING | | | CONDUCTOR FROM MAIN TO SUB PANEL. | | | 250.110, 250.24, 250.122 ETC. | | | | | | 15) NOTE: PLEASE KNOW WITH RESPECT TO FS 553.80(2)(B), | | | THE FEE AS REQUIRED BY THE FLORIDA STATUES AS NOTED | | | WHICH WOULD HAVE BEEN ASSESSED IS NOT ASSESSED DUE TO | | | NEW DESIGN TEAM. | | | | | | ** PLEASE KNOW AS MENTIONED ABOVE, AS THERE WILL BE | | | SEVERAL CHANGES ON PLANS AND AS THERE ARE SEVERAL ITEMS | | | NOT SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW | | | COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE | | | AT THIS TIME. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-05-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-05-11 |
Time |
09:16 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-05-10 |
Time |
16:48 |
Sent To |
|
|
| Notes |
| 2007-05-11 09:16:18 | ** UNSAT2ND REVIEW ** | | | | | | ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA | | | BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED | | | BY THE CITY OF WEST PALM BEACH. | | | | | | *** PLEASE SEE THAT IS A CHANGE IN OCCUPANCY TO DAY | | | CARE FACILITY. | | | | | | 1) NOTE: PLEASE STATE AND DESIGN TO ALL OF THE | | | FOLLOWING MINIMUM CODES AT A MINIMUM FOR ELECTRICAL | | | REVIEW. | | | NFPA-70 2005 (2002 STATES ON PLANS), 2002 NFPA-72, 2003 | | | NFPA-101, 2004 FBCW/2006 REVISIONS. | | | PLEASE SEE MISPRINT ON ELECTRICAL SHEETS ALONG WITH THE | | | CODE AND ?BUILDING LEVEL? ? BEING SHOWN AS #2? | | | ** PLEASE SEE THAT THE PLANS STATE A *LEVEL 2 | | | ALTERATION*, HOW IS THIS POSSIBLE WHEN THIS IS A CHANGE | | | IN OCCUPANCY AND ALL SHALL BE DESIGNED TO THE NEW AND | | | CURRENT CODES. | | | | | | 2) NOTE: PLEASE BE SURE PLANS ARE DONE IN A CLEAR AND | | | PRINTED MANOR WHICH ARE A MINIMUM OF DRAFTSMAN QUALITY | | | AS REQUIRED UNDER FBC 106.1.3 | | | | | | 3) NOTE:SAME COMMENT, NO INFORMATION SUBMITTED. | | | PLEASE LABEL ALL LIGHTING FIXTURES ON PLANS AND | | | CORRELATE WITH A COMPLETE FIXTURE LEGEND FOR FIXTURES | | | WHICH INDICATE TYPE AND ANY SAFETY ASPECTS FOR FIXTURES | | | (ENCLOSED LENSES ETC REQUIRED) PLEASE BE SURE FIXTURES | | | SPECIFIED MEET THE LIFE SAFETY CODE FOR DAY CARE | | | OCCUPANCIES. | | | PLEASE ALSO SEE THESE LIGHTING FIXTURES AND SCHEDULES | | | MUST MEET THE FLA-COM CALCULATIONS FOR CHAPTER 13 OF | | | THE FBC 2004 W/2006 REVISONS. | | | FBC 106.1.2 LS 101 CHAPTER 16. | | | | | | 4) NOTE: SAME NOTE: PLEASE SUBMIT COMPLETE ENERGY | | | CALCULATIONS TO MEET THE 2004 FBC 13-415.1.AB.1.ETC | | | PLEASE BE SURE COORDINATE ALL FIXTURES ON PLANS WITH | | | THAT OF THE FIXTURE SCHEDULE AND CALCULATIONS. PLEASE | | | ALSO PROVIDE INFORMATION ON LIGHTING POWER DENSITIES | | | PER 13-415.2 | | | PLEASE SEE THE ENERGY CALCULATIONS NOW SUBMITTED ARE | | | METHOD B FOR RESIDENTIAL. THIS IS NOT A RESIDENTIAL | | | OCCUPANCY AND MAY NOT USE THIS. PLEASE ALSO SEE THAT | | | WHEN THE CORRECTED CALCULATIONS ARE SUBMITTED, THESE | | | ARE REQUIRED TO BE SIGNED, DATED AND SEALED AS | | | PREVIOUSLY STATED AND REQUIRED UNDER THE FBC. PLEASE | | | ALSO SEE 13-103.1.1.1 FOR REQUIRED CERTIFICATIONS. | | | | | | 5) NOTE:SAME NOTE: PLEASE SEE A NOTE WAS ADDED FOR | | | REQUIRED DEVICES; HOWEVER NO CHANGES WERE MADE TO THE | | | SYMBOL LEGEND FOR TYPE? ETC. | | | PLEASE SEE LS-101 16.5.1.2 | | | SPECIAL PROTECTIVE COVERS FOR ALL ELECTRICAL | | | RECEPTACLES SHALL BE INSTALLED IN ALL AREAS OCCUPIED BY | | | CLIENTS. | | | PLEASE KNOW THAT THIS DOES NOT MEAN THE PLASTIC PLUG-IN | | | TYPE DEVICES, THIS MEANS THE RECEPTACLE DEVICE SHALL BE | | | LISTED FOR USE (110.3) AND BE OF THE TYPE WHICH | | | PROVIDES AUTOMATIC PROTECTION IF AN APPLIANCE IS NOT | | | PLUGGED IN OR IN USE. | | | | | | 5) NOTE: PLEASE CLARIFY THE NEW NOTE #6 WHICH WAS ADDED | | | TO PLANS. THIS NOTE AND THE CODE SECTION NOTED HAVE | | | NOTHING TO DO WITH ONE ANOTHER. | | | PLEASE SEE THE LS CODE STIPULATES THE MINIMUM LEVELS | | | FOR EGRESS LIGHTING PER 7.8.1.3, 7.9.2.2. | | | PLEASE SEE THE SECTION OF THE FBC NOTED IS FOR | | | ADDITIONAL INFORMATION REQUIRED ON PLANS ONLY. | | | | | | 6) NOTE: AS RISER HAS NOW CHANGED FROM THAT PREVIOUSLY | | | SUBMITTED, PLEASE SEE THE PANEL SCHEDULE SHOWS A MCB ( | | | MAIN CIRCUIT BREAKER) AND THE RISER SHOWS PANEL AS | | | MLO(MAIN LUG ONLY). PLEASE COORDINATE. | | | | | | 7) NOTE: PLEASE SEE THE PLANS APPEAR TO SHOW A PANEL | | | INSIDE, HOWEVER AS THE PLANS ARE NOT CLEAR, THE | | | LOCATION IS NOT CONFIRMED. | | | *IMPORTANT* | | | PLEASE BE SURE TO SEE THE LIFE SAFETY CODE WITH RESPECT | | | TO ELECTRICAL PANELS IN DAY CARE USE OCCUPANCIES. | | | (PANELS REQUIRED CONTAINING LOCKABLE COVERS IF INSIDE | | | BUILDING AND ACCESSIBLE FOR OCCUPANTS. | | | PLEASE SEE 110.26, 240.24, 408.7, LS 101CHAPTER 6. | | | | | | 8) NOTE:THIS IS THE SAME NOTE. THE LOAD CALCULATIONS | | | SUBMITTED ARE FOR A RESIDENTIAL USE AND NOT FOR | | | COMMERCIAL. PLEASE REVISE AND CORRECT. | | | PLEASE SEE THE LOAD CALCULATIONS SHALL MEET 2005 NEC, | | | THESE ARE SUBMITTED AND SHOWN FOR DWELLING USE AND | | | OCCUPANCY. | | | PLEASE SEE 220.3, 220.12, 220.14, 220.42, 220.44, | | | PLEASE BE SURE ALL CONTINUOUS LOADS AT SHOWN AT 125%. | | | 215.3, 230.42 | | | | | | 9) NOTE: PLEASE KNOW THAT SINCE THERE ARE MANY ITEMS | | | NOT YET SUBMITTED FOR REVIEW, PLEASE KNOW THAT THERE | | | MAY BE NEW COMMENTS ON THE NEXT REVIEW WHICH ARE NOT | | | MADE AT THIS TIME. | | | PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO REPEAT | | | COMMENTS FOR CODE COMPLIANCE. | | | | | | | | | ** ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-02-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-02-11 |
Time |
10:47 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-02-11 |
Time |
08:22 |
Sent To |
|
|
| Notes |
| 2007-02-11 10:48:14 | 2007-02-11 10:48:14 | | | **** UNSAT **** | | | | | | | | | *** PLEASE SEE THAT IS A CHANGE IN OCCUPANCY TO DAY | | | CARE FACILITY. | | | | | | | | | 1) NOTE: PLEASE STATE AND DESIGN TO ALL OF THE | | | FOLLOWING MINIMUM CODES AT A MINIMUM FOR ELECTRICAL | | | REVIEW. | | | NFPA-70 2005 (2002 STATES ON PLANS), 2002 NFPA-72, 2003 | | | NFPA-101, 2004 FBC. | | | | | | ** PLEASE SEE THAT THE PLANS STATE A *LEVEL 2 | | | ALTERATION*, HOW IS THIS POSSIBLE WHEN THIS IS A CHANGE | | | IN OCCUPANCY AND ALL SHALL BE DESIGNED TO THE NEW AND | | | CURRENT CODES. | | | | | | 2) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND | | | CORRELATE WITH A SUBMITTED PANEL SCHEDULE WHICH IS | | | CLEAR AND VISIBLE WITH ALL INFORMATION. PLEASE SEE THE | | | PANEL SCHEDULE IS NOT CLEAR FOR ITEMS ON PANEL. PLEASE | | | CORRELATE PLANS AND PANEL SCHEDULE AS THERE ARE | | | ELECTRICAL ITEMS ON PANEL SCHEDULE WHICH ARE NOT ON | | | PLANS. | | | PLEASE SEE 700.12E FOR CIRCUITING OF EMERGENCY AND EXIT | | | LIGHTS. | | | FBC 106.1.2, 106.3.5.1.2, 106.3.1. ETC | | | NEC 408.4, 310.16, 240.4. | | | PLEASE SEE THE FOLLOWING STATEMENT WHICH IS TAKEN | | | DIRECTLY FROM THE NEC. | | | *2005 CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY | | | CIRCUIT SUPPLIED BY A PANELBOARD OR SWITCHBOARD BE | | | LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR | | | WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME | | | PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR | | | EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY | | | OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN | | | COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL | | | APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD, | | | THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL | | | RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR | | | ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.'' | | | CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH | | | ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE | | | SUFFICIENT DETAIL REQUIRED BY THIS SECTION* | | | | | | 3) NOTE: PLEASE LABEL ALL LIGHTING FIXTURES ON PLANS | | | AND CORRELATE WITH A COMPLETE FIXTURE LEGEND FOR | | | FIXTURES WHICH INDICATE TYPE AND ANY SAFETY ASPECTS FOR | | | FIXTURES (ENCLOSED LENSES ETC REQUIRED) PLEASE BE SURE | | | FIXTURES SPECIFIED MEET THE LIFE SAFETY CODE FOR DAY | | | CARE OCCUPANCIES. | | | FBC 106.1.2 LS 101 CHAPTER 16. | | | | | | 4) NOTE: PLEASE SUBMIT COMPLETE ENERGY CALCULATIONS TO | | | MEET THE 2004 FBC 13-415.1.AB.1. | | | PLEASE ALSO PROVIDE INFORMATION ON LIGHTING POWER | | | DENSITIES PER 13-415.2 | | | PLEASE SEE THAT NONE WERE SUBMITTED. | | | PLEASE ALSO SEE 13-103.1.1.1 FOR REQUIRED | | | CERTIFICATIONS. | | | | | | 5) NOTE: PLEASE SEE LS-101 16.5.1.2 | | | SPECIAL PROTECTIVE COVERS FOR ALL ELECTRICAL | | | RECEPTACLES SHALL BE INSTALLED IN ALL AREAS OCCUPIED BY | | | CLIENTS. | | | PLEASE KNOW THAT THIS DOES NOT MEAN THE PLASTIC PLUG-IN | | | TYPE DEVICES, THIS MEANS THE RECEPTACLE DEVICE SHALL BE | | | LISTED FOR USE (110.3) AND BE OF THE TYPE WHICH | | | PROVIDES AUTOMATIC PROTECTION IF AN APPLIANCE IS NOT | | | PLUGGED IN OR IN USE. | | | | | | 5) NOTE: PLEASE SEE LS 101 2003, 6.1.4.1 FOR USE, | | | 9.6.4, 16.3.4.5. | | | PLEASE SEE ALL SMOKE DETECTION DEVICES AND SYSTEM SHALL | | | BE SHOWN. | | | THIS IS NOT A RESIDENCE OR SINGLE FAMILY DWELLING. | | | | | | 6) NOTE: PLEASE SEE THAT IN NO CASE MAY THERE BE | | | *WHITE-OUT* OR HAND WRITTEN CHANGES MADE TO PLANS. | | | PLEASE ALSO SEE THAT PLANS WHICH ARE SIGNED, DATED AND | | | SEALED SHALL ALSO NOT CONTAIN THESE ITEMS. | | | FS 481.221 | | | | | | 7) NOTE: PLEASE SEE MISSING NEW FOOTER STEEL AS PART OF | | | THE GROUNDING ELECTRODE SYSTEM PER 250.50. | | | | | | 8) NOTE: PLEASE PROVIDE SCHEDULE FOR THE METER/MAIN | | | COMBO PANEL WHICH DOES NOT INDICATE ANY OVER CURRENT | | | PROTECTION DEVICES FOR ANY ITEMS FROM THE METER/MAIN. | | | PLEASE SEE THAT ANY OTHER ELECTRICAL FED ITEMS FROM THE | | | METER/MAIN PANEL SHALL ALSO BE STATED WITH THE BREAKER | | | SIZE, CONDUCTOR SIZES ETC. | | | PLEASE SHOW THE LOCATION OF ALL ELECTRICAL SERVICE | | | EQUIPMENT LOCATIONS ON ELECTRICAL PLANS. | | | PLEASE BE SURE TO SEE THE LIFE SAFETY CODE WITH RESPECT | | | TO ELECTRICAL PANELS IN DAY CARE USE OCCUPANCIES. | | | (PANELS REQUIRED TO CONTAIN LOCKABLE COVERS IF INSIDE | | | BUILDING AND ACCESSIBLE FOR OCCUPANTS. | | | PLEASE SEE 110.26, 240.24, 408.7, LS 101CHAPTER 6. | | | | | | 9) NOTE: PLEASE SEE 16.28, 16.29 FOR REQUIRED EMERGENCY | | | EGRESS LIGHTING WHICH IS REQUIRED TO MEET 7.8 AND 7.9. | | | PLEASE SEE THE MINIMUM LIGHTING LEVELS FOR EGRESS DOES | | | NOT SEEM TO BE ACCOMPLISHED AT THIS TIME FOR THE | | | LOCATION AND NUMBER OF FIXTURES SHOWN ON PLANS. PLEASE | | | SEE A MINIMUM OF 1FT CANDLE IS REQUIRED AT ALL EGRESS | | | PATHS/LEVELS OF WALKING SURFACE. | | | THIS CAN BE ACCOMPLISHED BY PROVIDING PHOTO-METRICS FOR | | | VERIFICATION OF MINIMUM LIGHTING LEVELS. | | | FBC 106.1.2 | | | | | | 10) NOTE: PLEASE PROVIDE THE SERVICE ENTRANCE | | | CONDUCTORS ON RISER. | | | 240.4, 310.16 ETC. THIS IS CONSIDERED COMMERCIAL. | | | | | | 11) NOTE: PLEASE SEE THE LOAD CALCULATIONS SHALL MEET | | | 2005 NEC, THESE ARE SUBMITTED AND SHOWN FOR DWELLING | | | USE AND OCCUPANCY. | | | PLEASE SEE 220.3, 220.12, 220.14, 220.42, 220.44, | | | PLEASE BE SURE ALL CONTINUOUS LOADS AT SHOWN AT 125%. | | | 215.3, 230.42 | | | | | | 12) NOTE: PLEASE SEE NOTE ON PLANS MENTIONS *ALL PANELS | | | (1,2 AND 3) ARE EQUIPPED WITH FUSIBLE DISCONNECT* , | | | THIS IS NOT CLEAR AS OTHER INFORMATION MENTIONS MAIN | | | CIRCUIT BREAKER EQUIPMENT. | | | PLEASE CLARIFY. | | | FBC106.1.21 | | | | | | 13) NOTE: PLEASE SEE 600.5 A AND B. | | | | | | 14) NOTE: PLEASE KNOW THAT SINCE THERE ARE MANY ITEMS | | | NOT YET SUBMITTED FOR REVIEW, PLEASE KNOW THAT THERE | | | MAY BE NEW COMMENTS ON THE NEXT REVIEW WHICH ARE NOT | | | MADE AT THIS TIME. | | | | | | | | | ** ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
7 |
Status |
P |
Date |
2008-07-21 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-07-21 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-07-21 |
Time |
10:18 |
Sent To |
|
|
| Notes |
| 2008-07-21 10:19:22 | PLANS PREVIOUSLY APPROVED AND STAMPED ON THIS DATE. | | | SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR FIRE | | | ALARM SYSTEM. EMERGENCY EVACUATION PLAN TO BE POSTED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
6 |
Status |
P |
Date |
2008-05-29 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-05-29 |
Time |
12:43 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-05-29 |
Time |
12:34 |
Sent To |
|
|
| Notes |
| 2008-05-29 12:39:40 | *****PROVISO***** | | | | | | THE APPROPIATE PLAN SHEETS TO BE FIRE-STAMPED WHEN THE | | | OTHER REVIEWERS HAVE BEEN SATISFIED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2008-05-29 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-02-19 |
Time |
12:34 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-02-19 |
Time |
15:45 |
Sent To |
|
|
| Notes |
| 2008-02-19 16:07:52 | *****PROVISO***** | | | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE | | | BEEN ADDRESSED, HOWEVER, THE APPROPIATE PLAN SHEETS TO | | | BE FIRE-STAMPED WHEN THE OTHER REVIEWERS HAVE BEEN | | | SATISFIED. | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
F |
Date |
2007-10-30 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-10-30 |
Time |
14:56 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-10-30 |
Time |
14:56 |
Sent To |
|
|
| Notes |
| 2007-10-30 15:15:43 | REVIEW HAD ALREADY BEEN COMPLETED ON 10/10/07 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2007-10-10 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-10-10 |
Time |
12:37 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-10-10 |
Time |
11:23 |
Sent To |
|
|
| Notes |
| 2007-10-10 12:37:52 | *****DENIED***** | | | *THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN | | | REVIEW STILL NEED TO BE ADDRESSED: | | | | | | 07.SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE | | | APPROPIATE EXTERIOR ELEVATION WHICH FRONTS 13TH STREET. | | | AS PER WEST PALM BEACH CODE, THOSE NUMBERS SHALL BE NO | | | LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN WIDTH | | | CONTRASTING TO THE BACKGROUND.(NUMBERS SHALL NOT BE | | | ON THE DOOR)PLEASE SHOW ACTUAL ADDRESS NUMBER ON THE | | | APPROPIATE EXTERIOR ELEVATION | | | | | | 12.DAY-CARE OCCUPANCIES, OTHER THAN DAY-CARE | | | OCCUPANCIES HOUSED IN ONE ROOM, SHALL BE PROVIDED WITH | | | A FIRE ALARM SYSTEM (2003 NFPA 101 16.3.4.1).NO FIRE | | | ALARM SYSTEM NOTICED IN PLAN;PLEASE EXPLAIN RATIONALE | | | FOR A FIRE ALARM SYSTEM NOT REQUIRED | | | | | | | | | *NEW COMMENT | | | | | | AA.PLEASE EXPLAIN INCLUSION OF FLAMINGO PARK AS PART | | | OF THE ADDRESS AS SHOWN IN THE TITLE BLOCK OF THE | | | SUBMITTED PL;AN SHEETS.BETTER YET DELETE FLAMINGO | | | PARK FROM THE ADDRESS | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | SHEET INDICATING HOW / WHERE ON THE PLANS EACH COMMENT | | | WAS ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2007-05-22 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-05-22 |
Time |
17:06 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-05-22 |
Time |
16:49 |
Sent To |
|
|
| Notes |
| 2007-05-22 17:04:42 | *****DENIED***** | | | THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN | | | REVIEW STILL NEED TO BE ADDRESSED: | | | | | | | | | 01.THE LIFE SAFETY CODE, NFPA 101, 2003 EDITION SHALL | | | BE REFERENCED. | | | | | | 02.PROVIDE THE OCCUPANT LOAD, IN NUMBER OF PERSONS | | | FOR WHOM MEANS OF EGRESS AND OTHER PROVISIONS ARE | | | REQUIRED,EITHER SHALL BE DETERMINED ON THE BASIS OF | | | THE OCCUPANT LOAD FACTORS OF TABLE 7.3.1.2 THAT ARE | | | CHARACTERISTIC OF THE USE OF THE SPACE OR SHALL BE | | | DETERMINED AS THE MAXIMUMPROBABLE POPULATION OF THE | | | SPACE UNDER CONSIDERATION, WHICHEVER IS GREATER. | | | | | | 03.IF THE OCCUPANT LOAD IS DETERMINED BASED UPON THE | | | MAXIMUM PROBABLE POPULATION OF THE SPACE, AN APPROVED | | | AISLE, SEATING, AND EXITING DIAGRAM SHALL BE REQUIRED | | | TO SUBSTANTIATE SUCH A MODIFICATION. | | | | | | 04.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 05.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS | | | SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT | | | OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | | | 06.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF | | | NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE | | | OR HINDER WITH EMERGENCY RESPONSE ACCESS TO THE SAID | | | PROPERTY OR VICINITY THEREOF (INCLUDING STREETS OR | | | ROADWAYS). | | | | | | 07.SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE | | | APPROPIATE EXTERIOR ELEVATION WHICH FRONTS 13TH STREET. | | | AS PER WEST PALM BEACH CODE, THOSE NUMBERS SHALL BE NO | | | LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN WIDTH | | | CONTRASTING TO THE BACKGROUND.(NUMBERS SHALL NOT BE | | | ON THE DOOR) | | | | | | 08.PROVIDE A LIFE SAFETY PLAN SHEET WHICH INDICATES | | | THE TRAVEL DISTANCE TO THE EXITS.THIS SHEET MAY ALSO | | | INCLUDE THE LOCATION OF THE EXIT LIGHTS, EMERGENCY | | | LIGHTS, FIRE ALARM DEVICES, AND THE 2A:10BC RATED FIRE | | | EXTINGUISHERS APPLICABLE TO THE PROPOSED STRUCTURE. | | | | | | 09.EVERY CLOSET DOOR LATCH SHALL BE SUCH THAT CLIENTS | | | CAN OPEN THE DOOR FROM INSIDE THE CLOSET. | | | | | | 10.EVERY BATHROOM DOOR LOCK SHALL BE DESIGNED TO | | | ALLOW OPENING OF THE LOCKED DOOR FROM THE OUTSIDE BY AN | | | OPENING DEVICE THAT SHALL BE READILY ACCESSSIBLE TO THE | | | STAFF. | | | | | | 11.INTERIOR WALL AND CEILING FINISH MATERIALS SHALL | | | BE CLASS A OR CLASS B. | | | | | | 12.DAY-CARE OCCUPANCIES, OTHER THAN DAY-CARE | | | OCCUPANCIES HOUSED IN ONE ROOM, SHALL BE PROVIDED WITH | | | A FIRE ALARM SYSTEM. | | | | | | 13.OTHER THAN THOSE HOUSED IN ONE ROOM, A SMOKE | | | DETECTION SYSTEM SHALL BE INSTALLED IN DAY-CARE | | | OCCUPANCIES. | | | | | | 14.SPECIAL PROTECTIVE COVERINGS FOR ALL ELECTRICAL | | | RECEPTACLES SHALL BE INSTALLED IN ALL AREAS OCCUPIED BY | | | THE CLIENTS. | | | | | | 15.ADEQUATE ADULT STAFF SHALL BE ON DUTY, ALERT, | | | AWAKE, AND IN THE FACILITY AT ALL TIMES WHERE CLIENTS | | | ARE PRESENT. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | SHEET INDICATING HOW / WHERE ON THE PLANS EACH COMMENT | | | WAS ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-03-08 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-03-08 |
Time |
17:51 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-03-08 |
Time |
13:46 |
Sent To |
|
|
| Notes |
| 2007-03-08 14:08:12 | *****DENIED***** | | | | | | | | | PLEASE BE ADVISED THAT THIS IS A CHANGE IN OCCUPANCY | | | FROM AN EXISTING RESIDENTIAL STRUCTURE TO A NEW DAY | | | CARE OCCUPANCY | | | | | | | | | | | | 01.THE LIFE SAFETY CODE, NFPA 101, 2003 EDITION SHALL | | | BE REFERENCED. | | | | | | 02.PROVIDE THE OCCUPANT LOAD, IN NUMBER OF PERSONS | | | FOR WHOM MEANS OF EGRESS AND OTHER PROVISIONS ARE | | | REQUIRED,EITHER SHALL BE DETERMINED ON THE BASIS OF | | | THE OCCUPANT LOAD FACTORS OF TABLE 7.3.1.2 THAT ARE | | | CHARACTERISTIC OF THE USE OF THE SPACE OR SHALL BE | | | DETERMINED AS THE MAXIMUMPROBABLE POPULATION OF THE | | | SPACE UNDER CONSIDERATION, WHICHEVER IS GREATER. | | | | | | 03.IF THE OCCUPANT LOAD IS DETERMINED BASED UPON THE | | | MAXIMUM PROBABLE POPULATION OF THE SPACE, AN APPROVED | | | AISLE, SEATING, AND EXITING DIAGRAM SHALL BE REQUIRED | | | TO SUBSTANTIATE SUCH A MODIFICATION. | | | | | | 04.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 05.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS | | | SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT | | | OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | | | 06.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF | | | NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE | | | OR HINDER WITH EMERGENCY RESPONSE ACCESS TO THE SAID | | | PROPERTY OR VICINITY THEREOF (INCLUDING STREETS OR | | | ROADWAYS). | | | | | | 07.SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE | | | APPROPIATE EXTERIOR ELEVATION WHICH FRONTS 13TH STREET. | | | AS PER WEST PALM BEACH CODE, THOSE NUMBERS SHALL BE NO | | | LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN WIDTH | | | CONTRASTING TO THE BACKGROUND.(NUMBERS SHALL NOT BE | | | ON THE DOOR) | | | | | | 08.PROVIDE A LIFE SAFETY PLAN SHEET WHICH INDICATES | | | THE TRAVEL DISTANCE TO THE EXITS.THIS SHEET MAY ALSO | | | INCLUDE THE LOCATION OF THE EXIT LIGHTS, EMERGENCY | | | LIGHTS, FIRE ALARM DEVICES, AND THE 2A:10BC RATED FIRE | | | EXTINGUISHERS APPLICABLE TO THE PROPOSED STRUCTURE. | | | | | | 09.EVERY CLOSET DOOR LATCH SHALL BE SUCH THAT CLIENTS | | | CAN OPEN THE DOOR FROM INSIDE THE CLOSET. | | | | | | 10.EVERY BATHROOM DOOR LOCK SHALL BE DESIGNED TO | | | ALLOW OPENING OF THE LOCKED DOOR FROM THE OUTSIDE BY AN | | | OPENING DEVICE THAT SHALL BE READILY ACCESSSIBLE TO THE | | | STAFF. | | | | | | 11.INTERIOR WALL AND CEILING FINISH MATERIALS SHALL | | | BE CLASS A OR CLASS B. | | | | | | 12.DAY-CARE OCCUPANCIES, OTHER THAN DAY-CARE | | | OCCUPANCIES HOUSED IN ONE ROOM, SHALL BE PROVIDED WITH | | | A FIRE ALARM SYSTEM. | | | | | | 13.OTHER THAN THOSE HOUSED IN ONE ROOM, A SMOKE | | | DETECTION SYSTEM SHALL BE INSTALLED IN DAY-CARE | | | OCCUPANCIES. | | | | | | 14.SPECIAL PROTECTIVE COVERINGS FOR ALL ELECTRICAL | | | RECEPTACLES SHALL BE INSTALLED IN ALL AREAS OCCUPIED BY | | | THE CLIENTS. | | | | | | 15.ADEQUATE ADULT STAFF SHALL BE ON DUTY, ALERT, | | | AWAKE, AND IN THE FACILITY AT ALL TIMES WHERE CLIENTS | | | ARE PRESENT. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | SHEET INDICATING HOW / WHERE ON THE PLANS EACH COMMENT | | | WAS ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2008-12-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-12-09 |
Time |
08:57 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-12-09 |
Time |
08:57 |
Sent To |
M |
|
| Notes |
| 2008-12-09 08:58:00 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2008-07-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-07-09 |
Time |
10:01 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-07-09 |
Time |
10:01 |
Sent To |
|
|
| Notes |
| 2008-07-09 10:04:53 | TO "COMM" BD#7 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-05-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-05-07 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-05-07 |
Time |
14:31 |
Sent To |
|
|
| Notes |
| 2008-05-07 14:34:16 | TO "COMM" BD#7 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-01-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-01-28 |
Time |
08:44 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-01-28 |
Time |
08:44 |
Sent To |
|
|
| Notes |
| 2008-01-28 08:46:56 | TO "COMM" BD#25 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-04-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-04-24 |
Time |
14:32 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-04-24 |
Time |
14:32 |
Sent To |
|
|
| Notes |
| 2007-05-04 09:02:19 | TO "COMM" BD#34 | | 2007-04-24 14:32:48 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-03-12 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-03-12 |
Time |
11:38 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2007-01-29 |
Time |
17:05 |
Sent To |
|
|
| Notes |
| 2007-02-07 08:51:55 | TO "COMM" BD#34 | | 2007-01-29 17:15:01 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
P |
Date |
2008-05-15 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2008-05-15 |
Time |
14:44 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2008-05-15 |
Time |
14:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
10 |
Status |
P |
Date |
2009-03-24 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-03-24 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-03-24 |
Time |
16:35 |
Sent To |
PC |
|
| Notes |
| 2009-03-24 16:35:48 | AC-1 REVISION |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
9 |
Status |
P |
Date |
2008-12-22 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-12-22 |
Time |
19:24 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-12-22 |
Time |
19:17 |
Sent To |
PC |
|
| Notes |
| 2008-12-22 19:26:30 | REVISED A/C-1. PLANS STILL SHOW RETURN TRANSFERS TOO | | | SMALL TO MEET THE EXCEPTIONS UNDER FBCM 601.4. A FIELD | | | TEST WILL BE REQUIRED TO VERIFY BALANCED RETURN IN | | | ACCORDANCE WITH THIS SECTION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
8 |
Status |
F |
Date |
2008-12-14 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-12-14 |
Time |
14:25 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-12-14 |
Time |
14:22 |
Sent To |
PC |
|
| Notes |
| 2008-12-14 14:25:13 | REVISED AC-1: DENIED | | | | | | ORIGINAL PLANS SUBMITTED FOR PERMIT ARE SIGNED AND | | | SEALED BY AN ARCHITECT AS DESIGNER OF RECORD. THESE | | | PLANS WERE DRAWN BY AN A/C CONTRACTOR, NOT THE DESIGNER | | | OF RECORD. ANY CHANGES TO THE PERMIT SET OF PLANS SHALL | | | BE BY THE DESIGNER OF RECORD IN ACCORDANCE WITH FS 481. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
7 |
Status |
P |
Date |
2008-07-18 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-07-18 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-07-18 |
Time |
13:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
F |
Date |
2008-05-23 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-05-23 |
Time |
09:29 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-05-23 |
Time |
09:27 |
Sent To |
|
|
| Notes |
| 2008-05-23 09:29:44 | PLANS REMAIN CODE COMPLIANT FOR MECHANICAL. REVIEW WILL | | | REMIAN IN FAILED STATUS PENDING SUCCESSFUL REVIEW OF | | | ENERGY CALCULATIONS BY ALL AFFECTED TRADES. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
N |
Date |
2008-07-18 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-07-18 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-05-23 |
Time |
09:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2008-02-16 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-02-16 |
Time |
09:03 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-02-16 |
Time |
08:23 |
Sent To |
|
|
| Notes |
| 2008-02-16 08:43:14 | REVIEW #: 4TH | | | ACTION: FAILED/PENDING | | | | | | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC | | | CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN | | | RESPONSES FOR THE PURPOSE OF CONTINUITY. | | | | | | 1. NEW FOR 400A HAS BEEN SUBMITTED. HOWEVER, THE INPUT | | | DATA REPORT WAS NOT INCLUDED WITH THE COMPLIANCE FORM | | | AS REQUIRED. PAGE 2 OF THE COMPLIANCE REPORT STATES | | | "IMPORTANT NOTICE: AN INPUT REPORT OF THIS DESIGN | | | BUILDING MUST BE SUBMITTED ALONG WITH THIS COMPLIANCE | | | REPORT." | | | ADDITIONALLY, THE METHOD A COMPLIANCE FORM IS FOR THE | | | "WHOLE BUILDING" INCLUDING ALL MAJOR ENERGY UTILIZING | | | EQUIPMENT AND ALL BUILDING ENVELOPE COMPONENTS. NO | | | BUILDING ENVELOPE COMPONENTS WERE INCLUDED IN THIS | | | REPORT. IF METHOD A IS TO BE USED, THE WHOLE BUILDING | | | MUST BE DEMONSTRATED TO BE IN COMPLIANCE WITH THE | | | METHOD A CALCULATING PROCEDURES AS DEFINED IN THE | | | FLA/COM PROGRAM. METHOD A MAY ONLY BE USED IF THE | | | CONDITIONS UNDER FBC 13-101.4.2 HAVE BEEN MET. IN | | | ADDITION TO THIS SECTION, PLEASE SEE FBC 13-101.3 TO | | | SEE WHICH COMPLIANCE METHODS ARE AVAILABLE FOR THIS | | | PROJECT. | | | | | | 2. RETURNS HAVE NOT BEEN CHANGED TO SHOW COMPLIANCE | | | WITH THE EXCEPTIONS LISTED UNDER FBC, M 601.4. A FIELD | | | TEST WILL BE REQUIRED AT FINAL INSPECTION DEMONSTRATING | | | PRESSURE DIFFERENTIALS OF 0.01" WC OR LESS IN ROOMS | | | WHERE RETURN JUMPERS ARE UTILIZED. | | | | | | NOTE: PLANS HAVE BEEN REVIEWED FOR CODE COMPLIANCE AND | | | STAMPED. HOWEVER, PLAN REVIEW STOP WILL REMAIN IN | | | "FAILED" STATUS UNTIL A CORRECTED ENERGY CODE | | | COMPLIANCE FORM HAS BEEN SUBMITTED AND REVIEWED. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2007-11-11 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-11-11 |
Time |
12:50 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-11-11 |
Time |
11:47 |
Sent To |
|
|
| Notes |
| 2007-11-11 12:49:33 | REVIEW #: 3 | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC | | | CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN | | | RESPONSES FOR THE PURPOSE OF CONTINUITY. | | | *NOTE* A WRITTEN RESPONSE TO REVIEW COMMENTS FROM THE | | | DESIGN TEAM WILL AID IN THE REVIEW PROCESS. | | | | | | 1. ENERGY CALCULATIONS FORM 600 HAS BEEN SUBMITTED FOR | | | THE 3RD TIME. THIS IS NOT A RESIDENTIAL OCCUPANCY, | | | THERE IS A CHANGE OF OCCUPANCY AND SHALL THEREFORE THIS | | | PROJECT SHALL DEMONSTRATE COMPLIANCE WITH FBC | | | 13-101.3. | | | | | | 2. RETURN AIR TRANSFER DUCTS ARE STILL NOT DESIGNED TO | | | MEET TH BALANCED RETURN EXCEPTIONS UNDER FBC,M 601.4. A | | | FIELD TEST WILL BE REQUIRED AT FINAL INSPECTION TO | | | DETERMINE IF PRESSURE DIFFERENTIALS ACROSS CLOSED DOORS | | | ARE AT 0.01IN. WC OR LESS IN ACCORDANCE WITH THIS | | | SECTION. THIS STEP WILL NOT BE NECESSARY IF TRANSFERS | | | ARE DESIGNED TO MEET THE FOLLOWING EXCEPTION: "TRANSFER | | | DUCTS MAY ACHIEVE THIS BY INCREASING THE RETURN | | | TRANSFER ONE AND ONE-HALF TIMES THE CROSS-SECTIONAL | | | AREA (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE | | | ROOM OR SPACE IT IS SERVING AND THE DOOR HAVING AT | | | LEAST AN UNRESTRICTED 1-INCH UNDERCUT TO ACHIEVE PROPER | | | RETURN AIR BALANCE." | | | | | | 3. NATURAL VENTILATION AS SHOWN ON PLANS IS OK. | | | | | | 4. OK | | | | | | 5. OK | | | | | | 6. OK | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2007-05-14 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-05-14 |
Time |
11:40 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-05-14 |
Time |
08:10 |
Sent To |
|
|
| Notes |
| 2007-05-14 11:40:39 | -------------DENIED--------------- | | | | | | FBC 2004 CODE FAMILY W/2006 REVISIONS | | | | | | 1. FORM 600 OF THE ENERGY CALCULATIONS IS NOT | | | ACCEPTABBLE FOR THIS PROJECT AS THIS IS NO LONGER A | | | RESIDENTIAL OCCUPANCY. PLEASE ALSO INCLUDE COOLING LOAD | | | CALCULATIONS PER FBC CH 13-B SEC. 3.1. IS THIS SYSTEM | | | ADEQUATELY SIZED FOR THE ADDITIONAL SQ' FOOTAGE, | | | INCREASED OCCUPANT LOAD AND 600 CFM OUTSIDE AIR? | | | NOTE: THE MINIMUM EFFICIENCY FOR SPLIT SYSTEMS <65,000 | | | BTUH AS REQUIRED BY TABLE 13-407.1.ABC.3.2A IS 13.0 | | | SEER. | | | | | | 2. THERE IS NO RETURN AIR SHOWN ON PLAN, OTHER THAN THE | | | 12" ROUND TRANSFER FROM INFANT ROOM. WHAT IS THE SIZE | | | AND LOCATION OF MAIN RETURN? HOW IS BALANCED RETURN TO | | | BE ACHIEVED FROM OFFICE AND SERVICE AREA (IF IT IS NOT | | | TO BE A KITCHEN)? | | | NOTE: THE TRANSFER FROM INFANT ROOM DOES NOT MEET THE | | | EXCEPTIONS TO FBC,M 601.4. PLEASE DESIGN ALL TRANSFERS | | | TO THESE EXCEPTIONS OR A FIELD TEST WILL BE REQUIRED AT | | | FINAL INSPECTION TO DETERMINE PRESSURE DIFFERENTIALS AS | | | REQUIRED BY THIS SECTION. | | | | | | 3. VENTILATION SHALL BE PROVIDED TO ALL OCCUPUED SPACES | | | (IE: KITCHEN/SERVICE AREA AND OFFICE) PER FBC,M 403.1. | | | THE AMOUNT OF SUPPLY AIR IS TO BE APPROXIMATELY EQUAL | | | TO THE AMOUNT OF RETURN AND EXHAUST AIR PER FBC,M | | | 403.1. RETURN SHOULD BE 600 CFM LESS THAN SUPPLY WITH | | | 600 CFM OF EXHAUST. WHERE IS EXHAUST? | | | | | | 4. EXHAUST AIR IS REQUIRED FOR BATHROOMS PER FBC,M | | | TABLE 403.3 UNDER PUBLIC SPACES - TOILET ROOMS. | | | | | | 5. THE VENTILATION SYSTE SHALL RUN CONTINUOUSLY DURING | | | THE PERIOD THE BUILDING IS OCCUPIED PER FBC,M 403.3. | | | PLEASE SHOW HOW THE SYSTEM IS TO BE CONTROLLED TO | | | ACCOMPLISH THIS? | | | | | | 6. WHAT TYPE OF COOKING EQUIPMENT IS THE BE IN THE | | | SERVICE AREA? KITCHEN EXHAUST IS TO BE IN COMPLIANCE | | | WITH FBC,M CH. 506 PER FBC,EB 809.1. | | | | | | REVIEWED BY: | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-02-24 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2007-02-24 |
Time |
12:17 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2007-02-24 |
Time |
12:17 |
Sent To |
|
|
| Notes |
| 2007-02-24 12:23:01 | PLAN DENIED | | | PLEASE PROVIDE FRESH AIR CALCULATIONS FROM TABLE 403.4 | | | 2000 FBC(M) . | | | PLEASE REMOVE RETURN AIR DUCT FROM BATHROOM PER SECTION | | | 601.4 #3 | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2008-06-03 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2008-06-03 |
Time |
10:06 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2008-06-03 |
Time |
09:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2008-02-11 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2008-02-11 |
Time |
08:21 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2008-02-11 |
Time |
07:43 |
Sent To |
|
|
| Notes |
| 2008-02-11 08:57:40 | DENIED; | | | 1. PAGE P-1 BUILDING CONTRACTOR NOTE; PLUMBING CODE TO | | | BE USED IS THE FBC-PLUMBING SECTION 601, NOT THE | | | RESIDENTIAL CODE 2901 THIS IS A BUSINESS. | | | 2. WATER RISER DIAGRAM SHALL BE OF SUFFICIENT CLARITY, | | | FBC BUILDING CHAPTER 1 (ADMINISTRATION) SECTION | | | 106.1.1. DELETE SANITARY DIAGRAM ( UNDER WATER DIAGRAM) | | | , AND SHOW WATER SERVICE FROM SHUTOFF VALVE TO THE LAST | | | FIXTURE IN BUILDING. | | | 3. ADD NOTE TO WATER RISER DIAGRAM; " BACKFLOW | | | PREVENTER REQUIRED ON WATER SERVICE AT CITY WATER | | | METER". | | | 4. SANITARY RISER DIAGRAM; 3 COMPARTMENT SINK SHALL | | | DISCHARGE DOWN STREAM OF THE BATHROOM GROUP SEE FBC | | | PLUMBING SECTION 909.1. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2007-11-20 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-11-20 |
Time |
09:10 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-11-20 |
Time |
08:53 |
Sent To |
|
|
| Notes |
| 2007-11-20 09:43:22 | DENIED; | | | 1. SEE ELECTRICAL PLAN REVIEWER'S COMMENT # 13. | | | 2. INFORMATION ON CONSTRUCTION DOCUMENTS SHALL BE OF | | | SUFFICIENT CLARITY. FBC BUILDING CHAPTER 1 | | | (ADMINISTRATION) SECTION 106.1.1. | | | A) SEPARATE WATER AND SANITARY RISER | | | DIAGRAMS. | | | 1. SANITARY RISER DIAGRAM; | | | A)CLEARLY MARK EACH FIXTURE, | | | I.E. LAV, W/C, SINK. | | | B) DRAIN SIZES ARE NOT CORRECT. | | | LAVATORY'S ARE 1 1/4 SINKS ARE 1 1/2. | | | 2. WATER RISER DIAGRAM; | | | A) SHOW CALCULATIONS FOR WATER | | | DISTRIBUTION PIPING . SEE FBC PLUMBING TABLE 603.1. | | | B) SHOW SIZE OF WATER HEATER. | | | 3. SHOW DETAIL DRAWINGS OF HANDICAP FIXTURES WITH ALL | | | REQUIRED MESUREMENTS. ( LAV., W/C, D/F ) | | | 4. SHOW DETAIL DRAWINGS FOR CHILDRENS BATHROOMS AND | | | SPECK OUT FIXTURES. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2007-05-22 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2007-05-22 |
Time |
14:05 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2007-05-22 |
Time |
08:51 |
Sent To |
|
|
| Notes |
| 2007-05-22 14:04:49 | | | | | | | PAUL SCHMITZ | | | | | | [email protected] | | | FBC 2004 PLUMBING CODE | | | PLAN REVIEW | | | FBC 2004 FUEL GAS CODE PLAN REVIEW FBC | | | 2004 CH 11, FL ACCESSIBILITY CODE AMENDMENTS TO THE | | | FLORIDA BUILDING CODE | | | CHAPT.1, ADMINISTRATION, 2004 | | | EDITION | | | | | | DENIED 2ND | | | TIME 5-22-07 | | | "SEE COMMENTS IN CAPITOL | | | LETTERS" | | | | | | NOT ADDRESSED | | | 1)SHT 3. BOYS & GIRLS REST ROOM | | | COMPLY WITH 36 CFR PART 1191 [ DOCKET NO.94-2]"GUIDE | | | LINES" | | | ADA ACCESSIBILITY GUIDELINES FOR BUILDINGS AND | | | FACILITIES; BUILDING ELEMENTS DESIGNED FOR CHILDREN'S | | | USE. | | | | | | SHT 3. LABEL DRINKING FOUNTAIN AS D/F, WHY, 3 W/F | | | ? | | | 2) SHT 3.11-4.1.3 (10)DRINKING FOUNTAINS. | | | (A) WHERE ONLY ONE DRINKING FOUNTAIN IS PROVIDED ON A | | | FLOOR, THERE SHALL BE A DRINKING FOUNTAIN WHICH IS | | | ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS IN | | | ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE TO | | | THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING. (THIS | | | CAN BE ACCOMMODATED BY THE USE OF A ?HI-LO? FOUNTAIN; | | | BY PROVIDING ONE FOUNTAIN ACCESSIBLE TO THOSE WHO USE | | | WHEELCHAIRS AND ONE FOUNTAIN AT A STANDARD HEIGHT | | | CONVENIENT FOR THOSE WHO HAVE DIFFICULTY BENDING; BY | | | PROVIDING A FOUNTAIN ACCESSIBLE UNDER SECTION 11-4.15 | | | AND A WATER COOLER; OR BY SUCH OTHER MEANS AS WOULD | | | ACHIEVE THE REQUIRED ACCESSIBILITY FOR EACH GROUP ON | | | EACH FLOOR.) | | | | | | DIMENSIONS ON BOYS AND GIRLS REST RM, | | | WIDTH NOT TO SCALE, MIN 5'-2" | | | 3) SEC. (11) 11-4.1.3 ACCESSIBLE BUILDINGS: NEW | | | CONSTRUCTION, TOILET FACILITIES. IF TOILET ROOMS ARE | | | PROVIDED, THEN EACH PUBLIC AND COMMON USE TOILET ROOM | | | SHALL COMPLY WITH SECTION 11-4.22. OTHER TOILET ROOMS | | | PROVIDED FOR THE USE OF OCCUPANTS OF SPECIFIC SPACES | | | (I.E., A PRIVATE TOILET ROOM FOR THE OCCUPANT OF A | | | PRIVATE OFFICE) SHALL BE ADAPTABLE. IF BATHING ROOMS | | | ARE PROVIDED, THEN EACH PUBLIC AND COMMON USE BATHROOM | | | SHALL COMPLY WITH SECTION 11-4.23. ACCESSIBLE TOILET | | | ROOMS AND BATHING FACILITIES SHALL BE ON AN ACCESSIBLE | | | ROUTE. | | | | | | WATER PIPING ISOMETRIC NOT INCLUDED | | | 4) SHT 4. COMPLY WITH SEC 106 SANITARY AND WATER PIPE | | | ISOMETRIC, INCLUDE PIPE SIZES ON THE ISOMETRICS. | | | SHT 4 PLUMBING NOTES ARE NOT SUFFICENT TO INDICATE | | | NATURE OF WORK. | | | 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN | | | UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE | | | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE | | | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT | | | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | | DETERMINED BY THE BUILDING OFFICIAL (SEE ALSO SECTION | | | 106.3.5). | | | | | | | | | NOT ADDRESSED | | | 5)SECTION 608, BACK FLOW PREVENTER | | | PROTECTION OF POTABLE WATER SUPPLY | | | 608.1 GENERAL. | | | A POTABLE WATER SUPPLY SYSTEM SHALL BE DESIGNED, | | | INSTALLED AND MAINTAINED IN SUCH A MANNER SO AS TO | | | PREVENT CONTAMINATION FROM NONPOTABLE LIQUIDS, SOLIDS | | | OR GASES BEING INTRODUCED INTO THE POTABLE WATER SUPPLY | | | THROUGH CROSS-CONNECTIONS OR ANY OTHER PIPING | | | CONNECTIONS TO THE SYSTEM. BACKFLOW PREVENTER | | | APPLICATIONS SHALL CONFORM TO TABLE 608.1, EXCEPT AS | | | SPECIFICALLY STATED IN SECTIONS 608.2 THROUGH | | | 608.16.9. | | | | | | NOT ADDRESSED | | | 6) SEC 607.3 THERMAL EXPANSION CONTROL. | | | A MEANS OF CONTROLLING INCREASED PRESSURE CAUSED BY | | | THERMAL EXPANSION SHALL BE PROVIDED WHERE REQUIRED IN | | | ACCORDANCE WITH SECTIONS 607.3.1 AND 607.3.2. 607.3.2 | | | BACKFLOW PREVENTION DEVICE OR CHECK VALVE. WHERE A | | | BACKFLOW PREVENTION DEVICE, CHECK VALVE OR OTHER DEVICE | | | IS INSTALLED ON A WATER SUPPLY SYSTEM UTILIZING STORAGE | | | WATER HEATING EQUIPMENT SUCH THAT THERMAL EXPANSION | | | CAUSES AN INCREASE IN PRESSURE, A DEVICE FOR | | | CONTROLLING PRESSURE SHALL BE INSTALLED. | | | | | | NOT ADDRESSED | | | 7)SEE OTHER PLAN REVIEW COMMENTS, THAT MAY EFFECT | | | PLUMBING PLAN REVIEW. | | | | | | 8) NEW COMMENT:HEALTH DEPARTMENT NOTES, CHILD CHANGE | | | STATIONS TO BE INCLUDED ON REVISEED PLANS. | | | | | | 9) NEW COMMENT: SERVICE AREA IS NOT EXISTING, INCLUDE | | | ON DWV, WATER ISOMETRIC. | | | | | | END OF COMMENTS, QUESTIONS 561-805-6692 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-02-24 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2007-02-24 |
Time |
08:20 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2007-02-24 |
Time |
08:18 |
Sent To |
|
|
| Notes |
| 2007-02-24 09:41:16 | PAUL SCHMITZ | | | [email protected] FBC 2004 PLUMBING | | | CODE PLAN REVIEW | | | FBC2004 FUEL GAS CODEPLAN REVIEW | | | FBC 2004 CH 11, FL ACESSIBILITY CODE | | | AMENDMENTS TO THE FLORIDA BUILDING CODE | | | | | | CHAPT.1, ADMINISTRATION, 2004 EDITION | | | | | | DENIED | | | | | | 1) SHT 3. BOYS & GIRLS REST ROOM | | | COMPLY WITH 36 CFR PART 1191 [ DOCKET NO.94-2]"GUIDE | | | LINES" | | | ADA ACCESSIBILITY GUIDELINES FOR BUILDINGS AND | | | FACILITIES; BUILDING ELEMENTS DESIGNED FOR CHILDREN'S | | | USE. | | | | | | 2) SHT 3 .11-4.1.3 (10) DRINKING FOUNTAINS. | | | (A) WHERE ONLY ONE DRINKING FOUNTAIN IS PROVIDED ON A | | | FLOOR, THERE SHALL BE A DRINKING FOUNTAIN WHICH IS | | | ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS IN | | | ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE TO | | | THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING. (THIS | | | CAN BE ACCOMMODATED BY THE USE OF A ?HI-LO? FOUNTAIN; | | | BY PROVIDING ONE FOUNTAIN ACCESSIBLE TO THOSE WHO USE | | | WHEELCHAIRS AND ONE FOUNTAIN AT A STANDARD HEIGHT | | | CONVENIENT FOR THOSE WHO HAVE DIFFICULTY BENDING; BY | | | PROVIDING A FOUNTAIN ACCESSIBLE UNDER SECTION 11-4.15 | | | AND A WATER COOLER; OR BY SUCH OTHER MEANS AS WOULD | | | ACHIEVE THE REQUIRED ACCESSIBILITY FOR EACH GROUP ON | | | EACH FLOOR.) | | | | | | 3) SEC. (11) 11-4.1.3 ACCESSIBLE BUILDINGS: NEW | | | CONSTRUCTION. TOILET FACILITIES. IF TOILET ROOMS ARE | | | PROVIDED, THEN EACH PUBLIC AND COMMON USE TOILET ROOM | | | SHALL COMPLY WITH SECTION 11-4.22. OTHER TOILET ROOMS | | | PROVIDED FOR THE USE OF OCCUPANTS OF SPECIFIC SPACES | | | (I.E., A PRIVATE TOILET ROOM FOR THE OCCUPANT OF A | | | PRIVATE OFFICE) SHALL BE ADAPTABLE. IF BATHING ROOMS | | | ARE PROVIDED, THEN EACH PUBLIC AND COMMON USE BATHROOM | | | SHALL COMPLY WITH SECTION 11-4.23. ACCESSIBLE TOILET | | | ROOMS AND BATHING FACILITIES SHALL BE ON AN ACCESSIBLE | | | ROUTE. | | | | | | 4) SHT 4. COMPLY WITH SEC 106 SANITARY AND WATER PIPE | | | ISOMETRIC, INCLUDE PIPE SIZES ON THE ISOMETRICS. | | | DRINKING FOUNTAIN NOT ON PLUMBING ISOMETRIC | | | | | | 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN | | | UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE | | | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE | | | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT | | | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | | DETERMINED BY THE BUILDING OFFICIAL (SEE ALSO SECTION | | | 106.3.5). | | | | | | 5)SECTION 608, BACK FLOW PREVENTER | | | PROTECTION OF POTABLE WATER SUPPLY | | | 608.1 GENERAL. | | | A POTABLE WATER SUPPLY SYSTEM SHALL BE DESIGNED, | | | INSTALLED AND MAINTAINED IN SUCH A MANNER SO AS TO | | | PREVENT CONTAMINATION FROM NONPOTABLE LIQUIDS, SOLIDS | | | OR GASES BEING INTRODUCED INTO THE POTABLE WATER SUPPLY | | | THROUGH CROSS-CONNECTIONS OR ANY OTHER PIPING | | | CONNECTIONS TO THE SYSTEM. BACKFLOW PREVENTER | | | APPLICATIONS SHALL CONFORM TO TABLE 608.1, EXCEPT AS | | | SPECIFICALLY STATED IN SECTIONS 608.2 THROUGH | | | 608.16.9. | | | | | | | | | 6) SEC 607.3 THERMAL EXPANSION CONTROL. | | | A MEANS OF CONTROLLING INCREASED PRESSURE CAUSED BY | | | THERMAL EXPANSION SHALL BE PROVIDED WHERE REQUIRED IN | | | ACCORDANCE WITH SECTIONS 607.3.1 AND 607.3.2. 607.3.2 | | | BACKFLOW PREVENTION DEVICE OR CHECK VALVE. WHERE A | | | BACKFLOW PREVENTION DEVICE, CHECK VALVE OR OTHER DEVICE | | | IS INSTALLED ON A WATER SUPPLY SYSTEM UTILIZING STORAGE | | | WATER HEATING EQUIPMENT SUCH THAT THERMAL EXPANSION | | | CAUSES AN INCREASE IN PRESSURE, A DEVICE FOR | | | CONTROLLING PRESSURE SHALL BE INSTALLED. | | | | | | 7)SEE OTHER PLAN REVIEW COMMENTS, THAT MAY EFFECT | | | PLUMBING PLAN REVIEW. | | | | | | END OF COMMENTS, QUESTIONS 561-805-6692 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
7 |
Status |
P |
Date |
2008-07-18 |
|
|
Cont ID |
|
| Sent By |
adavila |
Date |
2008-07-18 |
Time |
14:34 |
Rev Time |
0.00 |
| Received By |
adavila |
Date |
2008-07-18 |
Time |
14:34 |
Sent To |
|
|
| Notes |
| 2008-07-18 14:35:55 | PROVISO APPLICANT SHALL OBTAIN A CERTIFICATE OF | | | OCCUPANCY ("CO") FOR THE PARKING LOT ON THE ADJACENT | | | PROPERTY (1117 13TH STREET) PRIOR TO OBTAINING A CO FOR | | | THIS BUILDING PERMIT (PERMIT NO. 07011175). | | | | | | PROVISO HANDICAP WALKWAY ACCESS TO PARKING SHALL MATCH | | | THE FIVE (5) FOOT ACCESS AISLE ON THE ADJACENT | | | PROPERTY. | | | | | | PROVISO ROOF OVERHANG PROJECTION SHALL NOT EXTEND | | | FARTHER THAN THREE (3) FEET INTO ANY SETBACK. | | | | | | PROVISO A REVISED LANDSCAPE PLAN SHALL BE REVIEWED AND | | | APPROVED BY THE PLANNING AND ZONING DEPARTMENT PRIOR TO | | | OBTAINING A CO. | | | | | | PER ANGELLA VANN, DEPUTY PLANNING DIRECTOR. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
6 |
Status |
F |
Date |
2008-07-16 |
|
|
Cont ID |
|
| Sent By |
adavila |
Date |
2008-07-16 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
adavila |
Date |
2008-07-16 |
Time |
10:39 |
Sent To |
|
|
| Notes |
| 2008-07-16 15:03:12 | PLANNING AND ZONING DEPARTMENT | | | | | | ***FAILED*** | | | | | | 1. PURSUANT TO SECTION 94-441(C)(2), RENOVATIONS, | | | REPAIRS, ALTERATION OR REDEVELOPMENT THAT EXCEED 50% OF | | | THE VALUE OF THE STRUCTURE SHALL REQUIRE THE SITE TO BE | | | BROUGHT INTO COMPLIANCE WITH ARTICLE XIV, LANDSCAPE | | | REGULATIONS, OF THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS ("ZLDRS").ACCORDING TO THE LATEST | | | RESUBMITTED PACKAGE, THE VALUE FOR THE PROPOSED WORK | | | HAS INCREASED TO $56,000.PER THE PALM BEACH COUNTY | | | PROPERTY APPRAISER'S OFFICE ("PAPA"), THE VALUE OF THE | | | STRUCTURE IS $87,457.AS THE TOTAL WORK VALUE EXCEEDS | | | 50% OF THE VALUE OF THE STRUCTURE ($43,728.5), YOU HAVE | | | TWO OPTIONS: | | | (1) PROVIDE 6 ADDITIONAL TREES ALONG THE NORTH, EAST | | | AND WEST PROPERTY LINES.A LANDSCAPE PLAN PREPARED, | | | SIGNED AND SEALED BY FLORIDA REGISTERED LANDSCAPE | | | ARCHITECT SHALL BE SUBMITTED SHOWING COMPLIANCE WITH | | | ARTICLE XIV OF THE ZLDRS.PLEASE CONTACT ROBERT | | | KUSSNER, LANDSCAPE PLANNER, FOR LANDSCAPE SPECIES AND | | | LOCATION OPTIONS; | | | (2) PROVIDE AN APPRAISAL BY A LICENSED PROPERTY | | | APPRAISAL THAT SHOWS THE VALUE OF THE STRUCTURE OVER | | | $112,000. | | | | | | 2. PROVIDE THE STATUS OF THE PARKING LOT ON THE | | | ADJOINING PROPERTY.PLEASE NOTE THAT A CERTIFICATE OF | | | OCCUPANCY ("CO") FOR THIS PERMIT SHALL NOT BE GRANTED | | | UNTIL A CO HAS BEEN ISSUED FOR THE PARKING LOT ON THE | | | ADJACENT PROPERTY (1117 13TH STREET). | | | | | | 3. HANDICAP WALKWAY ACCESS TO THE PARKING LOT SHALL | | | MATCH THE 5 FOOT ACCESS AISLE ON THE ADJACENT | | | PROPERTY. | | | | | | COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC | | | SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
P |
Date |
2008-05-16 |
|
|
Cont ID |
|
| Sent By |
adavila |
Date |
2008-05-16 |
Time |
10:37 |
Rev Time |
0.00 |
| Received By |
adavila |
Date |
2008-05-15 |
Time |
18:03 |
Sent To |
|
|
| Notes |
| 2008-05-16 10:37:21 | PROVISO APPLICANT SHALL OBTAIN A CERTIFICATE OF | | | OCCUPANCY ("CO") FOR THE PARKING LOT ON THE ADJACENT | | | PROPERTY (1117 13TH STREET) PRIOR TO OBTAINING A CO FOR | | | THIS BUILDING PERMIT (PERMIT NO. 07011175). | | | | | | PROVISO HANDICAP WALKWAY ACCESS TO PARKING SHALL MATCH | | | THE FIVE (5) FOOT ACCESS AISLE ON THE ADJACENT | | | PROPERTY. | | | | | | PROVISE ROOF OVERHANG PROJECTION SHALL NOT EXTEND | | | FARTHER THAN THREE (3) FEET INTO ANY SETBACK. | | | | | | PER ERIC SCHNEIDER, PRINCIPAL PLANNER. | | 2008-05-15 18:04:01 | IN ZONING FOR REVIEW. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
F |
Date |
2008-02-05 |
|
|
Cont ID |
|
| Sent By |
adavila |
Date |
2008-02-05 |
Time |
17:15 |
Rev Time |
0.00 |
| Received By |
adavila |
Date |
2008-02-05 |
Time |
16:38 |
Sent To |
|
|
| Notes |
| 2008-02-05 17:15:40 | PLANNING AND ZONING DEPARTMENT | | | | | | ***FAILED*** | | | | | | 1. REPEAT COMMENT - PER SECTION 94-443(B) OF THE ZONING | | | AND LAND DEVELOPMENT REGULATIONS, THE OWNER OF THE | | | PROPERTY SHALL MAINTAIN A LANDSCAPE BUFFER STRIP ALONG | | | THE ENTIRE EDGE OF THE PROPERTY ADJACENT TO A PUBLIC | | | THOROUGHFARE AND OTHER NONRESIDENTIAL ZONING DISTRICTS. | | | PER SECTION 94-443(B)(1), THE BUFFER STRIP SHALL BE AT | | | LEAST 5 FEET IN WIDTH. | | | A. LANDSCAPE PLANS, PREPARED, SIGNED AND SEALED BY A | | | LANDSCAPE ARCHITECT, SHALL BE PROVIDED SHOWING | | | COMPLIANCE WITH THIS REQUIREMENT.PLEASE REFER TO | | | SECTION 94-443(B) OF THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS. | | | | | | 2. ACCORDING TO THE FLOOR PLANS, THERE IS AN A/C UNIT | | | ALONG THE EAST BUILDING FA?ADE; HOWEVER, THIS IS NOT | | | SHOWN ON THE SITE PLAN.PLEASE SHOW THE LOCATION OF | | | THE A/C UNIT, WITH SETBACK DIMENSIONS, ON THE SITE | | | PLAN.PLEASE NOTE THAT PER SECTION 94-305(B)(4), A/C | | | UNITS MAY ONLY ENCROACH UP TO FOUR FEET INTO A | | | SETBACK. | | | | | | 3. PER SECTION 94-444(B), PROVIDE HEDGES AROUND THE A/C | | | UNIT TO SCREEN IT FROM ALL SIDES. | | | | | | 4. PROVIDE THE WIDTH, DEPTH, RADIUS AND SQUARE FOOTAGE | | | DIMENSIONS OF THE PROPOSED DRIVEWAY ON THE SOUTH SIDE | | | OF THE PROPERTY. | | | | | | 5. PROVIDE THE MATERIAL OF THE PROPOSED DRIVEWAY. | | | STAFF RECOMMENDS THE USE OF UNSEALED PAVERS. | | | | | | 6. PLEASE SHOW CONNECTION POINT AND ACCESS WAY FROM THE | | | BUILDING STRUCTURE TO THE PARKING LOT WEST OF THE SITE. | | | A NOTE STATING THAT PARKING SPACES, INCLUDING THE | | | HANDICAP PARKING SPACE, FOR THE DAYCARE FACILITY ARE | | | AVAILABLE OFF-SITE SHALL BE NOTED ON THE SITE PLAN. | | | | | | 7. REPEAT COMMENT - PROVIDE A LETTER FROM THE | | | ENGINEERING SERVICES DEPARTMENT STATING THERE IS NO | | | NEED FOR A DUMPSTER. | | | | | | 8. DEPTH DIMENSION OF THE DEPTH OF THE HOUSE SHOULD | | | READ 42.1 FEET AND NOT 42.1 INCHES.IN ADDITION, EAST | | | SETBACK DIMENSION AT THE REAR OF THE STRUCTURE SHOULD | | | READ 7.99 FEET AND NOT 7.99 INCHES. | | | | | | 9. PLEASE NOTE THAT REVISED/NEW PLANS MAY BE SUBJECT TO | | | ADDITIONAL COMMENTS. | | | | | | COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC | | | SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2007-10-11 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2007-10-11 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
ADAVILA |
Date |
2007-10-11 |
Time |
15:13 |
Sent To |
|
|
| Notes |
| 2007-10-11 15:12:39 | PLANNING AND ZONING DEPARTMENT | | | | | | ***FAILED*** | | | | | | 1.PROJECT DOES NOT COMPLY WITH ZONING AND LAND | | | DEVELOPMENT REGULATIONS.A MEETING WITH THE PLANNING | | | AND ZONING DEPARTMENT IS REQUIRED TO DISCUSS ZONING | | | ISSUES. | | | | | | COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC | | | SCHNEIDER, PRINCIPAL PLANNER. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2007-05-09 |
|
|
Cont ID |
|
| Sent By |
adavila |
Date |
2007-05-09 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
adavila |
Date |
2007-05-08 |
Time |
11:31 |
Sent To |
|
|
| Notes |
| 2007-05-09 15:51:56 | PLANNING AND ZONING DEPARTMENT | | | | | | ***FAILED*** | | | | | | 1) PLEASE PROVIDE RESPONSE TO COMMENTS IN WRITING. | | | | | | 2) PER SECTION 94-485(J) OF THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS, CONFIGURATIONS OF PARKING | | | SPACES WHICH REQUIRE BACKING DIRECTLY ONTO A STREET | | | SHALL BE PROHIBITED IN ALL NONRESIDENTIAL ZONING | | | DISTRICTS.PROPOSED PARKING SPACES SHALL BE | | | RECONFIGURED WHERE INGRESS AND EGRESS SHALL BE PROVIDED | | | BY MEANS OF CLEARLY DEFINED DRIVES WHICH LEAD FROM | | | PUBLIC RIGHTS-OF-WAY TO CLEARLY DEFINED MANEUVERING | | | LANES WHICH IN TURN PROVIDE ACCESS TO INDIVIDUAL | | | PARKING SPACES (REPEAT COMMENT). | | | | | | A) THE PROPOSED PARKING LAYOUT IS NOT PERMITTED AS IT | | | WILL REQUIRE BACKING DIRECTLY ONTO A STREET. | | | | | | 3) THE NEW ADDITION TO THE EXISTING STRUCTURE SHALL NOT | | | BE PERMITTED AS THE PARKING SPACES FOR THE EXTRA SQUARE | | | FOOTAGE CAN NOT BE PROVIDED (REPEAT COMMENT). | | | | | | A) PER SECTION 94-486 OF THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS, DAYCARE FACILITIES REQUIRE 1 | | | PARKING SPACE PER EMPLOYEE FOR SHIFT WITH MOST | | | EMPLOYEES, 5 VISITOR SPACES, CIRCULATION/PICKUP AREA. | | | THE PROPOSED ADDITION REQUIRES A MINIMUM OF 6 PARKING | | | SPACES, ONE OF WHICH IS AN ACCESSIBLE PARKING SPACE. | | | | | | B) PER SECTION 94-485(N)(1)(A) OF THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS, IF THE TOTAL PARKING | | | REQUIREMENTS IS LESS THAN 20 SPACES, NO SMALL CAR | | | SPACES ARE PERMITTED.THE SMALL CAR SPACES PROPOSED | | | ARE NOT PERMITTED. | | | | | | 4) PROVIDE PARKING AND HANDICAPPED PARKING STALL | | | DETAILS MEETING SECTION 94-484 OF THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS (REPEAT COMMENT). | | | | | | A) DETAILS PROVIDED DO NOT MEET PARKING STALL | | | REQUIREMENTS PER ZONING REGULATIONS.PLEASE REFER TO | | | THE ATTACHED DIAGRAM. | | | | | | 5) DUMPSTER AND DUMPSTER ENCLOSURE SHALL BE PROVIDED, | | | UNLESS A LETTER FROM THE ENGINEERING SERVICES | | | DEPARTMENT STATING THERE IS NO NEED FOR A DUMPSTER IS | | | PROVIDED. | | | | | | 6) DEPTH DIMENSION OF THE HOUSE ALONG THE WEST | | | PROPERTY LINE DOES NOT MATCH THE DEPTH DIMENSION ON THE | | | SURVEY.SURVEY AND SITE PLAN SHALL REFLECT SAME AND | | | ACTUAL CONDITIONS. | | | | | | 7) PER SECTION 94-443(B) OF THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS, THE OWNER OF PROPERTY USED FOR | | | NONRESIDENTIAL PURPOSES SHALL INSTALL AND MAINTAIN A | | | LANDSCAPED BUFFER STRIP ALONG THE ENTIRE EDGE OF THE | | | PROPERTY ADJACENT TO A PUBLIC THOROUGHFARE AND OTHER | | | NONRESIDENTIAL ZONING DISTRICTS.PER SECTION | | | 94-443(B)(1), THE BUFFER STRIP SHALL BE AT LEAST 5 FEET | | | WIDE. | | | | | | A) A BUFFER SHALL BE PROVIDED FOR THE SOUTH END OF THE | | | PROPERTY. | | | | | | COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA OR ERIC | | | SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-02-12 |
|
|
Cont ID |
|
| Sent By |
adavila |
Date |
2007-02-12 |
Time |
17:02 |
Rev Time |
0.00 |
| Received By |
adavila |
Date |
2007-02-12 |
Time |
13:29 |
Sent To |
|
|
| Notes |
| 2007-02-12 17:03:13 | PLANNING AND ZONING DEPARTMENT | | | | | | ***FAILED*** | | | | | | 1) PLEASE PROVIDE RESPONSE TO COMMENTS IN WRITING. | | | | | | 2) PROVIDE A SURVEY OF THE PROPERTY.THE SURVEY SHALL | | | BE LESS THAN A YEAR OLD. | | | | | | 3) PER SECTION 94-485(J) OF THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS, CONFIGURATIONS OF PARKING | | | SPACES WHICH REQUIRE BACKING DIRECTLY ONTO A STREET | | | SHALL BE PROHIBITED IN ALL NONRESIDENTIAL ZONING | | | DISTRICTS.PROPOSED PARKING SPACES SHALL BE | | | RECONFIGURED WHERE INGRESS AND EGRESS SHALL BE PROVIDED | | | BY MEANS OF CLEARLY DEFINED DRIVES WHICH LEAD FROM | | | PUBLIC RIGHTS-OF-WAY TO CLEARLY DEFINED MANEUVERING | | | LANES WHICH IN TURN PROVIDE ACCESS TO INDIVIDUAL | | | PARKING SPACES. | | | | | | 4) THE NEW ADDITION TO THE EXISTING STRUCTURE SHALL NOT | | | BE PERMITTED AS THE PARKING SPACES FOR THE EXTRA SQUARE | | | FOOTAGE CAN NOT BE PROVIDED. | | | | | | 5) PROVIDE PARKING AND HANDICAPPED PARKING STALL | | | DETAILS MEETING SECTION 94-484 OF THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS. | | | | | | 6) PROVIDE INFORMATION REGARDING HOW THE GARBAGE | | | SERVICE WILL BE ADDRESSED.IF A DUMPSTER IS REQUIRED | | | BY THE SANITATION DEPARTMENT, PROVIDE LOCATION AND | | | DUMPSTER ENCLOSURE DETAILS MEETING ZONING REGULATIONS. | | | | | | | | | COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA OR ERIC | | | SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435. |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |