Plan Review Details - Permit 07011148
Plan Review Stops For Permit 07011148
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-09-11 Cont ID  
Sent By jjohnsto Date 2007-09-11 Time 16:52 Rev Time 1.00
Received By jjohnsto Date 2007-09-11 Time 16:52 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-09-07 Cont ID  
Sent By jwitmer Date 2007-09-07 Time 12:50 Rev Time 1.22
Received By jwitmer Date 2007-09-07 Time 12:50 Sent To  
Notes
2007-09-07 12:52:09SPOKE WITH ARCHITECT GEORGE WHITE NEED A NEW A1 SHEET
 1) BUILDING TYPE : IA
 2 ) CURRENT ELEC CODE : 2005 NEC
  
 TO HOLD PLAN FOR NEW SHEET

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status N Date 2007-06-14 Cont ID  
Sent By lmartine Date 2007-06-14 Time 09:00 Rev Time 0.00
Received By lmartine Date 2007-06-14 Time 09:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-06-13 Cont ID  
Sent By kconrad Date 2007-06-13 Time 18:32 Rev Time 0.00
Received By kconrad Date 2007-06-12 Time 16:24 Sent To I
Notes
2007-06-13 17:11:01 
  
  
 PLANS EXAMINER: KEN CONRAD
 PROJECT: 250 SOUTH AUSTRALIAN/SUITE 300
 FL. BLDG. CODE: FLORIDA EXISTING BUILDING CODE/FLORIDA
 BUILDING CODE WITH 2006 REVISIONS
 PERMIT# 07011148
 PHONE: 561. 805.6666
  
 2ND REVIEW
 STATUS: DENIED
  
  
  
 COMMENTS:
  
 1) SHEET A-1, PROJECT INFORMATION INDICATES 2004 FBC.
 THE PROJECT INFORMATION SHOULDALSO INDICATE 2005/2006
 REVISIONS AND THE EXISTING BUILDING CODE WITH THE 2006
 REVISIONS AS PER THE WEST PALM BEACH ADMINISTRATIVE
 CODE, SECTION 110.1.2.
  
 2) ITEMS A THROUGH F HAVE NOT BEEN ADDRESSED FROM THE
 PREVIOUS PLAN REVIEW.
  
 3) PLEASE NOTE OCCUPANCY LOAD ON THE LIFE SAFETY PLAN.
  
 4) MISSING EXIT LIGHTS ON REVISED SHEETS A-5 AND A-10:
  
 1006.3.8
 WHERE THE DIRECTION OF TRAVEL TO REACH THE NEAREST EXIT
 IS NOT APPARENT, A DIRECTIONAL SIGN COMPLYING WITH
 SECTIONS 1006.3.5 OR 1006.3.6 READING ?EXIT,? OR A
 SIMILAR DESIGNATION WITH A DIRECTIONAL INDICATOR
 SHOWING THE DIRECTION OF TRAVEL SHALL BE PLACED IN
 EVERY LOCATION. DIRECTIONAL SIGNS SHALL BE LISTED.
  
 5) PLEASE INDICATE THE LEVEL OF ALTERATION WITHIN THE
 PROJECT INFORMATION LOCATED ON SHEET A-1 AS REQUIRED BY
 THE FEBC SECTION 301.5.
  
 6) REQUIRE APPLICABLE THROUGH PENETRATION FIRE-STOP
 ASSEMBLIES AT FIRE -RATED PARTITIONS:
  
 712.4.1.1 FIRE-RESISTANCE-RATED ASSEMBLIES.
 PENETRATIONS SHALL BE INSTALLED AS TESTED IN AN
 APPROVED FIRE-RESISTANCE-RATED ASSEMBLY.
  
 7) PROVIDE INTERIOR FLOOR FINISH DOCUMENTATION AS PER
 THE FOLLOWING SECTIONS:
  
 FEBC603.4INTERIOR FINISH.
 THE INTERIOR FINISH OF WALLS AND CEILINGS IN EXITS AND
 CORRIDORS IN ANY WORK AREA SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING.
 EXCEPTION: EXISTING INTERIOR FINISH MATERIALS THAT DO
 NOT COMPLY WITH THE INTERIOR FINISH REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING SHALL BE PERMITTED TO
 BE TREATED WITH AN APPROVED FIRE-RETARDANT COATING IN
 ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS TO
 ACHIEVE THE REQUIRED RATING.
  
 804.2 CLASSIFICATION.
 INTERIOR FLOOR FINISH AND FLOOR COVERING MATERIALS
 REQUIRED BY SECTION 804.5.1 TO BE OF CLASS I OR II
 MATERIALS SHALL BE CLASSIFIED IN ACCORDANCE WITH NFPA
 253. THE CLASSIFICATION REFERRED TO HEREIN
 CORRESPONDS TO THE CLASSIFICATIONS DETERMINED BY NFPA
 253 AS FOLLOWS: CLASS I, 0.45 WATTS/CM2 OR GREATER;
 CLASS II, 0.22 WATTS/CM2 OR GREATER.
  
 804.3 TESTING AND IDENTIFICATION.
 FLOOR COVERING MATERIALS SHALL BE TESTED BY AN APPROVED
 AGENCY IN ACCORDANCE WITH NFPA 253 AND IDENTIFIED BY A
 HANG TAG OR OTHER SUITABLE METHOD SO AS TO IDENTIFY THE
 MANUFACTURER OR SUPPLIER AND STYLE, AND SHALL INDICATE
 THE INTERIOR FLOOR FINISH OR FLOOR COVERING
 CLASSIFICATION ACCORDING TO SECTION 804.2. CARPET-TYPE
 FLOOR COVERINGS SHALL BE TESTED AS PROPOSED FOR USE,
 INCLUDING UNDERLAYMENT. TEST REPORTS CONFIRMING THE
 INFORMATION PROVIDED IN THE MANUFACTURER?S PRODUCT
 IDENTIFICATION SHALL BE FURNISHED TO THE BUILDING
 OFFICIAL UPON REQUEST.
  
 8)PROVIDE TACTILE SIGNAGE AT EXIT STAIR DOOR:
  
 1006.3.4 EXIT STAIR DOOR OR TACTILE
 SIGNAGE.
 TACTILE SIGNAGE STATING ?EXIT? AND COMPLYING WITH
 ICC/ANSI A117.1, AMERICAN NATIONAL STANDARD FOR
 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES, SHALL
 BE INSTALLED ADJACENT TO THE LATCH SIDE OF THE DOOR 60
 INCHES (1524 MM) ABOVE THE FINISHED FLOOR TO THE CENTER
 LINE OF THE SIGN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-07 Cont ID  
Sent By jwitmer Date 2007-03-07 Time 14:11 Rev Time 2.22
Received By jwitmer Date 2007-03-07 Time 14:11 Sent To PC
Notes
2007-03-07 14:31:06BUILDING PLAN REVIEW
 PERMIT: 07011148
 ADD: 250 S AUSTRALIAN AV 2ND& 3RD FLOOR
 CONT: ITASCA
 TEL: (561)241-4499
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS
 NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE
 OF COMMENCEMENT
 AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) DISCREPANCY? THE PERMIT APPLICATION INDICATES WORK
 ONLY IN SUITE# 200, NO WORK IS STATED FOR THE 3RD
 FLOOR? PLANS INDICATE WORK ALSO ON THE 3RD FLOOR, IS
 THIS PART OF THIS PERMIT, IF SO INCLUDE THIS WORK UNDER
 SCOPE OF WORK ON THE PERMIT APPLICATION.
  
 4A) SHEET A-1,PROJECT INFORMATION INDICATES 2004 FBC
 NO MENTION OF THE 2005/2006 REVISIONS.
 THERE IS NO MENTION OF THE 2004 EXISTING BUILDING CODE
 WITH 2006 REVISIONS.
 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601PLANS INDICATE TYPEI , AOR
 B?.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 5) PLEASE PROVIDE A LIFE SAFETY PLAN INCLUDE TRAVEL
 DISTANCES AND OCCUPANT LOADS, NOTE 3RD FLOOR TRAINING
 ROOM > 50 OCCUPANT LOAD REQUIRING 2 EXITS.
  
 6)SHEET A-8 & 9 BOTH SHEETS ARE MISSING EXIT LIGHTS.
 FBC 1006.1.2.
  
 7) SHEET A-11 DETAIL "F" DOOR AND SIDELITES PLEASE
 PROVIDE SIDELITES HAZARDOUS LOCATION TEMPERED GLASS.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-08-23 Cont ID  
Sent By dpalmer Date 2007-08-23 Time 11:28 Rev Time 0.00
Received By dpalmer Date 2007-08-22 Time 21:13 Sent To  
Notes
2007-08-23 11:29:02**** THE FP SHEETS ARE STILL MISSING REQUIRED LICENSE
 INFORMATION ON TITLE BLOCKS PER FAC 61G15-23.002 AND FS
 471.023.
 LOOK FOR COMMENTS FROM FIRE MARSHAL AND/OR BUILDING
 REVIEW. THIS INFORMATION IS FROWARDED TO THOSE TRADES.
2007-08-22 21:13:192007-08-22 21:13:19
 IN ELEC FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-05-07 Cont ID  
Sent By dpalmer Date 2007-05-07 Time 13:24 Rev Time 0.00
Received By dpalmer Date 2007-05-07 Time 08:40 Sent To  
Notes
2007-05-07 13:24:20** UNSAT 2ND REVIEW**
  
 ***** IMPORTANT *****
 ** PLEASE SEE THERE ARE SEVERAL ITEMS FROM THE PREVIOUS
 REVIEW WHICH ARE STILL IN NEED OF ADDRESSING.
 ** PLEASE ALSO SEE THAT THERE ARE SEVERAL NEW COMMENTS
 BASED ON THE RESPONSES AND THE REVISED PLANS. MANY
 ITEMS WERE SUBSTANTIALLY REVISED INCLUDING THE SCOPE OF
 WORK PER FLOOR UNDER SEPARATE PERMITS.
  
 ** PLEASE SEE THAT ANY REFERENCES TO THE FBC CHAPTER 1
 ARE FROM THE ADMINISTRATIVE CODE ADOPTED BY THE CITY OF
 WEST PALM BEACH.
  
  
 MANY COMMENTS ARE FROM THE FIRST REVIEW.
  
 1) NOTE:THIS IS THE SAME COMMENT AS PREVIOUS REVIEW.
 PLEASE SEE THE ARCHITECTURAL PLANS STILL INDICATE THE
 PREVIOUS CODES. PLEASE LIST THE FOLLOWING AS REQUESTED
 ON PREVIOUS REVIEW. PLEASE SEE ONLY THE CORRECTED CODES
 WERE ADDED TO THE ELECTRICAL SHEETS AND NOT TO A
 SHEETS.
 PLEASE SEE THE CODES SHALL BE STATED ON THE PLANS. ALL
 APPLICATIONS AFTER DECEMBER 8TH, 2006 ARE UNDER THE
 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70.
 PLEASE ALSO SEE THAT THE FOLLOWING SHALL ALSO BE
 STATED. 2003 NFPA-101 AND THE 2002 NFPA-72. **PLANS
 STATE LATEST EDITION.
 FBC 106.1.2, 106.3.5.1.2
  
 2) NOTE: PLEASE INDICATE THE SUITE/UNIT NUMBER(S) ON
 PLANS.
 SAME NOTE AS PREVIOUS REVIEW. ONLY THE ELECTRICAL
 SHEETS WERE CORRECTED TO INDICATE THE SUITE/UNIT
 NUMBER. PLEASE SEE THIS COMMENT IS FOR ALL TRADES AND
 FOR ALL SHEETS WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADES.
 ** PLEASE KNOW THAT ANY SHEETS WHICH ARE NOT REQUIRED
 TO BE CORRECTED FOR ANY TRADE/CODE RELATED COMMENT MAY
 HAVE THE SUITE/UNIT NUMBER WRITTEN/PRINTED OR STAMPED
 ON TITLE BLOCKS.
 FBC 106.1.2,
 FAC 61G1-16.004
  
 3) NOTE: PLEASE SEE THE MISSING PRINTED LICENSE NUMBER
 FOR THE ARCHITECT ON THE TITLE BLOCKS. 61G1-16.004.
 THIS COMMENT WAS MADE ON THE PREVIOUS REVIEW AND THE
 RESPONSE MENTIONS THAT PERHAPS THIS WAS MISSED AS IT IS
 LISTED ON THE UPPER RIGHT HAND CORNER OF THE
 PLANS/TITLE BLOCKS.
 PLEASE SEE THE TITLE BLOCKS INDICATE THE PRINTED *FIRM*
 CERTIFICATE OF AUTHORIZATION NUMBER WHICH IS OK AND
 REQUIRED BUT DOES NOT INDICATE THE PRINTED LICENSE
 NUMBER OF THE ARCHITECT AS REQUIRED PER SECTION STATED
 PREVIOUSLY. NONE OF THE SHEETS CONTAIN THIS ?PRINTED
 LICENSE NUMBER? OF THE ARCHITECT.
 THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES.
 PLEASE REVISE AND ADDRESS ACCORDINGLY. ** ONE SHEETS
 WHICH DO NOT NEED TO BE REVISED BY OTHER TRADES FOR
 CODE COMPLIANCE, THIS MAY BE PRINTED/STAMPED ON
 SHEETS.
  
 4) NOTE: PLEASE SUBMIT COMPLETE ENERGY CALCULATIONS AND
 PERFORMANCE DENSITIES PER 13-415.1.AB.1, 13-415.2.
 NO CALCULATIONS COULD BE LOCATED.
 ONLY THE LIGHTING PERFORMANCE FOR LIGHTING WAS LOCATED
 ON PLANS. PLEASE VERIFY THE NUMBER OF FIXTURES, THE
 WATTAGES, AND SQ FT FOR LPD.
 THE TOTAL WATTAGE WHICH WAS DERIVED USING THE NUMBER OF
 FIXTURES ON PLANS AND THE WATTAGE FOR EACH AS LISTED ON
 FIXTURE LEGEND SEEMS TO BE SLIGHTLY DIFFERENT THAN THAT
 SHOWN ON LIGHTING PLANS.
  
 5) NOTE:PLEASE SEE THIS NOTE AS LISTED IS THE SAME AS
 PREVIOUS REVIEW. IN FACT ONE OF THE SAME ELECTRICAL
 SHEETS SUBMITTED ON PREVIOUS PLANS WAS NOW SUBMITTED AS
 E3.3 WHICH IS MISSING MUCH OF THE INFORMATION WHICH WAS
 SHOWN ON PREVIOUS PLANS ON SHEET E3?
 PLEASE SEE NO SCHEDULING, OVER RIDE TIMES, SYSTEM,
 CONTROL PANEL LOCATION, CIRCUITS, ZONES, ETC IS SHOWN.
 PLEASE SEE RESPONSE MENTIONS 1HR OVER RIDES, HOWEVER ON
 AN OCCUPANCY SENSOR TYPE DEVICES, THE MAXIMUM OVER RIDE
 TIME IS 30MINS.
 PLEASE REVISE PLANS, PROVIDE COMPLETE DETAILS FOR
 CHAPTER 13 CODE COMPLIANCE.
 ** PLEASE SEE THERE ARE NOTES ON LIGHTING SHEETS WHICH
 REFLECT TO A NOTE #4, THIS NOTE #4 MENTIONS TO SEE
 DETAILS ON SHEET E-4,HOWEVER NO SHEET E4 IS IN SETS
 PR SUBMITTED?
 PLEASE ALSO SEE THAT RESPONSE LETTER MENTIONS TO SEE
 SHEET E-5.2, AND YET NO SHEET 5.2 WAS SUBMITTED IN THE
 SETS SUBMITTED FOR REVIEW?
 DEVICES ON LEGEND NEED TO COORDINATE WITH DETAIL FOR
 ALL DEVICES, TIMES, TYPES ETC. THE LEGEND DOES NOT
 INDICATE ANY SENTRY DEVICE AS NOTED ON PLANS.
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT COMPLETE SCHEDULING FOR THE TIMES IN USE
 FOR THE LIGHTING CONTROL SYSTEM. PLEASE SEE THE SECTION
 OF THE CODE OF CHAPTER 13 QUOTED AS 413 SHOULD BE 415.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 AS THERE IS
 MISSING CONTROLS FOR SEPARATE SPACES.
 PLEASE BE SURE TO INDICATE ALL OF THESE DEVICES AND
 CORRELATE WITH THE SYMBOL LEGEND. PLEASE INDICATE THE
 MAXIMUM AMOUNT OF TIME FOR OVER RIDE(S).
 (PLEASE SEE SOME DEVICES ON PLANS AND THE DESIGNATIONS
 ON PLAN SYMBOL LEGEND DO NOT SEEM TO INDICATE DEVICES
 FOR COMPLIANCE WITH CHAPTER 13.
  
  
 6) NOTE:IT ROOM REQUIREMENTS SEEMS TO HAVE BEEN
 ADDRESSED, HOWEVER QUESTION HAS NOW RISEN OVER SCOPE OF
 WORK AND WHICH PERMIT THIS WORK WILL BE UNDER. PLEASE
 SEE THE ELECTRICAL RISER NOW SHOWS, NOTES AND INDICATES
 THIS SCOPE OF WORK IS NOT INCLUDED FOR THIRD FLOOR AND
 IS UNDER 2ND FLOOR SCOPE?? PLEASE SEE THE PERMIT
 APPLICATION AND PLANS FOR THE SECOND FLOOR ALSO STATE
 THE SAME THING?
 PLEASE BE SURE TO COORDINATE ALL SCOPES OF WORK, UNDER
 WHICH PERMIT AND REVISE PLANS AS NEEDED. HOW WILL THE
 3RD FLOOR WHICH IS UNDER A SEPARATE PERMIT FROM THE 2ND
 FLOOR OBTAIN A FINAL/CERTIFICATE OF COMPLETE ION OR
 OCCUPANCY WHEN THE SCOPE FOR THAT FLOOR HAS NOT BEEN
 DONE YET?
 PLEASE SUBMIT THE SPECS/PLANS AND DOCUMENTS UNDER THE
 PERMIT BEING APPLIED FOR.
 FBC 106.1.2, 106.3.5.1.2ADMIN SECTION.
  
 7) NOTE: ** THIS COMMENT IS NOT FOR MEP FIRM:
 PLEASE SEE FIRE REVIEW COMMENTS AS THE FP SHEETS IN NEW
 SETS ARE OF NEW DESIGNER AND NOTE THAT SUBMITTED FROM
 PREVIOUS REVIEWED PLANS.
 PLEASE SEE THE FOLLOWING ITEMS ARE REQUIRED WHETHER OR
 NOT COMMENT IS MADE BY THE FIRE REVIEWER.
 PLEASE SEE NEW REVISED SHEET FP-2 IS THE ONLY SHEET IN
 SETS.
 ** PLEASE SEE THE SEAL WHICH IS NOW BEING USED ON THE
 REVISED FP-2 SHEETS IS NO LONGER VALID WITH THE FLORIDA
 BOARD OF PROFESSIONAL ENGINEERS. PLEASE SEE RULING FAC
 61G15-23.001 WHICH CHANGED IN FEB *04* REQUIRING ALL
 SEALS FOR ENGINEERS TO CHANGE AND USE THE WORDING OF
 *LICENSE* IN SAID SEAL AND COULD NOT LONGER USE THE
 WORDING OF *CERTIFICATE*. AN EXTENSION WAS GRANTED BY
 THE BOARD TO THE DATE OF 12/31/05 HOWEVER ALL SEALING
 OF DOCUMENTS AFTER THAT DATE MUST BE DONE USING NEW
 SEAL.
 PLEASE OBTAIN CORRECTED SEAL FROM THE STATE/BOARD.
 **PLEASE ALSO SEE MISSING TITLE BLOCK INFORMATION
 REQUIRED FOR THE ENGINEER OF RECORD FOR THE FP SHEETS.
 PLEASE KNOW IF THE ENGINEER OF RECORD IS EMPLOYED BY
 THE FIRE PROTECTION COMPANY ( PHILLIPS FIRE SPRINKLERS
 INC) WHICH IS OFFERING ENGINEERING SERVICES, THEN SAID
 COMPANY SHALL OBTAIN AN ENGINEERING BUSINESS LICENSE
 NUMBER AS REQUIRED UNDER FLORIDA STATUTES 471.023 AND
 SHALL INCLUDE THIS INFORMATION ON TITLE BLOCKS AS
 REQUIRED PER FAC 61G15-23.002
 PLEASE KNOW THAT IF THE ENGINEER IS PRACTICING AS AN
 INDIVIDUAL AND NOT EMPLOYED BY THE SAID COMPANY THEN
 THE SHEETS ARE REQUIRED TO CONTAIN INFORMATION FOR THE
 INDIVIDUAL TITLE BLOCK AS REQUIRED UNDER THE SAME
 SECTION OF THE FLORIDA ADMINISTRATIVE CODE.
 ** THIS HAS BEEN CONFIRMED WITH THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS AND THE BOARDS LEGAL COUNSEL.
 IF THERE ARE ANY QUESTIONS ON THIS PLEASE CONTACT THE
 BOARD AS NOTED.
  
 8) NOTE: PLEASE SEE THE ELECTRICAL RISER DIAGRAM HAS
 NOW BEEN COMPLETELY REVISED IN WHICH THERE ARE SEVERAL
 NEW COMMENTS AS WELL AS SOME ITEMS FROM PREVIOUS REVIEW
 WHICH ARE IN NEED OF ADDRESSING.
 PLEASE SEE THE RISER NOW INDICATES 277/480V SERVICE
 BEING INSTALLED FROM A NEW 1MA AND THE RISER STILL
 INDICATES THE BUS-DUCT RISER AS 277/480V? PLEASE SEE
 THE RISER FOR DISCONNECT WHICH IS NOTED #14 WHICH
 INDICATES THIS DISCONNECT AS 120/208V?
 PLEASE SEE RISER, THIS SHOWS A DISCONNECT FOR THE
 ASSUMED 277/480 OR 120/208 ON THE FORTH FLOOR WHICH IS
 FOR THE THIRD FLOOR AND THE DISCONNECT WHICH IS ON THE
 THIRD FLOOR WHICH FEEDS THE SECOND FLOOR? AS THE
 VOLTAGES CONFLICT, IT APPEARS THERE ARE TWO COMPLETELY
 SEPARATE 277/480VOLT SERVICES BEING FED FROM TWO
 SEPARATE MAINS??
 PLEASE SEE THIS SAME DISCONNECT #14 INDICATES A NEUTRAL
 ON THE LINE SIDE OF THE TRANSFORMER? IF THIS IS
 SUPPOSED TO BE A SEPARATELY DERIVED SYSTEM, THEN A
 NEUTRAL CONDUCTOR WOULD NOT BE INSTALLED TO THE
 TRANSFORMER FROM THIS DISCONNECT NOTED AS #14. SEE NOTE
 #15 FOR CONDUCTORS.
 THE RISER IS NOT CLEAR FOR VOLTAGES, SERVICES, CROSSING
 OVER OF SYSTEMS, WHAT IS OR IS NOT SEPARATELY DERIVED
 ETC. THESE ITEMS CAN NOT BE ASSUMED.
 PLEASE CLARIFY PANELS 3LA AND 3LB AS BOTH ARE SHOWN AS
 100AMP MCB, HOWEVER THIS IS BEING NOTED AND SHOWN ON
 RISER THAT EACH PANEL CONTAINS THIS AS PART OF THE
 EQUIPMENT, YET PANEL 3LB ALSO INDICATES THE PANEL
 CONTAINING A BACK FED BREAKER? IF THIS IS THE CASE,
 PLEASE NOTE REJECTION CLIP REQUIRED. 408.36F
 PLEASE SEE NEC 2005.
 FBC 106.3.5.1.2, 106.1.2.
  
 9) NOTE: PLEASE SEE THE NEW 1MA WHICH IS NOW SHOWN AS A
 500AMP MCB/MAIN CIRCUIT BREAKER PANEL WHICH CONTAINS AS
 BUS RATED AT 225AMPS.
 PLEASE EXPLAIN HOW THIS IS POSSIBLE.
 PLEASE SEE THE LOAD CALCULATIONS FOR THIS SAME PANEL
 INDICATES THE LOAD AT 297AMPS, AND THE BUS/SERVICE
 BEING RATED FOR 225AMPS.
 (ALSO LABELED AS 3MA)??
 THIS RISER IS STILL UNCLEAR FOR VOLTAGES AND
 INSTALLATION OF THE EQUIPMENT.
 PLEASE SEE THE 2005 NEC. PANELS AND EQUIPMENT MUST BE
 RATED FOR THE LOADS, ETC.
 FBC 106.3.5.1.2, 106.1.2
 ** PLEASE KNOW THAT AT THIS TIME THE RISER IS VERY
 CONFUSING AS THERE ARE MANY ITEMS THAT DO NOT CORRELATE
 OR ARE MISSING AT THIS TIME.
  
 10) NOTE: PLEASE SEE 3LD IS ALSO LABELED AS 3LB?
 PLEASE COORDINATE.
 FBC 106.1.2
  
 11) NOTE: PLEASE INDICATE ANY GROUNDING ATTACHMENTS AND
 SIZES FOR SD SYSTEMS PER 250.20, 250.30, 250.66, AND
 250.50
 THIS WAS NOTED ON PREVIOUS REVIEW. INDICATE THE
 ATTACHMENT LOCATIONS.
  
 12) NOTE: PLEASE SUBMIT AND SHOW LOAD CALCULATIONS ON
 ALL EXISTING WITH NEW LOADS BEING ADDED.
 THIS IS NOT ONLY FOR THE PANELS SHOWN, BUT FOR ALL
 EQUIPMENT WHICH LOADS, PANELS ETC ARE BEING ADDED.
 PLEASE SEE NOTE # 9 ABOVE WITH RESPECT TO 1MA.
 PLEASE SEE 220.10, 220.12, 220.14, 220.42, ETC,
 CONTINUOUS LOADS AT 125% PER 215.3, 230.42 ETC.
  
 13) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS
 ONLY NOTED AT THIS TIME.
 ** ONE SET OF EACH OF THE SETS OF PLANS SUBMITTED WILL
 BE RETAINED BY THIS OFFICE.
  
 ** PLEASE KNOW AT THIS TIME DUE TO SOME INFORMATION NOT
 YET AVAILABLE FOR REVIEW, THERE MAY BE NEW COMMENTS ON
 THE NEXT REVIEW WHICH HAVE NOT YET BEEN MADE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-02-09 Cont ID  
Sent By dpalmer Date 2007-02-09 Time 16:03 Rev Time 0.00
Received By dpalmer Date 2007-02-08 Time 14:09 Sent To  
Notes
2007-02-09 16:04:01***** UNSAT *****
  
  
 1) NOTE: PLEASE SEE THE CODES SHALL BE STATED ON THE
 PLANS. ALL APPLICATIONS AFTER DECEMBER 8TH, 2006 ARE
 UNDER THE 2006 REVISIONS TO THE 2004 FBC AND THE 2005
 NFPA-70.
 PLEASE ALSO SEE THAT THE FOLLOWING SHALL ALSO BE
 STATED. 2003 NFPA-101 AND THE 2002 NFPA-72. **PLANS
 STATE LATEST EDITION.
 FBC 106.1.2, 106.3.5.1.2
  
 2) NOTE: PLEASE INDICATE THE SUITE/UNIT NUMBER(S) ON
 PLANS.
 FBC 106.1.2,
 FAC 61G1-16.004
  
 3) NOTE: PLEASE SEE THE MISSING PRINTED LICENSE NUMBER
 FOR THE ARCHITECT ON THE TITLE BLOCKS. 61G1-16.004.
 REQUIRED WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADES.
  
 4) NOTE: PLEASE PLACE ALL ROOM AND AREA DESIGNATIONS ON
 PLANS AND CORRELATE WITH THE PANEL SCHEDULES. PLEASE
 COMPLETE ALL CIRCUITING ON PLANS AND CORRELATE WITH THE
 PANEL SCHEDULE(S) AND LIGHTING CONTROLS. PLEASE SEE
 SOME CIRCUITS WHICH ARE NOT INDICATED, PLEASE SEE SOME
 ROOMS WHICH ARE NOT DEFINED, PLEASE SEE PANEL SCHEDULES
 WHICH INDICATE MANY AS GEN LTS AND GEN RECEPTS.
 PLEASE SEE THE FOLLOWING TEXT FROM THE CODE. *SECTION
 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE THAT THE
 IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANELBOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 310.16, 240.4, 408.4, ETC
 FBC ADMIN SECTION 106.1.2
  
 5) NOTE: PLEASE SUBMIT COMPLETE ENERGY CALCULATIONS AND
 PERFORMANCE DENSITIES PER 13-415.1.AB.1, 13-415.2.
  
 6) NOTE: PLEASE SUBMIT COMPLETE SCHEDULING FOR THE
 TIMES IN USE FOR THE LIGHTING CONTROL SYSTEM. PLEASE
 SEE THE SECTION OF THE CODE OF CHAPTER 13 QUOTED AS 413
 SHOULD BE 415.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 AS THERE IS
 MISSING CONTROLS FOR SEPARATE SPACES.
 PLEASE BE SURE TO INDICATE ALL OF THESE DEVICES AND
 CORRELATE WITH THE SYMBOL LEGEND. PLEASE INDICATE THE
 MAXIMUM AMOUNT OF TIME FOR OVER RIDE(S).
 (PLEASE SEE SOME DEVICES ON PLANS AND THE DESIGNATIONS
 ON PLAN SYMBOL LEGEND DO NOT SEEM TO INDICATE DEVICES
 FOR COMPLIANCE WITH CHAPTER 13.
  
 7) NOTE: PLEASE INDICATE ALL MINIMUM LEVELS FOR STROBES
 AND HORNS OR COMBO DEVICES.
 PLEASE SEE FBC 200411-4.28.1, .2 AND .3(4).
  
 8) NOTE: PLEASE KNOW THAT ANY SECURITY CAMERAS/ITEMS
 SHALL BE UNDER A SEPARATE PERMIT AND PLANS.
 PLEASE KNOW THAT ALL CONTROL DEVICES FOR ANY ACCESS
 CONTROL SYSTEMS SHALL NOT IMPEDE EGRESS IN ANYWAY UNDER
 NORMAL POWER CONDITIONS OR UNDER EMERGENCY POWER.
 NFPA-101 CHAPTER 7
  
 9) NOTE: PLEASE SEE ROOM ON 3RD FLOOR SEEMS TO BE AN IT
 ROOM AND PLANS NEED TO MEET NFPA-75 AND NEC/NFPA-70 645
 FOR REQUIRED MEANS OF DISCONNECTS ETC.
 PLEASE SEE 645.10, 645.11 ETC.
 PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR THE
 UPS SYSTEMS BEING INSTALLED.
 PLEASE BE SURE THESE SHEETS CONTAIN THE LISTING
 INFORMATION FROM A NRTL.
 110.3,
 FBC 106.1.2 ADMIN SECTION.
  
 10) NOTE: PLEASE SHOW ALL PANELS AND SERVICE EQUIPMENT
 ON PLANS.
 PLEASE SHOW THE LOCATIONS OF TRANSFORMERS , DISCONNECTS
 AND PANELS.
 110.26, 240.24, 408.7, 450 ETC
 FBC 106.1.2, 106.3.5.1.2
  
 11) NOTE: PLEASE SEE 450.3 FOR THE MAXIMUM OVER CURRENT
 PROTECTION FOR THE TRANSFORMER(S).
 PLEASE SEE MAXIMUM OCP OF 125% UNLESS MEETING EXCEPTION
 AND NOTE #3.
  
 12) NOTE: PLEASE COMPLETE RISER SHOWING ALL FEEDS FROM
 BUS-DUCT ETC.
 PLEASE SEE THAT AT THIS TIME THERE ARE SEVERAL ITEMS
 WHICH CAN NOT BE VERIFIED.
 PLEASE SEE #LC, PLEASE SEE TRANSFORMER LABELING, PLEASE
 SEE MISSING FEEDERS ON RISER, PLEASE SEE PLANS APPEAR
 TO SHOW MULTIPLE TAPS FROM ONE TRANSFORMER AND ONLY ONE
 OCP AT HV PANEL?
 PLEASE CORRELATE RISER CONDUCTORS AS NOTED WITH THE
 PANEL SCHEDULES. (3MA TO UPS TRANSFORMER), NOTES #10,
 PANEL SCHEDULE #12 WITH 20A OCP.
 PLEASE SEE EXISTING PANELS WHICH ON ONE SHEETS MENTIONS
 MCB AS REQUIRED PER CODE, YET PANEL SCHEDULE SHOWS
 MLO.
 PLEASE SEE 240.21C, 310.16, 240.4ETC
 ** PLEASE KNOW THAT AT THIS TIME THE RISER IS VERY
 CONFUSING AS THERE ARE MANY ITEMS THAT DO NOT CORRELATE
 OR ARE MISSING AT THIS TIME.
  
 13) NOTE: PLEASE INDICATE ANY GROUNDING ATTACHMENTS AND
 SIZES FOR SD SYSTEMS PER 250.20, 250.30, 250.66, AND
 250.50
  
 14) NOTE: PLEASE SUBMIT AND SHOW LOAD CALCULATIONS ON
 ALL EXISTING WITH NEW LOADS BEING ADDED. PLEASE SEE
 220.10,220.12, 220.14, 220.42, ETC, CONTINUOUS LOADS AT
 125% PER 215.3, 230.42 ETC.
  
 ** PLEASE KNOW AT THIS TIME DUE TO SOME INFORMATION NOT
 YET AVAILABLE FOR REVIEW, THERE MAY BE NEW COMMENTS ON
 THE NEXT REVIEW WHICH HAVE NOT YET BEEN MADE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-09-04 Cont ID  
Sent By mawillia Date 2007-09-04 Time 12:33 Rev Time 0.00
Received By mawillia Date 2007-09-04 Time 12:05 Sent To  
Notes
2007-09-04 12:30:59*****APPROVED*****
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;PLAN SHEETS A-10, E2.3, AND FP-2 WERE
 STAMPED, INITIALED, AND DATED.
  
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-05-08 Cont ID  
Sent By mawillia Date 2007-05-08 Time 11:54 Rev Time 0.00
Received By mawillia Date 2007-05-08 Time 11:05 Sent To  
Notes
2007-05-08 11:53:58*****UNSAT*****
  
 PLEASE BE ADVISED THAT THE COMMENTS FROM THE PREVIOUS
 FIRE PLAN REVIEW HAVE BEEN SATISFIED, HOWEVER THE
 FOLLOWING NEW COMMENT NEEDS TO BE ADDRESSED:
  
 1.THE DRAWING INDEX ON SHEET A-2 INDICATES THAT THERE
 ARE TWO (2) FIRE PROTECTION DRAWINGS FP-1.3 & FP-2.3,
 BUT ONLY ONE SHEET (FP-2) IS INCLUDED IN ONE PLAN SET
 AND NO FP SHEETS IN THE OTHER PLAN SET THAT WAS
 RESUBMITTED.PLEASE SEE ELECTRICAL PLAN REVIEW NOTE #7
 FOR OTHER DISCREPANCIES WITH THE FIRE PROTECTION
 SHEET(S).
  
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE (ON THE PLANS) EACH COMMENT
 WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-03-06 Cont ID  
Sent By mawillia Date 2007-03-06 Time 11:54 Rev Time 0.00
Received By mawillia Date 2007-03-06 Time 10:09 Sent To  
Notes
2007-03-06 11:54:00*****DENIED*****
  
  
 1.ON SHEET A-1 UNDER PROJECT INFORMATION NOTE 1, LIFE
 SAFETY SHALL COMPLY WITH NFPA 101 2003 EDITION.
  
 2.ON SHEET A-1 UNDER APPLICABLE CODES, THE FLORIDA
 FIRE PREVENTION CODE 2004 EDITION SHALL BE REFERENCED.
  
 3.ON SHEET A-2 AND A-3, ADD " STRUCTURES UNDERGOING
 CONSTRUCTION, ALTERATION, OR DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241".
  
 4.ON SHEET A-6 AND A-7 NOTE 13, MAKE REFERENCE TO
 NFPA 241 NOT 2.4.1.
  
 5.SPECIFY WHAT THE INTERIOR WALL AND CEILING FINISH
 MATERIALS (IN COMPLIANCE WITH NFPA 101 - 39.3.3.2 ) ARE
 TO BE.AMEND SHEET A-6 AND A-7 UNDER FINISH NOTE (A)
 AND SHEET A-10 NOTE UNDER ROOM FINISH SCHEDULE.
  
 6.ON SHEET A-10A UNDER DOOR SCHEDULE, DOORS SHALL
 COMPLY WITH NFPA 101, 7.2.1 AND 7.2.1.5NOT 5-2.1.5
  
 7.DOORS WHICH LEAD DIRECTLY LEADING TO AN EXIT ACCESS
 CORRIDOR SHALL BE FIRE-RATED AND COMPLY WITH NFPA 80.
  
 8.PROVIDE A LIFE SAFETY PLAN SHEET FOR THE THE SECOND
 FLOOR AND THE THIRD FLOOR SHOWING THE TRAVELING
 DISTANCE TO THE EXIT(S).THE LOCATION OF THE EXIT
 LIGHTS, EMERGENCY LIGHTS, AND FIRE EXTINGUISHERS
 (SATISFYING THE 75' TRAVEL DISTANCE REQUIREMENT) MAY BE
 INCLUDED.
  
 9.SEPARATE PLANS AND PERMITS WILL BE REQUIRED FOR THE
 FIRE ALARM AND/OR FIRE SPRINKLER SYSTEM
 MODIFICATIONS/REMODEL.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE (ON THE PLANS) EACH COMMENT
 WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-11-06 Cont ID  
Sent By adarroug Date 2007-11-06 Time 08:32 Rev Time 0.00
Received By adarroug Date 2007-11-06 Time 08:32 Sent To M
Notes
2007-11-06 08:32:32TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-10-22 Cont ID  
Sent By adarroug Date 2007-10-22 Time 11:23 Rev Time 0.00
Received By adarroug Date 2007-10-22 Time 11:23 Sent To M
Notes
2007-10-22 11:23:33TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-02 Cont ID  
Sent By adarroug Date 2007-08-02 Time 13:47 Rev Time 0.00
Received By adarroug Date 2007-08-02 Time 13:47 Sent To  
Notes
2007-08-21 11:03:52TO "COMM" BD#61
2007-08-02 13:48:12WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-24 Cont ID  
Sent By adarroug Date 2007-04-24 Time 10:21 Rev Time 0.00
Received By adarroug Date 2007-04-24 Time 10:21 Sent To  
Notes
2007-05-03 08:21:36TO "COMM" BD#17
2007-04-24 10:21:57WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-07 Cont ID  
Sent By jwitmer Date 2007-03-07 Time 14:11 Rev Time 0.00
Received By jwitmer Date 2007-01-29 Time 18:47 Sent To  
Notes
2007-02-07 08:53:15TO "COMM" BD#36
2007-01-29 18:47:46WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-11-08 Cont ID  
Sent By tgordon Date 2007-11-08 Time 13:54 Rev Time 0.25
Received By tgordon Date 2007-11-08 Time 13:54 Sent To  
Notes
2007-11-08 13:55:14MECH. REVISION TO PLANS PAGE M-2.3.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-10-23 Cont ID  
Sent By tgordon Date 2007-10-23 Time 16:24 Rev Time 0.40
Received By tgordon Date 2007-10-23 Time 16:24 Sent To  
Notes
2007-10-23 16:25:43REVISION TO MECH. PLAN PAGE M-1.3.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-08-17 Cont ID  
Sent By tgordon Date 2007-08-17 Time 14:00 Rev Time 0.25
Received By tgordon Date 2007-08-17 Time 14:00 Sent To  
Notes
2007-08-20 15:47:54RETURNED TO INCOMING WAITING TO GET ON COMM. BOARD.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-05-07 Cont ID  
Sent By tgordon Date 2007-05-07 Time 14:19 Rev Time 0.30
Received By tgordon Date 2007-05-07 Time 14:19 Sent To  
Notes
2007-05-07 14:26:23*** DENIED ***
 1) MECHANICAL PLANS DO NOT SHOW THE DUCT (FLEX) SIZES,
 OR A DETAIL SHOWING CFM'S TO DUCT (FLEX) SIZES, PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-02-23 Cont ID  
Sent By tgordon Date 2007-02-23 Time 10:56 Rev Time 0.45
Received By tgordon Date 2007-02-23 Time 10:56 Sent To  
Notes
2007-02-23 11:08:47*** DENIED ***
 1) SEE PLANS PAGES M-1, M-2, AND M-3, YELLOW
 HIGH-LIGHTED WALLS ARE ONE HOUR FIRE RATED WALLS AND
 A/C DUCT WORK PENETRATING THEM WILL NEED FIRE DAMPERS
 AND COMPLY WITH 2004 FBC/M 607, PLEASE CORRECT.
  
 2) PLEASE SHOW ON MECHANICAL PLANS HOW THE RETURN AIR
 IS TO PASS THROUGH THE FIRE RATED WALLS, AND COMPLY
 WITH 2004 FBC/M 607.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-09-06 Cont ID  
Sent By kstevens Date 2007-09-06 Time 18:51 Rev Time 0.00
Received By kstevens Date 2007-09-06 Time 18:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-06-05 Cont ID  
Sent By kstevens Date 2007-06-05 Time 12:11 Rev Time 0.00
Received By kstevens Date 2007-06-05 Time 12:11 Sent To  
Notes
2007-06-05 12:19:15DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1.OK
  
 2. FBC-2004 PLUMBING SHALL BE INDICATED WITH OTHER
 APPLICABLE CODES ON SHT A-1.
 ****NO RESPONSE, NOT ADDRESSED
  
 3. ALL SHEETS. THE ADDRESS FOR THE ARCHITECTURAL
 BUSINESS SHOWN ON THE TITLE BLOCK DOES NOT REFLECT THE
 ADDRESS OF RECORD ON THE DBPR WEBSITE. PLEASE UPDATE
 THE DBPR WEBSITE OR SHOW THE CORRECT ADDRESS IN THE
 TITLE BLOCK.--THE TITLE BLOCK MUST SHOW THE
 BUSINESS LICENSE NUMBER. FAC 61G1-16.004(1)(2) & FS
 481.219 481.2055--(SEE ATTACHED SHEETS FROM DBPR
 WEBSITE).
 ****NO RESPONSE, NOT ADDRESSED
  
 4. SUBMIT A DETAIL SHOW COMPLIANCE WITH THE FOLLOWING:
  
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE - (FORWARD APPROACH
 REQUIRED MAXIMUM 19" UNDERNEATH THE SINK. SHOW ON SHTS
 A-7 & A-15) - (CABINET DOORS NOT ALLOWED).
 D. 11-4.24.6 EXPOSED PIPES & SURFACES.
 E. 11-4.24.7 FAUCETS
 ****NO RESPONSE, NOT ADDRESSED
  
 5. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-02-24 Cont ID  
Sent By kstevens Date 2007-02-24 Time 14:43 Rev Time 0.00
Received By kstevens Date 2007-02-24 Time 14:43 Sent To  
Notes
2007-02-24 16:01:33DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. APPLICATION INDICATES WORK IN SUITE 200. SHT A-3
 INDICATES WORK ON THE 3RD FLOOR. INDICATE ALL
 SUITES/FLOORS THAT WILL BE INVOLVED IN THE WORK FOR
 THIS PERMIT ON THE APPLICATION. SECTION 105.3.1.
  
 2. FBC-2004 PLUMBING SHALL BE INDICATED WITH OTHER
 APPLICABLE CODES ON SHT A-1.
  
 3. ALL SHEETS. THE ADDRESS FOR THE ARCHITECTURAL
 BUSINESS SHOWN ON THE TITLE BLOCK DOES NOT REFLECT THE
 ADDRESS OF RECORD ON THE DBPR WEBSITE. PLEASE UPDATE
 THE DBPR WEBSITE OR SHOW THE CORRECT ADDRESS IN THE
 TITLE BLOCK.--THE TITLE BLOCK MUST SHOW THE
 BUSINESS LICENSE NUMBER. FAC 61G1-16.004(1)(2) & FS
 481.219 481.2055--(SEE ATTACHED SHEETS FROM DBPR
 WEBSITE).
  
 4. SHT A-11 DETAIL SHOW COMPLIANCE WITH THE FOLLOWING:
  
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE - (FORWARD APPROACH
 REQUIRED MAXIMUM 19" UNDERNEATH THE SINK. SHOW ON SHTS
 A-7 & A-15) - (CABINET DOORS NOT ALLOWED).
 D. 11-4.24.6 EXPOSED PIPES & SURFACES.
 E. 11-4.24.7 FAUCETS
  
 5. SHT P-1 POTABLE WATER RISER INDICATES THE HOT WATER
 TO THE SINK ON THE RIGHT SIDE OF THE FIXTURE. SECTION
 607.4 REQUIRES THE HOT TO BE ON THE LEFT SIDE OF THE
 FIXTURE.- -IF THE REFRIDGERATORS HAVE ICE MAKERS,
 THEN A WATER HAMMER ARRESTOR SHALL BE REQUIRED NEAR THE
 FIXTURES PER SECTION 604.9.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2007-05-10 Cont ID  
Sent By mflis Date 2007-05-10 Time 09:07 Rev Time 0.00
Received By mflis Date 2007-05-10 Time 09:07 Sent To  
Notes
2007-05-10 09:07:53ZONING REVIEW: NOT REQUIRED
  
 *INTERIOR RENOVATION ONLY; NO EXTERIOR WORK FOR ZONING
 REVIEW
  
 MATT FLIS 822-1445