Plan Review Details - Permit 07011159
Plan Review Stops For Permit 07011159
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-06-19 Cont ID  
Sent By mjacobs Date 2007-06-19 Time 07:41 Rev Time 0.00
Received By mjacobs Date 2007-06-18 Time 15:26 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-05-07 Cont ID  
Sent By mjacobs Date 2007-05-07 Time 07:44 Rev Time 0.00
Received By mjacobs Date 2007-05-04 Time 14:39 Sent To PC
Notes
2007-05-04 16:53:29BUILDING PLAN REVIEW
 PERMIT:07011159
 ADD: 4114 WAVERLY DR.
 CONT: DONALD GIBSON
 TEL: (561)848-5982
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)OK.
  
 3). OK, HOWEVER, ON THE PRODUCT APPROVAL, MARK WHICH
 DETAILS APPLY TO THIS JOB ON .PLEASE USE INK RATHER
 THAN A HIGHLIGHTER.
  
 4)THE DESIGNER OF RECORD HAS TO APPROVED THE PRODUCT
 APPROVALS IN WRITING.
 WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 5)SUBMIT AN ELEVATION FRAMING DETAIL OF THE
 NORTH/SOUTH/EAST AND WEST ELEVATIONS. SEEWPB
 AMENDMENTS 106.3.5.
  
 6)THE DOOR HEADDER DETAILS DO NOT CORRESPOND WITH THE
 DRAWINGS. THE ELEVATION FRAMING DETAILS ARE REQUIRED.
  
 7)R613.6.1.1UNLESS OTHERWISE TESTED,BUCKS SHALL
 EXTEND BEYOND THE INTERIOR FACE OF THE WINDOW OR DOOR
 FRAME SUCH THAT FULL SUPPORT OF THE FRAME IS PROVIDED.
  
 8)106.1.3 THE BUILDING OFFICIAL
 MAY SET STANDARDS THROUGH DEPARTMENTAL
 POLICY STANDARDS FOR PLANS AND SPRCIFICA
 TIONS. "NO WHITE OUT"."NO HAND WRITING" ON DRAWINGS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-05 Cont ID  
Sent By mjacobs Date 2007-03-05 Time 09:50 Rev Time 0.00
Received By mjacobs Date 2007-03-05 Time 05:49 Sent To PC
Notes
2007-03-05 09:50:10BUILDING PLAN REVIEW
 PERMIT:
 ADD:
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3)THE INFORMATION ON THE SHUTTER SCHEDULE DOES NOT
 MATCH THE ANY OF THE PRODUCT APPROVAL SUBMITTED. THE
 OPENING DIMENTIONS ON THE SCHEDULE DOES NOT CORRESPOND
 WITH THE DIMENTIONS ON THE DRAWINGS CLARITY.
  
 4)WPB AMENDMENTS 106.3.3.THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 PROVIDE THE FLORIDA STATE APPROVAL COVER PAGES FOR THE
 PRODUCT APPROVALS.
  
 5)SUBMIT AN ELEVATION FRAMING DETAIL OF THE NORTH /
 SOUTH / EAST AND WEST ELEVATIONS. SEE WPB. AMENDMENTS
 106.3.5
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-06-18 Cont ID  
Sent By btrobaug Date 2007-06-18 Time 13:35 Rev Time 0.00
Received By btrobaug Date 2007-06-18 Time 13:35 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-04-27 Cont ID  
Sent By btrobaug Date 2007-04-27 Time 14:36 Rev Time 0.33
Received By btrobaug Date 2007-04-27 Time 14:31 Sent To B
Notes
2007-04-27 14:36:12 
  
 NONCOMPLIANT
  
 PLEASE NOTE THAT HAND DRAWN CHANGES TO THE PLAN ARE NOT
 ACCEPTABLE AS THEY CANNOT BE VERIFIED AS BEING MADE BY
 THE DESIGNER OF RECORD AS REQUIRED BY FS 471 OR 481, AS
 APPLICABLE.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2007-02-12 Cont ID  
Sent By btrobaug Date 2007-02-12 Time 07:50 Rev Time 0.25
Received By btrobaug Date 2007-02-12 Time 07:23 Sent To B
Notes
2007-02-12 07:50:40 
  
 INCOMPLETE INFORMATION
  
 1} THE ENGINEER OF RECORD SHALL INDICATE THE
 CERTIFICATE OF AUTHORIZATIONNUMBER ALONG WITH OTHER
 INFORMATION REQUIRED BY 61G15-23.002FLORIDA
 ADMINISTRATIVE CODE. ALSO T HE SEAL ON THE PLANS IS NOT
 LEGIBLE.
  
 AN ELECTRICAL PERMIT IS REQUIRED FOR THE SCOPE OF WORK
 ON THE APPLICATION.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-06-06 Cont ID  
Sent By adarroug Date 2007-06-06 Time 16:36 Rev Time 0.00
Received By adarroug Date 2007-06-06 Time 16:36 Sent To E
Notes
2007-06-06 16:36:49TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-04-23 Cont ID  
Sent By adarroug Date 2007-04-23 Time 14:30 Rev Time 0.00
Received By adarroug Date 2007-04-23 Time 14:30 Sent To E
Notes
2007-04-23 14:30:49TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-08 Cont ID  
Sent By adarroug Date 2007-02-08 Time 12:49 Rev Time 0.00
Received By adarroug Date 2007-02-08 Time 12:49 Sent To E
Notes
2007-02-08 12:49:37TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-05-07 Time   Rev Time 0.00
Received By adarroug Date 2007-01-30 Time 17:59 Sent To  
Notes
2007-01-30 17:59:34TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status P Date 2007-02-03 Cont ID  
Sent By mmclean Date 2007-02-03 Time 11:46 Rev Time 0.00
Received By mmclean Date 2007-02-03 Time 11:45 Sent To I
Notes
***NONE***