Plan Review Details - Permit 07011175
Plan Review Stops For Permit 07011175
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-07-21 Cont ID  
Sent By mjacobs Date 2008-07-21 Time 15:53 Rev Time 0.00
Received By mjacobs Date 2008-07-21 Time 13:52 Sent To PC
Notes
2008-07-21 15:26:51PROVISOR: 11-4.6.2 ACCESSIBLE PARKING SPACES SERVING
 THEBUILDING SHALL BE LOCATED ON THE SHORTEST SAFELY
 ACCESSIBLE ROUTE OF TRAVEL FROM ADJACENT PARKING TO AN
 ACCESSIBLE ENTRANCE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2008-05-22 Cont ID  
Sent By mjacobs Date 2008-05-22 Time 16:04 Rev Time 0.00
Received By mjacobs Date 2008-05-21 Time 15:43 Sent To  
Notes
2008-05-22 16:03:44BUILDING PLAN REVIEW
 PERMIT: 07011175
 ADD: 1115 ? 13TH STREET
 CONT: ALL SITE CONST.
 TEL: (561)848-1110
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 5TH
 ACTION: DENIED
 5-21-08
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)OK
  
 **NOTED; HOWEVER, THE VALUE INDICATED ON THE
 APPLICATION IS FOR THE ADDITION, THE ADDITIONAL VALUE
 FOR THE RENOVATION SHALL BE ADDED TO THE VALUE.
 4)5TH REQUEST. THE DECLARED VALUE OF THE PROJECT IS
 LOW IN VALUE. IF THE VALUE OF THE PROJECT IS NOT
 INCREASED, THE CITY WILL CALCULATE THE COST OF THE
 PROJECT USING MARSHALL & SWIFT FOR CALCULATION PURPOSES
 LATEST EDITION. 384 SQ FT X 105.10 (ADDITION ALONE) =
 $40,359. THE COST FOR REMODELING THE EXISTING STRUCTURE
 SHALL ALSO BE ADDED TO THE FIGURE MENTION ABOVE. THE
 VALUE SHALL BE THE TOTAL REPLACEMENT COST INCLUDING
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISHES AND
 ARCHITECTURAL DESIGN. WPB AMENDMENTS 108.3
  
 5)5TH REQUEST. A CHANGE IN OCCUPANCY PLUS AN ADDITION
 IMPACT FEES ASSESSMENT: BEFORE A PERMIT TO CONSTRUCT,
 MAY BE ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED
 BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED
 TO THE PERMIT APPLICATION. PLEASE CALL (561) 233-5025
 FOR MORE INFORMATION.
  
 6)OK
  
 NOTE
 7)EXISTING BUILDING CODE, 812.5 ACCESSIBILITY.
 EXISTING BUILDING OR PORTIONS THEREOF THAT UNDER GOES A
 CHANGE IN OCCUPANCY CLASSIFICATION, SHALL COMPLY WITH
 CHAPTER 11 OF THE FLORIDA BUILDING CODE.
  
 NOTE
 8)EXISTING BUILDING CODE 905.1 ACCESSIBILITY
 PROVISIONS FOR NEW ADDITION THAT AFFECTS THE
 ACCESSIBILITY TO OR CONTAIN AN AREA OF, PRIMARY
 FUNCTION SHALL COMPLY WITH THE REQUIREMENTS IN CHAPTER
 11 OF THE FLORIDA BUILDING CODE.
  
 *NOTED: HOWEVER SUBMIT ELEVATION DRAWINGS SHOWING THE
 SLOPE OF THE ACCESSIBLE ROUTE IN RELATION TO THE 5?X5?
 LANDING AT EACH DOOR. 11-4.8.2 SLOPE & RISE. THE LEAST
 POSSIBLE SLOPE SHALL BE USED FOR ANY RAMP. THE MAXIMUM
 SLOPE FOR A RAMP IN NEW CONSTRUCTION SHALL BE 1 TO 12.
 THE MAXIMUM RISE FOR RUN SHALL BE 30" (SEE FIGURE 16).
 ADDITIONAL INFORMATION REQUIRED: WPB AMENDMENTS
 106.1.2
 9)4TH REQUEST. PLEASE PROVIDE SITE PLAN INDICATING
 THE HANDICAPPED PARKING AND ACCESSIBLE ROUTE TO THE
 ENTRY 11-4.1.1 (A) (B) 11-4.1.2 (5) (A).
  
 *NOTED*
 10) 3RD REQUEST. FL BUILDING CODE 1609.1.4 COMPONENTS
 AND CLADDING PROVIDE 2 COPIES OF UPDATED PRODUCT
 APPROVALS FOR THE WINDOWS. THE ONES SUBMITTED WERE
 UNDER THE 2001 CODE VERSION. THERE IS A NEW PRODUCT
 APPROVAL FOR EXTERIOR DOORS IN THE PACKAGE WHICH WAS
 NOT APPROVED BY THE DESIGNER OF RECORD. PLEASE CIRCLE
 OR HI-LIGHT WHICH DOOR WILL BE USED FROM THE PACKAGE.
 THE PRODUCT APPROVAL SHALL BE APPROVED BY THE DESIGNER
 OF RECORD.
 SHEET S-2 INDICATES FOAM INSTALLATION INJECTED INTO THE
 NEW CMU WALLS (PROVIDE THE MANUFACTURE SPECS) AND FOAM
 INSULATION SPRAYED BETWEEN THE UPPER PORTIONS OF THE
 TRUSSES. THE INSULATION R-VALUE INDICATED IN THE ATTIC
 AREA IS R-20. PROVIDE THE MANUFACTURE SPECS AND
 INSTALLATION SPECIFICATIONS FOR THE SPRAYED INSULATION
 WHICH WILL MEET THE R-20 VALUE WHEN SPRAYED ON 2?X4?
 TRUSSES. SUBMIT THE PRODUCT APPROVAL FOR THE RIDGE VENT
 SYSTEM WHICH IS SHOWN ON SHEET S-2.
  
 11)OK
 12)OK
 13)OK
 14)OK
  
 **NEW: THE IMPUT DATA SHEETS DO NOT MATCH THE PLANS,
 THERE ARE NO ALUMINIUM DOORS ON THE PROJECT AS STATED
 ON SHEET #4.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 FAX (561) 805-6676
 [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-02-08 Cont ID  
Sent By mjacobs Date 2008-02-08 Time 09:28 Rev Time 0.00
Received By mjacobs Date 2008-02-07 Time 08:11 Sent To  
Notes
2008-02-08 09:27:56 
  
  
  
  
  
  
 BUILDING PLAN REVIEW
 PERMIT: 07011175
 ADD: 1115 ? 13TH STREET
 CONT: ALL SITE CONST.
 TEL: (561)848-1110
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 4TH
 ACTION: DENIED
 2-7-08
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)OK
  
 4)4TH REQUEST. THE DECLARED VALUE OF THE PROJECT IS
 LOW IN VALUE. IF THE VALUE OF THE PROJECT IS NOT
 INCREASED, THE CITY WILL CALCULATE THE COST OF THE
 PROJECT USING MARSHALL & SWIFT FOR CALCULATION PURPOSES
 LATEST EDITION. 384 SQ FT X 105.10 (ADDITION ALONE) =
 $40,359. THE COST FOR REMODELING THE EXISTING STRUCTURE
 SHALL ALSO BE ADDED TO THE FIGURE MENTION ABOVE. THE
 VALUE SHALL BE THE TOTAL REPLACEMENT COST INCLUDING
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISHES AND
 ARCHITECTURAL DESIGN. WPB AMENDMENTS 108.3
  
 5)4TH REQUEST. A CHANGE IN OCCUPANCY PLUS AN ADDITION
 IMPACT FEES ASSESSMENT: BEFORE A PERMIT TO CONSTRUCT,
 MAY BE ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED
 BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED
 TO THE PERMIT APPLICATION. PLEASE CALL (561) 233-5025
 FOR MORE INFORMATION.
  
 6)4TH REQUEST. PLANS INDICATE THE USE OF 32? DOORS,
 THE 32? POCKET DOORS ARE CODE COMPLIANT BUT THE OTHER
 DOORS THAT ARE 32? WILL NOT PROVIDE A 32? OPENING. FBC
 11-4.13.5 DOORS SHALL HAVE A MINIMUM CLEAR OPENING OF
 32? WITH THE DOOR OPEN 90 DEGREES, MEASURED BETWEEN THE
 FACE OF THE DOOR AND THE OPPOSITE STOP [SEE FIGURE
 24(A,B,C,D)]. PLEASE SEE INFORMATION IN PACKAGE SHOWING
 THE EXAMPLES OF DIFFERENT DOOR TYPES. RESTROOM DOORS
 ARE OK.
  
 NOTE
 7)EXISTING BUILDING CODE, 812.5 ACCESSIBILITY.
 EXISTING BUILDING OR PORTIONS THEREOF THAT UNDER GOES A
 CHANGE IN OCCUPANCY CLASSIFICATION, SHALL COMPLY WITH
 CHAPTER 11 OF THE FLORIDA BUILDING CODE.
  
 NOTE
 8)EXISTING BUILDING CODE 905.1 ACCESSIBILITY
 PROVISIONS FOR NEW ADDITION THAT AFFECTS THE
 ACCESSIBILITY TO OR CONTAIN AN AREA OF, PRIMARY
 FUNCTION SHALL COMPLY WITH THE REQUIREMENTS IN CHAPTER
 11 OF THE FLORIDA BUILDING CODE.
  
 9)4TH REQUEST. PLEASE PROVIDE SITE PLAN INDICATING
 THE HANDICAPPED PARKING AND ACCESSIBLE ROUTE TO THE
 ENTRY 11-4.1.1 (A) (B) 11-4.1.2 (5) (A).
  
 10) 3RD REQUEST. FL BUILDING CODE 1609.1.4 COMPONENTS
 AND CLADDING PROVIDE 2 COPIES OF UPDATED PRODUCT
 APPROVALS FOR THE WINDOWS. THE ONES SUBMITTED WERE
 UNDER THE 2001 CODE VERSION. THERE IS A NEW PRODUCT
 APPROVAL FOR EXTERIOR DOORS IN THE PACKAGE WHICH WAS
 NOT APPROVED BY THE DESIGNER OF RECORD. PLEASE CIRCLE
 OR HI-LIGHT WHICH DOOR WILL BE USED FROM THE PACKAGE.
 THE PRODUCT APPROVAL SHALL BE APPROVED BY THE DESIGNER
 OF RECORD.
  
 11)OK
 12)OK
 13)OK
 14)OK
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 FAX (561) 805-6676
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-10-30 Cont ID  
Sent By jjohnsto Date 2007-10-30 Time 10:28 Rev Time 6.00
Received By jjohnsto Date 2007-10-30 Time 10:26 Sent To  
Notes
2007-10-30 10:28:49CONSTRUCTION SERVICES DEPARTMENT
 200 SECOND STREET, 3RD FLOOR,
 WEST PALM BEACH, FLORIDA33401
 TEL:561-805-6713 FAX:561-805-6731
  
 JAMES JOHNSTON,
 BUILDING PLAN EXAMINER II
 E-MAIL:JJOHNSTON @WPB.ORG
  
  
 PERMIT NO 07011175
 PROJECT LIL KING & QUEEN ACADEMY
 ADDRESS 1115 13TH ST
 DATE OCTOBER 29, 2007
  
  
 BUILDINGPLANREVIEW
  
 FLORIDA BUILDING CODES 2004
  
 1
 FLORIDA STATUE713.13NOTICE OF COMMENCEMENT FILE
 NOTICE WITH THE CLERK OF COURT RECORDING DIVISION. IF
 THE WORK
 DESCRIBED IN THE NOTICE IS NOT COMMENCED WITHIN 90 DAYS
 OF
 FILING THE NOTICE WILL BECOME NULL AND VOID. SUBMIT THE
 NOTICE
 AT THE TIME OF PERMIT ISSUANCE AND POST A COPY AT THE
 JOB SITE
 BEFORE THE FIRST INSPECTION.
  
 COMMENT-FOR YOUR INFORMATION
  
  
 2(3)
 PROJECT INFORMATION
 FBC2004 BUILDING W/ 2005 AND 6 REVISIONS
 FBC2004 ACCESSIBILITYCHAPTER 11
 FBC2004 EXISTING BUILDING
 LEVEL OF ALTERATION,FBC EXISTING LEVEL III
 TYPE OF CONSTRUCTION, FBC503 V - B
 SPRINKLED / UN-SPRINKLED UN-SPRINKLED
 BASIC WIND SPEEDMPHWPB AMEND 117.1140
 WIND EXPOSUREFBC1609.4B
 WIND IMPORTANCE FACTOR,FBC 1604.5II-1
 TYPE OF OCCUPANCY, FBC CHAPTER 3D/E
 OCCUPANT LOAD,FBC 100460
  
 COMMENT-NOTE THE FOLLOWING INFORMATION ON THE COVER
 SHEET
 VERIFY THE INFORMATION PROVIDED WITH THE CODE SECTION
 SUBMITTED
  
  
 3
 PERMIT FEES (3RD REQUEST)
 (4)FEES ARE STILL OUTSTANDING.
  
 4
 IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT MAY BE ISSUED, IMPACT FEES
 MUST
 BE PAID TO PALM BEACH COUNTY.
 THE PERMITTED SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE INFORMATION. PALM
 BEACH COUNTY ASSESSMENT
 PALM BEACH COUNTY IMPACT FEE ASSESSMENT HAS MOVED TO:
 2300 N JOG ROAD, SUITE 2 WPB 33411
  
 COMMENT-FOR YOUR INFORMATION
  
  
 5
 FLORIDA STATUE481.2131INTERIOR DESIGN; PRACTICE
 REQUIREMENTS;
 DISCLOSURE OF COMPENSATION FOR PROFESSIONAL SERVICES.?
  
 COMMENT- THE CBD CHARLES FRANKLIN MUST BE LICENSED BY
 THE
 STATE OF FLORIDA TO HAVE THEIR NAME IN THE TITLE BLOCK.
 PLEASE REMOVE.
  
  
 6 (3RD REQUEST)
 FBC11-4HANDICAP PARKING
  
 COMMENT- PLEASE PROVIDE DETAILS FOR THE H.C. PARKING
 SPACE TO INCLUDE
 A-FREE STANDING SIGN, POLE HEIGHT FROM GRADE TO
 BOTTOM OF SIGN.
 B-SIGN WITH LETTERING AND FEE AMOUNT.
 C-STRIPING PER WPBFLORIDA BUILDING CODE AMENDMENTS
 DEFINING
 DOUBLE LINES, COLOR OF STRIPING AND H.C. SYMBOL. D-
 PROVIDE A SECTIONAL
 VIEW OF THE ASPHALT ACCESS ISLE TO THE SIDEWALK
  
  
  
 7 (3RD REQUEST)
 A-PLEASE PROVIDE AN EXTERIOR DOOR SCHEDULE WITH WIND
 DESIGN
 PRESSURES, HARDWARE, SIZE, TYPE
  
  
 8
 FLORIDA ENERGY CODE
 CEILING PLAN REFLECTSR-19
 ENERGY FORMR-30
  
 WALL INSULATIONPLAN DETAILR 4.2,
 ENERGY FORM R 5.0
  
 COMMENT ? PLEASE CORRECT THIS FORM
 SUBMIT TWO REPORTS COMPLETED IN INK , SIGNED SEALED
  
  
  
  
  
 STATUS OF COMMENTS FROM PREVIOUS
 REVIEWER
  
 (1) COMPLIED
  
 (6) COMPLIED
  
 (7) COMPLIED
  
 (8) COMPLIED
  
 (10)COMPLIED
  
 (11)COMPLIED
  
 (12)COMPLIED
  
 (14)COMPLIED

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-06-04 Cont ID  
Sent By jwitmer Date 2007-06-04 Time 15:28 Rev Time 2.22
Received By jwitmer Date 2007-06-04 Time 15:28 Sent To PC
Notes
2007-06-04 15:37:16BUILDING PLAN REVIEW
 PERMIT: 07011175
 ADD: 1115 13TH ST
 CONT: ALL-SITE CONSTRUCTION
 TEL: (561)317-6959
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS NULL & VOID.
 NOTE: 713.13(6)THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION
 SITE BEFORE THE FIRST INSPECTION.
  
 3 ) 2ND REQUEST110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD KEEPING & FOR
 CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WILL BE ISSUED. PLAANS SUBMITTED AFTER
 12-08-06 ARE TO BE DESIGNED UNDER THE 2006 FBC NOTE
 ALSO REFLECT EXISTING BUILDING CODE 2004/2006
 AMENDMENTS
 NOTE CHAPTER 8 FOR CHANGE IN OCCUPANCY 2006 FBC
 EXISTING BUILDING
 NOTE CHAPTER 9 FOR ADDITIONS 2006 FBC EXISTING BUILDING
 CODE
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.NOTE CHANGE IN
 OCCUPANCY.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601. RESPONSE INDICATES THE
 DESIGN AS TYPE III-B FOR A DAYCARE THE DAYCARE COULD
 HAVE 14,500 SQ FT AND 2 STORY, THIS IS A MINIMUM CODE
 PLEASE PROVIDE THE CORRECT INFORMATION.
 D) THE OCCUPANTLOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 *** THIS INFORMATION IS TO APPEAR ON THE PLANS**
  
 4) 2ND REQUEST,THE DECLARED VALUE OF THE PROJECT IS LOW
 IN VALUE. IF THE VALUE OF THE PROJECT IS NOT
 INCREASED,
 THE CITY WILL CALCULATE THE COST OF THE PROJECT USING
 MARSHALL & SWIFT FOR CALCULATING PURPOSES
 LATEST EDITION. 384 SQ FT X $105.10(ADDITION ALONE)=
 $40,359.00.I-4 OCCUPANCY / DAYCARE
 SEE CALCULATED FEES + STATE RADON FEES= FEE BALANCE OF
 $307.18.2ND REVIEW, M FEES ARE STILL OUTSTANDING.
  
 5) 2ND REQUEST, A CHANGE IN OCCUPANCY PLUS ANADDITION
 IMPACT FEES ASSESSMENT;
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 6) 2ND REQUEST,PLANS INDICATE THE USE OF 32" DOORS,
 THE 32" POCKET DOORS ARE
 CODE COMPLIANTBUT THE OTHER DOORS THAT ARE A 32" DOOR
 WILL NOT PROVIDE A 32" OPENING.
  
 RESTROOM DOORS:11-4.22.2 DOORS.
 ALL DOORS TO ACCESSIBLE TOLIET ROOMS SHALL COMPLY WITH
 11-4.13. DOORS SHALL NOT SWING INTO
 CLEAR FLOOR SPACE REQUIRED FOR ANY FIXTURE.
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARANCESAT DOORS THAT
 ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL BE AS SHOWN
 IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH IN THE REQUIRED
 CLEARANCES SHALL BE CLEAR & LEVEL.
 PROVIDE THE CLEAR FLOOR SPACE FOR THE PLUMBING
 FIXTURES, HIGHLIGHT THIS AREA, YOU WILL SEE THE
 RESTROOM DOORS SWING INTO THE CLEAR FLOOR SPACE
 REQUIRED FOR THE FIXTURES!!!!!
  
 7) EXISTING BUILDING CODE, 812.5 ACCESSIBILITY.
 EXISTING BUILDINGS OR PORTIONS THERREOF THAT UNDERGO A
 CHANGE IN OCCUPANCY CLASSIFICATION SHALL COMPLY WITH
 CHAPTER 11 OF THE FLORIDA BUILDING CODE.
  
 8) EXISTING BUILDING CODE 905.1 ACCESSIBILITY
 PROVISIONS FOR NEW CONSTRUCTION SHALL APPLY TO
 ADDITIONS. AN ADDITION THAT AFFECTS THE ACCESSIBILITY
 TO OR CONTAIN AN AREA OF, PRIMARY FUNCTION SHALL COMPLY
 WITH THE REQUIREMENTS IN CHAPTER 11 OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 9)2ND REQUEST,PLEASE PROVIDE SITE PLAN INDICATING THE
 HANDICAPPED PARKING AND ACCESSIBLE ROUTE TO THE
 ENTRY.11-4.1.1(A)(B) 11-4.1.2(5)(A). SHEET 2 INDICATES
 A 44" ACCESS AISLE LEADING FROM THE DISABLED PARKING
 SPACE BUT THE PLANS FAIL TO INDICATE A CURB CUT THROUGH
 THE4" THICK SIDEWALK. PLANS ALSO FAIL TO INDICATE THE
 TOP OF THE ACCESSIBLE SIDE WALK IN REGARDS TO THE
 INTERIOR FINISH FLOOR.
  
 10)2ND REQUEST,FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS SUBMITTED WERE 2001
  
 11 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 12)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 13) COMPLIED.
  
 14)2ND REQUEST, 1203.2 ATTIC SPACES.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 FRAMING MEMBERS SHALL HAVE CROSS VENTILATION FOR EACH
 SEPARATE SPACE BY VENTILATING OPENINGS PROTECTED
 AGAINST THE ENTRANCE OF RAIN. BLOCKING AND BRIDGING
 SHALL BE ARRANGED SO AS NOT TO INTERFERE WITH THE
 MOVEMENT OF AIR. A MINIMUM OF 1 INCH (25 MM) OF
 AIRSPACE SHALL BE PROVIDED BETWEEN THE INSULATION AND
 THE ROOF SHEATHING. THE NET FREE VENTILATING AREA SHALL
 NOT BE LESS THAN 1 / 150 OF THE AREA OF THE SPACE
 VENTILATED, WITH 50 PERCENT OF THE REQUIRED VENTILATING
 AREA PROVIDED BY VENTILATORS LOCATED IN THE UPPER
 PORTION OF THE SPACE TO BE VENTILATED AT LEAST 3 FEET
 (914 MM) ABOVE EAVE OR CORNICE VENTS WITH THE BALANCE
 OF THE REQUIRED VENTILATION PROVIDED BY EAVE OR CORNICE
 VENTS.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-12 Cont ID  
Sent By jwitmer Date 2007-03-12 Time 09:06 Rev Time 1.55
Received By jwitmer Date 2007-03-12 Time 09:07 Sent To PC
Notes
2007-03-12 09:25:21BUILDING PLAN REVIEW
 PERMIT: 07011175
 ADD: 1115 13TH ST
 CONT: ALL-SITE CONSTRUCTION
 TEL: (561)317-6959
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS NULL & VOID.
 NOTE: 713.13(6)THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION
 SITE BEFORE THE FIRST INSPECTION.
  
 3 ) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
  
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 NOTE ALSO REFLECT EXISTING BUILDING CODE 2004/2006
 AMENDMENTS
 NOTE CHAPTER 8 FOR CHANGE IN OCCUPANCY
 NOTE CHAPTER 9 FOR ADDITIONS
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.NOTE CHANGE IN
 OCCUPANCY.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
  
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 4) THE DECLARED VALUE OF THE PROJECT IS LOW IN VALUE.
 IF THE VALUE OF THE PROJECT IS NOT INCREASED,
 THE CITY WILL CALCULATE THE COST OF THE PROJECT USING
 MARSHALL & SWIFT FOR CALCULATING PURPOSES
 LATEST EDITION. 384 SQ FT X $105.10(ADDITION ALONE)=
 $40,359.00.I-4 OCCUPANCY / DAYCARE
 SEE CALCULATED FEES + STATE RADON FEES= FEE BALANCE OF
 $307.18.
  
 5) A CHANGE IN OCCUPANCY PLUS AN
 ADDITION IMPACT FEES ASSESSMENT;
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 6) PLANS INDICATE THE USE OF 32" DOORS, THE 32" POCKET
 DOORS ARE
 CODE COMPLIANTBUT THE OTHER DOORS THAT ARE A 32" DOOR
 WILL NOT PROVIDE A 32" OPENING.
 RESTROOM DOORS:11-4.22.2 DOORS.
 ALL DOORS TO ACCESSIBLE TOLIET ROOMS SHALL COMPLY WITH
 11-4.13. DOORS SHALL NOT SWING INTO
 CLEAR FLOOR SPACE REQUIRED FOR ANY
 FIXTURE.
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE
 CLEAR & LEVEL.
  
 7) EXISTING BUILDING CODE, 812.5 ACCESSIBILITY.
 EXISTING BUILDINGS OR PORTIONS THERREOF THAT UNDERGO A
 CHANGE IN OCCUPANCY CLASSIFICATION SHALL COMPLY WITH
 CHAPTER 11 OF THE FLORIDA BUILDING CODE.
  
 8) EXISTING BUILDING CODE 905.1 ACCESSIBILITY
 PROVISIONS FOR NEW CONSTRUCTION SHALL APPLY TO
 ADDITIONS. AN ADDITION THAT AFFECTS THE ACCESSIBILITY
 TO OR CONTAIN AN AREA OF, PRIMARY FUNCTION SHALL COMPLY
 WITH THE REQUIREMENTS IN CHAPTER 11 OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 9) PLEASE PROVIDE SITE PLAN INDICATING THE HANDICAPPED
 PARKING AND ACCESSIBLE ROUTE TO THE
 ENTRY.11-4.1.1(A)(B)/ 11-4.1.2(5)(A).
  
 10)FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS
 B) EXTERIOR DOORS
 C) TRUSS ANCHORS
 D) LOUVERS
 E) ROOF ASSEMBLIES
  
 11 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 12)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 13) PLANS DO NOT PROVIDE SLOPE OF ROOF PLEASE COMPLY
 WITH:
 1507.2.8 UNDERLAYMENT APPLICATION.
 FOR ROOF SLOPES FROM TWO UNITS VERTICAL IN 12 UNITS
 HORIZONTAL (17-PERCENT SLOPE), UP TO FOUR UNITS
 VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT SLOPE),
 UNDERLAYMENT SHALL BE TWO LAYERS APPLIED IN THE
 FOLLOWING MANNER. APPLY A MINIMUM 19-INCH-WIDE (483 MM)
 STRIP OF UNDERLAYMENT FELT PARALLEL WITH AND STARTING
 AT THE EAVES, FASTENED SUFFICIENTLY TO HOLD IN PLACE.
 STARTING AT THE EAVE, APPLY 36-INCH-WIDE (914 MM)
 SHEETS OF UNDERLAYMENT OVERLAPPING SUCCESSIVE SHEETS 19
 INCHES (483 MM) AND FASTENED SUFFICIENTLY TO HOLD IN
 PLACE. FOR ROOF SLOPES OF FOUR UNITS VERTICAL IN 12
 UNITS HORIZONTAL (33-PERCENT SLOPE) OR GREATER,
 UNDERLAYMENT SHALL BE ONE LAYER APPLIED IN THE
 FOLLOWING MANNER. UNDERLAYMENT SHALL BE APPLIED SHINGLE
 FASHION, PARALLEL TO AND STARTING FROM THE EAVE AND
 LAPPED 2 INCHES (51 MM), FASTENED ONLY AS NECESSARY TO
 HOLD IN PLACE.
  
 14) 1203.2 ATTIC SPACES.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 FRAMING MEMBERS SHALL HAVE CROSS VENTILATION FOR EACH
 SEPARATE SPACE BY VENTILATING OPENINGS PROTECTED
 AGAINST THE ENTRANCE OF RAIN. BLOCKING AND BRIDGING
 SHALL BE ARRANGED SO AS NOT TO INTERFERE WITH THE
 MOVEMENT OF AIR. A MINIMUM OF 1 INCH (25 MM) OF
 AIRSPACE SHALL BE PROVIDED BETWEEN THE INSULATION AND
 THE ROOF SHEATHING. THE NET FREE VENTILATING AREA SHALL
 NOT BE LESS THAN 1 / 150 OF THE AREA OF THE SPACE
 VENTILATED, WITH 50 PERCENT OF THE REQUIRED VENTILATING
 AREA PROVIDED BY VENTILATORS LOCATED IN THE UPPER
 PORTION OF THE SPACE TO BE VENTILATED AT LEAST 3 FEET
 (914 MM) ABOVE EAVE OR CORNICE VENTS WITH THE BALANCE
 OF THE REQUIRED VENTILATION PROVIDED BY EAVE OR CORNICE
 VENTS.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2008-07-18 Cont ID  
Sent By dpalmer Date 2008-07-18 Time 10:59 Rev Time 0.00
Received By dpalmer Date 2008-07-18 Time 10:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2008-05-27 Cont ID  
Sent By dpalmer Date 2008-05-27 Time 17:05 Rev Time 0.00
Received By dpalmer Date 2008-05-27 Time 17:05 Sent To  
Notes
2008-05-27 17:05:57** DENIED **
  
 1) NOTE: PLEASE KNOW AT THE REQUEST OF THE OWNER MR.
 SLYDELL NO REVIEW IS TO BE PERFORMED ON ELECTRICAL
 PLANS AS PLANS ARE KNOWN TO BE NON-CODE COMPLIANT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-01-31 Cont ID  
Sent By dpalmer Date 2008-01-31 Time 19:40 Rev Time 0.00
Received By dpalmer Date 2008-01-31 Time 19:40 Sent To  
Notes
2008-01-31 19:40:12** DENIED 4TH REVIEW **
  
 ** PLEASE SEE COMMENTS FROM PREVIOUS REVIEW ALONG WITH
 NEW COMMENTS NOW BASED ON ENERGY CALCULATIONS NOW ONLY
 BEING SUBMITTED FOR THE FIRST REVIEW. THESE WERE NOT
 SUBMITTED ON PREVIOUS REVIEW AS PREVIOUS REVIEWS HAD
 REQUESTED.
  
 *** IMPORTANT: PLEASE KNOW THIS IS THE 2ND REVIEW UNDER
 NEW DESIGN PROFESSIONALS. PLEASE SEE THE LAST COMMENT
 BELOW.
  
 1) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.2,
 13-101.1.3, 13-101.1.1, 13-400.3A, 13-400.3B
 PLEASE SEE NEW METHOD *A* IS NOW BEING SUBMITTED WHICH
 REQUIRES COMPLIANCE WITH WHOLE BUILDING.
 PLEASE SEE 13-103.1.1.1, FS 481.221, FAC 61G15-23.002,
 FS 471.025 AS THE CERTIFICATION SHEET IS NOT FILLED OUT
 WITH ALL INFORMATION AND CORRECT SIGNING, DATING AND
 SEALING OF DOCUMENTS.
 PLEASE SEE THIS IS BEING LEFT BLANK. THE ONLY SIGNATURE
 DONE CORRECTLY WAS THAT OF THE OWNER.
 PLEASE BE SURE THE DOCUMENTS ARE SIGNED, DATED AND
 SEALED BY THE RESPONSIBLE DESIGNER BASED ON SCOPE OF
 WORK.
 PLEASE CORRELATE ALL INFORMATION ON PLANS WITH THAT OF
 THE INFORMATION ON THE INPUT DATA REPORT WHICH IS PART
 OF THE ENERGY CALCULATIONS.
 FOR EXAMPLE: PLEASE SEE THE IDR DOES NOT SHOW ANY
 EXTERIOR LIGHTING ENTERED. HOW IS THIS POSSIBLE WHEN
 THE PLANS CLEARLY SHOW EXTERIOR LIGHTS?
  
 PLEASE SEE THE LIGHTING SHOWN ON PLANS ALONG WITH THE
 FIXTURE LEGEND AS SUBMITTED DOES NOT CORRELATE WITH THE
 INPUT DATA REPORT ON ENERGY CALCULATIONS. IN FACT THERE
 ARE NUMEROUS INCONSISTENCIES. PLEASE SEE SOME EXAMPLES
 GIVEN BELOW:
 FOR EXAMPLE: PLEASE SEE THE FIXTURES SHOWN IN BATHROOMS
 ARE NOTED WITH TWO-75WATT BULBSWHICH WOULD BE 150W
 YET THE FIXTURES ON THE IDR INDICATE ONLY ONE SINGLE
 60W BULB. HOW IS THIS POSSIBLE?
 FOR EXAMPLE: PLEASE SEE THE FLUORESCENT FIXTURES WHICH
 ARE SHOWN ON THE FIXTURE LEGEND AS CONTAINING TWO 75W
 BULBS WHICH WOULD BE 150W, YET THE IDR ONLY SHOWS 80W
 FOR THE SAME FIXTURES. THE FIRST COMMENT FROM THIS
 REVIEWER IS THAT A 75W FLUORESCENT BULB IS NOT PART OF
 ANY KNOWN FIXTURE AS SHOWN. PLEASE CHECK THE BULB
 WATTAGES ON THE PROPOSED FLUORESCENT FIXTURES.
 PLEASE ALSO SEE THE AMOUNT OF FIXTURES ON PLANS AND
 WATTAGES AS SHOWN WAY EXCEED THAT OF THE INFORMATION
 AND FIXTURES ON PLANS.
  
 PLEASE SEE THE USE MAY NOT BE ENTERED AS
 SCHOOL/UNIVERSITY. THIS OCCUPANCY IS NOT EITHER OF
 THESE.
 ** THESE ARE ONLY A FEW EXAMPLES ON HOW THE ENERGY
 CALCULATIONS DO NOT MATCH OR CORRELATE WITH PLANS.
  
 2) NOTE: PLEASE SEE PREVIOUS THREE REVIEWS WHICH
 SPECIFICALLY STATED THAT THE LOAD CALCULATIONS BEING
 SUBMITTED WERE FOR A *RESIDENTIAL HOUSE*. THIS IS NOT A
 RESIDENTIAL HOUSE AND MAY NOT USE THE CALCULATIONS AS
 SUBMITTED. PLEASE SEE ALL PREVIOUS REVIEW GAVE THE
 SPECIFIC CODES ON COMMERCIAL USE/OCCUPANCY LOAD
 CALCULATIONS YET THEY ARE STILL SHOWN FOR RESIDENTIAL
 USE??????
 PLEASE SEE 220.3, 220.12, 220.14, 220.42, 220.44, ETC,
 PLEASE SEE 215.3, 230.42 ETC FOR ALL CONTINUOUS LOADS
 WHICH ARE REQUIRED TO BE SHOWN AT 125%.
  
 3) NOTE: PLEASE SEE ONE OF THE NEW COMMENTS IS NOW THE
 WATER HEATER WHICH HAS NOW CHANGED FROM THE PREVIOUS
 REVIEWED PLANS.
 PLEASE SEE THE PREVIOUS ELECTRICAL PLANS LISTED ON THE
 PANEL SCHEDULE THE WH AT 4500VA AND YET NOW THE PANEL
 SCHEDULE LIST THIS UNIT AS 3500VA AND 6000VA. HOW IS
 THIS POSSIBLE? WHICH ONE IS IT?
 PLEASE CORRELATE AND SEE NOTES ABOVE WITH RESPECT TO
 LOAD CALCULATIONS.
  
 4) NOTE: PLEASE SEE THE PREVIOUS REVIEW NOTED THAT AN
 *EQUIPMENT GROUNDING CONDUCTOR* WAS MISSING AFTER THE
 FIRST MEANS OF DISCONNECT AND NOW THE RISER SHOWS AN
 EQUIPMENT GROUNDING CONDUCTOR WHICH IS OK EXCEPT IT IS
 NOT IN THE CONDUIT ALONG WITH THE OTHER FEEDERS. PLEASE
 PLACE THIS CONDUCTOR INSIDE THE NOTE FOR THE
 CONDUCTORS. THIS CAN NOT BE RUN SEPARATELY BY ITSELF.
 250.110, 250.122, ETC
  
 5) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE.
 THIS IS ONLY A NOTICE GIVEN AT THIS TIME DUE TO THE
 FACT THIS IS ONLY THE SECOND REVIEW UNDER NEW DESIGNER.
 PLEASE KNOW IF ANY OF THE SAME CODE COMPLIANCE COMMENTS
 ARE REPEATED ON THE NEXT REVIEW THIS OFFICE WILL AS
 REQUIRED UNDER FLORIDA STATUTES HAVE NO CHOICE BUT TO
 ASSESS A 4X PLAN REVIEW FEE TO THE DESIGNER OF RECORD.
 ** AS STATED ON ALL PREVIOUS REVIEWS,,,,, IF THERE ARE
 ANY QUESTIONS, PLEASE CALL THIS OFFICE OR REVIEWER TO
 GO OVER THESE NOTES.
 ONE COPY OF EACH ELECTRICAL SHEET ALONG WITH ENERGY
 CALCULATIONS SUBMITTED ARE BEING RETAINED BY THIS
 OFFICE.
  
 ** ONCE AGAIN IF COMMENTS ARE NOT UNDERSTOOD OR TYPED
 IN ANY FASHION WHICH IS NOT CLEAR, PLEASE CONTACT THIS
 REVIEWER AT THE CONTACT INFORMATION BELOW.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-10-22 Cont ID  
Sent By dpalmer Date 2007-10-22 Time 18:33 Rev Time 0.00
Received By dpalmer Date 2007-10-22 Time 17:35 Sent To  
Notes
2007-10-22 18:33:512007-10-22 18:33:51
  
 *** DENIED 3RD REVIEW ***
  
 1) NOTE: ** THIS IS THE FIRST REVIEW UNDER A NEW DESIGN
 TEAM AND ALL NEW PLANS WERE SUBMITTED.
  
 ** PLEASE SEE HOWEVER THERE ARE SEVERAL COMMENTS FROM
 THE TWO PREVIOUS REVIEWS WHICH ARE THE SAME AND STILL
 APPLY. THERE ARE MANY OF THESE WHICH HAVE NOT BEEN
 ADDRESSED AND THERE ARE SOME NEW COMMENTS ONCE AGAIN
 DUE TO THE FACT THAT THERE ARE COMPLETELY NEW PLANS
 SUBMITTED.
  
 ** PLEASE KNOW AS THERE IS STILL INFORMATION NOT
 SUBMITTED OR DESIGNED INTO THE PLANS FOR *MINIMUM* CODE
 COMPLIANCE, AND A FULL AND COMPLETE REVIEW CAN NOT BE
 DONE. THE REVIEW COMMENTS CAN ONLY BE BASED ON PLANS
 AND DOCUMENTS SUBMITTED.
  
 2) NOTE: PLEASE LIST THE BELOW CODES ON ELECTRICAL
 PLANS AS THEY ARE BEING PRINTED BELOW. THE PLANS APPEAR
 TO TAKE PART OF MY PREVIOUS REVIEW COMMENTS AND PLACE
 THIS ON THE SHEETS. PLEASE SEE CODE WHICH SEEMS TO BE
 MISPRINT FOR NEPA. PLEASE ONLY INDICATE THE FOLLOWING.
 2004 FBC W/2006 REVISIONS.
 2005 NPPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** SOME ARE OK, HOWEVER NOT ALL AND ONLY MINOR
 ADJUSTMENTS ARE NEEDED. PLANS ARE COMING BACK FOR
 CORRECTIONS AT THIS TIME.
  
 3) NOTE: PLEASE COMPLETE AND CORRELATE ALL CIRCUITING
 ON PLANS. PLEASE SEE THAT THERE ARE CIRCUITS ON PLANS
 FOR EXAMPLE FOR 120V GFI LOADS WHICH ARE SHOWN
 CIRCUITED TO A/C SYSTEM WHICH IS NOT POSSIBLE. PLEASE
 SEE FOR EXAMPLE: CIRCUITS 18 AND 19 ON PLANS. PLEASE
 SEE 700.12F FOR CIRCUITING OF EMERGENCY AND EXIT
 LIGHTS. THESE ARE REQUIRED TO BE CIRCUITED TO THE
 NORMAL LIGHTING BRANCH CIRCUITS IN THE AREAS IN WHICH
 THEY ARE LOCATED.
 FBC 106.1.2, 106.3.5.1.2, 106.3.1. ETC
 NEC 408.4, 310.16, 240.4.
 PLEASE SEE THE FOLLOWING STATEMENT WHICH IS TAKEN
 DIRECTLY FROM THE NEC.
 *2005 CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY
 CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE
 LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION*
 **SAME COMMENT ON TWO PREVIOUS REVIEWS.
  
 4) NOTE: PLEASE LABEL ALL LIGHTING FIXTURES ON PLANS
 AND CORRELATE WITH A COMPLETE FIXTURE LEGEND FOR
 FIXTURES WHICH INDICATE TYPE AND ANY SAFETY ASPECTS FOR
 FIXTURES (ENCLOSED LENSES ETC REQUIRED) PLEASE BE SURE
 FIXTURES SPECIFIED MEET THE LIFE SAFETY CODE FOR DAY
 CARE OCCUPANCIES.
 A COMPLETED FIXTURE LEGEND OF FIXTURES IS REQUIRED. FBC
 106.1.2 LS 101 CHAPTER 16.
 **SAME COMMENT ON PREVIOUS TWO REVIEWS.
  
 5) NOTE:THIS WAS THE SAME COMMENT FROM TWO PREVIOUS
 REVIEWS AND YET NO COMPLIANCE WITH FBC CHAPTER 13 OR
 CALCULATIONS HAS BEEN SUBMITTED.
 PLEASE SUBMIT COMPLETE ENERGY CALCULATIONS TO MEET THE
 2004 FBC 13-415.1.AB.1.
 PLEASE ALSO PROVIDE INFORMATION ON LIGHTING POWER
 DENSITIES PER 13-415.2
 PLEASE SEE THAT NONE WERE SUBMITTED.
 PLEASE ALSO SEE 13-103.1.1.1 FOR REQUIRED
 CERTIFICATIONS.
 ** SAME AS TWO PREVIOUS REVIEWS.
  
 6) NOTE: PLEASE SEE LS-101 16.5.1.2
 SPECIAL PROTECTIVE COVERS FOR ALL ELECTRICAL
 RECEPTACLES SHALL BE INSTALLED IN ALL AREAS OCCUPIED BY
 CLIENTS.
 PLEASE KNOW THAT THIS DOES NOT MEAN THE PLASTIC PLUG-IN
 TYPE DEVICES, THIS MEANS THE RECEPTACLE DEVICE SHALL BE
 LISTED FOR USE (110.3) AND BE OF THE TYPE WHICH
 PROVIDES AUTOMATIC PROTECTION IF AN APPLIANCE IS NOT
 PLUGGED IN OR IN USE.
 ** SAME AS TWO PREVIOUS REVIEWS. MAY NOT QUOTE THE CODE
 OR REQUIREMENT IN LIEU OF ACTUAL DESIGN OR SPECIFIC
 DETAILS NEEDED. 106.1.2
  
 7) NOTE: PLEASE SEE LS 101 2003, 6.1.4.1 FOR USE,
 9.6.4, 16.3.4.5.
 PLEASE SEE ALL SMOKE DETECTION DEVICES AND SYSTEM SHALL
 BE SHOWN.
 THIS IS NOT A RESIDENCE OR SINGLE FAMILY DWELLING.
 PLEASE SEE REVIEW COMMENTS FROM FIRE MARSHAL AS FIRE
 ALARM SYSTEM IS REQUIRED.
 PLEASE SEE FBC 11-4.28.1,.2 AND .3(4) FOR MINIMUM
 LOCATIONS AND DEVICE LEVELS TO MEET ADA.
  
  
 8) NOTE: PLEASE INDICATE THE MINIMUM LEVELS FOR EGRESS
 LIGHTING PER 7.8., 7.9.
 PLEASE SEE 106.1.2 FBC FOR ADDITIONAL INFORMATION
 NEEDED.
  
 9) NOTE: THE LOAD CALCULATIONS SUBMITTED ONCE AGAIN ARE
 FOR A RESIDENTIAL USE AND NOT FOR COMMERCIAL. PLEASE
 REVISE AND CORRECT.
 PLEASE SEE THE LOAD CALCULATIONS SHALL MEET 2005 NEC,
 THESE ARE SUBMITTED AND SHOWN FOR DWELLING USE AND
 OCCUPANCY.
 PLEASE SEE 220.3, 220.12, 220.14, 220.42, 220.44,
 PLEASE BE SURE ALL CONTINUOUS LOADS AT SHOWN AT 125%.
 215.3, 230.42
 ** SAME NOTE AS TWO PREVIOUS REVIEWS.
  
 10) NOTE: PLEASE SEE THE NOTE #3 ON PANEL SCHEDULE
 NOTES MENTIONS * AHU IS NOW- CONCURRENT WITH CONDENSING
 UNIT*.
 PLEASE VERIFY THIS AS THIS IS MOST LIKELY NOT WHAT IS
 MEANT TO BE NOTED. PLEASE SEE 220.60 WHICH IS FOR A/C.
 THIS IS EXTRACTED FROM THE NEC BELOW FOR CLARIFICATION
 OF CODE.
 *220.60 NONCOINCIDENT LOADS
 WHERE IT IS UNLIKELY THAT TWO OR MORE NONCOINCIDENT
 LOADS WILL BE IN USE SIMULTANEOUSLY, IT SHALL BE
 PERMISSIBLE TO USE ONLY THE LARGEST LOAD(S) THAT WILL
 BE USED AT ONE TIME FOR CALCULATING THE TOTAL LOAD OF A
 FEEDER OR SERVICE.*
  
 11) NOTE: PLEASE SEE MISSING DISCONNECT FOR WATER
 HEATER. PLANS SHOW A RECEPTACLE WHICH CAN NOT BE USED
 FOR CONNECTION OF WATER HEATERS. 422.30, 422.31.
  
 12) NOTE: PLEASE SEE 422.13 AS STORAGE TYPE WATER
 HEATERS ARE NOW CONSIDERED UNDER THE 2005 NEC AS A
 CONTINUOUS LOADS WHICH REQUIRES LOAD TO BE FIGURED AT
 125% IN CALCULATIONS.
 PLEASE SEE NOTE # 9 ABOVE AS ALL CALCULATIONS WILL BE
 ADJUSTED.
  
 13) NOTE: PLEASE PROVIDE ALL LICENSE INFORMATION AS
 REQUIRED FOR ALL DESIGNERS ON PLANS AS LICENSED UNDER
 FS 481.
 PLEASE SEE 481.229 AS *DESIGNERS/DRAFTSPERSONS* NOT
 LICENSED UNDER FS 481 MAY NOT DESIGN OR DO COMMERCIAL
 WORK AS IN THE SCOPE AS LISTED ON PLANS.
 PLEASE ADJUST TITLE BLOCKS WHICH REMOVES THE DESIGNER
 AS SHOWN ON INCLUDE THE LICENSE INFORMATION AS REQUIRED
 PER FAC61G1-16.004, FS 481.
 ** THE COMMENT IS NOT FOR MR. WRONKSKY.
 ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY ANY OF THE OTHER
 TRADE REVIEWS.
  
 14) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTOR FROM MAIN TO SUB PANEL.
 250.110, 250.24, 250.122 ETC.
  
 15) NOTE: PLEASE KNOW WITH RESPECT TO FS 553.80(2)(B),
 THE FEE AS REQUIRED BY THE FLORIDA STATUES AS NOTED
 WHICH WOULD HAVE BEEN ASSESSED IS NOT ASSESSED DUE TO
 NEW DESIGN TEAM.
  
 ** PLEASE KNOW AS MENTIONED ABOVE, AS THERE WILL BE
 SEVERAL CHANGES ON PLANS AND AS THERE ARE SEVERAL ITEMS
 NOT SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW
 COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE
 AT THIS TIME.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-05-11 Cont ID  
Sent By dpalmer Date 2007-05-11 Time 09:16 Rev Time 0.00
Received By dpalmer Date 2007-05-10 Time 16:48 Sent To  
Notes
2007-05-11 09:16:18** UNSAT2ND REVIEW **
  
 ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA
 BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED
 BY THE CITY OF WEST PALM BEACH.
  
 *** PLEASE SEE THAT IS A CHANGE IN OCCUPANCY TO DAY
 CARE FACILITY.
  
 1) NOTE: PLEASE STATE AND DESIGN TO ALL OF THE
 FOLLOWING MINIMUM CODES AT A MINIMUM FOR ELECTRICAL
 REVIEW.
 NFPA-70 2005 (2002 STATES ON PLANS), 2002 NFPA-72, 2003
 NFPA-101, 2004 FBCW/2006 REVISIONS.
 PLEASE SEE MISPRINT ON ELECTRICAL SHEETS ALONG WITH THE
 CODE AND ?BUILDING LEVEL? ? BEING SHOWN AS #2?
 ** PLEASE SEE THAT THE PLANS STATE A *LEVEL 2
 ALTERATION*, HOW IS THIS POSSIBLE WHEN THIS IS A CHANGE
 IN OCCUPANCY AND ALL SHALL BE DESIGNED TO THE NEW AND
 CURRENT CODES.
  
 2) NOTE: PLEASE BE SURE PLANS ARE DONE IN A CLEAR AND
 PRINTED MANOR WHICH ARE A MINIMUM OF DRAFTSMAN QUALITY
 AS REQUIRED UNDER FBC 106.1.3
  
 3) NOTE:SAME COMMENT, NO INFORMATION SUBMITTED.
 PLEASE LABEL ALL LIGHTING FIXTURES ON PLANS AND
 CORRELATE WITH A COMPLETE FIXTURE LEGEND FOR FIXTURES
 WHICH INDICATE TYPE AND ANY SAFETY ASPECTS FOR FIXTURES
 (ENCLOSED LENSES ETC REQUIRED) PLEASE BE SURE FIXTURES
 SPECIFIED MEET THE LIFE SAFETY CODE FOR DAY CARE
 OCCUPANCIES.
 PLEASE ALSO SEE THESE LIGHTING FIXTURES AND SCHEDULES
 MUST MEET THE FLA-COM CALCULATIONS FOR CHAPTER 13 OF
 THE FBC 2004 W/2006 REVISONS.
 FBC 106.1.2 LS 101 CHAPTER 16.
  
 4) NOTE: SAME NOTE: PLEASE SUBMIT COMPLETE ENERGY
 CALCULATIONS TO MEET THE 2004 FBC 13-415.1.AB.1.ETC
 PLEASE BE SURE COORDINATE ALL FIXTURES ON PLANS WITH
 THAT OF THE FIXTURE SCHEDULE AND CALCULATIONS. PLEASE
 ALSO PROVIDE INFORMATION ON LIGHTING POWER DENSITIES
 PER 13-415.2
 PLEASE SEE THE ENERGY CALCULATIONS NOW SUBMITTED ARE
 METHOD B FOR RESIDENTIAL. THIS IS NOT A RESIDENTIAL
 OCCUPANCY AND MAY NOT USE THIS. PLEASE ALSO SEE THAT
 WHEN THE CORRECTED CALCULATIONS ARE SUBMITTED, THESE
 ARE REQUIRED TO BE SIGNED, DATED AND SEALED AS
 PREVIOUSLY STATED AND REQUIRED UNDER THE FBC. PLEASE
 ALSO SEE 13-103.1.1.1 FOR REQUIRED CERTIFICATIONS.
  
 5) NOTE:SAME NOTE: PLEASE SEE A NOTE WAS ADDED FOR
 REQUIRED DEVICES; HOWEVER NO CHANGES WERE MADE TO THE
 SYMBOL LEGEND FOR TYPE? ETC.
 PLEASE SEE LS-101 16.5.1.2
 SPECIAL PROTECTIVE COVERS FOR ALL ELECTRICAL
 RECEPTACLES SHALL BE INSTALLED IN ALL AREAS OCCUPIED BY
 CLIENTS.
 PLEASE KNOW THAT THIS DOES NOT MEAN THE PLASTIC PLUG-IN
 TYPE DEVICES, THIS MEANS THE RECEPTACLE DEVICE SHALL BE
 LISTED FOR USE (110.3) AND BE OF THE TYPE WHICH
 PROVIDES AUTOMATIC PROTECTION IF AN APPLIANCE IS NOT
 PLUGGED IN OR IN USE.
  
 5) NOTE: PLEASE CLARIFY THE NEW NOTE #6 WHICH WAS ADDED
 TO PLANS. THIS NOTE AND THE CODE SECTION NOTED HAVE
 NOTHING TO DO WITH ONE ANOTHER.
 PLEASE SEE THE LS CODE STIPULATES THE MINIMUM LEVELS
 FOR EGRESS LIGHTING PER 7.8.1.3, 7.9.2.2.
 PLEASE SEE THE SECTION OF THE FBC NOTED IS FOR
 ADDITIONAL INFORMATION REQUIRED ON PLANS ONLY.
  
 6) NOTE: AS RISER HAS NOW CHANGED FROM THAT PREVIOUSLY
 SUBMITTED, PLEASE SEE THE PANEL SCHEDULE SHOWS A MCB (
 MAIN CIRCUIT BREAKER) AND THE RISER SHOWS PANEL AS
 MLO(MAIN LUG ONLY). PLEASE COORDINATE.
  
 7) NOTE: PLEASE SEE THE PLANS APPEAR TO SHOW A PANEL
 INSIDE, HOWEVER AS THE PLANS ARE NOT CLEAR, THE
 LOCATION IS NOT CONFIRMED.
 *IMPORTANT*
 PLEASE BE SURE TO SEE THE LIFE SAFETY CODE WITH RESPECT
 TO ELECTRICAL PANELS IN DAY CARE USE OCCUPANCIES.
 (PANELS REQUIRED CONTAINING LOCKABLE COVERS IF INSIDE
 BUILDING AND ACCESSIBLE FOR OCCUPANTS.
 PLEASE SEE 110.26, 240.24, 408.7, LS 101CHAPTER 6.
  
 8) NOTE:THIS IS THE SAME NOTE. THE LOAD CALCULATIONS
 SUBMITTED ARE FOR A RESIDENTIAL USE AND NOT FOR
 COMMERCIAL. PLEASE REVISE AND CORRECT.
 PLEASE SEE THE LOAD CALCULATIONS SHALL MEET 2005 NEC,
 THESE ARE SUBMITTED AND SHOWN FOR DWELLING USE AND
 OCCUPANCY.
 PLEASE SEE 220.3, 220.12, 220.14, 220.42, 220.44,
 PLEASE BE SURE ALL CONTINUOUS LOADS AT SHOWN AT 125%.
 215.3, 230.42
  
 9) NOTE: PLEASE KNOW THAT SINCE THERE ARE MANY ITEMS
 NOT YET SUBMITTED FOR REVIEW, PLEASE KNOW THAT THERE
 MAY BE NEW COMMENTS ON THE NEXT REVIEW WHICH ARE NOT
 MADE AT THIS TIME.
 PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO REPEAT
 COMMENTS FOR CODE COMPLIANCE.
  
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-02-11 Cont ID  
Sent By dpalmer Date 2007-02-11 Time 10:47 Rev Time 0.00
Received By dpalmer Date 2007-02-11 Time 08:22 Sent To  
Notes
2007-02-11 10:48:142007-02-11 10:48:14
 **** UNSAT ****
  
  
 *** PLEASE SEE THAT IS A CHANGE IN OCCUPANCY TO DAY
 CARE FACILITY.
  
  
 1) NOTE: PLEASE STATE AND DESIGN TO ALL OF THE
 FOLLOWING MINIMUM CODES AT A MINIMUM FOR ELECTRICAL
 REVIEW.
 NFPA-70 2005 (2002 STATES ON PLANS), 2002 NFPA-72, 2003
 NFPA-101, 2004 FBC.
  
 ** PLEASE SEE THAT THE PLANS STATE A *LEVEL 2
 ALTERATION*, HOW IS THIS POSSIBLE WHEN THIS IS A CHANGE
 IN OCCUPANCY AND ALL SHALL BE DESIGNED TO THE NEW AND
 CURRENT CODES.
  
 2) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND
 CORRELATE WITH A SUBMITTED PANEL SCHEDULE WHICH IS
 CLEAR AND VISIBLE WITH ALL INFORMATION. PLEASE SEE THE
 PANEL SCHEDULE IS NOT CLEAR FOR ITEMS ON PANEL. PLEASE
 CORRELATE PLANS AND PANEL SCHEDULE AS THERE ARE
 ELECTRICAL ITEMS ON PANEL SCHEDULE WHICH ARE NOT ON
 PLANS.
 PLEASE SEE 700.12E FOR CIRCUITING OF EMERGENCY AND EXIT
 LIGHTS.
 FBC 106.1.2, 106.3.5.1.2, 106.3.1. ETC
 NEC 408.4, 310.16, 240.4.
 PLEASE SEE THE FOLLOWING STATEMENT WHICH IS TAKEN
 DIRECTLY FROM THE NEC.
 *2005 CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY
 CIRCUIT SUPPLIED BY A PANELBOARD OR SWITCHBOARD BE
 LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION*
  
 3) NOTE: PLEASE LABEL ALL LIGHTING FIXTURES ON PLANS
 AND CORRELATE WITH A COMPLETE FIXTURE LEGEND FOR
 FIXTURES WHICH INDICATE TYPE AND ANY SAFETY ASPECTS FOR
 FIXTURES (ENCLOSED LENSES ETC REQUIRED) PLEASE BE SURE
 FIXTURES SPECIFIED MEET THE LIFE SAFETY CODE FOR DAY
 CARE OCCUPANCIES.
 FBC 106.1.2 LS 101 CHAPTER 16.
  
 4) NOTE: PLEASE SUBMIT COMPLETE ENERGY CALCULATIONS TO
 MEET THE 2004 FBC 13-415.1.AB.1.
 PLEASE ALSO PROVIDE INFORMATION ON LIGHTING POWER
 DENSITIES PER 13-415.2
 PLEASE SEE THAT NONE WERE SUBMITTED.
 PLEASE ALSO SEE 13-103.1.1.1 FOR REQUIRED
 CERTIFICATIONS.
  
 5) NOTE: PLEASE SEE LS-101 16.5.1.2
 SPECIAL PROTECTIVE COVERS FOR ALL ELECTRICAL
 RECEPTACLES SHALL BE INSTALLED IN ALL AREAS OCCUPIED BY
 CLIENTS.
 PLEASE KNOW THAT THIS DOES NOT MEAN THE PLASTIC PLUG-IN
 TYPE DEVICES, THIS MEANS THE RECEPTACLE DEVICE SHALL BE
 LISTED FOR USE (110.3) AND BE OF THE TYPE WHICH
 PROVIDES AUTOMATIC PROTECTION IF AN APPLIANCE IS NOT
 PLUGGED IN OR IN USE.
  
 5) NOTE: PLEASE SEE LS 101 2003, 6.1.4.1 FOR USE,
 9.6.4, 16.3.4.5.
 PLEASE SEE ALL SMOKE DETECTION DEVICES AND SYSTEM SHALL
 BE SHOWN.
 THIS IS NOT A RESIDENCE OR SINGLE FAMILY DWELLING.
  
 6) NOTE: PLEASE SEE THAT IN NO CASE MAY THERE BE
 *WHITE-OUT* OR HAND WRITTEN CHANGES MADE TO PLANS.
 PLEASE ALSO SEE THAT PLANS WHICH ARE SIGNED, DATED AND
 SEALED SHALL ALSO NOT CONTAIN THESE ITEMS.
 FS 481.221
  
 7) NOTE: PLEASE SEE MISSING NEW FOOTER STEEL AS PART OF
 THE GROUNDING ELECTRODE SYSTEM PER 250.50.
  
 8) NOTE: PLEASE PROVIDE SCHEDULE FOR THE METER/MAIN
 COMBO PANEL WHICH DOES NOT INDICATE ANY OVER CURRENT
 PROTECTION DEVICES FOR ANY ITEMS FROM THE METER/MAIN.
 PLEASE SEE THAT ANY OTHER ELECTRICAL FED ITEMS FROM THE
 METER/MAIN PANEL SHALL ALSO BE STATED WITH THE BREAKER
 SIZE, CONDUCTOR SIZES ETC.
 PLEASE SHOW THE LOCATION OF ALL ELECTRICAL SERVICE
 EQUIPMENT LOCATIONS ON ELECTRICAL PLANS.
 PLEASE BE SURE TO SEE THE LIFE SAFETY CODE WITH RESPECT
 TO ELECTRICAL PANELS IN DAY CARE USE OCCUPANCIES.
 (PANELS REQUIRED TO CONTAIN LOCKABLE COVERS IF INSIDE
 BUILDING AND ACCESSIBLE FOR OCCUPANTS.
 PLEASE SEE 110.26, 240.24, 408.7, LS 101CHAPTER 6.
  
 9) NOTE: PLEASE SEE 16.28, 16.29 FOR REQUIRED EMERGENCY
 EGRESS LIGHTING WHICH IS REQUIRED TO MEET 7.8 AND 7.9.
 PLEASE SEE THE MINIMUM LIGHTING LEVELS FOR EGRESS DOES
 NOT SEEM TO BE ACCOMPLISHED AT THIS TIME FOR THE
 LOCATION AND NUMBER OF FIXTURES SHOWN ON PLANS. PLEASE
 SEE A MINIMUM OF 1FT CANDLE IS REQUIRED AT ALL EGRESS
 PATHS/LEVELS OF WALKING SURFACE.
 THIS CAN BE ACCOMPLISHED BY PROVIDING PHOTO-METRICS FOR
 VERIFICATION OF MINIMUM LIGHTING LEVELS.
 FBC 106.1.2
  
 10) NOTE: PLEASE PROVIDE THE SERVICE ENTRANCE
 CONDUCTORS ON RISER.
 240.4, 310.16 ETC. THIS IS CONSIDERED COMMERCIAL.
  
 11) NOTE: PLEASE SEE THE LOAD CALCULATIONS SHALL MEET
 2005 NEC, THESE ARE SUBMITTED AND SHOWN FOR DWELLING
 USE AND OCCUPANCY.
 PLEASE SEE 220.3, 220.12, 220.14, 220.42, 220.44,
 PLEASE BE SURE ALL CONTINUOUS LOADS AT SHOWN AT 125%.
 215.3, 230.42
  
 12) NOTE: PLEASE SEE NOTE ON PLANS MENTIONS *ALL PANELS
 (1,2 AND 3) ARE EQUIPPED WITH FUSIBLE DISCONNECT* ,
 THIS IS NOT CLEAR AS OTHER INFORMATION MENTIONS MAIN
 CIRCUIT BREAKER EQUIPMENT.
 PLEASE CLARIFY.
 FBC106.1.21
  
 13) NOTE: PLEASE SEE 600.5 A AND B.
  
 14) NOTE: PLEASE KNOW THAT SINCE THERE ARE MANY ITEMS
 NOT YET SUBMITTED FOR REVIEW, PLEASE KNOW THAT THERE
 MAY BE NEW COMMENTS ON THE NEXT REVIEW WHICH ARE NOT
 MADE AT THIS TIME.
  
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2008-07-21 Cont ID  
Sent By mwennerg Date 2008-07-21 Time 10:18 Rev Time 0.00
Received By mwennerg Date 2008-07-21 Time 10:18 Sent To  
Notes
2008-07-21 10:19:22PLANS PREVIOUSLY APPROVED AND STAMPED ON THIS DATE.
 SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR FIRE
 ALARM SYSTEM. EMERGENCY EVACUATION PLAN TO BE POSTED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2008-05-29 Cont ID  
Sent By mawillia Date 2008-05-29 Time 12:43 Rev Time 0.00
Received By mawillia Date 2008-05-29 Time 12:34 Sent To  
Notes
2008-05-29 12:39:40*****PROVISO*****
  
 THE APPROPIATE PLAN SHEETS TO BE FIRE-STAMPED WHEN THE
 OTHER REVIEWERS HAVE BEEN SATISFIED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2008-05-29 Cont ID  
Sent By mawillia Date 2008-02-19 Time 12:34 Rev Time 0.00
Received By mawillia Date 2008-02-19 Time 15:45 Sent To  
Notes
2008-02-19 16:07:52*****PROVISO*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED, HOWEVER, THE APPROPIATE PLAN SHEETS TO
 BE FIRE-STAMPED WHEN THE OTHER REVIEWERS HAVE BEEN
 SATISFIED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2007-10-30 Cont ID  
Sent By mwennerg Date 2007-10-30 Time 14:56 Rev Time 0.00
Received By mwennerg Date 2007-10-30 Time 14:56 Sent To  
Notes
2007-10-30 15:15:43REVIEW HAD ALREADY BEEN COMPLETED ON 10/10/07

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-10-10 Cont ID  
Sent By mawillia Date 2007-10-10 Time 12:37 Rev Time 0.00
Received By mawillia Date 2007-10-10 Time 11:23 Sent To  
Notes
2007-10-10 12:37:52*****DENIED*****
 *THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN
 REVIEW STILL NEED TO BE ADDRESSED:
  
 07.SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE
 APPROPIATE EXTERIOR ELEVATION WHICH FRONTS 13TH STREET.
 AS PER WEST PALM BEACH CODE, THOSE NUMBERS SHALL BE NO
 LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN WIDTH
 CONTRASTING TO THE BACKGROUND.(NUMBERS SHALL NOT BE
 ON THE DOOR)PLEASE SHOW ACTUAL ADDRESS NUMBER ON THE
 APPROPIATE EXTERIOR ELEVATION
  
 12.DAY-CARE OCCUPANCIES, OTHER THAN DAY-CARE
 OCCUPANCIES HOUSED IN ONE ROOM, SHALL BE PROVIDED WITH
 A FIRE ALARM SYSTEM (2003 NFPA 101 16.3.4.1).NO FIRE
 ALARM SYSTEM NOTICED IN PLAN;PLEASE EXPLAIN RATIONALE
 FOR A FIRE ALARM SYSTEM NOT REQUIRED
  
  
 *NEW COMMENT
  
 AA.PLEASE EXPLAIN INCLUSION OF FLAMINGO PARK AS PART
 OF THE ADDRESS AS SHOWN IN THE TITLE BLOCK OF THE
 SUBMITTED PL;AN SHEETS.BETTER YET DELETE FLAMINGO
 PARK FROM THE ADDRESS
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 SHEET INDICATING HOW / WHERE ON THE PLANS EACH COMMENT
 WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-05-22 Cont ID  
Sent By mawillia Date 2007-05-22 Time 17:06 Rev Time 0.00
Received By mawillia Date 2007-05-22 Time 16:49 Sent To  
Notes
2007-05-22 17:04:42*****DENIED*****
 THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN
 REVIEW STILL NEED TO BE ADDRESSED:
  
  
 01.THE LIFE SAFETY CODE, NFPA 101, 2003 EDITION SHALL
 BE REFERENCED.
  
 02.PROVIDE THE OCCUPANT LOAD, IN NUMBER OF PERSONS
 FOR WHOM MEANS OF EGRESS AND OTHER PROVISIONS ARE
 REQUIRED,EITHER SHALL BE DETERMINED ON THE BASIS OF
 THE OCCUPANT LOAD FACTORS OF TABLE 7.3.1.2 THAT ARE
 CHARACTERISTIC OF THE USE OF THE SPACE OR SHALL BE
 DETERMINED AS THE MAXIMUMPROBABLE POPULATION OF THE
 SPACE UNDER CONSIDERATION, WHICHEVER IS GREATER.
  
 03.IF THE OCCUPANT LOAD IS DETERMINED BASED UPON THE
 MAXIMUM PROBABLE POPULATION OF THE SPACE, AN APPROVED
 AISLE, SEATING, AND EXITING DIAGRAM SHALL BE REQUIRED
 TO SUBSTANTIATE SUCH A MODIFICATION.
  
 04.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 05.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 06.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF
 NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE
 OR HINDER WITH EMERGENCY RESPONSE ACCESS TO THE SAID
 PROPERTY OR VICINITY THEREOF (INCLUDING STREETS OR
 ROADWAYS).
  
 07.SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE
 APPROPIATE EXTERIOR ELEVATION WHICH FRONTS 13TH STREET.
 AS PER WEST PALM BEACH CODE, THOSE NUMBERS SHALL BE NO
 LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN WIDTH
 CONTRASTING TO THE BACKGROUND.(NUMBERS SHALL NOT BE
 ON THE DOOR)
  
 08.PROVIDE A LIFE SAFETY PLAN SHEET WHICH INDICATES
 THE TRAVEL DISTANCE TO THE EXITS.THIS SHEET MAY ALSO
 INCLUDE THE LOCATION OF THE EXIT LIGHTS, EMERGENCY
 LIGHTS, FIRE ALARM DEVICES, AND THE 2A:10BC RATED FIRE
 EXTINGUISHERS APPLICABLE TO THE PROPOSED STRUCTURE.
  
 09.EVERY CLOSET DOOR LATCH SHALL BE SUCH THAT CLIENTS
 CAN OPEN THE DOOR FROM INSIDE THE CLOSET.
  
 10.EVERY BATHROOM DOOR LOCK SHALL BE DESIGNED TO
 ALLOW OPENING OF THE LOCKED DOOR FROM THE OUTSIDE BY AN
 OPENING DEVICE THAT SHALL BE READILY ACCESSSIBLE TO THE
 STAFF.
  
 11.INTERIOR WALL AND CEILING FINISH MATERIALS SHALL
 BE CLASS A OR CLASS B.
  
 12.DAY-CARE OCCUPANCIES, OTHER THAN DAY-CARE
 OCCUPANCIES HOUSED IN ONE ROOM, SHALL BE PROVIDED WITH
 A FIRE ALARM SYSTEM.
  
 13.OTHER THAN THOSE HOUSED IN ONE ROOM, A SMOKE
 DETECTION SYSTEM SHALL BE INSTALLED IN DAY-CARE
 OCCUPANCIES.
  
 14.SPECIAL PROTECTIVE COVERINGS FOR ALL ELECTRICAL
 RECEPTACLES SHALL BE INSTALLED IN ALL AREAS OCCUPIED BY
 THE CLIENTS.
  
 15.ADEQUATE ADULT STAFF SHALL BE ON DUTY, ALERT,
 AWAKE, AND IN THE FACILITY AT ALL TIMES WHERE CLIENTS
 ARE PRESENT.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 SHEET INDICATING HOW / WHERE ON THE PLANS EACH COMMENT
 WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-03-08 Cont ID  
Sent By mawillia Date 2007-03-08 Time 17:51 Rev Time 0.00
Received By mawillia Date 2007-03-08 Time 13:46 Sent To  
Notes
2007-03-08 14:08:12*****DENIED*****
  
  
 PLEASE BE ADVISED THAT THIS IS A CHANGE IN OCCUPANCY
 FROM AN EXISTING RESIDENTIAL STRUCTURE TO A NEW DAY
 CARE OCCUPANCY
  
  
  
 01.THE LIFE SAFETY CODE, NFPA 101, 2003 EDITION SHALL
 BE REFERENCED.
  
 02.PROVIDE THE OCCUPANT LOAD, IN NUMBER OF PERSONS
 FOR WHOM MEANS OF EGRESS AND OTHER PROVISIONS ARE
 REQUIRED,EITHER SHALL BE DETERMINED ON THE BASIS OF
 THE OCCUPANT LOAD FACTORS OF TABLE 7.3.1.2 THAT ARE
 CHARACTERISTIC OF THE USE OF THE SPACE OR SHALL BE
 DETERMINED AS THE MAXIMUMPROBABLE POPULATION OF THE
 SPACE UNDER CONSIDERATION, WHICHEVER IS GREATER.
  
 03.IF THE OCCUPANT LOAD IS DETERMINED BASED UPON THE
 MAXIMUM PROBABLE POPULATION OF THE SPACE, AN APPROVED
 AISLE, SEATING, AND EXITING DIAGRAM SHALL BE REQUIRED
 TO SUBSTANTIATE SUCH A MODIFICATION.
  
 04.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 05.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 06.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF
 NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE
 OR HINDER WITH EMERGENCY RESPONSE ACCESS TO THE SAID
 PROPERTY OR VICINITY THEREOF (INCLUDING STREETS OR
 ROADWAYS).
  
 07.SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE
 APPROPIATE EXTERIOR ELEVATION WHICH FRONTS 13TH STREET.
 AS PER WEST PALM BEACH CODE, THOSE NUMBERS SHALL BE NO
 LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN WIDTH
 CONTRASTING TO THE BACKGROUND.(NUMBERS SHALL NOT BE
 ON THE DOOR)
  
 08.PROVIDE A LIFE SAFETY PLAN SHEET WHICH INDICATES
 THE TRAVEL DISTANCE TO THE EXITS.THIS SHEET MAY ALSO
 INCLUDE THE LOCATION OF THE EXIT LIGHTS, EMERGENCY
 LIGHTS, FIRE ALARM DEVICES, AND THE 2A:10BC RATED FIRE
 EXTINGUISHERS APPLICABLE TO THE PROPOSED STRUCTURE.
  
 09.EVERY CLOSET DOOR LATCH SHALL BE SUCH THAT CLIENTS
 CAN OPEN THE DOOR FROM INSIDE THE CLOSET.
  
 10.EVERY BATHROOM DOOR LOCK SHALL BE DESIGNED TO
 ALLOW OPENING OF THE LOCKED DOOR FROM THE OUTSIDE BY AN
 OPENING DEVICE THAT SHALL BE READILY ACCESSSIBLE TO THE
 STAFF.
  
 11.INTERIOR WALL AND CEILING FINISH MATERIALS SHALL
 BE CLASS A OR CLASS B.
  
 12.DAY-CARE OCCUPANCIES, OTHER THAN DAY-CARE
 OCCUPANCIES HOUSED IN ONE ROOM, SHALL BE PROVIDED WITH
 A FIRE ALARM SYSTEM.
  
 13.OTHER THAN THOSE HOUSED IN ONE ROOM, A SMOKE
 DETECTION SYSTEM SHALL BE INSTALLED IN DAY-CARE
 OCCUPANCIES.
  
 14.SPECIAL PROTECTIVE COVERINGS FOR ALL ELECTRICAL
 RECEPTACLES SHALL BE INSTALLED IN ALL AREAS OCCUPIED BY
 THE CLIENTS.
  
 15.ADEQUATE ADULT STAFF SHALL BE ON DUTY, ALERT,
 AWAKE, AND IN THE FACILITY AT ALL TIMES WHERE CLIENTS
 ARE PRESENT.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 SHEET INDICATING HOW / WHERE ON THE PLANS EACH COMMENT
 WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-12-09 Cont ID  
Sent By adarroug Date 2008-12-09 Time 08:57 Rev Time 0.00
Received By adarroug Date 2008-12-09 Time 08:57 Sent To M
Notes
2008-12-09 08:58:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-07-09 Cont ID  
Sent By adarroug Date 2008-07-09 Time 10:01 Rev Time 0.00
Received By adarroug Date 2008-07-09 Time 10:01 Sent To  
Notes
2008-07-09 10:04:53TO "COMM" BD#7

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-05-07 Cont ID  
Sent By adarroug Date 2008-05-07 Time 14:31 Rev Time 0.00
Received By adarroug Date 2008-05-07 Time 14:31 Sent To  
Notes
2008-05-07 14:34:16TO "COMM" BD#7

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-01-28 Cont ID  
Sent By adarroug Date 2008-01-28 Time 08:44 Rev Time 0.00
Received By adarroug Date 2008-01-28 Time 08:44 Sent To  
Notes
2008-01-28 08:46:56TO "COMM" BD#25

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-24 Cont ID  
Sent By adarroug Date 2007-04-24 Time 14:32 Rev Time 0.00
Received By adarroug Date 2007-04-24 Time 14:32 Sent To  
Notes
2007-05-04 09:02:19TO "COMM" BD#34
2007-04-24 14:32:48WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-12 Cont ID  
Sent By jwitmer Date 2007-03-12 Time 11:38 Rev Time 0.00
Received By jwitmer Date 2007-01-29 Time 17:05 Sent To  
Notes
2007-02-07 08:51:55TO "COMM" BD#34
2007-01-29 17:15:01WAITING FOR "COMM" BD

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2008-05-15 Cont ID  
Sent By rkussner Date 2008-05-15 Time 14:44 Rev Time 0.00
Received By rkussner Date 2008-05-15 Time 14:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 10 Status P Date 2009-03-24 Cont ID  
Sent By rregueir Date 2009-03-24 Time 16:35 Rev Time 0.00
Received By rregueir Date 2009-03-24 Time 16:35 Sent To PC
Notes
2009-03-24 16:35:48AC-1 REVISION

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2008-12-22 Cont ID  
Sent By rregueir Date 2008-12-22 Time 19:24 Rev Time 0.00
Received By rregueir Date 2008-12-22 Time 19:17 Sent To PC
Notes
2008-12-22 19:26:30REVISED A/C-1. PLANS STILL SHOW RETURN TRANSFERS TOO
 SMALL TO MEET THE EXCEPTIONS UNDER FBCM 601.4. A FIELD
 TEST WILL BE REQUIRED TO VERIFY BALANCED RETURN IN
 ACCORDANCE WITH THIS SECTION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 8 Status F Date 2008-12-14 Cont ID  
Sent By rregueir Date 2008-12-14 Time 14:25 Rev Time 0.00
Received By rregueir Date 2008-12-14 Time 14:22 Sent To PC
Notes
2008-12-14 14:25:13REVISED AC-1: DENIED
  
 ORIGINAL PLANS SUBMITTED FOR PERMIT ARE SIGNED AND
 SEALED BY AN ARCHITECT AS DESIGNER OF RECORD. THESE
 PLANS WERE DRAWN BY AN A/C CONTRACTOR, NOT THE DESIGNER
 OF RECORD. ANY CHANGES TO THE PERMIT SET OF PLANS SHALL
 BE BY THE DESIGNER OF RECORD IN ACCORDANCE WITH FS 481.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2008-07-18 Cont ID  
Sent By rregueir Date 2008-07-18 Time 13:36 Rev Time 0.00
Received By rregueir Date 2008-07-18 Time 13:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2008-05-23 Cont ID  
Sent By rregueir Date 2008-05-23 Time 09:29 Rev Time 0.00
Received By rregueir Date 2008-05-23 Time 09:27 Sent To  
Notes
2008-05-23 09:29:44PLANS REMAIN CODE COMPLIANT FOR MECHANICAL. REVIEW WILL
 REMIAN IN FAILED STATUS PENDING SUCCESSFUL REVIEW OF
 ENERGY CALCULATIONS BY ALL AFFECTED TRADES.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 5 Status N Date 2008-07-18 Cont ID  
Sent By rregueir Date 2008-07-18 Time 13:36 Rev Time 0.00
Received By rregueir Date 2008-05-23 Time 09:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2008-02-16 Cont ID  
Sent By rregueir Date 2008-02-16 Time 09:03 Rev Time 0.00
Received By rregueir Date 2008-02-16 Time 08:23 Sent To  
Notes
2008-02-16 08:43:14REVIEW #: 4TH
 ACTION: FAILED/PENDING
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. NEW FOR 400A HAS BEEN SUBMITTED. HOWEVER, THE INPUT
 DATA REPORT WAS NOT INCLUDED WITH THE COMPLIANCE FORM
 AS REQUIRED. PAGE 2 OF THE COMPLIANCE REPORT STATES
 "IMPORTANT NOTICE: AN INPUT REPORT OF THIS DESIGN
 BUILDING MUST BE SUBMITTED ALONG WITH THIS COMPLIANCE
 REPORT."
 ADDITIONALLY, THE METHOD A COMPLIANCE FORM IS FOR THE
 "WHOLE BUILDING" INCLUDING ALL MAJOR ENERGY UTILIZING
 EQUIPMENT AND ALL BUILDING ENVELOPE COMPONENTS. NO
 BUILDING ENVELOPE COMPONENTS WERE INCLUDED IN THIS
 REPORT. IF METHOD A IS TO BE USED, THE WHOLE BUILDING
 MUST BE DEMONSTRATED TO BE IN COMPLIANCE WITH THE
 METHOD A CALCULATING PROCEDURES AS DEFINED IN THE
 FLA/COM PROGRAM. METHOD A MAY ONLY BE USED IF THE
 CONDITIONS UNDER FBC 13-101.4.2 HAVE BEEN MET. IN
 ADDITION TO THIS SECTION, PLEASE SEE FBC 13-101.3 TO
 SEE WHICH COMPLIANCE METHODS ARE AVAILABLE FOR THIS
 PROJECT.
  
 2. RETURNS HAVE NOT BEEN CHANGED TO SHOW COMPLIANCE
 WITH THE EXCEPTIONS LISTED UNDER FBC, M 601.4. A FIELD
 TEST WILL BE REQUIRED AT FINAL INSPECTION DEMONSTRATING
 PRESSURE DIFFERENTIALS OF 0.01" WC OR LESS IN ROOMS
 WHERE RETURN JUMPERS ARE UTILIZED.
  
 NOTE: PLANS HAVE BEEN REVIEWED FOR CODE COMPLIANCE AND
 STAMPED. HOWEVER, PLAN REVIEW STOP WILL REMAIN IN
 "FAILED" STATUS UNTIL A CORRECTED ENERGY CODE
 COMPLIANCE FORM HAS BEEN SUBMITTED AND REVIEWED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-11-11 Cont ID  
Sent By rregueir Date 2007-11-11 Time 12:50 Rev Time 0.00
Received By rregueir Date 2007-11-11 Time 11:47 Sent To  
Notes
2007-11-11 12:49:33REVIEW #: 3
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
 *NOTE* A WRITTEN RESPONSE TO REVIEW COMMENTS FROM THE
 DESIGN TEAM WILL AID IN THE REVIEW PROCESS.
  
 1. ENERGY CALCULATIONS FORM 600 HAS BEEN SUBMITTED FOR
 THE 3RD TIME. THIS IS NOT A RESIDENTIAL OCCUPANCY,
 THERE IS A CHANGE OF OCCUPANCY AND SHALL THEREFORE THIS
 PROJECT SHALL DEMONSTRATE COMPLIANCE WITH FBC
 13-101.3.
  
 2. RETURN AIR TRANSFER DUCTS ARE STILL NOT DESIGNED TO
 MEET TH BALANCED RETURN EXCEPTIONS UNDER FBC,M 601.4. A
 FIELD TEST WILL BE REQUIRED AT FINAL INSPECTION TO
 DETERMINE IF PRESSURE DIFFERENTIALS ACROSS CLOSED DOORS
 ARE AT 0.01IN. WC OR LESS IN ACCORDANCE WITH THIS
 SECTION. THIS STEP WILL NOT BE NECESSARY IF TRANSFERS
 ARE DESIGNED TO MEET THE FOLLOWING EXCEPTION: "TRANSFER
 DUCTS MAY ACHIEVE THIS BY INCREASING THE RETURN
 TRANSFER ONE AND ONE-HALF TIMES THE CROSS-SECTIONAL
 AREA (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE
 ROOM OR SPACE IT IS SERVING AND THE DOOR HAVING AT
 LEAST AN UNRESTRICTED 1-INCH UNDERCUT TO ACHIEVE PROPER
 RETURN AIR BALANCE."
  
 3. NATURAL VENTILATION AS SHOWN ON PLANS IS OK.
  
 4. OK
  
 5. OK
  
 6. OK
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-05-14 Cont ID  
Sent By rregueir Date 2007-05-14 Time 11:40 Rev Time 0.00
Received By rregueir Date 2007-05-14 Time 08:10 Sent To  
Notes
2007-05-14 11:40:39-------------DENIED---------------
  
 FBC 2004 CODE FAMILY W/2006 REVISIONS
  
 1. FORM 600 OF THE ENERGY CALCULATIONS IS NOT
 ACCEPTABBLE FOR THIS PROJECT AS THIS IS NO LONGER A
 RESIDENTIAL OCCUPANCY. PLEASE ALSO INCLUDE COOLING LOAD
 CALCULATIONS PER FBC CH 13-B SEC. 3.1. IS THIS SYSTEM
 ADEQUATELY SIZED FOR THE ADDITIONAL SQ' FOOTAGE,
 INCREASED OCCUPANT LOAD AND 600 CFM OUTSIDE AIR?
 NOTE: THE MINIMUM EFFICIENCY FOR SPLIT SYSTEMS <65,000
 BTUH AS REQUIRED BY TABLE 13-407.1.ABC.3.2A IS 13.0
 SEER.
  
 2. THERE IS NO RETURN AIR SHOWN ON PLAN, OTHER THAN THE
 12" ROUND TRANSFER FROM INFANT ROOM. WHAT IS THE SIZE
 AND LOCATION OF MAIN RETURN? HOW IS BALANCED RETURN TO
 BE ACHIEVED FROM OFFICE AND SERVICE AREA (IF IT IS NOT
 TO BE A KITCHEN)?
 NOTE: THE TRANSFER FROM INFANT ROOM DOES NOT MEET THE
 EXCEPTIONS TO FBC,M 601.4. PLEASE DESIGN ALL TRANSFERS
 TO THESE EXCEPTIONS OR A FIELD TEST WILL BE REQUIRED AT
 FINAL INSPECTION TO DETERMINE PRESSURE DIFFERENTIALS AS
 REQUIRED BY THIS SECTION.
  
 3. VENTILATION SHALL BE PROVIDED TO ALL OCCUPUED SPACES
 (IE: KITCHEN/SERVICE AREA AND OFFICE) PER FBC,M 403.1.
 THE AMOUNT OF SUPPLY AIR IS TO BE APPROXIMATELY EQUAL
 TO THE AMOUNT OF RETURN AND EXHAUST AIR PER FBC,M
 403.1. RETURN SHOULD BE 600 CFM LESS THAN SUPPLY WITH
 600 CFM OF EXHAUST. WHERE IS EXHAUST?
  
 4. EXHAUST AIR IS REQUIRED FOR BATHROOMS PER FBC,M
 TABLE 403.3 UNDER PUBLIC SPACES - TOILET ROOMS.
  
 5. THE VENTILATION SYSTE SHALL RUN CONTINUOUSLY DURING
 THE PERIOD THE BUILDING IS OCCUPIED PER FBC,M 403.3.
 PLEASE SHOW HOW THE SYSTEM IS TO BE CONTROLLED TO
 ACCOMPLISH THIS?
  
 6. WHAT TYPE OF COOKING EQUIPMENT IS THE BE IN THE
 SERVICE AREA? KITCHEN EXHAUST IS TO BE IN COMPLIANCE
 WITH FBC,M CH. 506 PER FBC,EB 809.1.
  
 REVIEWED BY:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-02-24 Cont ID  
Sent By hmoser Date 2007-02-24 Time 12:17 Rev Time 0.00
Received By hmoser Date 2007-02-24 Time 12:17 Sent To  
Notes
2007-02-24 12:23:01PLAN DENIED
 PLEASE PROVIDE FRESH AIR CALCULATIONS FROM TABLE 403.4
 2000 FBC(M) .
 PLEASE REMOVE RETURN AIR DUCT FROM BATHROOM PER SECTION
 601.4 #3
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 5 Status P Date 2008-06-03 Cont ID  
Sent By jleech Date 2008-06-03 Time 10:06 Rev Time 0.00
Received By jleech Date 2008-06-03 Time 09:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2008-02-11 Cont ID  
Sent By jleech Date 2008-02-11 Time 08:21 Rev Time 0.00
Received By jleech Date 2008-02-11 Time 07:43 Sent To  
Notes
2008-02-11 08:57:40DENIED;
 1. PAGE P-1 BUILDING CONTRACTOR NOTE; PLUMBING CODE TO
 BE USED IS THE FBC-PLUMBING SECTION 601, NOT THE
 RESIDENTIAL CODE 2901 THIS IS A BUSINESS.
 2. WATER RISER DIAGRAM SHALL BE OF SUFFICIENT CLARITY,
 FBC BUILDING CHAPTER 1 (ADMINISTRATION) SECTION
 106.1.1. DELETE SANITARY DIAGRAM ( UNDER WATER DIAGRAM)
 , AND SHOW WATER SERVICE FROM SHUTOFF VALVE TO THE LAST
 FIXTURE IN BUILDING.
 3. ADD NOTE TO WATER RISER DIAGRAM; " BACKFLOW
 PREVENTER REQUIRED ON WATER SERVICE AT CITY WATER
 METER".
 4. SANITARY RISER DIAGRAM; 3 COMPARTMENT SINK SHALL
 DISCHARGE DOWN STREAM OF THE BATHROOM GROUP SEE FBC
 PLUMBING SECTION 909.1.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-11-20 Cont ID  
Sent By jleech Date 2007-11-20 Time 09:10 Rev Time 0.00
Received By jleech Date 2007-11-20 Time 08:53 Sent To  
Notes
2007-11-20 09:43:22DENIED;
 1. SEE ELECTRICAL PLAN REVIEWER'S COMMENT # 13.
 2. INFORMATION ON CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY. FBC BUILDING CHAPTER 1
 (ADMINISTRATION) SECTION 106.1.1.
 A) SEPARATE WATER AND SANITARY RISER
 DIAGRAMS.
 1. SANITARY RISER DIAGRAM;
 A)CLEARLY MARK EACH FIXTURE,
 I.E. LAV, W/C, SINK.
 B) DRAIN SIZES ARE NOT CORRECT.
 LAVATORY'S ARE 1 1/4 SINKS ARE 1 1/2.
 2. WATER RISER DIAGRAM;
 A) SHOW CALCULATIONS FOR WATER
 DISTRIBUTION PIPING . SEE FBC PLUMBING TABLE 603.1.
 B) SHOW SIZE OF WATER HEATER.
 3. SHOW DETAIL DRAWINGS OF HANDICAP FIXTURES WITH ALL
 REQUIRED MESUREMENTS. ( LAV., W/C, D/F )
 4. SHOW DETAIL DRAWINGS FOR CHILDRENS BATHROOMS AND
 SPECK OUT FIXTURES.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-05-22 Cont ID  
Sent By pschmitz Date 2007-05-22 Time 14:05 Rev Time 0.00
Received By pschmitz Date 2007-05-22 Time 08:51 Sent To  
Notes
2007-05-22 14:04:49 
  
 PAUL SCHMITZ
  
 [email protected]
 FBC 2004 PLUMBING CODE
 PLAN REVIEW
 FBC 2004 FUEL GAS CODE PLAN REVIEW FBC
 2004 CH 11, FL ACCESSIBILITY CODE AMENDMENTS TO THE
 FLORIDA BUILDING CODE
 CHAPT.1, ADMINISTRATION, 2004
 EDITION
  
 DENIED 2ND
 TIME 5-22-07
 "SEE COMMENTS IN CAPITOL
 LETTERS"
  
 NOT ADDRESSED
 1)SHT 3. BOYS & GIRLS REST ROOM
 COMPLY WITH 36 CFR PART 1191 [ DOCKET NO.94-2]"GUIDE
 LINES"
 ADA ACCESSIBILITY GUIDELINES FOR BUILDINGS AND
 FACILITIES; BUILDING ELEMENTS DESIGNED FOR CHILDREN'S
 USE.
  
 SHT 3. LABEL DRINKING FOUNTAIN AS D/F, WHY, 3 W/F
 ?
 2) SHT 3.11-4.1.3 (10)DRINKING FOUNTAINS.
 (A) WHERE ONLY ONE DRINKING FOUNTAIN IS PROVIDED ON A
 FLOOR, THERE SHALL BE A DRINKING FOUNTAIN WHICH IS
 ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS IN
 ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE TO
 THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING. (THIS
 CAN BE ACCOMMODATED BY THE USE OF A ?HI-LO? FOUNTAIN;
 BY PROVIDING ONE FOUNTAIN ACCESSIBLE TO THOSE WHO USE
 WHEELCHAIRS AND ONE FOUNTAIN AT A STANDARD HEIGHT
 CONVENIENT FOR THOSE WHO HAVE DIFFICULTY BENDING; BY
 PROVIDING A FOUNTAIN ACCESSIBLE UNDER SECTION 11-4.15
 AND A WATER COOLER; OR BY SUCH OTHER MEANS AS WOULD
 ACHIEVE THE REQUIRED ACCESSIBILITY FOR EACH GROUP ON
 EACH FLOOR.)
  
 DIMENSIONS ON BOYS AND GIRLS REST RM,
 WIDTH NOT TO SCALE, MIN 5'-2"
 3) SEC. (11) 11-4.1.3 ACCESSIBLE BUILDINGS: NEW
 CONSTRUCTION, TOILET FACILITIES. IF TOILET ROOMS ARE
 PROVIDED, THEN EACH PUBLIC AND COMMON USE TOILET ROOM
 SHALL COMPLY WITH SECTION 11-4.22. OTHER TOILET ROOMS
 PROVIDED FOR THE USE OF OCCUPANTS OF SPECIFIC SPACES
 (I.E., A PRIVATE TOILET ROOM FOR THE OCCUPANT OF A
 PRIVATE OFFICE) SHALL BE ADAPTABLE. IF BATHING ROOMS
 ARE PROVIDED, THEN EACH PUBLIC AND COMMON USE BATHROOM
 SHALL COMPLY WITH SECTION 11-4.23. ACCESSIBLE TOILET
 ROOMS AND BATHING FACILITIES SHALL BE ON AN ACCESSIBLE
 ROUTE.
  
 WATER PIPING ISOMETRIC NOT INCLUDED
 4) SHT 4. COMPLY WITH SEC 106 SANITARY AND WATER PIPE
 ISOMETRIC, INCLUDE PIPE SIZES ON THE ISOMETRICS.
 SHT 4 PLUMBING NOTES ARE NOT SUFFICENT TO INDICATE
 NATURE OF WORK.
 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL (SEE ALSO SECTION
 106.3.5).
  
  
 NOT ADDRESSED
 5)SECTION 608, BACK FLOW PREVENTER
 PROTECTION OF POTABLE WATER SUPPLY
 608.1 GENERAL.
 A POTABLE WATER SUPPLY SYSTEM SHALL BE DESIGNED,
 INSTALLED AND MAINTAINED IN SUCH A MANNER SO AS TO
 PREVENT CONTAMINATION FROM NONPOTABLE LIQUIDS, SOLIDS
 OR GASES BEING INTRODUCED INTO THE POTABLE WATER SUPPLY
 THROUGH CROSS-CONNECTIONS OR ANY OTHER PIPING
 CONNECTIONS TO THE SYSTEM. BACKFLOW PREVENTER
 APPLICATIONS SHALL CONFORM TO TABLE 608.1, EXCEPT AS
 SPECIFICALLY STATED IN SECTIONS 608.2 THROUGH
 608.16.9.
  
 NOT ADDRESSED
 6) SEC 607.3 THERMAL EXPANSION CONTROL.
 A MEANS OF CONTROLLING INCREASED PRESSURE CAUSED BY
 THERMAL EXPANSION SHALL BE PROVIDED WHERE REQUIRED IN
 ACCORDANCE WITH SECTIONS 607.3.1 AND 607.3.2. 607.3.2
 BACKFLOW PREVENTION DEVICE OR CHECK VALVE. WHERE A
 BACKFLOW PREVENTION DEVICE, CHECK VALVE OR OTHER DEVICE
 IS INSTALLED ON A WATER SUPPLY SYSTEM UTILIZING STORAGE
 WATER HEATING EQUIPMENT SUCH THAT THERMAL EXPANSION
 CAUSES AN INCREASE IN PRESSURE, A DEVICE FOR
 CONTROLLING PRESSURE SHALL BE INSTALLED.
  
 NOT ADDRESSED
 7)SEE OTHER PLAN REVIEW COMMENTS, THAT MAY EFFECT
 PLUMBING PLAN REVIEW.
  
 8) NEW COMMENT:HEALTH DEPARTMENT NOTES, CHILD CHANGE
 STATIONS TO BE INCLUDED ON REVISEED PLANS.
  
 9) NEW COMMENT: SERVICE AREA IS NOT EXISTING, INCLUDE
 ON DWV, WATER ISOMETRIC.
  
 END OF COMMENTS, QUESTIONS 561-805-6692

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-02-24 Cont ID  
Sent By pschmitz Date 2007-02-24 Time 08:20 Rev Time 0.00
Received By pschmitz Date 2007-02-24 Time 08:18 Sent To  
Notes
2007-02-24 09:41:16PAUL SCHMITZ
 [email protected] FBC 2004 PLUMBING
 CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE
  
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 DENIED
  
 1) SHT 3. BOYS & GIRLS REST ROOM
 COMPLY WITH 36 CFR PART 1191 [ DOCKET NO.94-2]"GUIDE
 LINES"
 ADA ACCESSIBILITY GUIDELINES FOR BUILDINGS AND
 FACILITIES; BUILDING ELEMENTS DESIGNED FOR CHILDREN'S
 USE.
  
 2) SHT 3 .11-4.1.3 (10) DRINKING FOUNTAINS.
 (A) WHERE ONLY ONE DRINKING FOUNTAIN IS PROVIDED ON A
 FLOOR, THERE SHALL BE A DRINKING FOUNTAIN WHICH IS
 ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS IN
 ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE TO
 THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING. (THIS
 CAN BE ACCOMMODATED BY THE USE OF A ?HI-LO? FOUNTAIN;
 BY PROVIDING ONE FOUNTAIN ACCESSIBLE TO THOSE WHO USE
 WHEELCHAIRS AND ONE FOUNTAIN AT A STANDARD HEIGHT
 CONVENIENT FOR THOSE WHO HAVE DIFFICULTY BENDING; BY
 PROVIDING A FOUNTAIN ACCESSIBLE UNDER SECTION 11-4.15
 AND A WATER COOLER; OR BY SUCH OTHER MEANS AS WOULD
 ACHIEVE THE REQUIRED ACCESSIBILITY FOR EACH GROUP ON
 EACH FLOOR.)
  
 3) SEC. (11) 11-4.1.3 ACCESSIBLE BUILDINGS: NEW
 CONSTRUCTION. TOILET FACILITIES. IF TOILET ROOMS ARE
 PROVIDED, THEN EACH PUBLIC AND COMMON USE TOILET ROOM
 SHALL COMPLY WITH SECTION 11-4.22. OTHER TOILET ROOMS
 PROVIDED FOR THE USE OF OCCUPANTS OF SPECIFIC SPACES
 (I.E., A PRIVATE TOILET ROOM FOR THE OCCUPANT OF A
 PRIVATE OFFICE) SHALL BE ADAPTABLE. IF BATHING ROOMS
 ARE PROVIDED, THEN EACH PUBLIC AND COMMON USE BATHROOM
 SHALL COMPLY WITH SECTION 11-4.23. ACCESSIBLE TOILET
 ROOMS AND BATHING FACILITIES SHALL BE ON AN ACCESSIBLE
 ROUTE.
  
 4) SHT 4. COMPLY WITH SEC 106 SANITARY AND WATER PIPE
 ISOMETRIC, INCLUDE PIPE SIZES ON THE ISOMETRICS.
 DRINKING FOUNTAIN NOT ON PLUMBING ISOMETRIC
  
 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL (SEE ALSO SECTION
 106.3.5).
  
 5)SECTION 608, BACK FLOW PREVENTER
 PROTECTION OF POTABLE WATER SUPPLY
 608.1 GENERAL.
 A POTABLE WATER SUPPLY SYSTEM SHALL BE DESIGNED,
 INSTALLED AND MAINTAINED IN SUCH A MANNER SO AS TO
 PREVENT CONTAMINATION FROM NONPOTABLE LIQUIDS, SOLIDS
 OR GASES BEING INTRODUCED INTO THE POTABLE WATER SUPPLY
 THROUGH CROSS-CONNECTIONS OR ANY OTHER PIPING
 CONNECTIONS TO THE SYSTEM. BACKFLOW PREVENTER
 APPLICATIONS SHALL CONFORM TO TABLE 608.1, EXCEPT AS
 SPECIFICALLY STATED IN SECTIONS 608.2 THROUGH
 608.16.9.
  
  
 6) SEC 607.3 THERMAL EXPANSION CONTROL.
 A MEANS OF CONTROLLING INCREASED PRESSURE CAUSED BY
 THERMAL EXPANSION SHALL BE PROVIDED WHERE REQUIRED IN
 ACCORDANCE WITH SECTIONS 607.3.1 AND 607.3.2. 607.3.2
 BACKFLOW PREVENTION DEVICE OR CHECK VALVE. WHERE A
 BACKFLOW PREVENTION DEVICE, CHECK VALVE OR OTHER DEVICE
 IS INSTALLED ON A WATER SUPPLY SYSTEM UTILIZING STORAGE
 WATER HEATING EQUIPMENT SUCH THAT THERMAL EXPANSION
 CAUSES AN INCREASE IN PRESSURE, A DEVICE FOR
 CONTROLLING PRESSURE SHALL BE INSTALLED.
  
 7)SEE OTHER PLAN REVIEW COMMENTS, THAT MAY EFFECT
 PLUMBING PLAN REVIEW.
  
 END OF COMMENTS, QUESTIONS 561-805-6692

Review Stop Z ZONING
Rev No 7 Status P Date 2008-07-18 Cont ID  
Sent By adavila Date 2008-07-18 Time 14:34 Rev Time 0.00
Received By adavila Date 2008-07-18 Time 14:34 Sent To  
Notes
2008-07-18 14:35:55PROVISO APPLICANT SHALL OBTAIN A CERTIFICATE OF
 OCCUPANCY ("CO") FOR THE PARKING LOT ON THE ADJACENT
 PROPERTY (1117 13TH STREET) PRIOR TO OBTAINING A CO FOR
 THIS BUILDING PERMIT (PERMIT NO. 07011175).
  
 PROVISO HANDICAP WALKWAY ACCESS TO PARKING SHALL MATCH
 THE FIVE (5) FOOT ACCESS AISLE ON THE ADJACENT
 PROPERTY.
  
 PROVISO ROOF OVERHANG PROJECTION SHALL NOT EXTEND
 FARTHER THAN THREE (3) FEET INTO ANY SETBACK.
  
 PROVISO A REVISED LANDSCAPE PLAN SHALL BE REVIEWED AND
 APPROVED BY THE PLANNING AND ZONING DEPARTMENT PRIOR TO
 OBTAINING A CO.
  
 PER ANGELLA VANN, DEPUTY PLANNING DIRECTOR.

Review Stop Z ZONING
Rev No 6 Status F Date 2008-07-16 Cont ID  
Sent By adavila Date 2008-07-16 Time 15:02 Rev Time 0.00
Received By adavila Date 2008-07-16 Time 10:39 Sent To  
Notes
2008-07-16 15:03:12PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. PURSUANT TO SECTION 94-441(C)(2), RENOVATIONS,
 REPAIRS, ALTERATION OR REDEVELOPMENT THAT EXCEED 50% OF
 THE VALUE OF THE STRUCTURE SHALL REQUIRE THE SITE TO BE
 BROUGHT INTO COMPLIANCE WITH ARTICLE XIV, LANDSCAPE
 REGULATIONS, OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS ("ZLDRS").ACCORDING TO THE LATEST
 RESUBMITTED PACKAGE, THE VALUE FOR THE PROPOSED WORK
 HAS INCREASED TO $56,000.PER THE PALM BEACH COUNTY
 PROPERTY APPRAISER'S OFFICE ("PAPA"), THE VALUE OF THE
 STRUCTURE IS $87,457.AS THE TOTAL WORK VALUE EXCEEDS
 50% OF THE VALUE OF THE STRUCTURE ($43,728.5), YOU HAVE
 TWO OPTIONS:
 (1) PROVIDE 6 ADDITIONAL TREES ALONG THE NORTH, EAST
 AND WEST PROPERTY LINES.A LANDSCAPE PLAN PREPARED,
 SIGNED AND SEALED BY FLORIDA REGISTERED LANDSCAPE
 ARCHITECT SHALL BE SUBMITTED SHOWING COMPLIANCE WITH
 ARTICLE XIV OF THE ZLDRS.PLEASE CONTACT ROBERT
 KUSSNER, LANDSCAPE PLANNER, FOR LANDSCAPE SPECIES AND
 LOCATION OPTIONS;
 (2) PROVIDE AN APPRAISAL BY A LICENSED PROPERTY
 APPRAISAL THAT SHOWS THE VALUE OF THE STRUCTURE OVER
 $112,000.
  
 2. PROVIDE THE STATUS OF THE PARKING LOT ON THE
 ADJOINING PROPERTY.PLEASE NOTE THAT A CERTIFICATE OF
 OCCUPANCY ("CO") FOR THIS PERMIT SHALL NOT BE GRANTED
 UNTIL A CO HAS BEEN ISSUED FOR THE PARKING LOT ON THE
 ADJACENT PROPERTY (1117 13TH STREET).
  
 3. HANDICAP WALKWAY ACCESS TO THE PARKING LOT SHALL
 MATCH THE 5 FOOT ACCESS AISLE ON THE ADJACENT
 PROPERTY.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 5 Status P Date 2008-05-16 Cont ID  
Sent By adavila Date 2008-05-16 Time 10:37 Rev Time 0.00
Received By adavila Date 2008-05-15 Time 18:03 Sent To  
Notes
2008-05-16 10:37:21PROVISO APPLICANT SHALL OBTAIN A CERTIFICATE OF
 OCCUPANCY ("CO") FOR THE PARKING LOT ON THE ADJACENT
 PROPERTY (1117 13TH STREET) PRIOR TO OBTAINING A CO FOR
 THIS BUILDING PERMIT (PERMIT NO. 07011175).
  
 PROVISO HANDICAP WALKWAY ACCESS TO PARKING SHALL MATCH
 THE FIVE (5) FOOT ACCESS AISLE ON THE ADJACENT
 PROPERTY.
  
 PROVISE ROOF OVERHANG PROJECTION SHALL NOT EXTEND
 FARTHER THAN THREE (3) FEET INTO ANY SETBACK.
  
 PER ERIC SCHNEIDER, PRINCIPAL PLANNER.
2008-05-15 18:04:01IN ZONING FOR REVIEW.

Review Stop Z ZONING
Rev No 4 Status F Date 2008-02-05 Cont ID  
Sent By adavila Date 2008-02-05 Time 17:15 Rev Time 0.00
Received By adavila Date 2008-02-05 Time 16:38 Sent To  
Notes
2008-02-05 17:15:40PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. REPEAT COMMENT - PER SECTION 94-443(B) OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS, THE OWNER OF THE
 PROPERTY SHALL MAINTAIN A LANDSCAPE BUFFER STRIP ALONG
 THE ENTIRE EDGE OF THE PROPERTY ADJACENT TO A PUBLIC
 THOROUGHFARE AND OTHER NONRESIDENTIAL ZONING DISTRICTS.
 PER SECTION 94-443(B)(1), THE BUFFER STRIP SHALL BE AT
 LEAST 5 FEET IN WIDTH.
 A. LANDSCAPE PLANS, PREPARED, SIGNED AND SEALED BY A
 LANDSCAPE ARCHITECT, SHALL BE PROVIDED SHOWING
 COMPLIANCE WITH THIS REQUIREMENT.PLEASE REFER TO
 SECTION 94-443(B) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.
  
 2. ACCORDING TO THE FLOOR PLANS, THERE IS AN A/C UNIT
 ALONG THE EAST BUILDING FA?ADE; HOWEVER, THIS IS NOT
 SHOWN ON THE SITE PLAN.PLEASE SHOW THE LOCATION OF
 THE A/C UNIT, WITH SETBACK DIMENSIONS, ON THE SITE
 PLAN.PLEASE NOTE THAT PER SECTION 94-305(B)(4), A/C
 UNITS MAY ONLY ENCROACH UP TO FOUR FEET INTO A
 SETBACK.
  
 3. PER SECTION 94-444(B), PROVIDE HEDGES AROUND THE A/C
 UNIT TO SCREEN IT FROM ALL SIDES.
  
 4. PROVIDE THE WIDTH, DEPTH, RADIUS AND SQUARE FOOTAGE
 DIMENSIONS OF THE PROPOSED DRIVEWAY ON THE SOUTH SIDE
 OF THE PROPERTY.
  
 5. PROVIDE THE MATERIAL OF THE PROPOSED DRIVEWAY.
 STAFF RECOMMENDS THE USE OF UNSEALED PAVERS.
  
 6. PLEASE SHOW CONNECTION POINT AND ACCESS WAY FROM THE
 BUILDING STRUCTURE TO THE PARKING LOT WEST OF THE SITE.
 A NOTE STATING THAT PARKING SPACES, INCLUDING THE
 HANDICAP PARKING SPACE, FOR THE DAYCARE FACILITY ARE
 AVAILABLE OFF-SITE SHALL BE NOTED ON THE SITE PLAN.
  
 7. REPEAT COMMENT - PROVIDE A LETTER FROM THE
 ENGINEERING SERVICES DEPARTMENT STATING THERE IS NO
 NEED FOR A DUMPSTER.
  
 8. DEPTH DIMENSION OF THE DEPTH OF THE HOUSE SHOULD
 READ 42.1 FEET AND NOT 42.1 INCHES.IN ADDITION, EAST
 SETBACK DIMENSION AT THE REAR OF THE STRUCTURE SHOULD
 READ 7.99 FEET AND NOT 7.99 INCHES.
  
 9. PLEASE NOTE THAT REVISED/NEW PLANS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 3 Status F Date 2007-10-11 Cont ID  
Sent By eschneid Date 2007-10-11 Time 15:10 Rev Time 0.00
Received By ADAVILA Date 2007-10-11 Time 15:13 Sent To  
Notes
2007-10-11 15:12:39PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1.PROJECT DOES NOT COMPLY WITH ZONING AND LAND
 DEVELOPMENT REGULATIONS.A MEETING WITH THE PLANNING
 AND ZONING DEPARTMENT IS REQUIRED TO DISCUSS ZONING
 ISSUES.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-05-09 Cont ID  
Sent By adavila Date 2007-05-09 Time 15:51 Rev Time 0.00
Received By adavila Date 2007-05-08 Time 11:31 Sent To  
Notes
2007-05-09 15:51:56PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1) PLEASE PROVIDE RESPONSE TO COMMENTS IN WRITING.
  
 2) PER SECTION 94-485(J) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS, CONFIGURATIONS OF PARKING
 SPACES WHICH REQUIRE BACKING DIRECTLY ONTO A STREET
 SHALL BE PROHIBITED IN ALL NONRESIDENTIAL ZONING
 DISTRICTS.PROPOSED PARKING SPACES SHALL BE
 RECONFIGURED WHERE INGRESS AND EGRESS SHALL BE PROVIDED
 BY MEANS OF CLEARLY DEFINED DRIVES WHICH LEAD FROM
 PUBLIC RIGHTS-OF-WAY TO CLEARLY DEFINED MANEUVERING
 LANES WHICH IN TURN PROVIDE ACCESS TO INDIVIDUAL
 PARKING SPACES (REPEAT COMMENT).
  
 A) THE PROPOSED PARKING LAYOUT IS NOT PERMITTED AS IT
 WILL REQUIRE BACKING DIRECTLY ONTO A STREET.
  
 3) THE NEW ADDITION TO THE EXISTING STRUCTURE SHALL NOT
 BE PERMITTED AS THE PARKING SPACES FOR THE EXTRA SQUARE
 FOOTAGE CAN NOT BE PROVIDED (REPEAT COMMENT).
  
 A) PER SECTION 94-486 OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS, DAYCARE FACILITIES REQUIRE 1
 PARKING SPACE PER EMPLOYEE FOR SHIFT WITH MOST
 EMPLOYEES, 5 VISITOR SPACES, CIRCULATION/PICKUP AREA.
 THE PROPOSED ADDITION REQUIRES A MINIMUM OF 6 PARKING
 SPACES, ONE OF WHICH IS AN ACCESSIBLE PARKING SPACE.
  
 B) PER SECTION 94-485(N)(1)(A) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS, IF THE TOTAL PARKING
 REQUIREMENTS IS LESS THAN 20 SPACES, NO SMALL CAR
 SPACES ARE PERMITTED.THE SMALL CAR SPACES PROPOSED
 ARE NOT PERMITTED.
  
 4) PROVIDE PARKING AND HANDICAPPED PARKING STALL
 DETAILS MEETING SECTION 94-484 OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (REPEAT COMMENT).
  
 A) DETAILS PROVIDED DO NOT MEET PARKING STALL
 REQUIREMENTS PER ZONING REGULATIONS.PLEASE REFER TO
 THE ATTACHED DIAGRAM.
  
 5) DUMPSTER AND DUMPSTER ENCLOSURE SHALL BE PROVIDED,
 UNLESS A LETTER FROM THE ENGINEERING SERVICES
 DEPARTMENT STATING THERE IS NO NEED FOR A DUMPSTER IS
 PROVIDED.
  
 6) DEPTH DIMENSION OF THE HOUSE ALONG THE WEST
 PROPERTY LINE DOES NOT MATCH THE DEPTH DIMENSION ON THE
 SURVEY.SURVEY AND SITE PLAN SHALL REFLECT SAME AND
 ACTUAL CONDITIONS.
  
 7) PER SECTION 94-443(B) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS, THE OWNER OF PROPERTY USED FOR
 NONRESIDENTIAL PURPOSES SHALL INSTALL AND MAINTAIN A
 LANDSCAPED BUFFER STRIP ALONG THE ENTIRE EDGE OF THE
 PROPERTY ADJACENT TO A PUBLIC THOROUGHFARE AND OTHER
 NONRESIDENTIAL ZONING DISTRICTS.PER SECTION
 94-443(B)(1), THE BUFFER STRIP SHALL BE AT LEAST 5 FEET
 WIDE.
  
 A) A BUFFER SHALL BE PROVIDED FOR THE SOUTH END OF THE
 PROPERTY.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-02-12 Cont ID  
Sent By adavila Date 2007-02-12 Time 17:02 Rev Time 0.00
Received By adavila Date 2007-02-12 Time 13:29 Sent To  
Notes
2007-02-12 17:03:13PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1) PLEASE PROVIDE RESPONSE TO COMMENTS IN WRITING.
  
 2) PROVIDE A SURVEY OF THE PROPERTY.THE SURVEY SHALL
 BE LESS THAN A YEAR OLD.
  
 3) PER SECTION 94-485(J) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS, CONFIGURATIONS OF PARKING
 SPACES WHICH REQUIRE BACKING DIRECTLY ONTO A STREET
 SHALL BE PROHIBITED IN ALL NONRESIDENTIAL ZONING
 DISTRICTS.PROPOSED PARKING SPACES SHALL BE
 RECONFIGURED WHERE INGRESS AND EGRESS SHALL BE PROVIDED
 BY MEANS OF CLEARLY DEFINED DRIVES WHICH LEAD FROM
 PUBLIC RIGHTS-OF-WAY TO CLEARLY DEFINED MANEUVERING
 LANES WHICH IN TURN PROVIDE ACCESS TO INDIVIDUAL
 PARKING SPACES.
  
 4) THE NEW ADDITION TO THE EXISTING STRUCTURE SHALL NOT
 BE PERMITTED AS THE PARKING SPACES FOR THE EXTRA SQUARE
 FOOTAGE CAN NOT BE PROVIDED.
  
 5) PROVIDE PARKING AND HANDICAPPED PARKING STALL
 DETAILS MEETING SECTION 94-484 OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS.
  
 6) PROVIDE INFORMATION REGARDING HOW THE GARBAGE
 SERVICE WILL BE ADDRESSED.IF A DUMPSTER IS REQUIRED
 BY THE SANITATION DEPARTMENT, PROVIDE LOCATION AND
 DUMPSTER ENCLOSURE DETAILS MEETING ZONING REGULATIONS.
  
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved